Pressure controls, type KP



Similar documents
Pressure switches and thermostats, type KPS

Dual Pressure Controls for Refrigeration, Air-conditioning and Heatpump Applications

Table of contents. Danfoss A/S (RC-CM/sw), RF.5X.A1.02 3

D A T A S H E E T. PS3 Pressure Switch. Alco Controls PS3

Manual motor starter MS116

Solenoid valves Type EVU

P70, P72, and P170 Series Controls for Dual Pressure Applications

SQUARE D INDUSTRIAL CONTROL PRODUCTS

Assisted lift operated 2/2-way solenoid valves Type EV250B

Pressure transmitter For general industrial applications Model A-10

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Series 8146/5-V37 and Series 8150/5-V37

Electronic overload relay EF19 and EF45

3/2-way Solenoid Valve, direct-acting, NC or NO

9013 PUMPTROL Commercial Pressure Switches Type F and 9013 Commercial Pressure Switches Type G. January. Catalog

Compact pressure switch Flameproof enclosure Ex d Model PCA

Electronic overload relay EF65, EF96 and EF146

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Manual Motor Starter MS 116 up to 16 A Technical Data

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

Pressure Switch for gas and air

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Safety dialogue solutions

Threaded Resistance Thermometers Model TR10-D, Miniature Design

Plastic tube flowmeters Series PT/PS

NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE

OEM Pressure Transmitters for heavy-duty applications, Type MBS 1200 and MBS 1250

HS5D. Miniature Interlock Switches First in. Head Removal Detection Function for Safer Performance. First in. the Industry.

Digital inductive conductivity transmitter

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Technical Information RIA14

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

HERZ-Thermal Actuators

Three-phase monitoring relay CM-PFE

ISOMETER IRDH275. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Vorläufiges Datenblatt

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design

Command devices Pull-wire emergency stop switches One-side operation ZS 71 range Schmersal T [] C

Terminal Boxes Series 8146

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Cable Plug acc. to DIN EN , Form A

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Split units TH with hermetic compressors

VALVES FOR REFRIGERATING SYSTEMS

Oil / Air Cooling Units for mechanical engineering and mobile hydraulics

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Electronic, Digital and Mechanical Vibration Switches

Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version

Reaction Torque Sensor

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Electric Rotary Actuator - On/Off or programmable control actuator

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

CompactLogix Power Supplies Specifications

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

Sporlan V-Series Ruby Seat Solenoid Valves

SOLENOID VALVE FOR REFRIGERATING SYSTEMS

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

RM4TG20 three-phase network control relay RM4-T - range V

ECOCIAT. Domestic hot water heat recovery unit

Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

MasterINTERFACE 39 Series - Relay interface modules

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Series 6000 Torque measured metal bellow coupling

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

BRÖCKSKES D-VIERSEN PV1-F 4,0 mm BRÖCKSKES D-VIERSEN PV1-F 4,0 mm d d 2 2 C VDE-REG.-Nr /2009

Temperature sensor with integrated transmitter for industrial applications, MBT 3560

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Solenoid valves 2/2-way direct-operated Type EV210A

Ordering Information. Cylindrical Proximity Sensor E2E/E2E2

Electrically operated valves Series M-05, 3/2-, 5/2- and 5/3-way G1/8 650 and 750 Nl/min (0.661 and Cv)

Heating, air-conditioning, cooling

LEVEL GAUGES WITH MAGNETIC JOINT L 14 - L 22 - L 34

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Electro-pneumatic control valves

MasterINTERFACE 39 Series - Relay interface modules

49 Series - Relay interface modules A. Features

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

M1000 Process Alarm Monitor

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

3/2- and 2/2-way cartridge valve type BVE

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Capacitive Prox E2K-X

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Safety technique. Emergency stop module BO 5988 safemaster

Transcription:

