The Interaction of Contactors with PLCs



Similar documents
Contactor Monitoring Relay CMD Cost-Effective Solution for Safe Machines

Nothing s BetterThan the Original MODAN Power Distribution Systems

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Line Reactors and AC Drives

ABB i-bus KNX Switch Actuators SA/S Product Information

Easy Multifunctional Safe

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M Schaffhausen 1 / 10

A Practical Guide to Free Energy Devices

Type: DILM9 10(24VDC) Article No.:

3BASIC RELAY INSTRUCTIONS

ABB i-bus KNX Switch Actuators SA/S Product Information

Type: DILM32 10(24V50HZ) Article No.:

Number 1 in efficiency


THE INPUT/OUTPUT SYSTEM. Key Points

Specifications for EM VDC 4 In/4 Out and EM VDC 4 In/4 Relay Out

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Type: DILM50(230V50HZ,240V60HZ) Article No.:

DIL R Industrial Control Relays Basic Relay, Modules

SECTION VARIABLE FREQUENCY DRIVES

Three-phase monitoring relay CM-PFE

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Safety Relays ESM/ESM-F

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

48 SERIES Relay interface modules 10 A

Programming Logic controllers

Electrical Symbols and Line Diagrams

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

DC Motor control Reversing

49 Series - Relay interface modules A. Features

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Product Guide. Low voltage grounding system. Answers for industry.

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

INDUSTRIAL AUTOMATION EQUIPMENT EDITION

Type SA-1 Generator Differential Relay

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

40 Series - Miniature PCB/Plug-in relays A. Features

40.3. Control Relays and Timers

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Michelin North America

POINTS POSITION INDICATOR PPI4

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

38 Series - Relay interface modules A

Properties of electrical signals

IO-RM3 3-Stage Relay Module

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Export relevant information on supply distribution networks in North America

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Panorama. Motor protection and control Manual motor starters, contactors and overload relays

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Contact expansion modules

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3

Data Sheet. Electro-mechanical counters Hengstler 800 series

SAFETY MANUAL SIL RELAY MODULE

Electrical connection

Programming A PLC. Standard Instructions

Technicaldata General

conventional system operation

TEA1024/ TEA1124. Zero Voltage Switch with Fixed Ramp. Description. Features. Block Diagram

Considerations When Specifying a DC Power Supply

Points Position Indicator (PPI1) for Points Motors with Common Ground

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC C0201

Electrical safety. in control and auxiliary circuits. Safety objectives

Study Guide for the Electronics Technician Pre-Employment Examination

The full wave rectifier consists of two diodes and a resister as shown in Figure

Datasheet - DS0002 Indice Semiconductor Pty Ltd

7-41 POWER FACTOR CORRECTION

Rectifier filter stage post filtering sense

Modular I/O System Analog and Digital Interface Modules

SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

Smart DeviceNet Remote I/O Terminals

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

E-STOP relays, safety gate monitors

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.

Transformer circuit calculations

AlarmSense 2-wire detection and alarm system. Product Guide

SPI-8001TW. Switching Regulators. Dual 1.5 A, DC/DC Step-Down Converter. SANKEN ELECTRIC CO., LTD.

Reducing sizes of control power transformers and power supplies with Eaton s XT IEC motor control

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

60 Series - General purpose relays 6-10 A. Features

Technical catalogue. Modular DIN rail components Installation contactors

Pluggable interface relays CR-P Pcb relays

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

0.9V Boost Driver PR4403 for White LEDs in Solar Lamps

Contact expander modules

Application Note, Rev.1.0, September 2008 TLE8366. Application Information. Automotive Power

Application Note AN- 1095

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Transcription:

www.eaton.com/moellerproducts The Interaction of Contactors with PLCs Technical Paper Dipl.-Ing. Wolfgang Nitschky

