Feasibility Study of Air Conditioning System With Separated Dehumidification Process Using Low Temperature Exhaust Heat of Ice Storage



Similar documents
Performance Test of Solar Assisted Solid Desiccant Dryer

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Experimental Evaluation Of The Frost Formation

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

saving energy in comfort Factsheet Recair Enthalpy

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

PROCEEDINGS SOLAR 94

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Pool Dehumidification Basics

Dehumidification Frequently Asked Questions

Refrigerated Air Dryers. Catalogue

imagine SOLAR AIR CONDITIONING MADE EASY

Housing Fact Sheets. Moisture Condensation at the Windows

Energy Recovery Ventilation Equipment

Refrigeration Air Dryers. Catalogue

Draft UCL Heating, Cooling and Ventilation Policy

SOLAR DESSICANT COOLING EXAMPLE OF APPLICATION TO A LOW ENERGY BUILDING

ENERGY CARRIERS AND CONVERSION SYSTEMS Vol. II - Liquid Hydrogen Storage - Takuji Hanada, Kunihiro Takahashi

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

RESEARCH HIGHLIGHT. The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

POLLUTED EMISSION TREATMENTS FROM INCINERATOR GASES

Experimental Study on Super-heated Steam Drying of Lignite

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

Study of Snowdrift around Buildings of Antarctica using Numerical Analysis

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

A THEORETICAL STUDY OF THE IMPACT OF USING SMALL SCALE THERMO CHEMICAL STORAGE UNITS IN DISTRICT HEATING NETWORKS

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Effect of Self-Heat Circulation on VOCs Decomposition in Regenerative Thermal Oxidizer

Hospital Application Guide. Cost-effective climate control for hospitals

TEXTILE FABRICS AS THERMAL INSULATORS

THE HUMIDITY/MOISTURE HANDBOOK

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

UNIT 6a TEST REVIEW. 1. A weather instrument is shown below.

Exergy Analysis of a Water Heat Storage Tank

Federation of European Heating, Ventilation and Air-conditioning Associations

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

Delivering exceptional performance and Ecovalue. Ecocent

ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO

A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications

We will study the temperature-pressure diagram of nitrogen, in particular the triple point.

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM

Application of sandy bed solar collector system for water extraction from air

Sound pr. (db(a)) Phone: Pressure hpa Fax: Capacity kw

How To Understand Evaporator

FLORIDA SOLAR ENERGY CENTER

GLOBACON 05 HVAC Systems for Cogen

SORBTION MATERIALS FOR APPLICATION IN SOLAR HEAT ENERGY STORAGE

Precision Humidity Measurement for Pharmaceutical Fluid Bed Tablet Coating

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

Brewer s Spent Grain (BSG) is the granular byproduct from beer brewing. It mainly consists of barley as this is the major raw material used in the

Mechanical and Natural Ventilation

DEH software (Energy need of air conditioning units)

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2

ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM

Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology

FEASIBILITY OF A BRAYTON CYCLE AUTOMOTIVE AIR CONDITIONING SYSTEM

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT

AdSORPTION CHILLER NAK

Creating Efficient HVAC Systems

CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS

Application Potential of Solar-assisted Desiccant Cooling System in Sub-tropical Hong Kong

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Evaporative Cooling System for Aquacultural Production 1

The Second Law of Thermodynamics

Glossary of Heating, Ventilation and Air Conditioning Terms

HEAT TRANSFER ANALYSIS OF COLD STORAGE

Characteristics of Evaporators

Research on the Air Conditioning Water Heater System

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

Innovent LASER Packaged Fresh Air Conditioning Units

Energy and Buildings

Chapter 8: Heat Exchangers

On the Use of Data Loggers in Picture Frames (And Other) Micro Climates

Molds and mildew are fungi that grow

Solar Desiccant Air Conditioner

Improving Data Center Energy Efficiency Through Environmental Optimization

ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING

Boiler efficiency measurement. Department of Energy Engineering

Hydrogen Adsorption on Nanoporous Biocarbon

Temperature and Humidity

Effects of Solar Photovoltaic Panels on Roof Heat Transfer

Better Dry than Sorry

How To Know If A Refrigeration System Is Efficient

Soil Suction. Total Suction

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

Absolute and relative humidity Precise and comfort air-conditioning

Transcription:

