00 IS Catalog Page Introduction... 47 Transmitter (8 V entity parameter) KFD-CR-Ex1.30.00 (-wire transmitter)... 48 KFD-CR-Ex1.30.300 (- or 3-wire transmitter)... 49 KFD-CR-Ex1.30.300 90C (- or 3-wire, sink mode output)... 50 KFD-CR-Ex1.30.340 (- or 3-wire, 4-0 ma input, 0-0 ma output)... 51 KFD-CV-Ex1.30.305 (- or 3-wire, 0/4-0 ma input, 0/1-5 V output)... 5 KFD-CV-Ex1.30.310 (- or 3-wire, 0/4-0 ma input, 0/-10 V output)... 53 Transmitter (0 V Entity Parameter) KFD-CR-Ex1.0.00 (-wire, 4-0 ma input and output)... 54 KFD-CR-Ex1.0.300 (- or 3-wire, 0/4-0 ma input and output)... 55 SMART Transmitter (0-1 khz) KFD-STC1-Ex1 (SMART, 4-0 ma input and output)... 56 KFD-STV1-Ex1 (SMART, 4-0 ma input, 1-5 V output)... 57 SMART Transmitter (0-40 khz) KFD-STC3-Ex1 (4-0 ma input and output)... 58 KFD-STV3-Ex1-1 (4-0 ma input, 1-5 V output)... 59 KFD-STV3-Ex1- (4-0 ma input, -10 V output)... 60 HART Transmitter KFD-STC4-Ex1 (dual-channel, 4-0 ma input and output)... 61 KFD-STC4-Ex (dual-channel, 4-0 ma input and output)... 6 KFD-STC4-Ex-Y7195 (dual-channel, sink mode output)... 63 KFD-STC4-Ex1.0 (single-channel, outputs)... 64 KFD-STC4-Ex1.0-Y716 (single-channel, sink mode output)... 65 46 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
00 IS Catalog Introduction Transmitter power supplies transfer 4-0 ma signals from transmitters in hazardous areas and supply them with power. They deliver an electrical signal that is proportional to a measured value such as temperature, pressure or flow from hazardous areas to safe areas. The power supply and signal are transferred through the same conductors in -wire transmitters allowing only 4-0 ma signals. The power supply and signal are isolated from one another in 3-wire transmitters allowing for 0 ma signals. These ma signals can then be repeated on the safe side of the isolator or can be converted to other usable signals such as voltage. SMART transmitter power supplies repeat the transmitter current in addition to a digital signal, which is modulated onto the 4-0 ma signal. SMART transmitters can be calibrated remotely. This allows the transmitter s span and zero set point to be modified in the safe area and information on scheduled maintenance or statistical data to be accessed on-line. SMART transmitters normally operate in a -wire mode. This -wire connection is usually interfaced with a hand-held terminal or a PC for data transmission or accumulation. P+F SMART transmitter power supplies are shipped with terminal blocks to allow easy access to communication leads. SMART transmitters from ABB, Bailey, Chessel, Edress+Hauser, Fisher- Rosemount, Foxboro, Honeywell, Smar and Yokogawa have been successfully tested with P+F isolators. Please note that some higher communication frequencies require use of the KFD-STC3- Ex1 or the KFD-STV3-Ex1. These isolators are rated for frequencies up to 40 khz. Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 47
00 IS Catalog Transmitter Power rail or terminals 11+, 1-0-35 VDC 1.6 W Input (intrinsically safe) Terminals 1+, 3- Input Signal 4-0 ma at 0 ma 17.6 VDC Output (not intrinsically safe) Terminals 7-, 8+, 9-4-0 ma 0 VDC Load 1 kω < 0 µa ss KFD-CR-Ex1.30.00 Rise time ±10 µa nonlinearity, load fluctuations ± 0. µa/ºc range 0-60ºC 50 µs (at 50 Ω load) Analog Input Transmitters -wire transmitter power supply 1 kω max. output load 3-way isolation Suitable for Division mounting repeats the 4-0 ma signal from a - wire transmitter in hazardous areas. It has an open circuit voltage of 5 V with a minimum of 17.6 V at 0 ma. The transmitter must be connected to terminals 1 and 3 so the 4-0 ma transmitter current flows into the measurement circuit via terminal 3. A maximum load of 1 kω can be connected between terminals 7 and 8. Entity Parameters Terminals 1+, 3- FM control drawing no. 116-019 Voltage V OC 9 V Current I SC 96.1 ma ) 0.13 µf 0.39 µf 1.05 µf ) 3.60 mh 15.79 mh 31.91 mh 107 x 0 x 115 Weight 3.5 oz. (100 g) CSA approvals available upon request -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CR-Ex1.30 00 7 48 