111538E-05 2012-11. Flexit SPIRIT UNI 2. Installation Instructions. Air Treatment Unit & Automatic Control



Similar documents
FLEXIT S4 R S6 R S7 R

FLEXIT S3 X/TT A3 X/TT K3 X/TT S3 R S3 RK

Flexit air handling unit K2 R

94210E L7 X W. User Manual. Air Handling Unit Loft Models with water-based heating

94122E FLEXIT L4 X/TT L7 X/TT. User Manual. Air Handling Unit Loft Models with Heat Recovery

NEW! Flexit SL4 R. Air Handling Unit with rotating recovery system Energy-efficient New control system. Patent applied for!

News! Flexit S20 R. Air Handling Unit. A new generation of Air Handling Units. For a healthy indoor envionment

Flexit SPIRIT K2R. Air handling unit with integrated kitchen hood

Portable Air Conditioner

Rapide Inline Ceiling Extractor Fan, White Fascia Rapide Inline Ceiling Extractor Fan, Chrome Fascia

Drayton Digistat +2RF/+3RF

Topvex SX/C, Topvex TX/C. Air Handling Unit

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER S MANUAL HSC-24A

IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

ECOCIAT. Domestic hot water heat recovery unit

Cooling system components, removing and installing

Meaco 30L and Meaco 40L dehumidifier instruction manual

Important Safeguards

Installation, operation and maintenance manual TX 35A

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

3 IN 1 BATHROOM HEATER

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Instruction manual for Firstline FCS12000CH

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

Cooktop Low-Profile Ventilation Hoods

HERZ-Thermal Actuators

Installation and maintenance instructions. Danfoss Vent

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI

BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716

IH E Sigma Island 90

TIG INVERTER INSTRUCTION MANUAL

User Manual THR840DUK Digital Thermostat

SMD Rework Station TABLE OF CONTENTS

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Contact Details. Please note that some of the contact details on this PDF document may not be current.

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)

This section gives you some helpful information and tips on running your home and the equipment in it.

User's Instructions. Alpha HE CB25/33 and HE SY25

PORTABLE AIR CONDITIONER

MODEL: DV72. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual. Configuration Left Hand Right Hand

Accessory Manual Ventilation Section Model Comfort Circle

ELECTRIC CENTRAL HEATING FLOW BOILER

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

Oil and Coolant Circulating Heating System. Model - OCSM

Installation instructions. For the competent person. Installation instructions. VRT 350f. VRT 350f GB, IE

Ducoterra Radiant Heating Panel Installation Manual

AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

AIR-CONDITIONER SPLIT TYPE

AIR CONDITIONER INSTALLATION MANUAL

BeoLab 1. User s guide

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings

Industrial infrared heater IR For premises with large volumes and high ceilings

Use and Care Manual. Model CPA12KH AIR CONDITIONER

Duct Humidity Transmitter

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Cooling system components, removing and installing

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

MICA HEATER INSTRUCTION MANUAL Model No: UHM V 50Hz 2200W

Rousseau 10. User Guide

2-SLICE COOL TOUCH TOASTER

T7560A,B,C Digital Wall Module

RRV934. Multi-controller. Synco living

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SRA-125/SRAX-125 Double-Rail Lift-Out Rail System Installation & Service Manual with Parts List

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

Flexit Central Vacuum Cleaner

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

COLOR VIDEO DOOR PHONE CDV-71BE/D

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

INFRARED QUARTZ WALL HEATER

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

WB/WBS 3, 4, 5, 7, 8, 11, 14, 30

Infrarot-Bewegungsmelder IP44

E2 Series Electric Furnaces

MFU200 Integrated Under Counter Larder Fridge

VACUUM CLEANER INSTRUCTION MANUAL

LUCCI AIRFUSION QUEST II CEILING FAN

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

CE6500 Energy Recovery Ventilator

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SWIMMING POOL HEAT PUMP

DIAMOND Retractable Rodding Robot Model SPRAYROD-R

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Cross-beam scanning system to detect slim objects. 100 mm in

Transcription:

111538E-5 212-11 Flexit SPIRIT UNI 2 Installation Instructions Air Treatment Unit & Automatic Control

Contents 1 Planning and preparation work 4 1.1 Joiner / fitter 4 1.2 Plumber (if the unit has a water battery) 4 1.3 Electrician 4 2 Installation 5 2.1 In the box 5 2.2 Wall mounting 6 2.3 Floor mounting 8 2.4 Ceiling mounting 1 3 Duct connection 12 3.1 Connection to the unit 12 4 Cover 13 4.1 Preparations 13 4.2 Duct covers 13 5 Installation of the CI6/6 control panel 14 5.1 Contents 14 5.2 Installation of the CI6/6 14 5.3 Installation with a flush-mounted wall box 15 5.4 Surface mounting 15 5.5 Finishing off C16 15 5.6 Finishing off C16 15 6 Electrical work 16 6.1 Supply air sensor for heating (B1) (if unit has a water battery) 16 6.2 Frost sensor for water battery (B5) (if the unit has a water battery) 16 6.3 Outdoor air damper (if the unit has a water battery) 16 7 Plumbing work* 16 8 Adjusting EC units 17 8.1 Adjustment with CI6 17 8.2 Adjustment with CI6 18 9 Adjusting AC units 19 1 Installation of external cooker hood 2 1.1 Kitchen hood without motor 2 1.2 Kitchen hood with motor 2 11 Adjusting the kitchen hood 2 11.1 Kitchen hood without motor 2 11.2 Kitchen hood with motor 2 12 General and system drawings 21 12.1 System drawing (electric battery) 21 12.2 System drawing (without heater) 21 12.3 System drawing (electric battery) 22 12.4 System drawing (electric battery) 22 12.5 Nipple location 23 13 Technical data 23 14 Sizes/Physical dimensions 24 15 Capacity and sound data, EC 25 15.1 Supply air side 25 15.2 Extract air side 25 16 Capacity and sound data, AC 26 16.1 Supply air side 26 16.2 Extract air side 26 17 Final checks / Starting 27 17.1 Final checks 27 17.2 Starting 27 18 CE Declaration of Conformity 27 2

