1 2012 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm. General This XC21 outdoor unit is designed for use with HFC 410A refrigerant only. This unit must be installed with an approved indoor unit. See the Lennox XC21 Product Specifications bulletin (EHB) for approved indoor component match ups. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. STEP 1 SETTING THE UNIT Clearances INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XC21 System AIR CONDITIONERS /2012 Supersedes 4/2012 Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent) or service agency. CAUTION Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch. NOTICE! Litho U.S.A. For more in depth information, consult the Installation and Service Procedures manual, available as Corp.1007 L2 on DaveNet or through the Technical Support department at CLEARANCE ON ALL SIDES INCHES (MILLIMETERS) MINIMUM CLEARANCE ABOVE UNIT 12 (305) 6 (152) CONTROL PANEL ACCESS LOCATION 30 (762) NOTES: Clearance to access panel must be 30 inches (762mm). Clearance to one of the other three sides must be 36 inches (914mm). Clearance to one of the remaining two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm). 48 (1219) 36 (914) MINIMUM CLEARANCE BETWEEN TWO UNITS ACCESS PANEL 24 (610) SET CONNECTIONS FIGURE 1 REAR VIEW OF UNIT 7/2012 Page
2 UNIT DIMENSIONS INCHES (MM) 39 1/2 (1003) DISCHARGE AIR ELECTRICAL INLETS 35 1/2 (902) SUCTIOn INLET LIQUID INLET 47 (1194) 18 1/2 (470) 4 1/2 (114) 8 (203) SIDE VIEW 1 (25) ACCESS VIEW UNIT SUPPORT FEET 26 7/8 (683) 16 7/8 (429) 8 3/4 (222) 3 1/8 (79) 30 3/4 (781) BASE WITH ELONGATED LEGS 3 3/4 (95) 4 5/8 (117) STEP 1 SETTING THE UNIT (Continued) Unit Placement To prevent personal injury, as well as damage to panels, unit or structure, observe the following: While installing or servicing this unit, carefully stow all removed panels so that the panels will not cause injury to personnel, objects or nearby structures. Also, take care to store panels where they will not be subject to damage (e.g., being bent or scratched). While handling or stowing the panels, consider any weather conditions (especially wind) that may cause panels to be blown around and damaged. NOTICE! Roof Damage! This system contains both refrigerant and oil. Some rubber roofing material may absorb oil, causing the rubber to degrade. Failure to follow this notice could result in damage to roof surface. IMPORTANT! Exhaust vents from dryers, water heaters and furnaces should be directed away from the outdoor unit. Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit. This will diminish unit performance and longevity. Page 2
3 PLACEMENT INSTALL UNIT AWAY FROM WINDOWS STABILIZING UNIT ON UNEVEN SURFACES #10 X 1/2" LONG SELF DRILLING SHEET METAL SCREWS COIL STABILIZING BRACKET (18 GAUGE METAL 2" WIDTH; HEIGHT AS REQUIRED) #10 X 1 1/4" LONG HEX HD SCREW AND FLAT WASHER Concrete slab use two plastic anchors (hole drill 1/4") CORNER POST BASE PAN TWO 90 ELBOWS INSTALLED IN SET WILL REDUCE SET VIBRATION FIGURE 2 SLAB MOUNTING Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [ mm per 1.5 m]) away from building structure. BUILDING STRUCTURE DISCHARGE AIR! IMPORTANT! Unit Stabilizer Bracket Use (field provided): Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions.) Stabilizers may be used on any unit installed on unstable and uneven surfaces. FIGURE 5 2" (.8MM) SCH 40 FEMALE THREADED ADAPTER FIGURE 3 MOUNTING SLAB ELEVATED SLAB MOUNTING USING FEET EXTENDERS 2" (.8MM) SCH 40 MALE THREADED ADAPTER GROUND LEVEL Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit. STEP 2 REFRIGERANT PIPING Flushing Existing Line Set & Indoor Coil Flush the existing line set per the following instructions. For more information, refer to the Installation and Service Procedures manual available on Dave- Net. CAUTION DO NOT attempt to flush and re use existing line sets or indoor coil when the system contains contaminants (i.e., compressor burn out). NOTE When installing refrigerant lines longer than feet, refer to the Refrigerant Piping Design and Fabrication Guidelines manual available on DaveNet (Corp L9), or contact the Technical Support Department Product Application group for assistance. NOTE For new or replacement line set installation, refer to Service and Application Note Corp L4 (C 91 4). TABLE 1 REFRIGERANT SET INCHES (MM) Models Liquid Line Vapor/ Suction Line L15 Line Set LEG DETAIL BASE 024, 036 and 048 3/8 (10) 7/8 (22) L15 line set sizes are dependent on unit match up. See XP21 Engineering Handbook to determine correct line set sizes /8 (10) 1 1/8 (29) Field Fabricated NOTE Some applications may required a field provided 7/8" to 1 1/8" adapter. FIGURE 4 Page 3 XC21 SERIES