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power rail or terminals 11+, 1-0-35 VDC 1.7 W Transmitter Input (intrinsically safe) Terminals 1+, -, 3 Input 0/4-0 ma (term. 1+, -) 16.5 V at 5 ma (term. 1+, 3) 13.6 V at 0 ma Input resistance (term. -, 3) 0 Ω Output (not intrinsically safe) Terminals 7-, 8+, 9-0/4-0 ma 0 VDC Load 1 kω 0 µa ss ±10 µa nonlinearity, load fluctuations ± 0. µa/ºc range 0-60ºC Rise time 50 µs Entity Parameters Terminals 1+, 3 -, 3 FM control drawing no. 116-019 Voltage V OC 8 V 4.4 V Current I SC 93 ma. ma Terminals 1+, 3 ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh Terminals -, 3 ) 1000 µf 3000 µf 8000 µf ) 67.8 mh 39 mh 597 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) CSA approvals available upon request -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CR-Ex1.30 300 KFD-CR-Ex1.30.300 - or 3-wire transmitter power supply 4 VDC power supply 1 kω max. output load 3-way isolation Suitable for Division mounting repeats a 0/4-0 ma signal from a - or 3- wire transmitter in hazardous areas. It also repeats a 0/4-0 ma current source signal. -wire transmitters are connected to terminals 1 and 3 so the 0/4-0 ma transmitter current flows to terminal 3. A minimum of 13.6 V at 0 ma is available between terminals 1 and 3. The power supply is available at terminals 1 and in 3-wire transmitters with the transmitter current flowing to terminal 3. Approximately 16.5 V is available at 5 ma between terminals 1 and for the transmitter. Terminals and 3 are used for connections in applications requiring repeating source currents. This configuration has no terminal 1 connections. A maximum load of 1 kω can be connected between terminals 7 and 8. 3 3 3 I 3 8 7 9 + 11 1 4VDC Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 49
00 IS Catalog Transmitter Power Rail or terminals 11+, 1-0-35 VDC 1.7 W Analog Input Transmitters KFD-CR-Ex1.30.300 90C - or 3-wire transmitter power supply 4 VDC power supply 1 kω max. output (sink mode) 3-way isolation Suitable for Division mounting repeats the 4-0 ma signal from a - or 3- wire transmitter in hazardous areas. It also repeats a 4-0 ma current source signal. This isolator is specially designed with a sink mode output to work with a Moore Products SAM input card that supplies (sources) current. Two-wire transmitters are connected to terminals 1 and 3 so the 4-0 ma transmitter current flows to terminal 3. A minimum of 13.6 V at 0 ma is available between terminals 1 and 3. The power supply is available on terminals 1 and in 3-wire transmitters with the transmitter current flowing to terminal 3. Approximately 16.5 V is available at 5 ma between terminals 1 and for the transmitter. Terminals and 3 are used for connections in applications requiring repeating source currents. This configuration has no terminal 1 connections. A maximum load of 1 kω can be connected between terminals 8-9. Input (intrinsically safe) Terminals 1+, -, 3 Input 0/4-0 ma (term. 1+, -) 16.5 V at 5 ma (term. 1+, 3) 13.6 V at 0 ma Input resistance (term. -, 3) 0 Ω Output (not intrinsically safe) Terminals 8+, 9-4-0 ma Load 1 kω (with 475 Ω external resistor) 0 µa ss ±10 µa nonlinearity, load fluctuations ± 0. µa/ºc range 0-60ºC Rise time 50 µs Entity Parameters Terminals 1+, 3 -, 3 FM control drawing no. 116-019 8 V 4.4 V 93 ma. ma Terminals 1+, 3 ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh Terminals -, 3 ) 1000 µf 3000 µf 8000 µf ) 67.8 mh 39 mh 597 mh *Consult factory for additional certifications and entity parameters 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +60ºC (-4ºF to +140ºF) 3 3 3 I 3 Safe Area or Div KFD-CR-Ex1.30 300 90C 8 7 9 + 11 1 4VDC 50 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power Rail or terminals 11+, 1-0-35 VDC 1.9 W Transmitter Input (intrinsically safe) Terminals 1+, -, 3 Input 0/4-0 ma (term. 1+, -) 16.5 V at 5 ma (term. 1+, 3) 13.6 V at 0 ma Input resistance (term. -, 3) 0 Ω Output (not intrinsically safe) Terminals 7-, 8+, 9-0-0 ma 0 VDC Load 1 kω 0 µa ss ±10 µa nonlinearity, load fluctuations ± 0.5 µa / ºC range 0-60ºC Rise time 50 µs