Water Volume Calculation in Hydronic Heating & Cooling Systems



Similar documents
Frequently Asked Questions

Hydromx Instructions for Use for Space Heating

Link-Up. Solid Fuel Association Guide to Central Heating.

UNDERSTANDING HOT WATER SYSTEMS IN THE HOME

Electric Flow Boiler

UNDERSTANDING CENTRAL HEATING SYSTEMS

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

SOLAR HEATING SYSTEMS.

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Condensing Boiler Efficiency

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters

Non Domestic BER Assessors Technical Bulletin

StainlessLite. Unvented mains pressure and vented water storage in Duplex stainless steel SUPPLIERS TO THE MERCHANT TRADE FOR OVER 40 YEARS

Your tool for designing efficient balancing solutions for heating and cooling systems

Defining Quality. Building Comfort. Heating and Cooling Coils

Laddomat 21. For accumulation when using a wood-fired boiler. Picture 1. The wood-fired boiler is is connected to to. accumulator tank with bypass

PRESSURISATION UNITS EXPANSION VESSELS ELECTRONIC FILLING DEVICE (EFD) MAXI MAXI PLUS EXPANSION VESSELS

Hot water supply, distribution and use

Laddomat Charging unit

Solar Hot Water Heaters

FILLING AND PURGING THE SYSTEM

PRO-CLEAN. Technical Description. Specifications. Space-saving design with minimum heat loss (melamine resin insulation)

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC DRAFT V0.

HVAC Processes. Lecture 7

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Recover Heat from Boiler Blowdown Water

In-Line Air Separators

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

ECOCIAT. Domestic hot water heat recovery unit

HEAT INTERFACE UNITS (Modular)

Technical data. Danfoss DHP-A

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

The NEW Greenstar i. intuitive. innovative. improved performance. installation ease

Commissioning - Construction Documents (Page 1 of 6)

WC flushing cistern single or dual flush to fill in 2 minutes WC trough cistern 0.15 per WC Wash basin tap size 1 2

Session 2: Hot Water Supply

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B

Description of functions

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

Pipe Sizing for Commercial and Industrial Natural Gas at Operating Pressures 75 mbar

A Table of the Most Common Standard Pipe Sizes. Nominal Bore 1/2 inch (DN 15 mm), Outside Diameter mm

Commercial Hot Water. Make a difference...

BoilerMate SP. benchmark. user instructions A - C L A S S

Domestic Chemical Water Treatment Manufacturers Association

By Steven C. Severini, P.E., Member ASHRAE

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Stove-boiler for solid fuels KW Directions for use and assembling

High Output Boiler Systems

Morco House Riverview Road Beverley HU17 0LD

Delivering exceptional performance and Ecovalue. Ecocent

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

Current Transformers

1 DESCRIPTION OF THE APPLIANCE

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

HEAVY DUTY STORAGE GAS

YUTAKI S. Domestic Heating

Combi Unit Genius. The energy efficient Building Service Centre

Laddomat 21 Charging Unit

HEAT TRANSFER ENHANCEMENT ON DOUBLE PIPE HEAT EXCHANGER BY WIRE COILED AND TAPER WIRE COILED TURBULATOR INSERTS

Heating and Domestic Hot Water Systems for dwellings Achieving compliance with Part L 2008

Qualification Guide. BPEC 601/2514/7 - Level 1 Diploma in Plumbing Foundation. BPEC 600/9432/1 - Level 2 Diploma in Plumbing Foundation

LG Electronics AE Company, Commercial Air Conditioning

Application for a water connection to a commercial or mixed use development

Theta Dual service BFC, SGE, SGS for 20/30/40 kw heating capacity

main heating: pre1998 ducted warm air system main heating fuel: mains gas main heating SAP efficiency: 70.0% main heating controls: programmer

your water pressure explained

High efficiency, cast-iron gas boiler

Operators manual Basic water heater

Instructions for designing heating systems.

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

TABLE OF CONTENT

PELLEXIA COMFORT ENVIRONMENT COMPATIBLE

CGC s Hybrid System Loop Control

QZSR Fan Coil. Key features. Specifications. Product code example Cassette Unit QZSR, QZSR

Apartment and Communal Heating Solutions

Condensing unit type EPSILON-ECHOS LE Technical information manual

Steam System Best Practices Condensate System Piping

The heat is there let s use it! Using free environmental heat from the air with heat pump technology for central heating and domestic hot water

Versati Air to Water Heat Pump

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

PLBG/GAS SAFETY Information Bulletin

presents Hydraulic Separation Beyond Primary / Secondary Piping

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE

GUIDE TO AIR SOURCE HEAT PUMPS. Consumer, Specifier, Installer and Merchant guide to Air to water heat pump technology

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

Zenith Solar thermal 4.5m pump station Installation manual

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

Thermo Siphon Solar Systems

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R EN - Edition 01-26/10/2009

Laddomat 21 Charging package

Your guide to heating your home

Aerona Air Source Heat Pumps

Transcription:

Water Volume Calculation in Hydronic Heating & Cooling Systems Preface There are several methods which can be used to calculate the volume of water in a hydronic heating or cooling systems. However, these methods are not always 100% accurate due to inaccurate or incomplete systems information and variations in measurement techniques. Consequently it is recommended that at least two methods are used to calculate water volume in the system to cross check and help finalise the amount to be quoted or sold. Water Volume Calculation Methods The methods below are described in more detail later; here you can see which methods are most applicable during the sales and installation process. Domestic Method Indicative ROI Quote Installation/ Rollout 1 - Drawings and Specifications Yes Yes Yes 2 - Site Survey Yes Yes n/a 3 - Calculation based on Heat/Cooling load capacity n/a n/a n/a 4 - Measure Drained Water (Meter) n/a n/a Yes 5 - Measure Drained Water (Buckets) n/a n/a Yes 6 - Number of Radiator Panels Yes Yes n/a Commercial Method Indicative ROI Quote Installation/ Rollout 1 - Drawings and Specifications Yes Yes Yes 2 - Site Survey Yes Yes n/a 3 - Heat/ Cooling Load Capacity (kw) Yes Yes Yes 4 - Measure Drained Water (Meter) n/a n/a Yes 5 - Measure Drained Water (Buckets) n/a n/a n/a 6 - Number of Radiator Panels n/a n/a n/a DR0023 v1 PBA Energy Solutions Ltd 1

As can be seen some methods are only applicable at the time of installation. These methods will add time to the installation works, but will give the Installer a good indication that the correct amount of water has been drained, or indicate that there is more water in the system and it has not been fully drained. When water has been left in the system it can be further drained or alternatively a higher concentration of Hydromx can be installed to compensate and ensure the final solution is the optimum 50% (see DR0005 Instructions for Use). 1. Drawings and Specifications Water volume calculations can be made by taking sizing information from the building mechanical project materials lists and project drawings, (see Appendix A for pipe work volume calculation). Commercial buildings should have a mechanical project report and this report should include; Boiler/Chiller type and size, pipe type, length and diameters, main pump size and flow rates, fan coils, radiators, drainage points, air valves, pressure vessels etc. This information will enable a calculation of water volume in the system to be made. Also, many buildings have AutoCAD or similar computer drawings. In these cases, pipe work water volume can be calculated with the help of these programs as well. Accuracy rate 90%. NOTE: Engineering variations may have altered the system and may not have been recorded on original drawings or kept in up to date manuals. Where drawings are re-issued following variations, care should be taken to ensure information is taken from the latest issued drawings. 2. Site Survey Where drawings are not available a walk through survey can be done to provide the information to calculate volumes, (see Appendix A for pipe work volume calculation). Clearly this only applies for buildings of a size than can be surveyed without excessive expense. The details of boilers, chillers, expansion vessel, pipe work and heat exchangers, etc. can be collected. Details of water volume sizing can be acquired from manuals, online specifications and by phone/email from manufacturers and distributors. Accuracy rate 90%. DR0023 v1 PBA Energy Solutions Ltd 2

3. Heat/Cooling load capacity This method calculates water volume in heating and cooling systems based on heat load capacity. This is ONLY valid for Commercial installations, as Domestic boilers can be significantly oversized for the property. With this method the thermal capacity (kw) of the boiler/chiller should be known. Heating systems formula kw x 0.014 = m 3 m 3 less %20 = Estimated Water Volume in the system By applying the kw x 0.014 = m 3 formula the maximum water volume of the boiler is calculated; then subtract 20% (typical heat engineering boiler sizing tolerance margin) to give the estimated water volume in the system. In making this calculation it is very important to know the accurate kw heat capacity of the active boilers. For example there may be a primary boiler is the main feeder and a secondary/backup boiler. The calculation must use the kw of the heating needed for the building, and exclude backup and capacity tolerances. NOTE: 20% is a typical boiler capacity tolerance margin, but this may vary. This exact boiler capacity tolerance may be available in the original Heat Engineering calculations. EXAMPLES Example1 The system has one 1400 kw boiler. 1400 kw x 0.014 = 19.6 m 3 19.6 m 3 - %20 = 15.68 m 3 estimated water volume in the system. Example 2 The system has two boilers which are working together, (both are 1400 kw). In this situation the total kw (the working load) of the boilers must be used in the formula (1400 kw + 1400 kw) * 0.014 = 39.2 m 3 39.2 m 3 - %20 = 31.36 m 3 estimated water volume in the system. NOTE: If there is more than one boiler in the system and it is uncertain whether the other boilers are back ups or not, a different method should be used to calculate the water volume. DR0023 v1 PBA Energy Solutions Ltd 3

