Reliable Pressure Measurement with Remote Diaphragm Seals in Cold Weather Applications



Similar documents
1.1 Fill fluids. Rosemount DP Level Fill Fluid Specifications July Technical Note , Rev DB

Rosemount 1199 Submersible Seal

Rosemount 1199 Submersible Seal

Rosemount D Solids Scanners for Bulk Solids Inventory and Financial Reporting

EMERSON S ROSEMOUNT PROJECT MANAGEMENT OFFICE. Delivering project success for your instrumentation

Replacing Displacers with Guided Wave Radar

Rosemount 333 HART Tri-Loop

Rosemount 333 HART Tri-Loop

THE WORLD'S FIRST WIRELESS GUIDED WAVE RADAR

Techniques for Interconnecting Smart Wireless Gateways to ProSoft RadioLinx Devices

LEVEL AND VOLUME MEASUREMENTS OF BULK SOLIDS

Import the Gateway Certificate to the Browser

Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Chambers

Quick Start Guide , Rev DA March Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

Smart Wireless Solutions. Intelligent Well Production Starts Here

Rosemount 708 Wireless Acoustic Transmitter

Rosemount DP Level Transmitters and 1199 Diaphragm Seal System

Rosemount Manifolds. Product Data Sheet August , Rev PE. Factory assembled, leak-tested, and calibrated

Best Practices for Reducing Transmitter Life Cycle Costs

Monitoring Water Quality For Today s Demanding World

Rosemount 752 FOUNDATION fieldbus Remote Indicator

High Temperature Diaphragm Seal. Measuring process pressure at 600 o C

Quick Start Guide , Rev DA June Emerson Smart Wireless Gateway 1410

Level Instrumentation for the Refining Industry

Rosemount 5300 and 5400 Series Terminal Compartment Spare Part Instruction

Density Measurement. Technology: Pressure. Technical Data Sheet INTRODUCTION. S min =1.0 S max =1.2 CONSTANT LEVEL APPLICATIONS

Model 3051 Pressure Transmitter with HART Protocol

SupportNet Technical Services

OpenEnterprise. Lifecycle Services

Rosemount 248 Wireless Temperature Transmitter

Toroidal Conductivity Sensor

Steam System Best Practices Condensate System Piping

Rosemount 214C Temperature Sensors

Mobrey Ultrasonic. MSP900SH Level and MSP900FH Flow Transmitters. Product Data Sheet February 2015 IP2032, Rev BA

BaseCal 3. BaseCal, the web-based performance calculation tool for Diaphragm Seals

Baumann Flexsleev Sanitary Control Valve

Integrated Custom Systems

Enhance Your Oil & Gas Production and Transmission Operations

Rosemount 751 Field Signal Indicator

Liquid level measurement using hydrostatic pressure and buoyancy

Introduction Insurance Industry Overview and Major Trends

Diaphragm Seal with flush diaphragm and flange acc.to SMS. Completed with pressure gauge in stainless steel, liquid filled or pressure transmitter

Micro Motion ELITE CMFS Series Meter

Emerson Smart Wireless Gateway

Cooling system components, removing and installing

Roxar Electrical Resistance (ER) Probes 2 Retrievable System

Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement.

Natural Gas Solutions

Many Products...One Source

STATFlow. Direct-to-Drain System. For use with STATIM 2000 and STATIM 5000 Autoclaves. Installation Guide and Operator s Manual

Emerson s Smart Wireless and WIB Requirements

The DL8000 Preset Controller. The Ideal Device for Controlling and Measuring the Loading of Liquid Hydrocarbons into Transporting Tankers

Wireless Field Data Backhaul

SLAM-SHUT VALVE. Type OSE. Europe, Middle East, Africa and Asia Pacific Documents Only. Process Management TM

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves

Simulation of Process Conditions for Calibration of Fisher Level Controllers and Transmitters Supplement to 249 Sensor Instruction Manuals