4 IMPORTANT! If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC 410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device and reduce system performance and capacity. Failure to properly flush the system per this instruction and the detailed Installation and Service Procedures manual will void the warranty. When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kpa). Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an explosion, that could result in property damage, personal injury or death. Polyol ester (POE) oils used with HFC 410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections. IMPORTANT! Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COM- PRESSOR. CAUTION As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment. Page 4
5 STEP 2 REFRIGERANT PIPING Removing Existing Indoor Metering Device 1A TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL SHOWN) DISTRIBUTOR TUBES LIQUID ORIFICE HOUSING TEFLON RING FIXED ORIFICE OR 1B TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN) STUB END TWO PIECE PATCH PLATE (UNCASED COIL ONLY) DISTRIBUTOR TUBES LIQUID ORIFICE HOUSING EXPANSION VALVE TEFLON RING BRASS NUT TEFLON RING SENSING DISTRIBUTOR ASSEMBLY REMOVE AND DISCARD WHITE TEFLON SEAL (IF PRESENT) LIQUID ASSEMBLY (INCLUDES STRAINER) 1. On fully cased coils, remove the coil access and plumbing panels. 2. Remove any shipping clamps from the liquid line and distributor assembly. 3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process. 4. Remove and discard fixed orifice, valve stem assembly (if present) and Teflon washer as illustrated above. 5. Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing. 2 EXISTING INDOOR UNIT LIQUID SERVICE VALVE RECOVERY CYLINDER CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE VAPOR SERVICE VALVE D VAPOR LIQUID A CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING (Positioned to deliver liquid refrigerant) LOW 1 B NEW OUTDOOR UNIT C OPENED GAUGE MANIFOLD TANK RETURN INLET DISCHARGE CLOSED RECOVERY MACHINE HIGH 1. HCFC 22 cylinder with clean refrigerant (positioned to deliver liquid refrigerant) to the vapor service valve. 2. HCFC 22 gauge set (low side) to the liquid line valve. 3. HCFC 22 gauge set center port to inlet on the recovery machine with an empty recovery tank connected to the gauge set. 4. Connect recovery tank to recovery machine per machine instructions. DISTRIBUTOR ASSEMBLY MALE EQUALIZER FITTING EQUALIZER SENSING BULB VAPOR LIQUID ASSEMBLY WITH BRASS NUT LIQUID 1. On fully cased coils, remove the coil access and plumbing panels. 2. Remove any shipping clamps from the liquid line and distributor assembly. 3. Disconnect the equalizer line from the check expansion valve equalizer line fitting on the vapor line. 4. Remove the vapor line sensing bulb. 5. Disconnect the liquid line from the check expansion valve at the liquid line assembly. 6. Disconnect the check expansion valve from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process. 7. Remove and discard check expansion valve and the two Teflon rings. 8. Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing. 3FLUSHING SET The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding. 1. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil. B 2. Position the cylinder of clean HCFC 22 for delivery of liquid refrigerant and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine. 3. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC 22 vapor is recovered. Allow the recovery machine to pull the system down to Close the valve on the inverted HCFC 22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off. FIGURE 6 Page 5 XC21 SERIES
6 STEP 2 REFRIGERANT PIPING Brazing Procedures 1 2 vapor and liquid line service ports. PIPING PANEL REMOVAL / PREPARING SET Remove piping panel to access service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line. CAP AND CORE REMOVAL Remove service cap and core from both the suction / SERVICE PORT CAP SERVICE PORT CORE CUT AND DEBUR COPPER TUBE STUB REDUCER SERVICE VALVE CONNECTION SET SIZE MATCHES SERVICE VALVE CONNECTION SET SIZE IS SMALLER THAN CONNECTION LIQUID SERVICE VALVE REFRIGERANT SERVICE PORT CORE SERVICE PORT CAP 3 DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION SUCTION / VAPOR SERVICE VALVE ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR SERVICE VALVES A. Connect gauge set low pressure side to liquid line service valve (service port). B. Connect gauge set center port to bottle of nitrogen with regulator. C. With valve core removed from the suction / vapor line service port, nitrogen flow will have an exit point. LOW HIGH ATTACH GAUGES SUCTION / VAPOR SERVICE PORT MUST BE OPEN AND SERVICE PORT CORE REMOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW INDOOR UNIT SUCTION / VAPOR C SUCTION / VAPOR SERVICE VALVE B OUTDOOR UNIT LIQUID LIQUID SERVICE VALVE A NITROGEN FIGURE 7 Page 6