Entity Parameters Terminals 1+, -, 3 FM control drawing no. 116-019 8 V 4.4 V Current I oc 93 ma. ma Terminals 1+, 3 ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh Terminals -, 3 ) 1000 µf 3000 µf 8000 µf ) 67.8 mh 39 mh 597 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) CSA approvals available upon request -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CR-Ex1.30 340 KFD-CR-Ex1.30.340 - or 3-wire transmitter power supply 4 VDC power supply 4-0 ma input 0-0 ma output Suitable for Division mounting repeats a 4-0 ma signal from a - or 3-wire transmitter in hazardous areas. It also repeats a 4-0 ma current source signal. Two-wire transmitters are connected to terminals 1 and 3 so the 4-0 ma transmitter current flows into terminal 3. A minimum of 13.6 V at 0 ma is available between terminals 1 and 3. The power supply is available on terminals 1 and in 3-wire transmitters with the transmitter current flowing to terminal 3. Approximately 16.5 V is available at 5 ma between terminals 1 and for the transmitter. Terminals and 3 are used for connections in applications requiring repeating source currents. This configuration has no terminal 1 connections. A maximum load of 1 kω can be connected between terminals 8 and 9. 3 3 3 I 3 8 7 9 + 11 1 4VDC Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 51
00 IS Catalog Transmitter Power Rail or terminals 11+, 1-0-35 VDC 1.3 W Input (intrinsically safe) Terminals 1+, -, 3 Input signal 0/4-0 ma (term. 1+, -) 15.3 V at 5 ma (term. 1+, 3) 16.8 V at 0 ma Input resistance (term. -, 3) 56 Ω Output (not intrinsically safe) Terminals 7, 8+, 9-, 10+ 0/1-5 V Load kω 5 mv pp Analog Input Transmitters KFD-CV-EX1.30.305 - or 3-wire transmitter power supply 0/4-0 ma input 0/1-5 V output Suitable for Division mounting repeats a 0/4-0 ma signal from a - or 3- wire transmitter in hazardous areas and converts it into a voltage output. It also repeats a 0/4-0 ma signal from a current source. Two-wire transmitters are connected to terminals 1 and 3 so the 0/4-0 ma transmitter current flows to terminal 3. A minimum of 16.8 V at 0 ma is available between terminals 1 and 3. The power supply is available on terminals 1 and in 3-wire transmitters with the transmitter current flowing to terminal 3. Approximately 15.3 V is available at 5 ma between terminals 1 and for the transmitter. Terminals and 3 are used for connections in applications requiring repeating source currents. This configuration has no terminal 1 connections. The measurement current is converted into a proportional voltage signal once transmitted to the output. The output circuit has two sets of terminal blocks for the parallel connection of two voltage measurement circuits. The voltage measurement circuits must have a resistance of at least kω. 5 mv 0.005% of span/ ºC Rise time 5. ms Entity Parameters BASEEFA no. 3 3 3 I 3 Ex 97D085 6 V 93 ma Explosion group II A II B II C ) 0.79 µf 0.97 µf 0.099 µf ) 33.6 mh 1.6 mh 4. mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CV-Ex1.30 305 8 7 9 + 11 1 4VDC 0/1-5V 5 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power Rail or terminals 11+, 1-0-35 VDC 1.3 W Transmitter Input (intrinsically safe) Terminals 1+, -, 3 Input signal 0/4-0 ma (term. 1+, -) 15.3 V at 5 ma (term. 1+, 3) 16.8 V at 0 ma Input resistance (term -, 3) 56 Ω Output (not intrinsically safe) Terminals 7-, 8+, 9-, 10+ 0/-10 V Load kω 10 mv pp Rise time 3 3 3 I 3 10 mv ± 0.005% of span/ºc 5. ms Entity Parameters BASEEFA no. Ex 97D085 6 V 93 ma Explosion group IIA IIB IIC Max. external capacitance 0.79 µf 0.97 µf 0.099 µf Max. external inductance 33.6 mh 1.6 mh 4. mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CV-Ex1.30 310 7 8 0/-10V KFD-CV-Ex1.30.310 - or 3-wire transmitter power supply 0/4-4-0 ma input 0/-10 V output Suitable for Division mounting repeats a 0/4-0 ma signal from a - or 3- wire transmitter in hazardous areas and converts it into a voltage output. It also repeats a 0/4-0 ma current source signal. Two-wire transmitters are connected to terminals 1 and 3 so the 0/4-0 ma transmitter