! Important Safety Instructions: It is the installer's responsibility to carry out a full safety and function assessment of the appliance. To reduce the risk of fire, electric shock or injury, read all the safety instructions and warning texts before using the appliance. This unit is only designed for ventilation air in homes and commercial buildings. It must not be used to extract combustible or flammable gases. Remove the power plug before commencing any service and maintenance work. Before opening the door: switch off the heat, let the fans continue for 3 minutes to remove hot air, unplug the unit and wait 2 minutes before opening the doors. The unit contains heating elements that must not be touched when they are hot. The unit must not be operated without the filters being in place. Tumble dryers should not be connected to the unit. To maintain a good indoor climate, comply with regulations and avoid condensation damage, the unit must never be stopped apart from during service/maintenance or in connection with an accident. Symbols used These products bear a number of symbols used for labelling the actual product and in installation and user documentation. Supply air Extract air Kitchen air Danger! electricity DANGER! DO NOT TOUCH Exhaust air Outdoor air 111679! CAUTION! When a text bears this symbol, it means that personal injury or serious damage to the equipment may result if the instructions are not followed. NB! When a text bears this symbol, damage to equipment or poor efficiency may be the consequence of not following the instructions. EXAMPLE OF NIPPLE LOCATION (shown as a right-hand model) 3 According to IEC/EN 6335-1 Note that the product is not designed for operation by persons with impaired physical, motor or mental abilities. Nor may the product be used by persons lacking experience or knowledge, unless they have received guidance or instructions in operating the product safely by a person responsible for safety. Children must be instructed not to play with the unit. R Our products are subject to continuous development and we therefore reserve the right to make changes. We also disclaim liability for any printing errors that may occur.

1 Planning and preparation work 1.1 Joiner / fitter Door gaps At least 1-2 mm from the floor where air is to pass through. The air moves from rooms with supply air valves to rooms with extract air valves. Kitchen If the kitchen fan is designed with a motor, sufficient supply air must be ensured. See chapters 1 and 11 for more information. Fireplace If a fireplace is used, sufficient supply air must be ensured, e.g. by installing a wireless forcing switch (product code 11983). Location in the building Location of the unit on an internal wall requires insulation of the wall, cut-off studs and boards, and double plasterboard or a wall structure of similar quality (see chapter 2.1 on installation). Cabinet units in wet rooms should be placed outside zone 2. Hanging a cabinet unit Suitable transoms between studs are required for the screws (min. 48x98 mm). Access The unit must have good access for service/maintenance. See chapters 2 and 3 for details. 1.3 Electrician Power supply The units have an approx. 2.5 m cable with plug and require a single-phase earthed socket nearby. Plug requirements: 1 A. It is important for the plug to be accessible for servicing when the unit is fully installed. If a separate kitchen hood is used, it must have its own socket (1A) in the area above the cabinet. If the kitchen hood is going to be connected to the ventilation unit, a minimum Ø16 conduit must be installed for the two-core signal cable. NB! The PG nipple for the power cable must be tightened with a torque of 6. Nm if the cable is replaced. Wiring for control switches. Ø2 conduit for running the trailing cable for controlling the unit to be laid between the unit and an easily accessible place in the home (e.g. outside the bathroom) and terminated with a flush-mounted single wall box. The control switch is located here. The control cable must be located min. 3 cm away from any power cables. The control cable must be max. 24 m to ensure a signal. Control panel The control panel is designed for flush mounting over a single wall box or surface mounting on the wall. Fire requirements Any fire safety requirements must be clarified. Duct covers Plan and calculate the exact positioning of the unit and duct cover carefully before you start. See chapters 2.3 and 4 for more information. The positioning of heat sources must be coordinated with extract air valves so that heat is not sucked straight out through a valve or door gap. 1.2 Plumber (if the unit has a water battery) The water pipe layout and positioning of the water battery (channel battery) must be planned. These must be kept warm to avoid frost damage. A closing air damper with spring must be used. See separate instructions that accompany the water battery.! The installation instructions for the individual products must be followed. 4

