Fiber Optic Cable Installation



Similar documents
Fiber Optic Cable Installation and Handling Instructions

ControlNet Standard and High-flex Coax Cable

Hard Disk Drive (HDD)

Universal Serial Bus (USB) to DH-485 Interface Converter

Stratix 5700 Network Address Translation. Quick Start

CompactLogix Power Supplies Specifications

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

MicroLogix 1100 Embedded Web Server

PREVENTIVE MAINTENANCE OF FIBER OPTIC CABLES AND OPTICS

Micro800 Programmable Controllers. Bulletin 2080 Selection Guide

Application Note Optical Fiber Cable

758 Heavy-duty Ratchet Guy Wire Cutter

Logix5000 Controllers Nonvolatile Memory Card

Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.

USB-to-Data Highway Plus Cable

Application Technique. Safety Function: Magnetic Door Switch Monitoring

INSTRUCTION MANUAL IM042. Slide Rail Systems - Series A10 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

PART 1 - INTRODUCTION...

Logix5000 Controllers Import/Export Project Components

Reference Manual. Pressure/Temperature Compensated Flow (P_PTComp) Version 3.1

Inspection and Cleaning Procedures for Fiber Optic Connections

User Manual. DeviceNet Network Configuration

Compaq Presario Desktop Products. Upgrading and Servicing Guide

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

RayClic Connection System Installation Instructions

RayClic Connection System Installation Instructions

4RU High Density Shelf Installation Instructions

Super Slider ADJUSTABLE FROM Model #HD26229

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

Product Compatibility and Download Center

Logix5000 Controllers Security

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

Cable management for rack-mounted systems

Optocore Guideline for Fiber Optical Cabling in Permanent Installations

Sip/Puff Switch User Guide

PowerFlex Dynamic Braking Resistor Calculator

Logix5000 Controllers Import/Export Project Components Programming Manual. Programming Manual

VERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249

Honda CX500 & GL500 Forum

RSLogix Guard PLUS! Programming Software

1756 ControlLogix Integrated Motion Modules Specifications

Module Connectors and Cable Specifications

INSTALLATION & OPERATING INSTRUCTIONS

POOL ROVER SERIES 2 ROBOTIC POOL CLEANER PRODUCT SETTINGS AND TROUBLESHOOTING GUIDE

Scotchgard Multi-Layer Protective Film 1004

MAINTENANCE & TROUBLESHOOTING

Logix5000 Controllers Function Block Diagram

Trillium 40 Axis Spring Tensioner Wire Replacement Instructions

BREEZE XLS ROBOTIC POOL CLEANER SETTINGS AND TROUBLESHOOTING GUIDE

Upgrading and Servicing Guide

INSTRUCTIONS FOR USE HUMIRA 40 MG/0.8 ML, 20 MG/0.4 ML AND 10 MG/0.2 ML SINGLE-USE PREFILLED SYRINGE

Dissolved Oxygen Sensors

WARNING: This product contains chemicals known to the state of California to cause cancer, or birth defects or other reproductive harm.

IMPORTANT SAFETY RULES TO FOLLOW

AERIAL FIBER OPTIC CABLE PLACEMENT

HDMI Fiber Optic Cable. DVI-D Fiber Optic Cable. User Guide

tire inflator with pressure gauge

Time Recorder Extension Module for the Dynamix 2500 Data Collector

Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement

AC and DC Drive System Installation Information

SC, FC and ST * Hot Melt Fiber Optic Connectors

AMERBRITE UNDERWATER WHITE LED POOL LAMP

INSTRUCTIONS FOR USE HUMIRA 40 MG/0.8 ML SINGLE-USE PEN

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

SERVICE GUIDE For WARN PULLZALL 120v AC &100v AC P/N &

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

Procedure for Cutting and Respooling Fiber Optic Cable

AutoRanging Digital MultiMeter

Zebra RW 420 Mobile Battery Eliminator Kits

Quick Start Guide See Inside for Use and Safety Information

CHECK WITH LOCAL CODE AUTHORITIES ABOUT INSTALLATION REQUIREMENTS FOR THIS PRODUCT INSTALLATION INSTRUCTIONS

DVD-60C The Seven Sins of Wire Harness Assembly

1756 ControlLogix Chassis Specifications

AT&T. PARTNER Plus Door Phone. Installation and Operation Manual

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

jbs nfb INSTALLATION INSTRUCTIONS AND OWNERS MANUAL Mechanical Steering for Inboard, Outboard, and Sterndrive Powered Vessels

ERGONOMICS. Improve your ergonomic intelligence by avoiding these issues: Awkward postures Repetitive tasks Forceful exertions Lifting heavy objects

MicroLogix 1400 Embedded Web Server

Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information

MICRO-COAX Space Grade Cable Assembly Integration Manual

CIRCULAR SAW SAFETY Reviewed 9/24/2007

GPS AutoSteer System Installation Manual

4 in 1 Strength Station

NFC Communication Tray Model: HHX-IT3-Z

User Guide. HDMI Active Cable Extender. DVI-7370c

SEAT BELT Installation Manual

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES

Owner s Manual & Safety Instructions

DASH KIT INSTALLATION

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual

National- Spencer Inc.