7 CAUTION Brazing alloys and flux contain materials which are hazardous to your health. Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas. Wear gloves and protective goggles or face shield to protect against burns. Wash hands with soap and water after handling brazing alloys and flux. Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat. WRAP SERVICE VALVES To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use 4additional water saturated cloths under the valve body to protect the base paint. 5 FLOW NITROGEN Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on previous page and below for manifold gauge setup. BRAZE SET Cloths must remain water saturated throughout the brazing and 6cool down process. 1. Braze liquid line to liquid line service valve. 2. Braze suction / vapor line to suction / vapor service valve. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a water saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing the line set! The braze, when complete, must be quenched with water to absorb any residual heat. Do not open service valves until refrigerant lines and indoor coil have been leak tested and evacuated. Refer to Installation and Service Procedures manual found on DAVENET. 6B WHEN BRAZING SET TO SERVICE VALVES, POINT FLAME AWAY FROM SERVICE VALVE. SUCTION / VAPOR SUCTION / VAPOR SERVICE PORT MUST BE OPEN AND SERVICE PORT CORE RE- MOVED TO ALLOW EXIT POINT FOR NITROGEN FLOW WATER SATURATED CLOTHS IMPORTANT! Allow braze joint to cool. Apply additional water saturated cloths to help cool brazed joints. Do not remove water saturated cloths until piping has cooled. Temperatures above 2ºF will damage valve seals. 6A LIQUID WATER SATURATED CLOTHS 7 PREPARATION FOR NEXT STEP After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both services valves to cool piping. Once piping is cool, remove all water saturated cloths. FIGURE 8 Page 7 XC21 SERIES
8 STEP 3 INSTALLING INDOOR EXPANSION VALVE This outdoor unit is designed for use in systems that include an expansion valve metering device. See the XC21 Product Specifications bulletin (EHB) for approved expansion valve kit match ups and application information. The expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field provided plenum, install the expansion valve in a manner that will provide access for future field service of the expansion valve. Refer to below illustration for reference during installation of expansion valve. INDOOR EXPANSION VALVE INSTALLATION TWO PIECE PATCH PLATE (UNCASED COIL ONLY) DISTRIBUTOR TUBES DISTRIBUTOR ASSEMBLY (Uncased Coil Shown) LIQUID ORIFICE HOUSING STUB END TEFLON RING EQUALIZER EXPANSION VALVE TEFLON RING SENSING 3. Install one of the provided Teflon rings around the stubbed end of the expansion valve and use refrigerant oil to lightly lubricate the connector threads and exposed surface of the Teflon ring. 4. Attach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten, then use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure to the right, or tighten to 20 ft lb. 5. Place the remaining Teflon washer around the other end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil. 6. Attach the liquid line assembly to the expansion valve. Finger tighten, then use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft lb. 1/2 Turn MALE EQUALIZER FITTING (SEE EQUALIZER INSTALLATION FOR DETAILS) VAPOR Sensing bulb insulation is required if expansion valve is installed external to the coil casing. See sensing bulb installation for bulb positioning. EQUALIZER INSTALLATION LIQUID ASSEMBLY WITH BRASS NUT LIQUID 1. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below. 2. Remove the field provided fitting that temporarily reconnected the liquid line to the indoor unit s distributor assembly. SENSING BULB INSTALLATION 1. Attach the vapor line sensing bulb in the proper orientation as illustrated below using the clamp and screws provided. 2. NOTE Though it is preferred to have the sensing bulb installed on a horizontal run of the vapor line, installation on a vertical run of piping is acceptable if necessary. NOTE Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb. 3. Connect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut, then tighten an additional 1/8 turn (7 ft lbs) as illustrated to the right. VAPOR BULB 12 BULB 1/8 Turn ON S SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O CLOCK POSITION FLARE SEAL CAP FLARE NUT OR COPPER FLARE SEAL BONNET VAPOR 12 ON 7/8" AND LARGER S, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O CLOCK POSITION. NEVER MOUNT THE SENSING BULB ON BOTTOM OF. MALE BRASS EQUALIZER FITTING BULB BULB VAPOR NOTE NEVER MOUNT THE SENSING BULB ON BOTTOM OF. FIGURE 9 Page 8