Feasibility Study of Air Conditioning System With Separated Dehumidification Process Using Low Temperature Exhaust Heat of Ice Storage S. Nakabayashi, K. Nagano, M. Nakamura, S. Okabe Hokkaido University Sapporo, JAPAN Tel: +81-11-706-6286 saya@eng.hokudai.ac.jp J. Togawa, A. Kurokawa Wakkanai Green Factory Co., Ltd. Wakkanai, JAPAN ABSTRACT The aim of this study is to develop an advanced air conditioning system. The dehumidification process of this system is separated from the cooling process and combined with an ice storage system. We use Wakkanai siliceous shale as a desiccant material. This is a natural mesoporous material produced in the northern area of Hokkaido, Japan. A honeycombed desiccant material made of the shale is cheaper than the one with silica-gel, and it can release vapor easily even by using low-temperature air. It was found that the desiccant process by using the shale honeycomb enables the temperature of regeneration to decrease to 40ºC, whereas the desiccant process using silica-gel needs the temperature of 80ºC. 1. INTRODUCTION Recently the demand for cooling is increasing for comfortable conditions, especially in the urban areas. Because of this demand, energy consumption in the daytime is very large and causes the shortage of electricity. Therefore, a peak shaving using night power for a cold storage is effective for energy saving and the electric load leveling. On the other hand, the humidity control is one of the key factors for indoor comfort. As a comfortable indoor condition, 26ºC and 50 60%RH is recommended in the summertime in Japan. The average temperature and relative humidity of summer in Tokyo is shown in Fig. 1. This shows that dehumidification is necessary. However, the conventional air-conditioning system needs a lot of energy for dehumidification. It cools the humid air to remove moisture condensing the humidity into a droplet. Briefly it spends much energy for removing latent heat. As a result, a desiccant cooling system attracts increasing attention. The desiccant system is an open heat driven cycle, and it consumes less energy for dehumidification. A typical desiccant system is shown in Fig. 2. Because a desiccant wheel adsorbs moisture from the humid air, this system doesn t need supercooling for condensation. Furthermore, we can use the desiccant wheel repeatedly by regenerating with high temperature air. As the regenerating air, waste heat of micro gas turbine, solar energy, and other exhaust heat are useful. In Japan, the solid desiccant systems using silica gel or zeolite filter are mainly used. Although they

Temperature [ºC] 32 30 28 26 24 22 85 80 75 70 65 60 Relative humidity [%] 18 55 Temperature Relative humidity 16 50 6/1 7/1 7/31 8/30 9/29 Day Figure 1: 3-year average temperature and relative humidity of summer in Tokyo (06-08). Air handling unit (desiccant) Exhaust heat Refrigerator Regeneration Heater OA Adsorption Desiccant wheel Heat exchange wheel RA Cooler Supply air Dry air Cool air Ice storage in the midnight GL Figure 2: A desiccant system Ice storage tank Figure 3: Concept figure of the desiccant system using the exhaust heat of ice storage have high adsorption performance, they are not familiar to the air-conditioning market because of their prices and high regeneration temperature around 80ºC. In this paper, as an effective utilization of exhaust heat from the refrigerator for the ice storage, the combination with a desiccant system was introduced (Fig. 3). Part of the cooling load is shifted from peak hours to off-peak hours like midnight. And the exhaust heat is used for regenerating the desiccant material. Authors developed a desiccant wheel using Wakkanai siliceous shale as a new desiccant material. Performance evaluation and numerical calculation were achieved. 2. WAKKANAI SILICEOUS SHALE Wakkanai siliceous shale (WSS) is a kind of siliceous mudstone. Figure 4 shows the appearance of this shale. It is widely distributed in northern part of Hokkaido (Soya area) in Japan as shown in Fig. 5, and laid down in layers more than 1,000 meters below the surface. This shale is natural meso-porous material, and it has characteristic pore size distribution as

