Recharge Procedure for Telemark TVP-2000 and TVP-3500



Similar documents
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Refrigerants and the Refrigeration System

FILLING AND PURGING THE SYSTEM

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Cryogenic Vacuum Pumps

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Operations and Maintenance Manual

OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

This equipment has been certified by ITS/ETL to meet or excees SAE J1990 and J1991 for AR512 series and SAE J2099 and J2210 for AR500 series

Rexroth Hydraulic Pump A10VO Series User Manual

INSTALLATION INSTRUCTIONS

NITROUS TRANSFER PUMP INSTRUCTIONS

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

Automotive Air-Conditioning Service Equipment Ariazone 5001 OPERATOR MANUAL Ariazone 5001

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTION

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Guide to good leak testing

COMPRESSOR REPLACEMENT PROCEDURE

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. Page

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

UNDERSTANDING REFRIGERANT TABLES

ON-VEHICLE INSPECTION

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Flushing and Cleaning the A/C System

Refrigeration Basics 101. By: Eric Nelson

1 / 4 IN. FFL x 4 FT. 9 IN. 1 / 2 IN. ACME x 4 FT. 9 IN. Gauge Accuracy +/-2% Set includes Quick Disconnect Valves

INSTALLATION INSTRUCTIONS

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR İ-COLD Rev. 00

Recovery/ Recycling/ Recharging Unit

MACHINES RECOVERY SYSTEMS SUPEREVAC CHARGING HOSES VACUUM AND HOSE ADAPTERS, VALVES AND PARTS CHARGING SYSTEMS GAUGES INSTRUMENTS ELECTRONIC

Installation Instructions S

ACCUMULATOR INSTALLATION

AIR CONDITIONING GENERAL... 2 HEATER... 7 BLOWER... 9 VENTILATOR AIR CONDITIONING SYSTEM AIR CONDITIONING SERVICE COMPRESSOR...

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

Ductless Split Air Conditioner

Model No. XP XP XP XP XP XP XP XP Data Nominal Tonnage Connections (sweat)

Refrigerant Recovery Unit, Model RRU999

Installer s Guide 18-AH39D1-13

Instructions For SF 6 Refill Kit

Car and commercial cial air conditioning service solutions

Tools & Instruments. Totaline P920-RECOVERY115 Oil-Less Refrigerant Recovery Unit

SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner

PC1131 Electric Air Compressor

YELLOW JACKET Hose Adapters, Valves, and Parts right to the last detail

Air conditioning service unit CAAS500

CHRYSLER HEATER-AIR CONDITIONING SYSTEM

Test Code: 8297 / Version 1

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)

Service Manual ROBINAIR. Model 34800/34801/AC900 Refrigerant Management Center CFC 12, HFC 134a Recycling Equipment

CASSETTE Split System, 18,000-48,000 Btu/h Under ceiling T ype MCC Series 50 Hz

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER...

Element D Services Plumbing

DESIGN STANDARDS SECTION

PC1130 Electric Air Compressor

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Elements Elements describe the essential outcomes.

NFPA31FuelOilPiping 1 Revised

AUTOMOTIVE AIR CONDITIONING

UNIT INFORMATION. Corp L12 Revised SPECIFICATIONS (Early Model) Model No. HS HS HS HS26 461

Customized Assessment Blueprint

Air vacuum pump with r134a & r12/22

User s Guide CARBON DIOXIDE CYLINDERS AND REGULATORS

USC CFC Leak Repair and Recordkeeping Procedures

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

GAS HANDLING SYSTEMS VACUUM INSTRUMENT CORPORATION

Direct Expansion Split Marine Air Conditioning System

Installation Instructions

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

MODEL G300 BRAKE BLEEDER

Your safety and the safety of others are very important.