ROC800-Series Advanced Pulse Module

Brooks Models SLA5850, SLA5851, SLA5853 Mass Flow Controllers and Models SLA5860, SLA5861, SLA5863 Mass Flow Meters

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Rosemount 3095 MultiVariable Transmitter with MODBUS Protocol ProductDiscontinued

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

SELECTING PRESSURE TRANSMITTERS TO IMPROVE CENTRIFUGAL COMPRESSOR SAFETY & EFFICIENCY

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

T0118 T2118 T3118. Instruction Manual

Type 119 Control Valve

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

Bristol Series 5453 Indicating Pneumatic Pressure Controllers/Transmitters

D A cost effective monitor that meets your clinical needs VISTA 120

Typical Aluminum GFM Mass Flow Meter

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Trunnion-Design Ball Valves

Baumann Mikroseal Control Valve

The Unique Accelabar Flow Meter

Rosemount 2088 Absolute and Gage Pressure Transmitter

Take total control of your HVAC system with cost-saving flow and thermal energy meters

Micro Motion Model D and DL Coriolis Flow and Density Meters

DUPONT PERFORMANCE POLYMERS Joint Design: A Critical Factor in Strong Bonds GENERAL GUIDELINES FOR ULTRASONIC, VIBRATION AND SPIN WELDING

The Do s and Don ts of Pressure Transducers

Mechanical Seal Piping Plans

Mobrey Hydrastep and Hydratect

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

RGC-IR Remote Gas Calibrator for IR400

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

Evolving your plant with Field Digital Solutions

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

Type 92S Pilot-Operated Steam Regulator

Submersion/Insertion Toroidal Sensor

Rosemount 2088 Absolute and Gage Pressure Transmitter

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE

A Practical Overview of Level Measurement Technologies

S-series DeviceNet Interface Card

Centricut plasma torches and consumables for Whitney

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

Baumann Way Bronze or Stainless Steel Control Valve

Rosemount 3051 Pressure Transmitter

Fisher 657 and 667 Diaphragm Actuators

What s the Difference? 2 Pipe vs 4 Pipe Fan Coil

Transcription:

Reliable Pressure Measurement with Remote Diaphragm Reliable Pressure Measurement with Remote Diaphragm Introduction............................................................... page 1 Rosemount 3051S Thermal Range Expander................................... page 2 Rosemount Thermal Optimizer............................................... page 4 Heat trace................................................................. page 5 Technology comparison..................................................... page 6 1.1 Introduction Making a pressure or DP Level measurement of a hot process in a cold ambient environment has some challenges associated with it. A Rosemount transmitter with Rosemount 1199 Diaphragm Seal from Emerson can be directly connected to processes up to 401 F (205 C); above that temperature, either an extension is required for the Rosemount 1199 Direct Mount Seal, or a remote mount seal with capillary is needed. A sufficiently hot process would require the use of a high temperature fill fluid such as Silicone 704, Silicone 705, or Rosemount UltraTherm 805. These high temperature fill fluids are stable in high temperature processes. Unfortunately, these high temperature fill fluids are challenged by low ambient temperature environments because as the temperature decreases, the response time increases and the measurement can eventually become nonresponsive. Emerson offers multiple solutions to the challenge of taking pressure or DP Level readings in a system that has a hot process temperature combined with a low ambient temperature. The methods discussed here apply to the Rosemount Thermal Range Expander, the Rosemount Thermal Optimizer, and heat tracing.