Design and function of the DC operated contactors DILM7 to DILM170 The market for DC operated contactors continues to grow because of the advances in electronics manufacturing. Whereas 20 years ago AC operated contactors were fitted with additional resistors, and only recently special DC coils incorporating lots of copper were wound, the next quantum jump has been undertaken with the introduction of electronics in the magnet systems of DC operated contactors. The Xstart contactor series DIL M7 to DIL M170 has been optimised in particular during development to DC A1o A2o Surge protection Polarity Protection EMC filter Switching regulator DC DC Threshold value on Figure 1: Electronic contactor circuit block diagram Filter operated contactors. The DC operated contactors DIL M17 to DIL M170 are no longer switched on and off in the conventional manner via a coil, but rather the coil is controlled by electronics. [1] The electronic actuation features protection against polarity reversal which is used to supply the control voltage of the electronic control. Here the protection against polarity reversal will protect the contactor electronics from incorrect connection of the control voltage. The contactor will remain switched off in this case. Following the protection against Decoupling Threshold value off Control loop De-exicitation Drive Timer Logic Driver & Figure 2: Electronic contactor magnet system polarity reversal a filter circuit as well as a threshold trigger will regulate the level of the control voltage. Only after a minimum level for safe switch-on is achieved will a timer be triggered, which controls a driver for a defined switch on time and which thus initiates the switch on process of the magnetic drive. The driver is switched off after the set make time has timed out. The power supply to the magnet system coil is now undertaken using a DC/DC converter which provides a constant supply voltage that is about 10 % of the magnitude of the rated voltage. If there is an undershoot of the shut off threshold, the energization circuit is activated and the drive is de-energized via a defined freewheeling voltage. Based on the configuration of this circuit the break time of the contactor is on the one hand very constant and on the other fully independent of the mains power factors as well as the external circuitry. In conjunction with protection against polarity reversal the shutdown of a contactor has no negative effects on the power supply. Therefore an external suppressor circuit is not required. Technical characteristics of the DC operated contactors with integrated electronics and their advantages in engineering The integration of electronics in the contactor magnetic system makes various technical features possible which distinguish the contactor in its day to day use. Wide voltage range coils The DC operated contactors DIL M17 DIL M170 cover the complete DC control voltage range with just 4 control voltage variants. Rated actuating voltage: RDC24 24-27 VDC RDC60 48-60 VDC RDC130 110-130 VDC RDC240 200-240 VDC Table 1: Rated actuating voltage range 3

Voltage tolerance: RDC24 17-32 VDC RDC60 34-72 VDC RDC130 77-156 VDC RDC240 140-288 VDC Table 2: Range of the voltage tolerance Voltage tolerance Contactors are designed in compliance to the IEC/EN 60947-4-1 [2] standard. In order to guarantee operating security even with small deviations in the power supply, this demands safe switch on of the contactor in a range from 85 % to 110 % of the rated actuating voltage. The DC operated contactors DIL M17 DIL M170 feature an even wider range in which the contactors switch reliably. This enables safe operation between (0.7 x Ucmin) and (1.2 x Ucmax) of the rated actuating voltage. Integrated suppressor circuit Conventionally controlled contactors generate voltage peaks on the coil due to the di/dt change in the current which can have negative effects on the other components in the same control circuit. In order to avoid damage, suppressor coils are frequently connected in parallel with additional suppressor circuits (RC networks, varistors or diodes). The DC operated contactors DIL M17 DIL M170 switch off without noninteraction with the power supply (l Design and function of the DC operated contactors DILM7 to DILM170). The large contactors DIL M185 DIL H2000 are also controlled accordingly via electronics and are also free of interaction with the power sup- 4 140 V 70 % Plus 170 V 85 % Norm 200 V 100 % ply. An additional suppressor is therefore unnecessary as the coils do not generate any external overvoltages. All other DC operated contactors from Eaton Moeller feature an integrated suppressor circuit. All in all the issue of overvoltage protection in control circuits is no longer a problem when engineering DC operated contactors from Eaton Moeller, as all DC operated contactors are free of interaction with the power supply. Contactor dimensions The electronics provide the coil with a high switch on power for switching on 240 V 100 % Rated voltage of the contactor coils Figure 3: Representation of voltage tolerance 264 V 110 % Norm the contactor and reduces this after the switch on process has been completed to the required holding power. This makes it possible to implement AC operated and DC operated contactors of the same dimensions. When engineering AC and DC operated contactors consideration of the different mounting depths is no longer an issue. Pick-up and holding power Motor rating AC-3 at 400 V 288 V 120 % Plus Contactor type The electronics with the DC operated contactors DIL M17 DIL M170 controls the switch on process of the contactors. For pick-up of the contactor a correspondingly high power is provided which enables the contactor to safely switch. A very low power is required in order to retain the contactors state. The electronics only provide this power. The minimised holding powers mean a significant reduction in the heat development in the control panel in the engineering phase. This allows side-by-side installation of the devices in the control panel. Control of the contactors directly by the PLC s A typical application for DC operated contactors is the direct control from the PLC. Hereby a semiconductor output of the contactor is supplied directly with the control voltage. Typical semiconductor outputs of PLC s provide a power of 500 ma at 24 V. Contactors up to 32 A can be operated directly by a semi-conductor output of this type without the need for additional coupler relays. The engineering costs of DC power supplies can be reduced by the use of electronics. The power supply no longer needs to be engineered as with conventional contactor coils according to the sum of the pick-up powers. The power supply is engineered according to the following considerations: The sum of the switchon powers of all contactors which pick-up simultaneously are added to the sum of all holding powers of all contactors which are switched on simultaneously. As the holding powers are very low the power supply can be significantly smaller. Comparison of the holding powers with the competitors In direct comparison with the holding powers of DC operated contactors from 4 to 75 kw (Figure 4), it becomes apparent that the new Xstart series sets new standards on the market. The holding power of the contactors with integrated electronics is considerably less than all of the competitors. Pick-up power Holding power 7.5-15 kw DILM17 - DILM32 12 W 0.5 W 18.5-37 kw DILM40 - DILM72 24 W 0.5 W 37-45 kw DILM80 - DILM95 90 W 1.3 W 55-90 kw DILM115 - DILM170 149 W 2.1 W Table 3: Overview of the pick-up and holding powers for the new DC operated contactor series