Introduction KP pressure controls are for use in refrigeration and air conditioning systems to give protection against excessively low suction pressure or excessively high discharge pressure. KP pressure controls are also used for starting and stopping refrigeration compressors and fans on air-cooled condensers. KP pressure controls are fitted with a single-pole double-throw (SPDT) switch. The position of the switch is determined by the pressure control setting and the pressure at the connector. KP pressure controls are available in IP 30 and IP 44 enclosures. Features Ultra-short bounce times Reduces wear to a minimum and increases reliability. Manual control Electrical contact function can be tested without the use of tools. KP 2 with low differential for low-pressure regulation KP 6 for HP refrigerants (R 40A, CO 2 ) KP 6, 7 and 7 with fail-safe bellows element Vibration and shock resistant Compact design Fully welded bellows element High reliability both electronically and mechanically. Approvals CE-marked in accordance with LVD 73/23/EC and EN 60947-4-5 for sale in Europe. KP, 2, 6, 7 and KP 7: CE marked in accordance with PED 97/23/EC, category IV, safety equipment and EN 2263, DIN 32733 Germanischer Lloyd, Germany UL approval for USA and Canada DNV, Det Norske Veritas, Norway RINA, Registro Italiano Navale, Italy BV, Bureau Veritas, France LR, Lloyd's Register, UK RMRS, Russian Maritime Register of Shipping, Russia CCC, China Compulsory Certificate Materials in contact with the medium Unit type KP, 2, 5, 6, 7, 5 and 7 KP A, 5A, 6, 7A and 5A only Material Tinbronze, no. 2.020 to DIN 7662 Free cutting steel, no..0737 /.078 to DIN 65 Stainless steel 8/8, no..0737 /.078 to DIN 7440 Free cutting steel, no..079 to DIN 65 Steel, no..0330 to DIN 624 Aluminium, no. 3.0255 to DIN 72 RD5AB502 DKRCC.PD.CD0.A.02-520H89 Danfoss A/S (AC-DSL /mr),2-2006

Technical data Ambient temperature 40 +65 C (+80 C for max. 2 hours). DIN-approved units: 25 +65 C (+80 C for max. 2 hours). Max. working pressure LP: PB = 7 HP: PB = 35 KP 6: PB = 46.5 Max. test pressure LP: p = 20 HP: p = 35 KP 6: p' = 46.5 Contact load Alternating current: AC: 6 A, 400 V AC3: 6 A, 400 V AC5: 0 A, 400 V Max. starting current (L.R.): 2 A, 400 V Direct current: DC3: 2 W, 220 V control current Properties according to EN 60947: Wire dimensions solid/stranded 0.75-2.5 mm 2 flexible, w/out ferrules 0.7-2.5 mm 2 flexible, with ferrules 0.5 -.5 mm 2 Tightning torque max. 2 NM Rated impulse voltage 4 kv Pollution degree 3 Short circuit protection, fuse 20 Amp Insulation 400 V IP 30/44 Cable connection The cable entry can be used for 6 4 mm dia. cables. A Pg 3.5 screwed cable entry can also be used for 6 4 mm cable. With 8 6 mm cable a standard Pg 6 screwed cable entry can be used. Enclosure IP 30 to EN 60529 / IEC 60529 Enclosure IP 30 is obtained when the units without top cover are mounted on a flat surface or bracket. The bracket must be fixed to the unit so that all unused holes are covered. IP 44 to EN 60529 / IEC 60529 Enclosure IP 44 is obtained when the units with top cover are mounted on a flat surface or bracket. The bracket must be fixed to the unit so that all unused holes are covered. KP pressure controls with auto reset are supplied with top cover. For KP pressure controls with manual reset, the top cover must be separately ordered. Contact systems Low pressure (LP) High pressure (HP) Dual pressure (HP/HP) Dual pressure (LP/HP) Dual pressure (LP/HP) IP 55 to EN 60529 / IEC 60529 IP 55 is obtained when the KP pressure controls are mounted in an IP 55 enclosure, (code no. 060-033066 for single pressure controls and code no. 060-035066 for dual pressure controls). IP 55 enclosure has to be ordered separately. 2 RD5AB502 DKRCC.PD.CD0.A.02-520H890 Danfoss A/S (AC-DSL /mr),2-2006