Chiller systems formula kw x 0.014 x 1.32 = m 3 m 3 - %20 = Water Volume in the system To use this formula it is essential to know which is the Primary chiller and which chiller is the secondary/back up. The maximum working load of PRIMARY feeders ONLY should be calculated. As with the Heating Systems Formula this formula also includes a tolerance factor of 20%. EXAMPLES Example 1 The system has one 488 kw chiller. 488 kw x 0.014 x 1.32 = 9 m 3 9m3 - %20 = 7.2 m 3 estimated water volume in the system. NOTE: If there is more than one chiller the maximum working load should be calculated as below and one other method should be used for verification. Example 2 The system has three chillers of 500 kw, 300 kw and 300 kw respectively, which are working together as a main feeder. (500 kw + 300 kw + 300 kw) x 0.014 x 1.32 = 20.328 m 3 20.3 m3 - %20 = 16.24 m 3 estimated water volume in the system If the kw of the Boiler/Chiller is unknown If the main pump/pumps flow rate and the ΔT of the chiller/boiler (for example, chillers usually have 3 C ΔT (input 10 C, output 7 C) are known the estimated kw of the system can be calculated using the formula: kw = (m/h) * ΔT/0.86 Secondary pumps are only for back up and should not be included in the calculation if they are not working together as main pumps. DR0023 v1 PBA Energy Solutions Ltd 4

EXAMPLE The main pump of the system has 120 lt/h flow rate and if there is 3 C ΔT. 120 lt/h x 3 C / 0.86 = 418 KW Water volume calculation based on heat load capacity generally gives the minimum amount of water. The accuracy of this method depends on the accuracy and completeness of the information provided by customer s technical team. It is strongly recommended that another method is also used to calculate the volume of water in the system. Accuracy rate 80-90%. depending on the accuracy of the engineering calculations on the original construction drawings and the accurate tracking of any engineering variations. 4. Measure drained water (meter) Providing there is a single connection point through which the whole system can be drained this is the easiest way to measure water volume in the system. Whilst draining the system the water temperature should be the same as normal tap water. If the water is hotter it will be less dense and this may affect the accuracy of the measurement. DR0023 v1 PBA Energy Solutions Ltd 5

In larger systems this method can increase draining time and therefore several draining points may be required with a meter connected at each point. Care should be taken to avoid the formation of bubbles while draining the system as this may give inaccurate results as the water meter will count bubbles as water. Accuracy rate for smaller systems 90%. Accuracy rate for large systems 70-80% as this assumes that the residual water left in larger systems is a greater proportion than smaller ones. 5. Measure drained water (bucket) This method is the preferable method for small domestic type properties where drained water can be collected in a measuring bucket and the total water volume is summed from the number of buckets and measured amounts. Accuracy rate 90% assumes 10% residual water is left in system. 6. Number of radiator panels x average number of litres per panel This method is suitable as a method for indicative quotes for domestic scale properties and can be varied with experience of house types. Although this method does not always accurately allow for open vented header tanks, over sized expansion vessels, or low water capacity radiators/emitters, it is a good initial assessment. EXAMPLE This example assumes a typical 3/4 bedroom detached house would have installed 15mm copper pipes and steel radiators. For each radiator panel a figure of 7 litres per panel is used, which gives an average water volume for the entire system. Therefore in a house with 6 single panel radiators and 5 double radiators (10 panels) the estimated volume of water in the system is 112 litres. e.g. ( 6 single panels + 10 panels in double radiators) x 7 litres = 112 litres Accuracy rate for domestic type systems 85%. DR0023 v1 PBA Energy Solutions Ltd 6

Appendix A - Pipe Volume Calculations The following formulas and worked example show how to calculate the volume of pipe work, once an assessment of the length of pipe work and sizes has been made from a walk through survey or from drawings. Pipe capacity calculation formula V = π x R1 x R1 x L x 1000 Where: V = volume in Litres π = 3.14159 R1 = internal radius of pipe in meters L = length in meters 1000 = number of litres in 1m 3 ^ DN = diameter nominal EXAMPLES Example 1 Calculation of 10 meters of 1" (DN ^ 25) pipe. Using the figures in Table 1 R1 is calculated as: R1 = Inner diameter/1000/2 26.9/1000/2 = 0.014 V = π x R1 x R1 x L x 1000 3.14 x 0.014 x 0.014 x 10 x 1000 = 6.15 litres DR0023 v1 PBA Energy Solutions Ltd 7

Example 2 Calculation of 3 meters of 1/2 (DN 15) pipe. Using the figures in Table 1 R1 is calculated as: R1 = Inner diameter/1000/2 15.7/1000/2 = 0.008 V = π x R1 x R1 x L x 1000 3.14 x 0.008 x 0.008 x 3 x 1000 = 0.6 litres Table of nominal diameter and pipe diameters Imperial Size Metric Size OUTER DIAMETER (mm) PIPE THICKNESS (mm) INNER DIAMETER (mm) 1/2 DN 15 21.3 2.8 15.7 3/4 DN 20 26.9 2.9 21.1 1 DN 25 33.7 3.4 26.9 1 1/4 DN 32 42.4 3.6 35.2 1 1/2 DN 40 48.3 3.7 40.9 2 DN 50 60.3 3.9 52.5 2 1/2 DN 65 73.0 5.20 62.6 3 DN 80 88.9 5.5 77.9 4 DN 100 114.3 6 102.3 5 DN 125 141.0 6.6 127.8 6 DN 150 168.3 7.1 154.1 8 DN 200 219.1 8.18 202.74 12 DN 300 323 9.5 304.0 16 DN 400 406 9.5 387.0 18 DN 450 470 9.5 451.0 Table 1 DR0023 v1 PBA Energy Solutions Ltd 8