Understanding Anesthetic Delivery Systems Dean Knoll, CVT, VTS (Anes.) Anesthesia Technician Supervisor University of Wisconsin Madison, WI May 2003

ENGINE COOLING SYSTEM

INSTALLATION INSTRUCTIONS

Line to Refrigerator Ice/Water Dispenser

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Heavy Duty Air Conditioning Service Manual

Oxy-Fuel Gas Welding. Given a functional oxy-fuel gas unit, instruction and demonstration of use, each student will be able to:

EVAPORATIVE (EVAP) EMISSION CONTROL SYSTEM CLEANING PROCEDURE FOR EVAP CANISTER CHARCOAL LEAKAGE INCIDENTS

Air Conditio. Subaru Air Conditioning Systems. End Wrench

Vortex AC. Refrigerant Recovery Machine

RR839. A study of current working practices for refrigeration field service engineers

INSTALLATION MANUAL UH070CAV1 UH105CAV UH140CAV

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

USER MANUAL. Bottom Loading Bottled Water Dispenser SAVE THIS MANUAL FOR FUTURE USE. Model #

Hi Wall Split Air Conditioners

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Model 2128 AIR COMPRESSOR PUMP Operating Instructions

Reverse Cycle Inverter Split System Air Conditioner

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

COMPRESSOR REPLACEMENT PROCEDURE

Not required for most applications Not required for most applications High pressure ( provided) High pressure ( provided)

Transcription:

Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure regulator will be needed 4.) Cylinder of R-22 halogen gas. 5.) Halogen leak detector for refrigerants. 6.) Leak check soap 7.) Vacuum pump capable of 5 x 10-2 Torr or 50 microns. Insure Technician is properly certified and follows US Federal Law when doing any refrigerant recovery. The following terms will be used to describe the position of the 3 way compressor service valve: Back Seated Position: Turn valve stem counter-clockwise until the valve stem is fully extended. This closes off the service port ( the small port on the side of the valve with the brass blank off nut). Mid Seated: From the backseat (per above) turn the valve stem three turns clockwise. This allows refrigerant to flow to the service port. This is a common position during servicing. Front Seated Position: Turn valve stem clockwise until fully shortened. This stops any flow of refrigerant. THE COMPRESSOR SHOULD NOT BE RUN WITH THE VALVE IN THIS POSITION. Step #1 Check the TVP for Leaks. You must locate the source of leak before putting new a charge into the TVP. Remove side panels to access compressor area. Leak check the full system before adjusting any valves or installing the manifold. You don t want to inveterately fix the leak by adjusting a valve before you find the leak. Leak test the line and coil as well as the TVP. Check the water side of the condenser by removing the water lines and blowing out the water. 1

Step #2 Connect the Manifold to the Unit 1.) Insure Manifold s valves are closed. 2.) Connect the manifolds suction hose to the compressors suction service valve. 3.) Connect the manifolds discharge hose to the compressor s discharge service valve. 4.) Midseat the compressors suction and discharge service valves. Step #3 Recover Any Remaining Refrigerant from the Unit You may need one or two 50lb recovery cylinders depending on how much gas in the TVP. Remove the cap from the recovery cylinder s vapor access port (the one with the blue hand valve). Evacuate each recovery cylinder according to the cylinder manufacturer s instructions. Follow all local and federal codes. US federal law requires that cylinders be evacuated to 25-29 Hg vacuum. 1.) Connect the manifold s center port to your charge recovery system s inlet. Connect a recovery cylinder to the outlet of your charge recovery system. (If the discharge side of your recovery system does not have a pressure gauge, install a gauge between your recovery system and the cylinder.) 2.) Open the valves on the manifold and on the recovery cylinder. Turn on the charge recovery system to pump the refrigerant out of the TVP. 2