Ordering Pressure Type Low pressure (LP) High pressure (HP) Reset Contact Regulating Differential Regulating Differential Low High system range Δp range Δp pressure pressure LP HP / 4 in. 6 mm flare Code no. / 4 in. ODF solder 6 mm ODF solder For fluorinated refrigerants Low KP 0.2 7.5 0.7 4.0 Aut. 060-066 3 ) 060-266 3 ) 060-066 3 ) Low KP 0.2 7.5 0.7 4.0 Aut. 060-466 ) 3 ) Low KP 0.9 7.0 Fixed 0.7 Man. 060-0366 060-66 060-0966 SPDT Low KP 2 0.2 5.0 0.4.5 Aut. 060-2066 3 ) 060-2366 3 ) High KP 5 8 32.8 6.0 Aut. 060-766 3 ) 060-7966 3 ) 060-7766 3 ) High KP 5 8 32 Fixed 3 Man. 060-7366 060-8066 060-7866 Dual KP 5 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut. Aut. 060-2466 3 ) 060-25466 3 ) Dual KP 5 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut. Man. SPDT + 060-24366 Dual KP 5 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut. Man. LP 060-4866 ) Dual KP 5 0.9 7.0 Fixed 0.7 8 32 Fixed 4 Man. Man. signal 060-24566 Dual KP 5 0.9 7.0 Fixed 0.7 8 32 Fixed 4 Conv. 2 ) Conv. 2 ) 060-2666 Dual KP 5 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut. Aut. SPDT + 060-26566 3 ) 060-29966 3 ) Dual KP 5 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut. Man. LP and 060-26466 060-28466 Dual KP 5 0.2 7.5 0.7 4.0 8 32 Fixed 4 Conv. 2 ) Conv. 2 ) HP 060-5466 3 ) 060-00066 3 ) Dual KP 5 0.9 7.0 Fixed 0.7 8 32 Fixed 4 Conv. 2 ) Conv. 2 ) signal 060-22066 Pressure Type Low pressure (LP) High pressure (HP) Reset Contact Regulating Differential Regulating Differential system range Δp range Δp LP/HP M0 0.75 Code no. m cap. tube with M0 0.75 For fluorinated refrigerants and R 77 (NH 3 ) Low KP A 0.2 7.5 0.7 4.0 Aut. 060-6266 060-6066 3 ) Low KP A 0.9 7.0 Fixed 0.7 Man. 060-666 SPDT High KP 5A 8 32.8 6.0 Aut. 060-23066 3 ) High KP 5A 8 32 Fixed 3 Man. 060-5366 060-2366 Dual KP 5A 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut./Aut. SPDT + LP and HP 060-29566 060-29366 3 ) Dual KP 5A 0.2 7.5 0.7 4.0 8 32 Fixed 4 Aut./Man. signal 060-29666 060-29466 Dual KP 5A 0.9 7.0 Fixed 0.7 8 32 Fixed 4 Conv./Conv. 2 ) SPDT LP signal 060-28366 ) Pressure controls with gold-plated contacts 2 ) Conv.: optional automatic or manual reset 3 ) Enclosure IP 44 Accessories for KP pressure controls with M0 0.75 connections: Weld connections: M0 0.75 nut and 6 50 mm seamless steel pipe, code no. 060-005766 Steel cap. tube: m with 2 M0 0.75 nuts, code no. 060-007866 Steel cap. tube: m with M0 0.75 and G 3 /8 nut, code no. 060-008266 Adaptor: M 0 0.75 /4 to /8 NPT int. thread, code no. 060-0466 IP 55 enclosure for single pressure controls, code no. 060-033066 IP 55 enclosure for dual pressure controls, code no. 060-035066 For other accessories: see "Spare parts and accessories", RX5AB302 Danfoss A/S (AC-DSL /mr),2-2006 RD5AB502 DKRCC.PD.CD0.A.02-520H890 3