2 Installation The unit can be installed in the following ways: 1. Horizontally on a wall. In this case the enclosed wall bracket is used for installation. Duct covers are available as accessories. 2. On the floor (lying on its back). In this case absorption feet are recommended (available as an accessory). 3. On the ceiling. The unit is mounted straight on the ceiling without a wall bracket. The unit comes in both a left-hand and a right-hand version, depending on what is best with regard to duct positioning. Fig. 1 3 1 2 2.1 In the box Fig. 2 A 1x B 4x C D E F G H 1x 4x 4x 1x 1x 1x # Description For installation Wall Ceiling Floor A Wall mounting x - - B Ties for duct insulation x x x C Screws for wall mounting x x - D Wall plugs (x) (x) - E, F Hinge stop for door - x x G Screws for hinge stop - x x H Strap for securing door - x x 5

2.2 Wall mounting Fig. 2 2.2.1 Positioning requirements The unit is designed to be installed in boiler rooms, laundry rooms, stores, lofts or other suitable areas. living ROOMS In wet rooms the unit and electrical connection must be located outside zone 2: min..6 m from the edge of the bath and 1.2 m from the shower head. The unit should be positioned against a wall that has no room on the other side that is sensitive to noise. The wall should be soundproofed with, for example, rock wool, to reduce the transfer of sound. Double plasterboard in the wall, cut-off studs and cut-off plasterboard are recommended (see Fig. 2). If the unit is put in a warm room where a lot of moisture is generated (shower, drying cupboard, etc.), condensation may form on the outside of the unit during periods when the outside temperature is low. BOIleR ROOM living ROOMS 2.2.2 Space requirements The unit must be installed with sufficient space for servicing and maintenance such as changing the filters and cleaning the fans and rotary wheel-type heat exchanger (see Fig. 3). The control cable with plug for automatic operation on top of the unit must be easily accessible when the unit is fully installed. suitable insulation these are minimum requirements and only take service needs into account. BOIleR ROOM National statutory requirements for electrical safety may deviate from this. Check which rules apply in your country. Fig. 3 78 mm 4 mm (minimum) 5 mm 5 mm ROTOR 4 mm 6

Fig. 4 The wall bracket provided is used for wall mounting. CeIlING The wall bracket (Fig. 4) screws to the wall with the screws provided. The unit is suspended from the wall bracket (Fig. 5). The top edge of the wall bracket should be mounted 75mm higher than the top of the unit. If, for example, the top of the unit is be 4 mm below the ceiling, the wall bracket should be mounted 325 mm from the ceiling, measured from the ceiling to the top edge of the wall bracket. A Fig. 5 A 7

2.3 Floor mounting 2.3.1 Positioning requirements In the case of floor installation absorption feet should be used (see Fig. 6) to reduce noise and vibration. Flexit offers suitable absorption feet as accessories (product code 11955). They fit in the holes on the back of the unit. The unit should be positioned in such a way that there is no danger of noise nuisance in nearby rooms. It is especially important not to position the unit directly above bedrooms. The base should be stable and level. In wet rooms the unit and electrical connection must be located outside zone 2: min..6 m from the edge of the bath and 1.2 m from the shower head. If the unit is put in a warm room where a lot of moisture is generated (shower, drying cupboard, etc.), condensation may form on the outside of the unit during periods when the outside temperature is low. 2.3.2 Space requirements The unit must be installed with sufficient space for servicing and maintenance such as changing the filters and cleaning the fans and recovery system (see Fig. 17). The control cable with plug for automatic control must be easily accessible. these are minimum requirements and only take service needs into account. National statutory requirements for electrical safety may deviate from this. Check which rules apply in your country. Fig. 7 Fig. 6 4 mm ROTOR 1mm 78 mm 4mm absorption feet 5 mm 5 mm 8

Fig. 8 The door of the unit is too heavy to support itself when the unit is on its back. It therefore has to be secured with two hinge stops and a safety strap. The hinge stops attach with the screws provided when the door is closed (see Fig. 8 and 9). The strap is attached to the inside of the door and the inside of the unit (see Fig. 1). It can be attached to either the leftor right-hand side, as required. Fig. 9 e,f G Fig. 1 H 9

2.4 Ceiling mounting 2.4.1 Positioning requirements The unit should be positioned in such a way that there is no danger of noise nuisance in nearby rooms. It is especially important not to position the unit in the vicinity of bedrooms. The base should be stable and level. In wet rooms the unit and electrical connection must be located outside zone 2: min..6 m from the edge of the bath and 1.2 m from the shower head. If the unit is put in a warm room where a lot of moisture is generated (shower, drying cupboard, etc.), condensation may form on the outside of the unit during periods when the outside temperature is low. 2.4.2 Space requirements The unit must be installed with sufficient space for servicing and maintenance such as changing the filters and cleaning the fans and recovery system (see Fig. 12). The control cable with plug for automatic control must be easily accessible when the unit is fully installed. 2.4.3 Mounting The unit has five holes for ceiling mounting (see figur 13). 2.4.4 Mounting in concrete Steel expansion bolts (M5 or M6) are recommended for mounting in concrete. Plastic wall plugs are not recommended. Fig. 13 742 mm 16mm 6 mm these are minimum requirements and only take service needs into account. National statutory requirements for electrical safety may deviate from this. Check which rules apply in your country. 3 mm 3 mm 16mm Fig. 11 Fig. 12 5mm 5mm 4mm 1mm 78mm ROTOR 4mm 1