1. SAFETY RULES. 8. Avoid placing objects in the path of the blades.

Programming Manual Catalog Numbers 1756 ControlLogix, 1769 CompactLogix, 1789 SoftLogix, 1794 FlexLogix, PowerFlex 700S with DriveLogix

Class 5 to 7 Truck and Bus Hydraulic Brake System

QWALL 4 ACRYLIC SHOWER WALL INSTALLATION INSTRUCTIONS

Underground Cable Installation

CompactLogix 5370 L1 Controllers

Transcription:

Quick Guide Fiber Optic Cable Installation Introduction Fiber optic cables can be easily damaged if they are improperly handled or installed. It is imperative that certain procedures be followed in the handling of these cables to avoid damage and/or limiting their usefulness. The information contained in this manual should serve as a guide to proper handling, installing, testing, and for troubleshooting problems with fiber optic cables. For: See page: Important User Information 2 Overview 3 Fiber Optic Cable Mechanical Limits 4 Fiber Optic Cable Installation Guidelines 5 Fiber Optic Cable Pulling Techniques 5 Fiber Optic Cable Routing Guidelines 7 Installation Checklist 9 Cleaning Techniques for Fiber Optic Cables 10 Additional Fiber Optic Cable Installation and Handling Instructions 10 Rockwell Automation Support BackCover

2 Fiber Optic Cable Installation Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual, when necessary we use notes to make you aware of safety considerations. WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. IMPORTANT ATTENTION SHOCK HAZARD Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: identify a hazard avoid a hazard recognize the consequence Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present. BURN HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.

Fiber Optic Cable Installation 3 Overview Optical fibers require special care during installation to ensure reliable operation. Installation guidelines regarding minimum bend radius, tensile loads, twisting, squeezing, or pinching of cable must be followed. Cable connectors should be protected from contamination and scratching at all times. Violation of any of these parameters causes increased attenuation or permanent damage to the cable. The following are a few general comments to consider when installing fiber optic cables. Do Not Exceed Maximum Cable Lengths Make sure you check the installation instructions of the module for the appropriate cable lengths to ensure proper operation. You may experience additional attenuation loss when using bulkhead connectors to join cables even when the total length is less than maximum. Care should be used in maintaining total attenuation budget when joining cables with bulkhead connectors. Do Not Exceed Minimum Bend Radius for a Given Cable Type Exceeding the bend radius of the cable can cause unseen damage to the fibers of the cables that may not manifest itself for a period of time. This can lead to an expensive restringing of cables at a later date. See the following cable specification tables for appropriate bend radii for each catalog number. Figure 1 Correct Bend Radius

4 Fiber Optic Cable Installation Fiber Optic Cable Mechanical Limits Catalog Number 2090-SCVGx-0 Glass 2090-SCVPx-x Plastic 2090-SCEPx-x Plastic 2090-SCNPx-x Plastic Length meters (in.) 50 to 200 (1968 to 7872) 0.1 to 32 (4 to 1260) 0.1 to 32 (4 to 1260) 0.1 to 32 (4 to 1260) Long Term Bend Radius No Load millimeter (in.) 30.0 (1.2) < 98 (22) 40.0 (1.6) < 245 (55) 25.4 (1.0) < 70 (15) 25.4 (1.0) < 70 (15) Maximum Tensile Load Newton (lbs.)

Fiber Optic Cable Installation 5 Fiber Optic Cable Installation Guidelines General practices to follow when installing fiber optic cables include: Avoid Twisting Fiber Optic Cable Use proper pulling techniques in laying out your cable. Putting twists in the cable greatly increases your chances of breaking the fibers. Use Proper Pulling Techniques for Fiber Optic Cable Installation methods for both wire cables and optical fiber cables are similar. Just remember these rules: Never pull on the connector. The connector/cable interface is not designed for pulling. Use a pulling grip designed for pre-connected fiber optic cables. Grips with a fixed pull ring should use a swivel to attach the pull rope. Monitor tension. Do not exceed the maximum tensile load. On runs from 40m to 100m, use proper lubricants and make sure they are compatible with the cable jacket. On runs over 100m, use proper lubricants and pull from the middle out to both ends. If possible, use an automated puller with tension control or at least a breakaway-pulling eye. Always use a straight pull. Use cable guides to maintain the recommended bend radius. Do not exceed the cable bend radius. Exceeding the bend radius harms the fibers. It may not be immediate, and it may even take a few years but eventually by exceeding the recommended bend radius of the cable you reduce the useful life of the cable. Conduit Cable Conduit Cable Straight Pull is OK. Offset Pull is Not Recommended Figure 2 Proper Pulling Technique Through Conduit