Ordering (continued) Pressure control setting with convertible reset Low press. Manual reset ) Automatic reset Automatic reset Manual reset High press. Manual reset ) Manual reset Automatic reset Automatic reset ) Factory setting Pressure controls with EN 2263 and DIN 32733 approval ) Pressure Type 2 ) Low pressure (LP) High pressure (HP) Reset Contact Regulating Differential Regulating Differential system range Δp range Δp LP/HP / 4 in. 6 mm flare Code no. 6 mm ODF solder For fluorinated refrigerants Low KP 0.2 7.5 0.7 4.0 Aut. SPDT 060-066 3 ) 060-066 3 ) Low KP 0.9 7 Fixed 0.7 Man. SPDT 060-0366 060-0966 Low KP 0.5 3.0 Fixed 0.7 Aut. SPDT 060-766 Low KP 2 0.2 5 0.4.5 Aut. SPDT 060-2066 3 ) 060-2366 3 ) High KP 6W 8 42 4 0 Aut. SPDT 060-59066 3 ) High KP 6B 8 42 Fixed 4 Man. SPDT 060-5966 High KP 7W 8 32 4 0 Aut. SPDT 060-9066 3 ) 060-20366 3 ) High KP 7B 8 32 Fixed 4 Man. SPDT 060-966 High KP 7S 8 32 Fixed 4 Man. SPDT 060-9266 3 ) Dual KP 7BS 8 32 Fixed 4 Man. / Man. SPST 060-20066 Dual KP 7W 0.2 7.5 0.7 4 8 32 Fixed 4 Aut. / Aut. SPDT + LP and HP signal 060-27566 3 ) 060-27666 3 ) Dual KP 7W 0.2 7.5 0.7 4 8 32 Fixed 4 Aut. / Aut. SPDT 060-26766 3 ) Dual KP 7B 0.2 7.5 0.7 4 8 32 Fixed 4 Aut. / Man. SPDT 060-26866 060-27466 Dual KP 7WB 0.2 7.5 0.7 4 8 32 Fixed 4 Aut./Conv. 5 ) SPDT + LP and HP signal 060-539766 3 ) 4 ) Pressure controls with EN 2263 and DIN 32733 approval ) Pressure Type 2 ) Low pressure (LP) High pressure (HP) Reset Contact Code no. Regulating Differential Regulating Differential system m cap. range Δp range Δp LP/HP M0 0.75 tube with M0 0.75 For ammonia Low KP A -0.2 7.5 0.7 4.0 Aut. SPDT 060-6266 060-6066 3 ) Low KP A 0.9 7 Fixed 0.7 Man. SPDT 060-666 High KP 7ABS 8 32 Fixed 4 Man./Man. SPST 060-20566 ) Meets the requirements in VBG 20 dealing with safety equipment and excess pressures. KP, 2, 6, 7 and KP 7 are CE marked acc. to PED, Pressure Equipment Directive. 2 ) W = Wächter (pressostat), B = Begrenzer (pressure control with ext. reset), S = Sicherheitsdruckbegrenzer (pressure control with int. reset). 3 ) Enclosure IP 44 4 ) factory setting: LP side: Range Pe, Diff. ; HP side: Range 8 Pe, Diff. 4 fixed 5 ) Conv.: optional automatic or manual reset 4 RD5AB502 DKRCC.PD.CD0.A.02-520H890 Danfoss A/S (AC-DSL /mr),2-2006

Design / Function Capillary tube Key sketch of KP pressure control Capillary tube for KP A, 5A and 5A KP. Low pressure (LP) setting spindle 2. Differential setting spindle, LP 3. Main arm 5. High pressure (HP) setting spindle 7. Main spring 8. Differential spring 9. Bellows 0. LP connection. HP connection 2. Switch 3. Terminals 4. Earth terminal 5. Cable entry 6. Tumbler 8. Locking plate 9. Arm 30. Reset button KP 5 The switch in the KP has a snap-action function and the bellows moves only when the cut-in or cut-out value is reached. The bellows becomes connected to the low or high pressure side of the plant through connection (0) or (). The design of the KP affords the following advantages: high contact load ultra-short bounce time high resistance to pulsation vibration resistance up to 4 g in the range 0-000 Hz long mechanical and electrical life Danfoss A/S (AC-DSL /mr),2-2006 RD5AB502 DKRCC.PD.CD0.A.02-520H890 5