9 STEP 4 LEAK TEST AND EVACUATION LOW HIGH MANIFOLD GAUGE SET OUTDOOR UNIT B A TO VAPOR SERVICE VALVE NOTE Position canister to deliver liquid refrigerant. NITROGEN HFC 410A 1 2 CONNECT GAUGE SET A. Connect the high pressure hose of an HFC 410A manifold gauge set to the vapor valve service port. NOTE Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage. B. With both manifold valves closed, connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set. NOTE Later in the procedure, the HFC 410A container will be replaced by the nitrogen container. TEST FOR LEAKS After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks: A. With both manifold valves closed, connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC 410A cylinder (vapor only). B. Open the high pressure side of the manifold to allow HFC 410A into the line set and indoor unit. Weigh in a trace amount of HFC 410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kpa) pressure.] Close the valve on the HFC 410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC 410A cylinder. C. Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set. D. Adjust nitrogen pressure to 1 psig (1034 kpa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit. E. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector. F. After leak testing, disconnect gauges from service ports. FIGURE 10 Page 9 XC21 SERIES
10 STEP 4 LEAK TEST AND EVACUATION (Continued) EVACUATION 3CONNECT GAUGE SET A. Connect low side of manifold gauge set with 1/4 SAE in line tee to vapor line service valve B. Connect high side of manifold gauge set to liquid line service valve C. Connect available micron gauge connector on the 1/4 SAE in line tee. D. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC 410A and nitrogen containers. NOTE Remove cores from service valves (if not already done). NITROGEN HFC 410A NOTE Position canister to deliver liquid refrigerant. VACUUM PUMP OUTDOOR UNIT A B 1/4 SAE TEE WITH SWIVEL COUPLER C 0 MICRON GAUGE MANIFOLD GAUGE SET TO VAPOR SERVICE VALVE TO LIQUID SERVICE VALVE LOW HIGH 4 EVACUATE THE SYSTEM A. Open both manifold valves and start the vacuum pump. B. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure. NOTE The term absolute pressure means the total actual pressure above zero within a given volume or system. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. C. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:! Close manifold gauge valves. Close valve on vacuum pump. Possible equipment damage. Turn off vacuum pump. Disconnect manifold gauge center port hose from vacuum pump. Attach manifold center port hose to a nitrogen cylinder with pressure regulator set to 1 psig (1034 kpa) and purge the hose. Open manifold gauge valves to break the vacuum in the line set and indoor unit. Close manifold gauge valves. D. Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit. E. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 0 microns (29.9 inches of mercury) within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves. F. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit. G. Perform the following: Close manifold gauge valves. Shut off HFC 410A cylinder. Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure. Replace stem caps and finger tighten them, then tighten an additional one sixth (1/6) of a turn as illustrated. FIGURE 11 Page 10 D RECOMMEND MINIMUM 3/8" HOSE Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuum can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty /6 TURN
11 STEP 5 ELECTRICAL Circuit Sizing and Wire Routing In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 24VAC TRANSFORMER Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC 40 VA minimum) Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. IMPORTANT! If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start up to prevent compressor damage as a result of slugging. ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures CAUTION Electrostatic discharge can affect electronic components. Take care during unit installation and service to protect the unit s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge. 1 SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker size (HACR per NEC). Install power wiring and properly sized disconnect switch. SERVICE DISCONNECT SWITCH 2 INSTALL THERMOSTAT Install room thermostat (ordered separately) on an inside wall in the center of the conditioned area and 5 feet (1.5m) from the floor. The thermostat should not be installed on an outside wall or where it can be affected by sunlight or drafts. THERMOSTAT 5 FEET (1.5M) NOTE Units are approved for use only with copper conductors. Ground unit at disconnect switch or connect to an earth ground. NOTE 24VAC, Class II circuit connections are made in the control box. FIGURE 12 Page 11 XC21 SERIES