25 [mm] Figure 4: Appearance of Wakkanai siliceous shale Soya area Hokkaido Cape Souya Cape Nosyappu Wakkanai Mining point Toyotomi Sarufutsu Horonobe Tokyo Teshio Figure 5: Distribution map of Wakkanai siliceous shale in Soya area, Hokkaido 0.012 Pore volume [cm 3 /g] 0.008 0.004 0.000 2 3 4 5 10 30 40 50 Pore size distribution [nm] Figure 6: Pore size distribution of Wakkanai siliceous shale shown in Fig. 6. The pores in the range from 4 to nm contribute to the moisture adsorption. The primary constituent of this shale is silicon dioxide (SiO 2 ). This shale s specific surface area calculated by BET equation is 149 m 2 /g, and the fine pore volume is 0.382 cm 3 /g. Figure 7 shows the water adsorption isotherms of WSS at 25ºC. WSS adsorbs a lot of water vapor when the relative humidity of air is higher than 70%, however it doesn t adsorb well under the dry condition. Compared with silica gel (type A), WSS starts to adsorb the moisture in the range of higher relative humidity. Although the maximum adsorption amount of WSS is about 3/4 of silica gel (type A), WSS is easier to be regenerated than silica gel because WSS releases the moisture simply when the relative humidity decreases. And the price is about 1/10 of that of silica gel.

Adsorption amount [mg/g] 400 350 300 250 0 150 100 50 WSS Silica gel (type A) 0 0 40 60 80 100 Relative humidity [%] Figure 7: Water adsorption isotherms of Wakkanai siliceous shale and silica gel (type A) analyzed at 25ºC. 3. DESICCANT WHEEL CONTAINING WAKKANAI SILICEOUS SHALE To develop a desiccant wheel containing WSS, we made paper using pulp and the WSS powder. WSS powder was obtained by a ball-milling treatment. The highest-frequent diameter of WSS particle was 3.1 µm. The WSS paper was formed into a corrugate-structure filter as shown in Fig.8. The diameter is 150 mm, and the length is 0 mm just for a test production. Two types of pulp were used as WSS filters. For analyzing the adsorption performance, short-term cyclic test was carried out. The experiment condition is shown in Table 2. A condition of term A adsorption- was the simulation of the outside air in the daytime of summer in Tokyo. The other, term B -regeneration- was simulated the return-air from the room (26ºC, 60%RH) heated to 40ºC by using the exhaust heat of the refrigerator. Figure 9 shows the experimental setup and its picture. Summary of the test pieces is shown in Table 3. 150 mm 0 mm Overall view Cross section Extended view 10 mm Figure 8: Appearance of the test production of the desiccant filter containing WSS

Table 2: Experiment condition Term A adsorption- Term B -regeneration- Temperature 30ºC 40ºC Relative humidity 75% 32% Time interval 60 min 30 min Table 3: The list of tested filters Base material Adsorbent Weight Filter A Natural pulp WSS 912.7 g Filter B Chemical fiber WSS 618.4 g Filter C Chemical fiber Silica gel (type A) 608.0 g Filter D - Zeolite 893.3 g Thermo-hygrostat chamber 30ºC, 75%RH Flowmeter Thermal insulator thermoelectric thermometer Thermo & hygrometer Polyethylene film Fan Thermometry point 3-way valve 40ºC 32%RH Supporting leg Electric balance Supporting leg Fan Picture of the test section Thermometry point of a desiccant filter Constant temperature bath Heater Humidifier filter No.1 No.2 No3 No.4 No.5 inlet 50 mm outlet 0 mm Figure 9: Experimental setup The weight changes of these filters in the first and second cycles are shown in Fig. 10. It was confirmed that Filter C silica gel (type A)- and Filter D zeolite- adsorbed moisture in the first cycle, but they couldn t be regenerated enough by 40ºC air. Then, in the second cycle, they couldn t adsorb the same amount of moisture as in the first cycle. On the other hand, Filter A WSS and natural pulp- adsorbed about the same amount of moisture as Filter C, and it could be completely regenerated by 40ºC air. Filter B didn t have a good ability of the moisture adsorption though it contained WSS. The amount of contained WSS was supposed to be less than that of Filter A. This cyclic test showed that Filter A had the best performance for the moisture adsorption in this condition. However, this amount was not enough for a dehumidifying in the humid season in Tokyo. So we must improve the adsorption ability of this filter. In the next section, the numerical calculation program for Filter A was constructed by using the result of this cyclic test.