When the recovery cylinder is filled to its rated pressure, turn off the charge recovery system. Close the valves on the recovery system and on the recovery cylinder. Remove the full recovery cylinder and connect an empty recovery cylinder. Continue this process until the unit is evacuated to the required level (per your local codes or to US federal law which requires refrigerant to be recovered to 10 inches Hg vacuum.) 3.) Re-install the flare cap on the recovery cylinder s vapor access port. Step #4 ReCheck the TVP for Leaks. Connect the R-22 cylinder to the manifolds enter hose. Open both manifold valves and the R-22 cylinder valve to pressurize the unit to 10 to 20 psig (70 140 kpa). Close both manifold valves and the R-22 cylinder valve. Remove the R-22 cylinder from the center hose. Attach the dry nitrogen to the manifold s center hose. Open both manifold valves and the cylinder valve and increase pressure in the unit to 250 psig. Check the entire system (including lines and in-chamber cryosurface) for leaks with the halogen leak detector. Insure that there are no leaks anywhere in the system. Step #5 Evacuate the TVP. Turn on the unit and allow the compressor to run for 30 seconds. Remove the dry nitrogen connection from the manifold s center hose. Release the vapors/gasses from the unit by opening both manifold valves. Connect the vacuum pump to the manifold s center hose and turn on the pump. Evacuate the system to at least 2.5 inches Hg vacuum (17 kpa). Continue pumping for another 30 minutes. Upon finishing, close both manifold valves. b.) Evacuate the unit for a second time Connect the dry nitrogen to the manifold s center hose. Open the manifold s suction valve and pressurize to 100 120 psig. Turn on the unit and allow the compressor to run for 30 seconds. Remove the dry nitrogen connection from the manifold s center hose. Release the vapors/gasses from the unit by opening both manifold valves. Connect the vacuum pump to the manifold s center hose and turn on the pump. Evacuate the system to at least 0.1 Torr or 100 microns (13 Pa) to insure it is completely clean and 3

dry. Use caution to prevent any contaminants from entering the system while connecting or disconnecting any part of the unit or manifold. Step #6 Recharge the Refrigeration Unit 1.) Insure manifold s valves are closed. Insure the compressor s suction and discharge valves are in the midseated position. 2.) Connect tank #1 of the replacement refrigerant charge to the manifold s center hose. 3.) Purge the manifold s center hose of air: loosen the hose where it connects to the manifold; slightly open the cylinder s valve for no more than 1 to 2 seconds; then immediately tighten the hose at the manifold. 4.) Open the cylinder valve. Turn the cylinder upside down so that the liquid refrigerant will be drawn into the unit first. 5.) Open the manifold s discharge valve. Wait for the pressure to equalize (suction and discharge gauge s would show the same pressure). The pressures should equalize within 2 minutes. 6.) Close the manifold s discharge valve. 7.) Repeat steps 1 6 for Tank #2 and Tank #3 of the replacement refrigerant charge. You will need to draw the remaining gas out of the cylinders. This can be accomplished one of the following ways: A) With a charge recovery system (preferred) A1) Connect the manifold s center port to the outlet of your charge recovery system. Connect cylinder #1 to the inlet of your charge recovery system. Purge hoses of air. A2) Open the valves on the manifold and on the cylinder. Turn on the charge recovery system to pump the refrigerant into the TVP. A3) Repeat steps 8 9 for Tank #2 and Tank #3 of the replacement refrigerant charge. Stop charging when the replacement charge cylinder is empty or the DP reaches 260 psig. B) Using the units compressor B1) Connect Tank #1 to the manifold s center port. B2) Start compressor and open the manifold s suction valve and the valve on tank #1. B3) When the system reaches the Standby Ready mode, close the manifold s suction valve and the valve on Tank #1. The compressor should be left operation while this work is done. 4

B4) Remove Tank #1 and Connect Tank #2 to the manifold s center port. Open the manifold s suction valve and the valve on Tank #2. B5) When the pressure in Tank #2 reaches the compressors suction pressure close the manifold s suction valve and the valve on Tank #2. B6) Remove Tank #2 and Connect Tank #3 to the manifold s center port. Open the manifold s suction valve and the valve on Tank #3. B7) When Tank #3 reaches the compressors suction pressure, close the manifold s suction valve and the valve on Tank #3. - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Step #7 Prepare the Refrigeration Unit for Operation Remove the manifold 1.) Backseat the compressor s suction and discharge service valves. 2.) Remove the hoses. 3.) Re-install the Re-install the flare nuts and seals on the access fittings of the service valves. 4.) Leak check the stems of the service valves. Replace valve stem caps Refrigerant recharges are shipped in disposable cylinders. They are intended for one time use only. Cylinders should be properly disposed of per US federal regulations or local regulations. 5