Holding power DC of contactors 4-75 kw of important competitors 25 Competitor 1 20 Competitor 2 Holding power (W) 15 10 Competitor 3 Competitor 4 Eaton Moeller xstart 5 0 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 Motor rating (kw) Figure 4: Comparison of the holding power for DC operated contactors from 4-75 kw Combination with PLC s The direct control of contactor coils from the PLC reduces the costs for coupler relays and reduces the wiring effort involved. For this the output must provide both the pick-up and the holding power for the contactor coils. PLC s with different outputs are available on the market. In addition to expensive relay outputs, there are also semi-conductor outputs with different output currents available. Typically the semi-conductor outputs are offered with 0.1 A or 0.5 A, and the most common are the semi-conductor outputs with 500 ma. Table 4 provides an overview of the output required to control the corresponding contactor. For control with 100 ma outputs Eaton Moeller provides a special interface solution DIL M7-SOND516 to DIL M12- SOND516. Output power on transistor output DIL M7-SOND516 - DIL M12-SOND516 100 ma 500 ma DIL M7 - DIL M15 DIL M17 - DIL M32 DIL M40 - DIL M72 Table 4: Control of the Xstart contactors from the PLC s Combination with safe PLC s Monitoring function of safe PLC outputs A significant difference between PLC s for control of normal operational functions and safe PLC s is the cyclic monitoring of the PLC outputs in safety PLC s. Typically the outputs of master drives are controlled and cyclically briefly interrupted in safety PLC s. The interruption is in the order of just 10-50 ms, so that the connected actuators (contactors, valves) do not shut off. During the interruption it is monitored if the output voltage drops below a defined level. If this is not the case the PLC detects a defective output and switches off. A capacitive connection of the outputs dampens the drop of the voltage so that some manufacturers stipulate a maximum permissible capacitance on the safe outputs. Furthermore, the outputs are monitored for negative voltages. Combinations The contactors DIL M7 to DIL M15 contactors are controlled by conventional coils with varistor protective circuitry. They generate a negative voltage on terminals A1 A2 during switch off. Siemens Pilz Jokab Saftey Permissible output capacitance s 20nF 5nF not available Table 5: Permissible capacitance s on safe PLC outputs This is reliably prevented with an additional diode suppressor DIL M12-XSPD. Contactors DIL M7 to DIL M15, which feature diode suppressors operate reliably with all safe semi-conductor outputs of the conventional safety PLC s available. The magnet system of the contactors DIL M17 to DIL M32 are controlled by electronics. In order to protect the electronics against EMC the input on the PCB is protected against polarity reversal by a varistor which always represents a capacitive load. The coil input of the contactors DIL M17 to DIL M32 features a capacitive load of 5 nf. These contactors have been tested in combination with the safety PLC s from Pilz, Siemens and Jokab Saftey. Contactors DIL M17 to DIL M32 from manufacturing code 3106 and more recent devices operate perfectly with PLC s. 5