Temp. [ o C] Adsorption amount [g] 45 40 35 30 1 25 100 80 60 RH Temp. Term A Filter C Filter D Term B Term A Term B 40 Filter A Filter B 0 0 30 60 90 1 150 180 - Elapsed time [min] Figure 10: The results of weight changes on the short-term cyclic test when the air flow rate was 24m 3 /hr. 80 65 50 35 RH [%] 4. NUMERICAL SIMULATION MODEL Feasibility study of the desiccant wheel containing WSS (Filter A) was simulated with a numerical model shown in Fig.11. It was assumed that heat and mass transfer occurred at the same time at each element of the honeycomb. In addition, a micro element was replaced by the slab model. Equations of heat and mass transfer were solved by dividing a micro element into 5 parts along the flowing direction (z-direction). A desiccant wheel Ads Re Each micro element L z Modeling L T ain x ain u a Air ρ a m ad Desiccant material T d Q h x a T a a a α s a d T aout x aout u a Z-direction dz Figure 11: Numerical simulation models In the airflow path, the pressure and the velocity of air were assumed to be constant. And advection flow was singly considered in the one-dimensional direction. Furthermore, heat and mass transfer in the desiccant material was neglected. It was assumed that the distribution of temperature and adsorption amount was homogeneous in the direction of thickness.

The dominant equations are as follows: <Mass balance at the layer of air> x x md ρ a + ρ aua + z aa = 0 (1) <Mass balance at the adsorption layer> q mad = ρ d ad (2) <Heat balance at the layer of air> Ta Ta α s ρ acpa + ρ auacpa + ( Ta z aa Td ) = 0 (3) <Heat balance at the adsorption layer> Td q α s ρ d cpd = ρ d qh + ( Ta ad Td ) (4) <Boundary conditions> x = x ain, T a = Tain at z = 0 <Initial conditions> x = x 0, T a = Tain, T d = Tain at t = 0 <Symbols> a: thickness [m], c p : specific heat [kj/kg/k], L: length [m], m: mass transfer amount [kg/m 2 /s], q h : heat of adsorption [W/m 2 ], q: adsorption amount [kg/kg], T: temperature [ºC], t: time [s], u: velocity [m/s], x: absolute humidity [kg/kg], z: position of z-axis direction [m] αs: heat transfer coefficient [W/(m 2 K)], ρ: density [kg/(m 3 )] <Subscripts> a: air, d: desiccant, in: inlet, out: outlet, s: surface, 0: initial condition,ad: adsorption 5. RESULTS AND DISCUSSION Figure 12 shows the comparison of the results of the numerical simulation with those of the experimental measurement about the temperatures of the inlet and the No. 2 point (about 6 cm from the filter s entrance) in Fig. 9, and the inlet and the outlet absolute humidity. As a result, it was confirmed that this numerical model could reproduce the temperature rising immediately after the start of ventilating. And a falling tendency of temperature was approximately reproduced. Furthermore, when the filter length was changed in this simulation, the half length of the 0mm-filter resulted in 75% of the total adsorption amount. It meant the latter half of the filter didn t fully contribute to the adsorption. Next, by using this Filter A model, the outlet absolute humidity was calculated according to the changes of the air flow rates. It was assumed that the diameter of the desiccant wheel was 900 mm and the length was 100 mm. Adsorbing condition (T: 30ºC, AH:.1 g/kg) and regenerating condition (T: 40ºC, AH: 12.6 g/kg) recurred every 6 minutes. The result of the numerical simulation is shown in Fig. 13. The outlet humidity became lower with the reduction of the air flow rates.

Temperature [oc] 45 40 35 30 25 15 No.2-T (Experimental) No.2-T (Numerical) Inlet-T (Experimental) Inlet-AH (Experimental) Outlet-AH (Experimental) Outlet-AH (Numerical) 0 15 30 45 60 75 90 Elapsed time [min] Figure 12: The results of the numerical simulation and the experimental measurement 40 35 30 25 15 10 Absolute humidity [g/kg] Absolute humidity [g/kg] 22 18 16 14 12 10 0 6 12 18 24 Elapsed time [min] Inlet 0.3 m/s 0.6 m/s 0.9 m/s 0.12 m/s Figure 13: Outlet absolute humidity predicted by the numerical simulation with the changes of the air flow rates when the diameter of the desiccant wheel is 900 mm. 6. CONCLUSION This study shows that Wakkanai siliceous shale is introduced as a new desiccant material. The filter containing the shale can be regenerated by using 40ºC air from the experiment. Thus, an exhaust heat from the refrigerator of the ice storage is reasonable to regenerate this filter. However, the adsorption amount is still the pending issue. REFERENCES Handbook of the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan (13 th edition), Vol. 5, 18-19 (01) Japan Meteorological Agency: Statistical information of previous meteorological data, Available from: (http://www.jma.go.jp/, in Japanese)