! The door must be secured with the end studs and strap provided when the unit is mounted on the ceiling. There would otherwise be a risk of the door falling off and causing injury. Fig. 13 The end studs attach with the screws provided when the door is closed (see Fig. 13 and 14). The strap is attached to the inside of the door and the inside of the unit (see Fig. 15). It can be attached to either the leftor right-hand side. Fig. 14 e,f G Fig. 15 H 11

3 Duct connection 3.1 Connection to the unit See Fig. 16. Ensure that the ducts arrive at the right nipple - see the markings on top of the unit and chapter 11. Pull the duct insulation well up to the unit. To avoid the formation of condensation, it is particularly important for the outdoor and exhaust air ducts to have insulation and a plastic sleeve pulled right down to the unit. Seal the plastic sleeve to the unit with the ties provided. The outdoor air duct normally requires 5 mm insulation. Lay the outdoor air duct with a slight incline towards the outdoor air cap so that any water that enters drains out again. The supply air and extract air ducts should have good sound insulation, particularly above the unit. All ducts that pass through a cold zone must be insulated. If flexible sound insulation is used, additional insulation is recommended with regard to noise. Fig. 16 The plastic sleeve is pulled right down to the unit. 3 Fasten the sleeve with ties. The duct insulation with plastic jacket is guided right down to the polystyrene around the nipple. It is very important that there are no gaps between the duct insulation and the polystyrene, as this could lead to condensation and/or the formation of ice. 4 2 Pull the spiral pipe well down over the seal on the nipple. 1 12

4 Cover For service reasons the cover must have a hatch or removable front. 4.2 Duct covers Flexit duct covers are available as accessories (see Fig. 17). To prevent the transmission of noise and vibrations, the cover and unit should not be in direct contact with each other. 4.1 Preparations The positioning of the cover is naturally affected by the positioning of the unit. Therefore plan the positioning of both the unit and the cover prior to installation. The radiated noise from the unit specified in the sound data does not include possible noise from ducting. The cover should therefore be soundproofed too. Fig. 17 13

5 Installation of the CI6/6 control panel 5.1 Contents Fig. 18 4 1 2 3 5 1. Control panel 2. Back piece for flush mounting 3. Back piece for surface mounting 4. Installation instructions 5. Cable for control panel 5.2 Installation of the CI6/6 Fig. 19! The control units must be connected to the unit before power is connected to the unit in order to ensure communication. Run the cable for the control panel between the ventilation unit and the control panel. The control panel is designed for flush mounting over a single wall box (use shallow back piece (2)) or surface mounting on the wall (use deep back piece (3)). The cable clicks into the contact on the control panel from the back and into the contact on the top of the ventilation unit. The low-voltage cable must be at least 3 cm from power cables and not exceed 24 m in length. In the case of flush mounting the cable is run in a 2 mm wiring conduit. It is possible to connect two CI6 panels and one CI6 panel to each unit. If several CI6 panels are used, each panel must have a separate identity. This can be selected by means of a switch on the panel's circuit board (see Fig. 19). Use relevant settings from the table. The panels can be connected in series in any way. OFF = MASteR ON = SlAVe Configuration CI 6 (MASTER) CI6 1 (SLAVE) CI6 2 (SLAVE) CI6 1 (MASTER) CI6 2 (SLAVE) CI 6 (MASTER) CI6 (SLAVE) ON OFF Setting Automatic OFF ON OFF ON Automatic Any 14

5.3 Installation with a flush-mounted wall box Run the cable between the wall box and the ventilation unit in the pre-installed wiring conduit. Fit the back piece (2) over the wall box and click the cable in straight from the back as shown in the illustration (see Fig. 2). 5.5 Finishing off CI6 Slide the panel off as shown by arrow no. 1 (see Fig. 22) and fit the control panel straight into the back piece as shown by arrow no. 2 (see Fig 23) until it clicks into place. Slide the panel back on. Fig. 22 Fig. 23 Fig. 2 1 2 5.4 Surface mounting Lay the cable between the back piece (3) and the ventilation unit. Cut out the most suitable perforation in the corner of the back piece. Secure the back piece to the wall with suitable screws. Click the cable into the control panel from below where there is a socket in the circuit board (see Fig. 21). 5.6 Finishing off CI6 Fit the control panel over the hooks in the back piece as shown by arrow no. 1 and then click the panel into place at the bottom edge as shown by arrow no. 2 (see Fig. 24). Fig. 24 1 Fig. 21 2 15