Reliable Pressure Measurement with Remote Diaphragm Technical Note 1.2 Rosemount 3051S Thermal Range Expander The Rosemount 3051S Thermal Range Expander is a seal system that uses an intermediate diaphragm to separate two different fill fluids; this allows each of the fill fluids to operate within its optimal temperature range. Figure 1-1. Rosemount 3051S Tuned-System Assembly with a Thermal Range Expander B A C A. Process diaphragm B. Intermediate seal C. Primary fill fluid D. Secondary fill fluid D The primary fill fluid, which is closer to the hot process, is designed to operate in the high process temperature, while the secondary fill fluid, located on the other side of the intermediate diaphragm, is designed to operate in the colder ambient temperature. This allows the Thermal Range Expander to cover ambient temperatures as low as -103 F (-75 C), and process temperatures up to 770 F (410 C), with comparable response time to a system that only uses low temperature fill fluid. Figure 1-2. Temperature Limits Standard Capillary Thermal Range Expander Note The top two bars above illustrate the temperature limits of a single fill fluid system. The bottom two bars represent two specific temperature ranges with the Thermal Range Expander. 2 Reliable Pressure Measurement with Remote Diaphragm

Reliable Pressure Measurement with Remote Diaphragm The Thermal Range Expander is available on all Rosemount 3051SAL (Scalable Advanced Level) systems including Electronic Remote Sensor (ERS ) Systems, Tuned-System Assemblies, Balanced Systems, single capillary, and single direct mount configurations. It is also available in both all-welded or welded-repairable construction types and with the following seal types: Flush Flanged Seal (FF) Extended Flanged Seal (EF) Flanged Seal (RF) Threaded Seal (RT) Flushed Flanged Ring Type Joint (FC) Ring Type Joint Flanged (RC) UltraTherm 805 is the fill fluid that allows the Thermal Range Expander to handle high temperatures up to 770 F (410 C) and it is only available in a Thermal Range Expander system. Figure 1-3. Thermal Range Expander Configurations Direct mount in-line Thermal Range Expander ERS System with Thermal Range Expander connections Reliable Pressure Measurement with Remote Diaphragm 3

Reliable Pressure Measurement with Remote Diaphragm Technical Note 1.3 Rosemount Thermal Optimizer The Thermal Optimizer is a single fill seal system that uses the heat from a hot process to keep the fill fluid within its operating temperature range. There is a patented heating element enclosed inside the Thermal Optimizer that helps heat transfer throughout the Thermal Optimizer, as shown in Figure 1-4. Figure 1-4. Thermal Optimizer and Thermal Optimizer Cutaway A A. Patented heating element This allows for a reliable pressure measurement in applications with increased process temperatures in low ambient temperature climates. By maintaining an optimal temperature, the fill fluid is prevented from becoming too viscous and this allows for fast time response with excellent accuracy. The Thermal Optimizer is only available for Rosemount In-line pressure transmitter configurations (3051ST, 3051T, 2051T, or 2088 models), but when coupled with Rosemount 3051S ERS System, it is also capable of measuring differential pressure. Figure 1-5. ERS System with Thermal Optimizer Connections 4 Reliable Pressure Measurement with Remote Diaphragm

1.4 Heat trace Reliable Pressure Measurement with Remote Diaphragm Traditionally, when high temperature fill fluids are used to measure the pressure of the hot process and then the capillaries would be kept warm with heat tracing so the fill fluid can operate. Heat tracing can refer to either electrical heat tracing or steam heat tracing. Steam heat tracing uses steam that may or may not be routed from somewhere else in the plant. Steam heat tracing has many disadvantages such as potential steam leaks, poor temperature control, high operating costs, trap maintenance, and water treatment costs. Electrical heat tracing uses a cable connected to a power source to generate heat to warm the capillaries; a continuous flow of electricity is required to keep the heat traces working. Heat tracing can allow a consistent pressure measurement if it can always keep the capillaries at the same temperature, but there will be a shift in the output as the heat tracing is turned on or off. In order to keep the temperature constant, a temperature controller is required. Even with a temperature controller heat tracing can still cause problems if there are separate heating elements on the upper and lower seals. Separate heating elements turn on and off independently, so the heat tracing on one side could be turned on while the other side is turned off making the response time different for each side. Using heat tracing is expensive and can be complicated to install. If the heat tracing loses electricity it will fail and can cause an inaccurate reading on the pressure transmitter which could lead to catastrophic failure. On top of that, heat tracing can be difficult to remove and replace if the heat tracing fails. Alternatively, wet/dry legs can be used and heat traced instead of remote seals with capillaries. Wet/dry legs in a cold ambient environment would still require heat tracing and it's associated complications, which is in addition to the complications of wet/dry legs themselves such as draining and refilling the legs. Figure 1-6. Balanced System with Heat Trace Reliable Pressure Measurement with Remote Diaphragm 5