Design (continued) KP, KPA, KP2, KP6, KP6A, KP7 and KP7 units with designat-ion W, B or S have been tested and approved by TÜV, Rheinland in accordance with DIN 32733 and EN 2263 W = Wächter (pressure control) B = Begrenzer (pressure control with external reset) S = Sicherheitsdruckbegrenzer (pressure control with internal reset). KP6, KP6A, KP7 and KP7 have a double bellows: an outer bellows and a regulating bellows. When system pressure exceeds the set value, the KP will automatically stop the plant. The double bellows system prevents loss of charge in the event of bellows rupture. A rupture in the inner bellows will cause the control cut-out pressure to fall about 3 times less the set value, thus the refrigeration plant compressor will stop. A rupture in the outer bellows will cause the control cut-out pressure to fall to about 3 under the set value, thus providing a fail-safe function. Versions with designation W or AW cut in again automatically when the pressure has fallen to the set value minus the differential. Versions with designation B or AB can be cut in manually with the external reset button when the pressure in KP has raised 0.7 above set value and in KP6 and KP7 has fallen 4 under the set value. Versions with designation S or AS can be cut in manually with the internal reset arm when the pressure has fallen 4 under the set value. All KP pressure controls, including those which are PED-approved, operate independently of changes in the ambient temperature around the control housing. Therefore the set cut-out pressure and differential are held constant provided the permissible ambient temperatures are not exceeded. KP 7W, flare KP 7W, solder. Pressure setting spindle 2. Differential setting spindle 3. Main arm 5. Pressure setting spindle, DBK 5. Cable entry 8. Locking plate 9. Arm 25. Int. reset arm 30. Ext. reset button KP 7BS 6 RD5AB502 DKRCC.PD.CD0.A.02-520H890 Danfoss A/S (AC-DSL /mr),2-2006

Terminology Reset. Manual reset: Units with manual reset can only be reset during operation by activation of the reset button. 2. Automatic reset: After operational stop, these units reset automatically. 3. Convertible reset: Units with optional reset can be activated by automatic and/or manual reset. Permissible working pressure The permissible working pressure is determined by the pressure that can be safely allowed in the refrigerating system or any of the units within it. The permissible working pressure is designated PB (Der zulässige Betriebsüberdruck). Test pressure The test pressure is the pressure used in strength tests and/or leakage tests on refrigerating systems or individual parts in systems. The test pressure is designated p. "Snap function" A certain contact force is maintained until irrevocable "snap" is initiated. The time during which the contact force approaches zero is thus limited to a very few milliseconds. Therefore contact bounce cannot occur as a result of, for example, slight vibrations, before the cut-out point. Contact systems with "Snap function" will change over even when micro-welds are created between the contacts during cut-in. A very high force is created during cut-out to separate the contacts. This force immediately shears off all the welds. Thus the cut-out point of the unit remains very accurate and completely independent of the magnitude of the current load. Setting Pressure controls with automatic reset - LP: Set the LP start pressure on the "CUT-IN" scale (range scale). One rotation of the low pressure spindle 0.7. Set the LP differential on the "DIFF" scale. One rotation of the differential spindle 0.5. The LP stop pressure is the LP start pressure minus the differential. Note: The LP stop pressure must be above absolute vacuum (p e = )! If with low stop pressure the refrigeration compressor will not stop, check to ensure that the differential value has not been set too high! Pressure controls with automatic reset - HP: Set the HP pressure on the "CUT-OUT" scale. One rotation of the HP spindle 2.3. Set the HP differential on the "DIFF" scale. One rotation of the differential spindle 0.3. The HP start pressure is the HP stop pressure minus the differential. Start and stop pressures for both the LP and HP sides of the system should always be checked with an accurate pressure gauge. Pressure controls with manual reset Set the stop pressure on "CUT-OUT" scale (range scale). Low pressure controls can be manually reset when the pressure is equal to the stop pressure plus the differential. High pressure controls can be manually reset when the pressure is equal to the stop pressure minus the differential. Danfoss A/S (AC-DSL /mr),2-2006 RD5AB502 DKRCC.PD.CD0.A.02-520H890 7

Dimensions and weights Flare connection KP with top cover KP, 2, 5, 6, 7B, 7S and 7W KP 5 and 7W M0 0.75 connection KP with IP 55 enclosure KP A, 2A and 5A KP 5A, 7 AS and 7ABS Solder connection KP with IP 55 enclosure IP 55 enclosure KP, 2, 5, 7B, 7S and 7W KP 5, 7W IP 55 enclosure Weld nipple for KP-A Weight KP, 2, 5 and 7: approx. 0.3 kg KP 5, 7 and 7BS: approx. 0.5 kg KP A and 5A: approx. 0.3 kg KP 5A and 7ABS: approx. 0.5 kg 8 RD5AB502 DKRCC.PD.CD0.A.02-520H890 Danfoss A/S (AC-DSL /mr),2-2006