6 Electrical work! The unit must be installed with an earth fault breaker. All electrical connections must be carried out by qualified electricians. The unit is supplied with a 2 m cable with plug. The cable comes out of the top of the unit and is connected to a 23 V 5 Hz single-phase earthed power point that is placed in an easily accessible position close by. The power plug should be used as the service switch. See chapter 12 for fuse sizes. Ensure that the plug for the unit is not boxed in. 6.2 Frost sensor for water battery (B5) (if the unit has a water battery) To avoid frost in the battery, a water battery sensor (B5) must be installed in the water battery pipe where the cold water leaves the battery. For more information see instructions for water battery. 6.3 Outdoor air damper (if the unit has a water battery) To avoid frost damage to the water battery during outages/ power cuts, a closing air damper must be installed on the outdoor air duct. The damper motor must have a spring so that it closes when power is disconnected. The control panel is designed for flush mounting over a single wall box or surface mounting on the wall. The unit has a control cable (with joint) that is intended for the control panel. It is important that this plug is easily accessible afterwards for possible faults, or when changing the unit. The control cable is enclosed in the packaging for the control panel. 7 Plumbing work* *If the unit is going to have heating with a water battery. All plumbing work must be carried out by an authorised plumber. See instructions for water battery. The control panel is an a box in the unit's packaging. The low-voltage cable must be laid between the unit and the switch unit. See chapter 5 about automatic control. The control cable must be max. 24 m long. It must be at least 3 cm from power cables and should be laid in a 2 mm wiring conduit at installation. 6.1 Supply air sensor for heating (B1) (if unit has a water battery) Temperatre sensor B1 must be positioned after the water battery. This must be placed in the supply air duct (red on Flexit drawing/symbol use page 3) approx. 1 m from the water battery. Roll out the marked coil of cable on the unit near the supply air nipple. Drill a Ø 7 mm hole in the duct where the sensor can be inserted. Seal the hole with acrylic sealant and tape the cable in place on the outside of the duct so that it stays in place. See the wiring diagram enclosed with the unit and the instructions that come with the water battery. 16

8 Adjusting EC units 8.1 Adjustment with CI6 The unit's air supply MUST be adjusted before the unit is used for the first time. This should be done in accordance with the projection documents. Adjust the values based on the projected values. Fig. 25 8.1.1 Adjustment 9 8 Only stage 2 (NORMAL) needs to be adjusted. Stages 1 and 3 have fixed settings, while stage 2 has to be adjusted as required in the individual home. The function of the different stages: MIN Must not be used when the home is in use. Must not be used in the first two heating seasons. NORMAL Used under normal conditions. On this setting the air supply must be adjusted according to current regulations. MAX Used if there is a need for increased air supply on account of higher occupancy or a raised humidity level, for example during showering or when clothes are being dried. This setting is normally used for limited periods. 1 11 The ventilation unit's air supply is adjusted in speed level NORMAL using the knobs on the back of the cover. Knob 9 is used for supply air level and knob 8 for extract air level (see Fig. 25). The adjustment range is 2-1% of the maximum level according to the scale on the knob. Factory settings for supply air/extract air: MIN 5% (fixed) NORMAL 75% (variable) MAX 1% (fixed) 8.1.2. Adjusting the temperature The temperature required for the supply air can be set with knob 11. The adjustment range is 1-3 C. It should normally be set to around 18 C. Use of the factory setting is recommended. If necessary, the ventilation unit's additional heating can also be switched ON/OFF with switch 1. In this case only the rotating heat exchanger is used as a source of heat. It is best to leave it in ON position, as the unit will then respond automatically when there is a need for additional heating. 17