current flows to terminal 3. A minimum of 16.8 V at 0 ma is available between terminals 1 and 3. The power supply is available on terminals 1 and in 3- wire transmitters with the transmitter current flowing to terminal 3. Approximately 15.3 V is available at 5 ma between terminals 1 and for the transmitter. Terminals and 3 are used for connections in applications requiring repeating source currents. This configuration has no terminal 1 connections. The measurement current is converted into a proportional voltage of 0/-10 V once transmitted to the output. The output circuit has two sets of terminal blocks to allow the parallel connection of two voltage measurement circuits. The voltage measurement circuits must have a resistance of at least kω. 11 + 1 4VDC Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 53
00 IS Catalog Transmitter Power Rail or terminals 11+, 1-0-35 VDC 1.6 W Input (intrinsically safe) Terminals 1+, 3- Input signal 4-0 ma 16 VDC at 0 ma Output (not intrinsically safe) Terminals 7-, 8+, 9-4-0 ma 0 VDC Load 1 kω 0 µa ss Analog Input Transmitters KFD-CR-Ex1.0.00 -wire transmitter power supply 4 VDC power supply 1kΩ max. output load 3-way isolation Special design with low entity parameters Suitable for Division mounting repeats the 4-0 ma signal from a -wire transmitter in hazardous areas. This isolator is specially designed for transmitters with entity parameters less than 8 V. The open circuit voltage of the isolator is 18 V with a minimum of 16 V at 0 ma. The transmitter must be connected to terminals 1 and 3 so the 4-0 ma transmitter current flows into the measurement circuit across terminal 3. A maximum load of 1 kω can be connected between terminals 8-9. ±10 µa nonlinearity, load fluctuations ± 0. µa/ºc range 0-60ºC Rise time 50 µs Entity Parameters Terminals 1+, 3- FM control drawing no. 116-019 0 V 93 ma ) 0.34 µf 1.01 µf.70 µf ) 4.18 mh 16.84 mh 34.3 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) CSA approvals available upon request -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CR-Ex1.0 00 7 4VDC 54 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power Rail or terminals 11+, 1-0-35 VDC 1.7 W Transmitter Input (intrinsically safe) Terminals 1+, -, 3 Input 0/4-0 ma (term. 1+, -) 16.5 V at 5 ma (term. 1+, 3-) 13.6 V at 0 ma Input resistance (term. -, 3) 0 Ω Output (not intrinsically safe) Terminals 8+, 9-0-0 ma 0 VDC Load 1 kω 0 µa ss ±10 µa nonlinearity, load fluctuations ± 0. µa/ºc range 0-60ºC Rise time 50 µs Entity Parameters FM control drawing no. 116-019 Terminals 1+, 3 -, 3 1+, -, 3 (V t ) 0 V 4.4 V 0 V (I t ) 93 ma. ma 115 ma Terminals 1+, -, 3 ) 0.34 µf 1.01 µf.70 µf ).65 mh 11.35 mh.1 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) CSA approvals available upon request -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-CR-Ex1.0 300 KFD-CR-Ex1.0.300 - or 3-wire transmitter power supply 4 VDC power supply 1 kω max. output load Special design with low entity parameters Suitable for Division mounting repeats a 0-0 ma signal from a - or 3-wire transmitter in hazardous areas. It can also repeat a 0-0 ma signal from a current source. This isolator is specially designed for transmitters with entity parameters of less than 8 V. Two-wire transmitters are connected to terminals 1 and 3 so the 0-0 ma transmitter current flows to terminal 3. A minimum of 1 V at 0 ma exist between terminals 1 and 3. The power supply is available on terminals 1 and in 3-wire transmitters with the transmitter current flowing to terminal 3. Approximately 16 V are available at 5 ma between terminals 1 and for the transmitter. Terminals and 3 are used for connections in applications requiring repeating source currents. This configuration has no terminal 1 connections. 3 3 3 I 3 9 7 + 11 1 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 55