12 3 A. ROUTE CONTROL WIRES NON COMMUNICATING Install low voltage control wiring from outdoor to indoor unit and from thermostat to indoor unit. All low voltage wiring must enter unit through provided field installed busing installed in electrical inlet. Run 24VAC control wires through hole with grommet. Make 24VAC control wire connections to outdoor control (A175). NOTE Do not bundle any excess 24VAC control wires inside control box. NOTE Wire tie provides low voltage wire strain relief and maintains separation of field installed low and high voltage circuits. NOTE For proper voltages, select control wires gauge per table below. B CONTROL (A175) WIRE RUN LENGTH AWG# INSULATION TYPE LESS THAN 100 (30 METERS) 18 TEMPERATURE RATING MORE THAN 100 (30 METERS) 16 35ºC MINIMUM. A B. ROUTE CONTROL WIRES COMMUNICATING Maximum length of wiring (18 gauge) for all connections on the RSBus is 10 feet (457 meters). Wires should be color coded, with a temperature rating of 95 º F (35 º C) minimum, and solid core (Class II Rated Wiring). All low voltage wiring must enter unit through provided field installed busing installed in electrical inlet. Communicating systems using the icomfort enabled thermostat require four thermostat wires between the thermostat and the furnace/air handler control and four wires between the outdoor unit and the furnace/air handler control. When a thermostat cable with more than four wires is used, the extra wires must be properly connected to avoid electrical noise (see illustration below). Use a wire nut to bundle the four unused wires at each end of the cable. Each bundle should also include an additional wire that should be connected on each end to the C terminal as shown in the figure below. icomfort enabled Outdoor Unit icomfort enabled Indoor Unit HOLE Single Wire To C Terminal icomfort enabled thermostat Single Wire To C Terminal Unused Wires 4 Unused Wires ROUTE HIGH VOLTAGE AND GROUND WIRES Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. GROUND LUG* WATERTIGHT CONTROL BOX CONDUIT FITTING WATERTIGHT FLEX- IBLE CONDUIT TO SERVICE DISCONNECT BOX CONTACTOR ELECTRICAL INLET (HIGH VOLTAGE) WIRING ENTRY POINTS * Attach field provided green ground wire to provided ground lug. NOTE Grounding wire must be a single, continuous wire run from unit ground lug to earth ground. DO NOT splice wire. ELECTRICAL INLET (CONTROL WIRING LOW VOLTAGE). USE BUSHING PROVIDED IN BAG ASSEMBLY HERE. ACCESS VIEW FIGURE 13 Page 12
13 STEP 5 ELECTRICAL (Continued) Outdoor Control (A175) Jumpers and Terminals 55 DEGREE TARGET DEGREE TARGET (HP ONLY) J4 COMPRESSOR SHIFT DELAY 30 SECOND DELAY (DEFAULT) 0 SECOND DELAY 30 (TWO STAGE HEAT PUMP ONLY) J2 SECOND STAGE LOCK IN TEMPERATURE Communication System The jumper settings and link are default settings and ONLY control system operation if configuration settings in the icomfort enabled thermostat are not available. Non Communicating System The unit will operate based on jumper settings and R TO DS link on the MAIN CONTROL. All unit setting changes must be done at the MAIN CONTROL. The Lennox ComfortSense 7000 thermostat may be used, as well as other non communicating electronic only thermostats. Set up of jumpers on replacement outdoor control SEGMENT DISPLAY PUSH BUTTON The Lennox icomfort enabled thermostat must be used in communicating applications. NOTE Fan cycling routine when activated will cycle the fan ON for five minutes if the outdoor ambient air temperature is between 15ºF and 35ºF and the compressor has been OFF for 25 to 30 minutes. This option is to help reduce the potential for ice build up on the orifice ring during system OFF cycles that are greater than 25 to 30 minutes. J3 ALL UNITS) FAN CYCLING J1 (HP ONLY) DEFROST TERMINATION TEMPERATURE 100 DEGREE TARGET 90 DEGREE TARGET 70 DEGREE TARGET DEGREE TARGET (DEFAULT) JUMPER ON FAN ON FOR 5 MINUTES JUMPER OFF DISABLE (DEFAULT) DS TO R TWO STAGE UNIT ONLY) Cut for Humiditrol Enhanced Dehumification Accessory (EDA) applications. ON OFF SEE NOTE ABOVE FOR FURTHER DETAILS (DEFAULT WHEN JUMPER IS REMOVED OR MISSING) 45 DEGREE TARGET NOTE LINK NOT APPLICABLE TO ONE STAGE UNITS. CUTTING LINK WILL HAVE NO AFFECT ON OPERATION OF ONE STAGE UNITS. 40 DEGREE TARGET (DEFAULT) FIGURE 14 Page 13 XC21 SERIES
14 STEP 5 ELECTRICAL (Continued) Field Control Wiring The following two illustrations provide examples of control wiring connections when using a non communicating thermostat. For examples of control wiring in complete or partial communicating systems, see the icomfort enabled thermostat Quick Start Guide which is provided with the thermostat. XC21 Two Stage Air Conditioner Control Air Handler 7 DS ComfortSense 7000 Thermostats Catalog # Y0349 or Y2081 R W O G On board link L L W2 Low voltage thermostat wiring Y2 H W1 Flat metal jumper Y1 DH O O DS R L H 2 C C D 5 Y1 B 6 Y2 G Y2 Y1 1 R W3 C 3 W2 W1 4 T T 1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat s outdoor temperature display (optional). 2. R to L connection is required for this model when using the ComfortSense 7000 catalog number Y0349 only. Resistor Kit (catalog number 47W97) required and ordered separately. 3. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For one stage electric heat, do not remove factory installed metal jumpers. 4. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For two stage electric heat, remove factory installed metal jumper between W1 to W2. Then connect thermostat wire between the air handler control s W2 and the thermostat s W2 terminal. 5. Cut on board link (clippable wire) from Y1 Y2 2 STAGE COMPR for two stage compressor and two speed fan operation. 6. Cut loop jumper (clippable wire) DS to R on two stage units for Humiditrol applications. This will slow the outdoor unit s fan speed to a specific RPM. A wire must be installed between the DS terminals on the air handler and outdoor unit controls. 7. Cut on board link (clippable wire) DS R for Humiditrol or Harmony III applications. This will slow the indoor blower motor to the lowest speed setting. See air handler installation instruction or engineering handbook for lowest fan speed information. FIGURE 15 Page 14