COOLING TIME AND DATE EXTRACT AIR NORMAL FIRE NEUTRAL MAIN TIME ZONE AND MENU DATE OK? TIMER MAX NORMAL OK? COM EXT. MAIN TEMP. CONTROL MENU AIR VOLUME MAX MAX COMP OK? TIMER STAR MAX TIMER REST START MENU MAIN MENU TEMPERA UNI 2 Installation Instructions LANGUAGE OK? MIN TIME AND DATE NORMAL SETTINGS MAIN MENU MAX SETTINGS OK? 8.2 Adjustment with CI6 MAX TIMER START UP MENU TEMPERATURE START UP REGULATION MENU This dialog is identical FAN MAIN REGULATION MENU The unit's air supply MUST be adjusted before MAIN MENU for the 2supply air and extract air fans. 18 the unit is used for the first time. This should The fans are adjusted individually to the desired capacity for be done in accordance with the projection the SETTINGS respective speed. HEATING documents. Adjust the values based on the projected values. REGULATION START UP TYPE SUPPLY MAIN MENU AIR MENU SEN HE MAIN MENU HE MAIN MENU 2 8.2.1 Adjustment REGULATION EXTR OK? MIN SPEEDMIN 5% OK? SUP MAX SUPPLY AIR TEMP 35 NORMAL SPEED NORMAL MIN 75% EXT HEA MIN SUPPLY AIR TEMP 15 MAX SPEEDMAX NORMAL 1% OK? OUT HEA Only stage 2 (NORMAL) needs to be adjusted. MAX MAX OK? TIMER RETU MAX TIMER FILT Note that it is also possible to adjusted stages 1 and 3 MAIN MENU HEATING with a CI6 control panel. This should only be done if a MIN special need arises, however. This is because it is extremely NORMAL SETTINGS important to have adequate air flow rates. MAX SETTINGS OK? HEATING EL MAX TIMER The function of the different stages: Factory settings REGULATION TYPE 1 MAIN for INLET MENU supply air/extract air: AIR MIN Must not be used when the home is in use. Must MIN MAIN 5% MENU (variable) 2 not be used in the first two heating seasons. SETTINGS NORMAL 75% (variable) NORMAL Used under normal conditions. On this setting MAX 1% (variable) the air supply must be adjusted according to REGULATION current regulations. TYPE EXTRACT AIR SU 8.2.2 MAIN temperature MENU 2 regulation MAX REGULATION Used if there is a need for increased SUPPL OK? air supply MIN SPEED 5% OK? In this menu screen (located under "Advanced user") you CAL NORMAL SPEED 75% on account of higher occupancy or a raised configure MAX SPEED the temperature regulation 1% and cooling functions. humidity level, for example during showering PIN or CODE when clothes are being dried. This setting is PIN normally CODE used for limited periods. TEMPERATURE REGULATION TEMPERATURE REGULATION FA FA First go to the "Advanced user" menu, enter the PIN and press OK: OK? PIN CODE1 OK? REGULATION TYPE 2 1 COOLING COOLING MIN OUTDOOR TEMP MIN SPEED RESTART DELAY OK? COOLNESS ADVANCED RECOVERY USER Then go to ADVANCED the "Fan PIN control" CODE USER menu. The fans are selected and configured in TEMPERATURE this menu screen. REGULATION Then go to adjustment of FAN TEMPERATURE REGULATION REGULATION OK? the extract air fan and supply air fan. CONFIGURATION FAN REGULATION OPERATING CONFIGURATION TIME FAN REGULATION FACTORY OPERATING SETTINGS TIME ADVANCED SERVICE FACTORY USERSETTINGS SUPPLY AIR SERVICE EXTRACT TEMPERATURE AIR REGULATION TIMER FAN REGULATION AIR VOLUME CONFIGURATION COMP OPERATING TIME FACTORY SETTINGS SERVICE KJØLING OK? OK? COOLNESS ADVANCED RECOVERYUSER ADVANCED USER COOLNESS RECOVERY DIFF PIN CODE PIN CODE AV 18 MIN 18 s OFF 1 OK? OK? OK? REGULATION TYPE COOLING REGULATION TYPE NEUTRAL COOLING ZONE EXT. NEUTRAL TEMP. ZONE CONTROL EXT. TEMP. CONTROL TEMPERATURE REGULATION EXTRACT AIR REGULATION TYPE COOLING NEUTRAL ZONE EXT. TEMP. CONTROL OK? Regulation TIMER TEMPERATURE type REGULATION If supply TEMPERATURE STANDARD air regulation SPEED is REGULATION selected, MAXno OK? further settings can be set STANDARD here. If TIME extract air regulation 3 m is selected, the max. and min. supply air temperatures can also be specified. REGULATION TYPE TEMPERATURE REGULATION TYPE REGULATION REGULATION MAX REGULATION SUPPLY AIR TEMP MIN MAX SUPPLY AIR TEMP MIN SUPPLY AIR TEMP REGULATION TYPE REGULATION MAX SUPPLY AIR TEMP MIN SUPPLY AIR TEMP TIMER EXTR OK? 35 15 AIR VOLUME REGULATION COMPENSATION TYPE REGULATION TYPE 1 SUPPLY AIR EXTRACT AIR MAX MIN OK? OK? EXTR OK? 35 EXTR OK? 15 35 15 OK? SUP EXT SUP TIM EXT AIR TIM AIR FAN REG SUPPLY AIR EXTRACT A TIMER AIR VOLUM FILT ACT SU SU MIN NO MIN MA NO MA SUPPLY A MIN SPEED NORMAL SP MAX SPEED FIR MO OPERATING FAN REGULATION INFORMATION OPERATING ADVANCED INFORMATION USER SET TEMPERATURE 22 DAY SET TEMPERATURE / WEEK SETTINGS AKTIV 22 18 REGULATION TYPE REGULATION REGULATION TYPE TYPE 1 REGULATION REGULATION SUPPL OK? SUPPL OK? EX EX MIN NO MIN NO

9 Adjusting AC units The unit's air supply MUST be adjusted before the unit is used for the first time. This should be done in accordance with the projection documents. Adjust the values based on the projected values. Fig. 26 Only stage 2 (NORMAL) needs to be adjusted. Stages 1 and 3 have fixed settings, while stage 2 has to be adjusted as required in the individual home. The function of the different stages: MIN Must not be used when the home is in use. Must not be used in the first two heating seasons. NORMAL Used under normal conditions. On this setting the air supply must be adjusted according to current regulations. MAX Used if there is a need for increased air supply on account of higher occupancy or a raised humidity level, for example during showering or when clothes are being dried. This setting is normally used for limited periods. Unlike units with EC fans, AC models are adjusted using switches in the electrical compartment (see Figure 26). Adjusting parameters on the CI6 or CI6 control panel will not affect fan speeds on a unit with AC fans. It is possible to access a wide range of voltages by moving the cable set's contacts on the transformer and so adjust the air flow rate for stage 2. Supply air/extract air setting: MAX 23 V 19 V (only available by making change on transformer) NORMAL 17 V 15 V (factory setting) 12 V 15 V (only available by making change on transformer) MIN 85 V SUPPlY AIR extract AIR 19