00 IS Catalog SMART Transmitter Power Rail or terminals 7+, 8-0-35 VDC 1. W Input (intrinsically safe) Terminals 1+, 3- Input 4-0 ma at 0 ma 16.5 VDC at 0 ma Output (not intrinsically safe) Terminals 9+, 10-, 11+ 4-0 ma, max. load 500 Ω 75 µa ss Analog Input Transmitters KFD-STC1-Ex1 4 VDC power supply SMART communication to 1 khz (-1dB) 4-0 ma output Suitable for Division mounting repeats the 4-0 ma signal from a -wire transmitter inside hazardous area. This isolator can also repeat a maximum 1 khz digital signal that is modulated on the 4-0 ma signal. A processing system, field device or hand-held terminal generates this digital information, which is transferred bidirectionally by the isolator. This allows the operator to interrogate and reprogram the transmitter from a safe area using uncertified communication equipment. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF- STP-BU and KF-STP-GN terminals with test probe access holes for the easy interface of hand-held terminals. 10 µa 0.00% of span/ºc Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 ma pp Signal 0 Hz to 1 khz (-1 db) Freq. range (50 Ω load) Safe area into hazardous area Band width at 1 V pp Signal 1 Hz to 1 khz (-1 db) Rise/fall time 40 µs/40 µs Entity Parameters Terminals 1+, 3- FM control drawing no. 116-019 8 V 93 ma ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh 107 x 0 x 115 mm Weight 150 g (5.3 oz.) Safe Area or Div KFD-STC1-Ex1-0ºC to +60ºC (-4ºF to +140ºF) 11 9 56 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power rail or terminals 7+, 8-0-35 VDC 1. W SMART Transmitter Input (intrinsically safe) Terminals 1+, 3- Input 4-0 ma 15.8 V at 0 ma Output (not intrinsically safe) Terminals 9+, 10-, +1 1-5 V 75 µa ss 10 µa 0.00% of span/ºc Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 ma pp Signal 0 Hz to 1 khz (-1 db) Freq. range (50 Ω load) Safe area into hazardous area Band width at 1 V pp Signal 1 Hz to 1 khz (-1 db) Rise/fall time 40 µs/40 µs Entity Parameters Terminals 1+, 3- FM control drawing no. 116-019 8 V 93 ma ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh 107 x 0 x 115 mm Weight 150 g (5.3 oz.) -0ºC to +60ºC (-4ºF to +140ºF) Safe Area or Div KFD-STV1-Ex1 KFD-STV1-Ex1 4 VDC power supply SMART communication to 1 khz (-1dB) 1-5 V output Suitable for Division mounting repeats the 4-0 ma signal from a -wire transmitter inside a hazardous area. This 4-0 ma current is converted into a 1-5 V signal. This isolator can also repeat a maximum 1 khz digital signal that is modulated on the 4-0 ma signal. A processing system, field device or hand-held terminal generates this digital information, which is transferred bidirectionally by the isolator. This allows the operator to interrogate and reprogram the transmitter from a safe area using uncertified communication equipment. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF-STP- BU and KF-STP-GN terminals with test probe access holes for the easy interface of handheld terminals. Note: Terminal 1 is placed across an internally applied capacitance. Active input cards, such as Foxboro FMB 18, can operate using this connection. 11 9 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 57
00 IS Catalog SMART Transmitter Power rail or terminals 7+, 8-0-35 VDC 1.7 W Input (intrinsically safe) Terminals 1+, 3- Input signal 4-0 ma 16.5 V @ 0 ma Output (not intrinsically safe) Terminals 9+, 10-, 11+ 4-0 ma, max. load 1 kω 0.05% output signal range Analog Input Transmitters KFD-STC3-Ex1 4 VDC supply SMART communication to 40 khz (-1dB) 4-0 ma output 3-way isolation Suitable for Division mounting repeats the 4-0 ma signal from a -wire transmitter inside the hazardous area. This isolator can also repeat a maximum 40 khz digital signal that is modulated on the 4-0 ma signal. A processing system, field device or hand-held terminal generates this digital information, which is transferred bidirectionally by the isolator. This allows the operator to interrogate and reprogram the transmitter from a safe area using uncertified communication equipment. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF-STP-BU and KF-STP- GN terminals with test probe access holes for the easy interface of hand-held terminals. 