15 Furnace XC21 Two Stage Air Conditioner Control 5 DS ComfortSense 7000 Thermostats Catalog # Y0349 or Y2081 R W O G On board link L L W2 Low voltage thermostat wiring Y2 Y1 O DS H DH R W1 O L H 2 C C D 3 Y1 B 4 Y2 G Y2 Y1 1 R C W2 W1 T T 1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat s outdoor temperature display (optional). 2. R to L connection is required for this model when using the ComfortSense 7000 catalog number Y0349 only. Resistor Kit (catalog number 47W97) required and ordered separately. 3. Cut on board link W915 (clippable wire) for two stage operation. 4. Cut loop jumper (clippable wire) DS to R on two stage units for Humiditrol applications. This will slow the outdoor unit s fan speed to a specific RPM. A wire must be installed between the DS terminals on the furnace and outdoor unit controls. 5. Cut on board link (clippable wire) DS R for Humiditrol or Harmony III applications. This will slow the indoor blower motor to the lowest speed setting. See furnace installation instruction or engineering handbook for lowest fan speed information. FIGURE 16 Page 15 XC21 SERIES
16 Charging The XC21 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping. Charge should be checked and adjusted using the tables provided on the charging procedure sticker on the unit access panel. Detailed information is given in the XC21 Installation and Service Procedures manual, which is available on DaveNet. Start Up Checklists TWO STAGE COMPRESSOR PERFORMANCE Use this procedure to verify part- and full-load capacity operation of the two-stage compressor. IMPORTANT! This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning properly to correctly perform compressor operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings). TOOLS REQUIRED Refrigeration gauge set Digital volt/amp meter Electronic temperature thermometer On-off toggle switch PROCEDURE 1. Turn main power OFF to outdoor unit. 2. Adjust room thermostat set point 5ºF above (heating operation) or 5ºF below (cooling operation) the room temperature. 3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor. 4. Turn toggle switch OFF. Install switch in series with Y2 wire from room thermostat. (See note ** in the Field Operational Checklist on page 17). 5. Cycle main power ON. 6. Allow pressures and temperatures to stabilize before taking any reading (may take up to 10 minutes). 7. Record all of the readings for the Y1 demand. 8. Close switch to energize Y2 demand. Verify power is going to compressor solenoid (see note ** in the Field Operational Checklist on page 17). 9. Allow pressures and temperatures to stabilize before taking any reading (may take up to 10 minutes). 10. Record all of the readings with the Y1 and Y2 demand. 11. If temperatures and pressures change in the direction noted in chart, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not switching between low and high capacity and replacement is necessary.) 12. After testing is complete, return unit to original set up. Page 16
17 XC21 Field Operational Checklist Cooling*** Heating*** Unit Readings Y1 First Stage Expected results during Y2 demand (toggle switch ON) Y2 Second Stage Y1 First Stage Expected results during Y2 demand (toggle switch ON) Y2 Second Stage Compressor Voltage Same Same Amperage Higher Higher Condenser Fan motor Amperage Same or Higher Same or Higher Temperature Ambient Same Same Outdoor Coil Discharge Air Higher Lower Compressor Discharge Line Higher Higher Indoor Return Air Same Same Indoor Coil Discharge Air Lower Higher Pressures Suction (Vapor) Lower Down Liquid Higher Higher Note Unit may have a low ambient control or control that locks in second stage operation below its set point. It may be necessary to remove a wire from the control when performing this check. ** On the XC21 units, the System Operation Monitor controls the second stage solenoid coil in compressor. *** Cooling Mode Operation Block outdoor coil to maintain a minimum of 375 psig during testing. Page 17 XC21 SERIES