1 Installation of external cooker hood If an external kitchen hood is going to be used, documentation regarding installation and adjustment of air flow rates is supplied with the product. Duct length between ventilation unit and cooker hood should not exceed 6m. 1.1 Kitchen hood without motor The ventilation unit has a separate connection point for kitchen hoods without a motor. A two-core low-voltage cable with a potential-free contact on the kitchen hood must be run between the unit and the hood in order to force the system. 1.2 Kitchen hood with motor A forcing switch (product code 11983) can be installed as an accessory to send a signal to the ventilation unit when the hood is in use. 11 Adjusting the kitchen hood If the hood is not supplied by Flexit, the supplier of the kitchen hood must plan air flow rates both for extract air and in the hood, and arrange for supply air to the hood. 11.1 Kitchen hood without motor The air flow rate over the hood is regulated according to the planned air flow rate. Flexit's kitchen hoods handle odour absorption up to 15 m³/h. It is not necessary to compensate for the supply air fan to achieve a balanced air flow rate. 11.2 Kitchen hood with motor If a kitchen hood with a motor is used, the volume of air extracted from the building increases. The ventilation unit can be adjusted to provide more supply air than extract air to compensate for this. This can be done using a forcing switch (accessory product code 11983), which sends a signal to the ventilation unit when the hood is in use. The supply air fan will shift up to MAX, while the extract air fan continues on NORMAL. This is necessary in order to balance the ventilation in the building. Check the maximum air capacity of the kitchen hood (based on the capacity diagram) against the maximum capacity of the supply air fan. If the kitchen hood has a higher capacity than the unit's supply air fan, the unit will not manage to compensate for the loss of air and sufficient supply air must be arranged in some other way. 2

12 General and system drawings Fig. 26 12.1 System drawing (electric battery) (shown as left-hand model) B1 Supply air temperature sensor B4 Outdoor air temperature sensor EB1 Heating element F1 Overheating thermostat, manual reset F2 Overheating thermostat, automatic reset FI1 Supply air filter FI2 Extract air filter M1 Supply air fan M2 Extract air fan HR-R Rotary wheel-type heat exchanger M4 Rotor motor K Kitchen hood F1 F2 Supply air EB1 B1 Outdoor air FI1 B4 HR-R Exhaust air M2 K Extract 11xxx air FI2 M4 M1 12.2 System drawing (without heater) (shown as left-hand model) B1 Supply air temperature sensor B4 Outdoor air temperature sensor FI1 Supply air filter FI2 Extract air filter M1 Supply air fan M2 Extract air fan HR-R Rotary wheel-type heat exchanger M4 Rotor motor K Kitchen hood Fig. 27 Supply air B1 Outdoor air FI1 Exhaust air M2 K Extract 11xxx air FI2 B4 HR-R M4 M1 21

12.3 System drawing (electric battery) (shown as right-hand model) 1 FI1 Supply air filter F7 2 FI2 Extract air filter F7 3 M1 Supply air fan 4 M2 Extract air fan 5 HR-R Rotary wheel-type heat exchanger 6 M4 Rotor motor 7 Control unit 8 K Kitchen hood 9 B1 Supply air temperature sensor 1 B4 Outdoor air temperature sensor 11 EB1 Heating element 12 F1 Heating overheating thermostat man. 13 F2 Heating overheating thermostat auto 4 2 6 Fig. 28 8 9 1 7 12 13 11 1 5 3 12.4 System drawing (without electric battery) (shown as right-hand model) 1 FI1 Supply air filter F7 2 FI2 Extract air filter F7 3 M1 Supply air fan 4 M2 Extract air fan 5 HR-R Rotary wheel-type heat exchanger 6 M4 Rotor motor 7 Control unit 8 K Kitchen hood 9 B1 Supply air temperature sensor 1 B4 Outdoor air temperature sensor 4 2 6 Fig. 29 8 9 1 7 1 5 3 22

12.5 Nipple location Fig. 3 Left-hand model 111678 Right-hand model 111679 13 Technical data L R UNI 2 RE EC UNI 2 R EC UNI 2 RE AC Rated voltage 23 V 5 Hz 23 V 5 Hz 23 V 5 Hz Fuse 1 A 1 A 1 A Rated current, total 4,4 A,9 A 4, A Rated power, total 115 W 215 W 931 W Rated power, electric battery 8 W - 8 W Summed rated power, fans 212 W 212 W 128 W Rated preheating power - - - Fan type B wheel B wheel B wheel Fan motor control -1 V -1 V Transformer Fan speed - max. rpm 339 rpm 339 rpm 25 rpm Automatic control standard CU6 CU6 CU6 Filter type (TO/FROM) F7 F7 F7 Filter dimensions (WxHxD) 335x13x113 mm 335x13x113 mm 335x13x113 mm Weight 45 kg 45 kg 45 kg Duct connection Ø125mm Ø125mm Ø125mm Height 78 mm 78 mm 78 mm Width 632 mm 632 mm 632 mm Depth 48 mm 48 mm 48 mm 23

14 Sizes/Physical dimensions Fig. 31 632 mm 48mm 78mm 73mm 374mm 29mm 1 mm 121 mm 95 mm 95 mm 121 mm 48mm 11 mm 131 mm 39 mm Ø=125mm Ø=172mm Left-hand model 1 mm 121 mm 95 mm 95 mm 121 mm 11 mm 34 mm 131 mm Ø=125mm Ø=172mm Right-hand model 24