0.05% of output signal 0.00% of span/ºc Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 ma pp Signal 0 Hz to 40 khz (-1 db) Freq. range (50 Ω load) Safe area into hazardous area Band width at 1 V pp Signal 0 Hz to 40 khz (-1 db) Rise/fall time 10 µs/10 µs Entity Parameters Terminals 1+, 3- FM control drawing no. 116-019 8 V 93 ma ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh 107 x 0 x 115 mm Weight 150 g (5.3 oz.) -0ºC to +65ºC (-4ºF to +149ºF) Safe Area or Div KFD-STC3-Ex1 58 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power rail or terminals 7+, 8-0-35 VDC 1.7 W SMART Transmitter Input (intrinsically safe) Terminals 1+, 3- Input 4-0 ma 16.5 V at 0 ma Output (not intrinsically safe) Terminals 9+, 10-, 11+ 1-5 V, internal resistance 305 Ω 0.05% output signal range Freq. range (50 Ω load) Band width at 1 ma pp Signal Freq. range (50 Ω load) Band width at 1 V pp Signal 0.03% of output signal 0.00% of span/ºc Hazardous area into safe area 0 Hz to 40 khz (-1 db) Safe area into hazardous area 0 Hz to 40 khz (-1 db) Enity Parameters Terminals 1+, 3- FM control drawing no. 116-019 8 V 93 ma ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh 107 x 0 x 115 mm Weight 150 g (5.3 oz.) -0ºC to +65ºC (-4ºF to +149ºF) Safe Area or Div KFD-STV3-Ex1-1 KFD-STV3-Ex1-1 4 VDC supply SMART communication to 40 khz (-1dB) 1-5 V output 3-way isolation Suitable for Division mounting This single channel isolator powers and repeats the 4-0 ma signal from a -wire transmitter inside the hazardous area. This isolator can also repeat a maximum 40 khz digital signal that is modulated on the 4-0 ma signal. A processing system, field device or hand-held terminal generates this digital information, which is transferred bidirectionally by the isolator. This allows the operator to interrogate and reprogram the transmitter from a safe area using uncertified communication equipment. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF- STP-BU and KF-STP-GN terminals with test probe access holes for the easy interface of hand-held terminals. Note: Terminal 1 is placed across an internally applied capacitance. Active input cards, such as Foxboro FMB 18, can operate using this connection. Power Rail Connection Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 59
00 IS Catalog SMART Transmitter Power rail or terminals 7+, 8-0-35 VDC 1.7 W Input (intrinsically safe) Terminals 1+, 3- Input signal 4-0 ma 16.5 V at 0 ma Output (not intrinsically safe) Terminals 10-, 11+, +1-10 V, internal resistance 305 Ω 0.05% output signal range 0.03% of output signal 0.00% of span/ºc Analog Input Transmitters KFD-STV3-Ex1-4 VDC power supply SMART communication to 40 khz (-1dB) -10 V output 3-way isolation Suitable for Division mounting repeats the 4-0 ma signal from a -wire transmitter inside the hazardous area. This 4-0 ma current is repeated or converted into a or -10 V signal This isolator can also repeat a maximum 40 khz digital signal that is modulated on the 4-0 ma signal. A processing system, field device or hand-held terminal generates this digital information, which is transferred bidirectionally by the isolator. This allows the operator to interrogate and reprogram the transmitter from a safe area using uncertified communication equipment. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF- STP-BU and KF-STP-GN terminals with test probe access holes for the easy interface of hand-held terminals. Note: Terminal 1 is placed across an internally applied capacitance. Active input cards, such as Foxboro FMB 18, can operate using this connection. Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 ma pp Signal 0 Hz to 40 khz (-1 db) Safe area into hazardous area Band width at 1 ma pp Signal 0 Hz to 40 khz (-1 db) Rise/fall time 10 µs/10 µs Enity Parameters Terminals 1+, 3- FM control drawing no. 116-019 8 V 93 ma ) 0.14 µf 0.43 µf 1.14 µf ) 4.18 mh 16.83 mh 34.1 mh 107 x 0 x 115 mm Weight 150 g (5.3 oz.) -0ºC to +65ºC (-4ºF to +149ºF) Safe Area or Div KFD-STV3-Ex1- Power Rail Connection 60 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power Rail or terminals 14+, 15-0-35 VDC.5 W HART Transmitter Input (intrinsically safe) Terminals 1+, -, 3 Input 4-0 ma 16 V at 0 ma Output (not intrinsically safe) Terminals 7-, 8+ 4-0 ma Load resistance* 0-550 Ω 50 µa ss 0 µa 0.00% of span/ºc Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 ma pp Signal 0 Hz to 7.5 khz (-3 db) Freq. range (50 Ω load) Safe area into hazardous area Band width at 1 V pp Signal 300 Hz to 7.5 khz (-3 db) Rise/fall time 0µs/0µs Entity Parameters Terminals 1+, 3- UL control drawing no. 116-0173 5.4 V 88. ma ) 0.095µF 0.808 µf.88 µf ) 4. mh 17 mh 33 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +65ºC (-4ºF to +140ºF) Safe Area or Div KFD-STC4-Ex1 KFD-STC4-Ex1 HART compatible 4 VDC power supply 3 way isolation Suitable for Division mounting The SMART transmitter power supplies supply a -wire SMART transmitter within a hazardous area and transfer the analog 4-0 ma signal from the hazardous area to the safe area. Digital signals which can be modulated onto the analog signal, can also be transmitted bidirectionally on the hazardous or safe side. Hand-held terminals can be connected as shown in the block diagram. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF-STP-BU and KF-STP- GN terminals with test probe access holes for the easy interface of hand-held terminals. If the communicator is connected in the safe area, the load resistance must not be less than 30 Ω 8 7 3 3 3 I 3 4-0mA + 11 1 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 61
00 IS Catalog HART Transmitter Power Rail or terminals 14+, 15-0-35 VDC.5 W Input (intrinsically safe) Terminals 1+, 3-; 4+, 6- Input 4-0 ma 16 V at 0 ma Output (not intrinsically safe) Terminals 7-, 8+, 10-, 11+ 4-0 ma Load resistance 0-550 Ω 50 µa ss Analog Input Transmitters KFD-STC4-Ex Dual-channel HART compatible 4 VDC power supply 3 way isolation Suitable for Division mounting The SMART transmitter power supplies supply a -wire SMART transmitter within a hazardous area and transfer the analog 4-0 ma signal from the hazardous area to the safe area. Digital signals which can be modulated onto the analog signal, can also be transmitted bidirectionally on the hazardous or safe side. Handheld terminals can be connected as shown in the block diagram. Hand-held terminals can be connected as shown in the circuit diagram. These isolators have KF-STP-BU and KF-STP-GN terminals with test probe access holes for the easy interface of hand-held terminals. If the communicator is connected in the safe area, the load resistance must not be less than 30 Ω. 0 µa 0.00% of span/ºc Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 ma pp Signal 0 Hz to 7.5 khz (-3 db) Freq. range (50 Ω load) Safe area into hazardous area Band width at 1 V pp Signal 300 Hz to 7.5 khz (-3 db) Rise/fall time 0µs/0µs Entity Parameters Terminals 1, 3; 4, 6 UL control drawing no. 116-0173 5. V 93 ma ) 0.095µF 0.808 µf.88 µf ) 4. mh 17 mh 33 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +65ºC (-4ºF to +140ºF) Safe Area or Div KFD-STC4-Ex 6 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
Analog Input Transmitters 00 IS Catalog Power Rail or terminals 14+, 15-0-35 VDC.5 W HART Transmitter Input (intrinsically safe) Terminals 1+, 3-,; 4+, 6- Input 0/4-0 ma 16.0 V at 0 ma Output (not intrinsically safe) Terminals 7-,8+; 10-, 11+ 0/4-0 ma Load resistance 0-550 Ω 50 µa ss 0 µa 1µA/ºC Freq. range (50 Ω load) Hazardous area into safe area Band width at 1 V pp -Signal 0 Hz to 7.5 khz (-3 db) Freq. range (50 Ω load) Safe area into hazardous area Band width at 1 V pp -Signal 300 Hz to 7.5 khz (-3 db) Entity Parameters Terminals 1, 3, 4, 6 UL control drawing no. 116-0173 5. V 93.0 ma ) 0.093µF 0.798 µf.808 µf ) 4.6 mh 18 mh 36 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +65ºC (-4ºF to +140ºF) Safe Area or Div KFD-STC4-Ex-Y7195 KFD-STC4-Ex-Y7195 Dual-Channel HART compatible 4 VDC power supply Sink mode output 3-way isolation Suitable for Division mounting The SMART transmitter power supplies supply a -wire SMART transmitter within a hazardous area and transfer the analog 4-0 ma signal from the hazardous area to the safe area. This isolator is designed to provide a sink mode output on the safe area terminals. Digital signals which can be modulated onto the analog signal, can also be transmitted bidirectionally on the hazardous or safe side. Handheld terminals can be connected as shown in the block diagram. The SMART transmitters are normally delivered with the KF-STP-BU and KF-STP- GN terminals. Connector jacks are integrated in these terminals for the connection of the handheld terminals. If the communicator is connected in the safe area, the load resistance must not be less than 30 Ω. 0-35VDC 0-35VDC Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 63