18 XC21 Start Up and Performance Checklist Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Solar Module Mfg and Model Serial Notes: START UP CHECKS Refrigerant Type: Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps: COOLING MODE Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Temperature: HEATING MODE Vapor Pressure: Liquid Pressure: Supply Air Temperature: Ambient Temperature: Return Air Temperature: System Refrigerant Charge (Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temperatures.) Subcooling: Approach: Indoor Coil Temp. Drop (18 to 22 F) Saturated Condensing Temperature (A) minus Liquid Line Temperature (B) Liquid Line Temperature (A) minus Outdoor Air Temperature (B) Return Air Temperature (A) minus Supply Air Temperature (B) A B = SUBCOOLING A B = APPROACH A B = COIL TEMP DROP Page 18
19 Homeowner Information CAUTION Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch. Cleaning of the outdoor unit s coil should be performed by a licensed professional service technician (or equivalent). Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner. IMPORTANT! Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts, diminish performance and affect longevity of the unit. Outdoor Coil The outdoor unit must be properly maintained to ensure its proper operation. Please contact your dealer to schedule proper inspection and maintenance for your equipment. Make sure no obstructions restrict airflow to the outdoor unit. Grass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit. Keep snow level below the louvered panels to ensure proper performance. Routine Maintenance In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. NOTE The filter and all access panels must be in place any time the unit is in operation. If you are unsure about the filter required for your system, call your Lennox dealer for assistance. 1. Ask your Lennox dealer to show you where your indoor unit s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed. 2. Disposable filters should be replaced with a filter of the same type and size. 3. The indoor evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.) Thermostat Operation See the ComfortSense 7000 or icomfort enabled thermostat homeowner manual for instructions on how to operate your thermostat. Preservice Check If your system fails to operate, check the following before calling for service: Verify room thermostat settings are correct. Verify that all electrical disconnect switches are ON. Check for any blown fuses or tripped circuit breakers. Verify unit access panels are in place. Verify air filter is clean. If service is needed, locate and write down the unit model number and have it handy before calling. Page 19 XC21 SERIES
INSTALLATION INSTRUCTIONS
2011 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XP17 System HEAT PUMPS 506586 01 06/11 Supersedes 05/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
INSTALLATION INSTRUCTIONS
2010 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XC17 Units AIR CONDITIONER 04/10 Supersedes 506498 01 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit Series13ACD Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service
INSTALLATION INSTRUCTIONS
2011 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Elite Series XP14 Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE These instructions are intended as a general guide and do
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Installation Instructions
CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS
Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
How To Install An Evaporator Coil
EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...
SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner
Service Literature Corp. 0628 L5 Revised 07 2010 SSB*H4 Commercial Air Conditioner SSB*H4 The SSB*H4 is a high efficiency commercial split system condensing unit, which features a two stage scroll compressor
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
Refrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Ductless Split Air Conditioner
Ductless Split Air Conditioner Installation Manual Indoor HSU09VHG(DB)-W HSU12VHG(DB)-W HSU18VHH(DB)-W HSU24VHG(DB)-W Outdoor HSU09VHG(DB)-G HSU12VHG(DB)-G HSU18VHH(DB)-G HSU24VHG(DB)-G Table of Contents
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR
INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR (For NEW 2007 ALL WHITE KWIK-KITS ONLY) Warning do not attempt to install A/C units unless you are experienced with servicing
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / START-UP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / START-UP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL These instructions must be read and understood completely before attempting installation. TABLE
Model No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat)
Service Literature Corp. 0528 L10 Revised 05 2008 XP13 SERIES UNITS XP13 The XP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor and R 410A refrigerant.
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
INSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION OUTDOOR SPLIT-SYSTEM AIR CONDITIONER MODELS: 10, 12, 13 AND 14 SEER 1 PHASE - 1.5 TO 5 TONS TABLE OF CONTENTS GENERAL INFORMATION.................... 2 INSPECTION..............................