5 4 1% 8% 15 Capacity and sound 3 data, EC 1% UNI 2 Installation Instructions 1 8 6 15.1 Supply air side Fig. 32 Contact resistance [Pa] 15.2 Extract air side Fig. 33 2 6% 1 64% 5 2 8% 6% 1 4% 8% 4% 1 6% Air flow rate [l/s] 2 4 6 8 1 77dB (A) 75dB (A) (A) 65dB (A)7dB 6dB (A) 2 3 4 1% 4-6 -15-26 [Pa] 1% 8% 3 [Pa] 4% 1 6% -6-1 -15-19 -22-25 -28-29 77dB (A) 75dB (A) (A) 65dB (A)7dB 6dB (A) 2 3 4-6 Air flow -15-26 rate [l/s] [Pa] 2 4 6 8 1-6 -1-15 -19-22 -25-28 -29 [Pa] 1% 4 2 1 8 6 4 2 Yellow field: SFP < 1. per fan Power consumption [W] Air flow rate [m³/h] Yellow field: SFP < 1. per fan vann hybrid vann hybrid 5 1 Fig. 34 Contact resistance [Pa] 4 3 2 5 1% 8% 6% 1 4% 6% 8% 4% 2 4 6 8 1 73dB (A) 7dB (A) 55dB (A) 6dB 1% (A) 65dB (A) 1 2 3 4 Correction 4-6 -15-25 factor for Lw 8% 8 [Pa] Hz 1% 63 125 25 5 1 2 4 8 LwA Supply 3air -6-1 -15-19 -8-22 -25-1 -28-18 -29-35 6 [Pa] Extract air 6 4 4-1 -13-14 -31-47 8% 6% Radiated 2-44 -37-31 -35-38 -4-5 -56-32,3 4 8 6 4 2 1 Power consumption [W] Air flow rate [m³/h] 1 6% 4% 4% 25 73dB (A) 7dB (A) 65dB (A) 6dB (A) 2

UNI 2 2 Installation 4 Instructions 6 16 Capacity and sound 3 data, AC 6 16.1 Supply air side Fig. 35 Contact resistance [Pa] 16.2 Extract air side Fig. 36 23V 2 19V 17V 15V Air flow rate [l/s] 12V 3 15V 1 85V 12V 23V 15V 6V 85V 19V 23V 2 19V 17V 5dB (A) 17V 7dB (A) 6V 15V 15V 1 2 3 12V 15V 12V 1 85V -1 [Pa] 15V -25-55 -9 6V -6 85V -1-15 -19-22 -25-28 -29 7dB (A) [Pa] 6V 65dB (A) (A) 55dB (A)6dB 5dB (A) 1 2 3 [Pa] [Pa] -1-25 -55-9 2 19V 23V 4 6 17V 15V -6-1 -15-19 -22-25 -28-29 Air flow rate [l/s] 2 4 6 Yellow 4field: SFP < 1. per fan Power consumption [W] 6 2 4 2 Air flow rate [m³/h] Yellow field: SFP < 1. per fan vann hybrid vann hybrid Contact resistance [Pa] 3 23V 23V 19V 17V 2 2 19V 15V 4 6 17V 15V 12V 12V 3 15V 1 23V 85V 15V 23V 19V 6V 85V 17V 65dB (A) 2 19V 6V 15V (A) 6dB (A) 5dB (A)55dB 17V 45dB (A) 15V 1 2 12V 12V 15V 1-1 -25-55 -9 [Pa] 85V 15V Correction 6V factor -6 for -1 Lw -15-19 -22-25 -28-29 [Pa] Hz 63 125 25 5 1 2 4 8 LwA 5dB (A)55dB (A) 6dB (A) 65dB (A) Supply air 7 6 45dB 2 (A) -1-9 -11-15 -4 Extract air 4 1 5-7 -21-21 -4-54 Radiated -39-33 -1-24 -25-31 -37-55 -37-9 -42-56 -28,3 [Pa] -6-1 -15-19 -22 26-25 -28-29 [Pa] 85V 6V 1 2 3 3 6 4 6 2 4 Power consumption [W] Air flow rate [m³/h] 2

17 Final checks / Starting 17.1 Final checks Check the following points: Description Chapter Performed Duct insulation has been carried out 3 in accordance with the manual and technical documents Ducts have been connected to the 11 correct nipples Adjustment has been carried in 8 accordance with the manual and projection documents The unit operates normally in all stages - Rotor rotates freely (sense of rotation - indicated on rotor module) Rotor rotates when heating is required - Heating comes on - Unit has filters for both outdoor air and extract air 11 18 CE Declaration of Conformity This declaration confirms that the products meet the requirements in the following Council Directives and standards: 24/18/EC Electromagnetic Compatibility (EMC) 26/95/EC Low-voltage Directive (LVD) 26/42/EC Machine Directive (Safety) Producer: FLEXIT AS, Televeien 15, 187 Ørje, Norway Type: UNI 2 R Ventilation Unit Complies with the following standards: Safety standard EN 6335-1:22 EMF standard: EN 5366:23 EMC standard: EN 5514-1.2 EN 61-3-2:2 EN 61-3-3:1995 EN 5514-2:2:1997 17.2 Starting Check that the control panel has been wired up and was connected before the unit was started up. Connect the mains plug to the unit. The unit will now start. The unit will automatically carry out a startup procedure lasting approx. 1 min. After the startup procedure the unit will follow the operating settings set on the control panel and, in the case of AC models, on the adjustment panel/transformer. Changes in settings are made from the control panel. Adjustment has been carried out in accordance with the manual and projection documents (documentation of ventilation data). The product is CE-marked: 211 FLEXIT AS 23.8.211 Frank Petersen CEO 27

Flexit AS, Televeien 15, N-187 Ørje www.flexit.com