I 00 IS Catalog HART Transmitter Power Rail or terminals 14+, 15-0-35 VDC.5 W Input (intrinsically safe) Terminals 1+, -, 3 Input signal 4-0 ma (term. 1, 3) 16 V at 0 ma Output (not intrinsically safe) Terminals 7-, 8+, 10-, 11+ 4-0 ma Load resistance* 0-550 Ω 75 µa pp Analog Input Transmitters KFD-STC4-Ex1.0 Dual outputs HART compatible 4-0mA current source outputs 3-way isolation SMART transmitter power supplies supply a -wire SMART transmitter within a hazardous area and transfer the analog 4-0 ma signal from the hazardous area to the safe area as two current sources. Digital signals which can be modulated onto the analog signal, can also be transmitted bidirectionally on the hazardous or safe side. Handheld terminals can be connected as shown in the block diagram. The SMART transmitters are normally delivered with the KF-STP-BU and KF-STP- GN terminals. Connector jacks are integrated in these terminals for the connection of the handheld terminals. If the communicator is connected in the safe area, the load resistance must not be less than 30 Ω. 0 µa 1 µa/ºc Freq. range (50 Ω load) (Hazardous area into safe area) Band width at 0.5 V pp Signal 0 Hz to 7.5 khz (-3 db) (Safe area into hazardous area) Band width at 0.5 V pp Signal 300 Hz to 7.5 khz (-3 db) Interference rejection Unaffected by 60 V, 50 Hz common mode input signal with any safe side terminal grounded, and 7 MHz walkie-talkies Entity Parameters Terminals 1+, 3- UL control drawing no. 116-0173 5.4 V 88. ma ) 0.01 µf 0.081 µf.89 µf ) 4. mh 17 mh 33 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +60ºC (-4ºF to +140ºF ) 3 3 3 3 Safe Area or Div KFD-STC4-Ex1.0 8 7 11 10 14 15 4VDC 64 Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607
I Analog Input Transmitters 00 IS Catalog Power Rail or terminals 14+, 15-0-35 VDC.5 W HART Transmitter Input (intrinsically safe) Terminals 1+, -, 3 Input signal 4-0 ma (term. 1, 3) 16 V at 0 ma Output (not intrinsically safe) Terminals 7-, 8+, 10-, 11+ 4-0 ma Load resistance* 0-550 Ω 75 µa pp 0 µa 1 µa/ºc Freq. range (50 Ω load) (Hazardous area into safe area) Band width at 0.5 V pp Signal 0 Hz to 7.5 khz (-3 db) (Safe area into hazardous area) Band width at 0.5 V pp Signal 300 Hz to 7.5 khz (-3 db) Interference rejection Unaffected by 60 V, 50 Hz common mode input signal with any safe side terminal grounded, and 7 MHz walkie-talkies Entity Parameters Terminals 1+, 3- UL control drawing no. 116-0173 5.4 V 88. ma ) 0.01 µf 0.081 µf.89 µf ) 4. mh 17 mh 33 mh 107 x 0 x 115 mm Weight 100 g (3.5 oz.) -0ºC to +60ºC (-4ºF to +140ºF ) KFD-STC4-Ex1.0-Y716 Dual outputs HART compatible Sink mode outputs 3-way isolation SMART transmitter power supplies supply a -wire SMART transmitter within a hazardous area and transfer the analog 4-0 ma signal from the hazardous area to the safe area as two current sink outputs. Digital signals which can be modulated onto the analog signal, can also be transmitted bidirectionally on the hazardous or safe side. Handheld terminals can be connected as shown in the block diagram. The SMART transmitters are normally delivered with the KF-STP-BU and KF-STP- GN terminals. Connector jacks are integrated in these terminals for the connection of the handheld terminals. Safe Area or Div KFD-STC4-Ex1.0-Y716 If the communicator is connected in the safe area, the load resistance must not be less than 30 Ω. 8 0-35VDC 3 3 3 3 7 11 10 0-35VDC 14 15 4VDC Pepperl+Fuchs Inc. Telephone (330) 486-000 FAX (330) 45-4607 65