Power Cube Open Source Ecology Page 1. Power Cube. Version 4
Power Cube Open Source Ecology Page 1 Power Cube Version 4 Power Cube Open Source Ecology Page 2 Contents Table of Contents Power Cube... 1 Contents...2 Introduction... 3 Bill Of Materials...4 Discrete
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Air Conditioner Water Heater Model ACWH18
Air Conditioner Water Heater Model ACWH18 Installation Guide IMPORTANT! READ THIS FIRST! Commissioning of this unit must be done by a licensed HVAC technician. Commissioning includes making the electrical
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00
E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test
APTA STANDARDS DEVELOPMENT PROGRAM RECOMMENDED PRACTICE American Public Transportation Association 1666 K Street, NW, Washington, DC, 20006-1215 APTA BTS-BMT-RP-001-10 Approved October, 2010 APTA Bus Maintenance
Central Air Conditioner
Central Air Conditioner USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL AIR CONDITIONER NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Geyser-R Heat pump water heater Installation manual
Geyser-R Heat pump water heater Installation manual 1 Version 2.9 SAFETY INFORMATION Please read carefully to prevent serious accidents or injury. The Geyser-R Heat Pump Water Heater must be installed
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
VOYAGER 570G. 744A Sprayer Control
VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER
Recharge Procedure for Telemark TVP-2000 and TVP-3500
Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
ROOM AIR CONDITIONER INSTALLATION MANUAL
ROOM AIR CONDITIONER INSTALLATION MANUAL ( Split Type) Please read this installation manual completely before installing the product When the power cord is damaged, replacement work shall be performed
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
Air Conditioning System
Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
COOLING SYSTEM Section Page
5 COOLING SYSTEM Section Page 5.1 COOLANT PRE-HEATER... 5-3 5.2 COOLANT PUMP NON-EGR ENGINE... 5-7 5.3 COOLANT PUMP EGR ENGINE... 5-13 5.4 FRONT CONNECTOR HOUSING NON-EGR ENGINE... 5-17 5.5 FRONT CONNECTOR
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477
Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.
Model Number: Serial Number: Information Manual Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. ATTENTION: IF YOU ARE NOT A LICENSED PLUMBER OR A LICENSED
specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1967-72 CHEVROLET PICKUP
specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1967-72 CHEVROLET PICKUP CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect
Miami Heat Pump HP Series Installation Guide
CAUTION- THIS UNIT IS FOR INDOOR USE ONLY!! WARNING BEFORE ANY INSTALLATION OR MAINTANCE IS STARTED PLEASE READ COMPLETE INSTLLATION GUIDE. INSTALLATION START-UP AND SERVICE INSTRUCTION- The HP Water Source
WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
XL PREMIUM OIL COOLER KIT
-J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
Air Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS Installation and service must be provided by a qualified installer, service agency or gas supplier Grand Canyon Gas Logs, logs are made
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
Evaporator Coil Installation Instructions
Part # 96654008 July 2010 Evaporator Coil Installation Instructions A-Coil Page 4 Multi-position A-Coil Page 4-7 Slab Coil Page 5 Horizontal A-Coil Top Connection Page 5 Horizontal A-Coil Side Connection
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Application Outboards Faria 5 Gauge Set* Publication No. Description Part Number Honda Code PII53606A White faced, flat lens 06300-ZW5-010ZB 6315410 Issue Date Black faced, flat
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / STARTUP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / STARTUP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL These instructions must be read and understood completely before attempting installation. TABLE
IMPORTANT SAFETY RULES TO FOLLOW
WARNING FLOOR & CARPET CLEANER Any piece of equipment can be dangerous if not operated properly. YOU are responsible for the safe operation of this equipment. The operator must carefully read and follow
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS
RV Products Division INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS Service Contact: Coast to Coast RV Services Pty Ltd. 20 George Young St. Auburn NSW 2144 Australia
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01
682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
PORTABLE AIR CONDITIONER
PORTABLE AIR CONDITIONER MAC 7500 Owner s Manual Air Conditioner Dehumidifier Oscillating Fan Please read this owner s manual carefully before operating the unit. POWERED BY 66126113.p65 17 INTRODUCTION
Refrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Installation Instructions
VentilAire IV Whole-House Fresh Air Supply System Installation Instructions 914228 Flat Roof Kit 914229 Sloped Roof Kit 5" x 11' Class I Insulated Flexible Duct Plastic Clamps (2) Metal Clamps (2) Ceiling
Evaporator Coil. Installation Instructions GENERAL
IM-HAC-0966540-12 December 2013 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Metering Device... 6 Condensate Drain...