Feedback in the PLC In addition to direct control of the contactors from the PLC a feedback to the system concerning the state of the contactor is also generally required. This is generally possible with every contactor auxiliary contact. Eaton Moeller provides an electronic auxiliary contact DIL M32- XHIR11 specially optimised for smaller currents and voltages. This is suitable for currents of 1 ma at 5 V. The enhanced contact reliability ensures reliable feedback even in unfavourable environmental conditions, e.g. dusty atmosphere s. 1) does not apply for late-break contacts In combination with safety applications the state of the contactor must be fed back correctly even during a fault. Auxiliary NC contacts which are rated as mirror contacts are used for this purpose. All auxiliary contacts of the Eaton Moeller contactor series DIL M and DIL A are approved as mirror contacts. Even the electronic auxiliary switch is approved as a mirror contact and ideal for the combination with safety PLC s. Summary The new Xstart contactors DIL M17 to DIL M170 with DC operation excel due to their integrated electronics in the contactor magnet system. Because of the considerable reduction of the heat dissipation they enable direct actuation of the contactors DIL M7 to DIL M32 with a Mirror contacts to IEC EN 697-4-1 Annex F Integrated auxiliary contact 1) Auxiliary break contact 1) in additional auxiliary contact module DIL EM-10 No auxiliary break contact available yes DIL EM-01 yes yes DIL M7-10 - DIL M15-10 No auxiliary break contact available yes DIL M7-01 - DIL M15-01 yes yes DIL M17-10 - DIL M32-10 No auxiliary break contact available yes DIL M17-01 - DIL M32-01 yes yes DIL M40 - DIL M72 No auxiliary break contact available yes DIL M80 - DIL M170 No auxiliary break contact available yes DIL M185/22 - DIL M250/22 yes yes DIL M300/22 - DIL M500/22 yes yes DIL M580/22 - DIL M1000/22 yes yes PLC semi-conductor output without coupler relays. The control by a safety PLC with monitored outputs has also been tested. The new electronic auxiliary contact provides reliable feedback to the PLC and is also suitable as a mirror contact for safety applications. Author: Dipl.-Wirt. Ing. Wolfgang Nitschky Product Support Switching & Protection Devices Eaton Industries GmbH, Bonn Literature [1] Wilhelm Melchert and Gerd Schmitz Electronic contactor control Moeller GmbH 2004 [2] IEC/EN 60947-4-1: 2004-04, Low-voltage switchgear and controlgear Part 4-1: Contactors and motor-starters; Electromechanical contactors and motor-starters Table 6: Mirror contacts with Moeller contactors Advantages of the xstart contactor series in combination with PLCs Contactors with wide voltage range coils Simplifies engineering The enhanced voltage tolerance of the contactor coils Integrated suppressor circuit in the DC operated contactors Identical dimensions with AC and DC operated contactors Reduced heat dissipation of the contactors coils Tested combinations of contactors and safety PLC Electronic auxiliary contact Auxiliary contact with mirror contact function Guarantees reliable operation even in less stable power supply networks Provides protection for electronic components Simplifies engineering Improves the heat balance in the control panel, saves coupling relays as the contactors can be directly actuated, reduces costs for the power supply as a smaller power supply is required Offers a high level of functional safety Enables reliable feedback with small signal levels Reliably signals the position of the main contactor contacts Table 7: Advantages of the interaction of Xstart contactors with PLCs 6

Eaton Corporation Eaton is a leading power management company. Eaton operates worldwide with products, systems and services in the electrical, hydraulic, aerospace, truck and automotive sectors. Eatons Electrical Sector Eatons Electrical Sector is the worldwide leader in products, systems and services for energy distribution, safe electricity supply and automation in industrial, residential and purpose-built buildings, public facilities, energy providers, commerce and OEMs. E-Mail: Internet: Publisher: Eaton Corporation Electrical Sector EMEA Eaton Industries GmbH Hein-Moeller-Str. 7 11 D-53115 Bonn info-int@eaton.com www.eaton.com/moellerproducts 2010 by Eaton Industries GmbH Subject to alterations VER2100-957GB ip 03/11 Printed in Germany (03/11) Article No.:?????? Eaton Electrical Sector includes the brands Cutler-Hammer, Moeller, Micro Innovation, Powerware, Holec, MEM and Santak. www.eaton.com