6 Fiber Optic Cable Installation Do not twist the cable. Putting a twist in the cable can stress the fibers. Figure 8 for a 40m or longer pull. If you are installing cable of lengths 40m or longer, use a figure 8" on the ground to prevent twisting (the figure 8 puts a half twist in on one side of the 8 and takes it out on the other, preventing twists.). Figure 3 Prevent Twisting the Cable By Laying Cable in a Figure 8 Pattern 1. Lay cable on floor in a figure 8 pattern. 2. Turn Figure 8 cable 360 degrees (upside down) before continuing. 3. Pull in opposite direction (may require two people). Use a swivel-pulling eye, to prevent additional twisting of the cable during installation.

Fiber Optic Cable Installation 7 Properly Route Fiber Optic Cables Take care when routing through cabinets and right angle raceways. Install cables in raceways without loops. Avoid placing fiber optic cables in raceways and conduits with copper cables to avoid excessive loading or twisting. Figure 4 Using Raceways and Conduits Fiber Optic Cables Power Cables Figure 5 Using Raceways and Conduits

8 Fiber Optic Cable Installation Protect cables from excessive or frequent bending. Cables do not have a flex rating. Routing on a cabinet door should be used as a last resort. Figure 6 Routing Technique for Cabinet Door Use proper cable pulling techniques when routing cables. See the section entitled Use Proper Pulling Techniques for Fiber Optic Cable earlier in this manual. Attach cables with plastic clamps having large surface areas. Avoid pinching or squeezing cable. Cable clamps should be installed manually with gentle pressure. Figure 7 Proper Use of Plastic Clamps

Fiber Optic Cable Installation 9 Installation Checklist Use the following installation checklist to ensure proper handling. Installation procedure Complete Comments Maximum cable length not exceeded Bending radius not exceeded Maximum tensile load not exceeded; proper pulling techniques used Cable not squeezed or bent Cable installed without loops in raceways Cable protected from sharp edges Fiber cable installed in separate raceways from copper Cable connector cleanliness maintained Cable connector finger tight to transceivers ATTENTION Hand tighten connectors. Do not use tools to tighten connectors as they may cause damage to cables and inhibit signal transmission.

10 Fiber Optic Cable Installation Cleaning Techniques for Fiber Optic Cables Proper cleaning of the fiber optic cable ends and transceivers is essential to minimize system attenuation. Dirty fiber optic cables cross contaminate their mating transceivers. Conversely a dirty transceiver contaminates its mating fiber optic cable. There are a variety of ways to clean fiber optic components. Cleaning Fiber Optic Cable Ends Use a wet wipe to loosen particles on the end of the cable connector using a circular or straight wiping motion while using care to avoid wiping over area of pad that has already been used. Do not use a back and forth scrubbing action. Always use a clean area of the swab for each connector. When in doubt use a fresh wipe. Follow up the wet wipe cleaning with a dry wipe to remove any residue. Use canned air to remove any lint from the cable end. Cleaning Fiber Optic Transceivers Choose an optical grade lint free swab that fits easily into the transceiver barrel. The swab should be gently placed into the barrel of the connector and rotate no more than one turn. Do NOT rotate back-and-forth or round-and-round because debris may be ground into the transceiver. Swabs should only be used ONCE. Use a dry clean swab and insert into barrel and rotate once. Discard swab. Use canned air to blow out the barrel. Fiber Optic Cable Installation and Handling Instructions For more detailed information on the proper care, handling, and installation of these cables see the Fiber Optic Cable Installation and Handling Instructions manual, publication number 2090-IN010x-EN-P. This manual can be downloaded free of charge in pdf format from the following website: http://literature.rockwellautomation.com

Fiber Optic Cable Installation 11 Notes:

Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com. Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States 1.440.646.3223 Monday Friday, 8am 5pm EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues. Ultra3000 and Kinetix are trademarks of Rockwell Automation. PN 957955-27 Supersedes publication 2090-IN010B-EN-P September 2004 Copyright 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.