Reliable Pressure Measurement with Remote Diaphragm Technical Note 1.5 Technology comparison While all three options are designed for similar applications, there are some key differences that will help determine which is better for different applications. Use Table 1-1 to compare the technologies and determine which works best for your application. Table 1-1. Comparison of Thermal Range Expander, Thermal Optimizer, and Heat Trace Characteristic Thermal Range Expander Thermal Optimizer Heat trace Temperature Range (above atmospheric pressure) -103 F (-75 C) Ambient to 770 F (410 C) Process Refer to Figure 1-7. -76 F (-60 C) Ambient to 698 F (370 C) Process Refer to Figure 1-7. Dependent upon customer controlled temperature Pressure Range 1500 psi (10342 kpa) Max Working Pressure 4000 psi (27579 kpa) Max Working Pressure Determined by configuration or flange rating Transmitter Type Coplanar (AP, GP, DP) In-line (AP, GP,DP with ERS) In-line (AP,GP, DP with ERS) Any transmitter with capillaries Connection Type Direct Mount Remote Mount Direct Mount Remote Mount Technology Intermediate diaphragm separating a high temperature fill fluid and a low temperature fill fluid. Requires single 3051SAL Level Transmitter System. Copper tube insulates high temperature fill fluid, requires hot process to maintain the fill fluids temperature. Limited by hot ambient environments. Requires: In-line transmitter Thermal Optimizer seal system Uses steam or electricity to heat fill fluid inside capillaries. Requires large installation and high ongoing maintain cost. Requires: Transmitter Remote Seal System Heat trace Temperature controller Power supply Recommended Applications Process temperature above 401 F (205 C) Ambient temperature below 32 F (0 C) Process pressure below 1500 psi (10342 kpa) Process temperature above 401 F (205 C) Ambient temperature below 32 F (0 C) Process pressure above 1500 psi (10342 kpa) Pressures up to 10,000 psi Note The Thermal Range Expander temperature range depends on the combination of primary, secondary fill fluids, and process temperature; see Figure 1-7 on page 7. 6 Reliable Pressure Measurement with Remote Diaphragm

Reliable Pressure Measurement with Remote Diaphragm Figure 1-7. Process Temperature Ranges (1)(2) (1) The Thermal Range Expander is designed to transfer heat from the process to the intermediate isolator; therefore, the ambient temperature limit is interdependent on the process temperature. (2) It is recommended to not violate the lower temperature limits of the secondary fill fluid. Reliable Pressure Measurement with Remote Diaphragm 7

Global Headquarters Emerson Process Management 6021 Innovation Blvd Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com North America Regional Office Emerson Process Management 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com Latin America Regional Office Emerson Process Management 1300 Concord Terrace, Suite 400 Sunrise, Florida, 33323, USA +1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com Europe Regional Office Emerson Process Management Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland +41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com Asia Pacific Regional Office Emerson Process Management Asia Pacific Pte Ltd 1 Pandan Crescent Singapore 128461 +65 6777 8211 +65 6777 0947 Enquiries@AP.EmersonProcess.com Middle East and Africa Regional Office Emerson Process Management Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates +971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com Standard Terms and Conditions of Sale can be found at: www.rosemount.com\terms_of_sale. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are registered trademarks of Rosemount Inc. ERS, Scalable, Tuned-System, and UltraTherm are trademarks of Rosemount Inc. SYLTHERM is a trademark of Dow Corning Corporation. All other marks are the property of their respective owners. 2015 Rosemount Inc. All rights reserved.