GSHP Design Recommendations- Residential & Light Commercial



Similar documents
Application Guide AG Geothermal Heat Pump. Design Manual McQuay International

GEOTHERMAL HEATING AND COOLING INTRODUCTION

GROUND SOURCE HEAT PUMPS. An Overview

DESIGN OF CLOSED-LOOP GEOTHERMAL HEAT EXCHANGERS IN THE U.S.

Geothermal Heat Pump Systems

GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut John F. Sima III P.E.

How Ground/Water Source Heat Pumps Work

Basic Design Considerations for Geothermal Heat Pump Systems

HVAC Applications for PE Pipe

Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems

Geothermal Heat Pumps in Agricultural Applications

Closed-Loop Ground-Coupled Heat Pump Systems

AE-1483 Ground-source Heat Pumps. Carl Pedersen Energy Educator

How To Use A Water Source Heat Pump

How a Ground Source Heat Pump Works for a School or College

Heating & Cooling Efficiency

How a Ground Source Heat Pump Works for Commercial Buildings

GROUND-SOURCE (GEOTHERMAL) HEAT PUMPS

Rocks & Minerals. 10. Which rock type is most likely to be monomineralic? 1) rock salt 3) basalt 2) rhyolite 4) conglomerate

Keeping Clients Happy AND The Lawyers at Bay

ADVANTAGES OF USING THE HYBRID GEOTHERMAL OPTION

Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses

HOME HEATING USING GEOTHERMAL ENERGY. An introduction to using ground sourced central heating in New Zealand

Design and Implementation of Geothermal Systems for Heating and Air Conditioning

Contents. 1 Introduction systems and applications Types of system Applications Potential benefits 4. 2 General design 6

WaterFurnace Explains GEOTHERMAL HEATING & COOLING

Evaporative Cooling System for Aquacultural Production 1

Heating Your Home or Business in Vermont with a Geothermal System

The efficient heat pump

GEOTHERMAL HEATING & COOLING SYSTEMS

Three-years operation experience of a ground source heat pump system in Northern Greece

MAC-120HE-01 Air-Cooled Chiller

GEOTHERMAL ENERGY: ANOTHER ALTERNATIVE

Earth-Coupled Air Conditioning Unit Design Analysis. Abstract

Energy Efficiency. Energy Efficient Home Cooling:

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Geology 200 Getting Started...

Utilization of Closed Loop Geothermal Heat Pumps at Verizon Wireless Cellular Towers

Heating, Ventilation & Air Conditioning Equipment

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

Commercial Earth Energy Systems:

GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

HVAC Calculations and Duct Sizing

Geothermal Heat Pumps

Ground-Source Variable Refrigerant Flow Heat Pumps:

DOWFROST GEO 20: Propylene Glycol-Based Heat Transfer Fluid for Geothermal Heat Pump Systems

Technical Description of the Stockton College Geothermal HVAC Retrofit

) 0- ML of Technology, Kbmth Fdk, UIIILlR FAX 641IU1764

Geothermal Comfort Systems

Tom Brooke, PE, MBA, CEM

Design Considerations for Underfloor Heating Systems. What is Frost Heave Protection?

GEOTHERMAL ENERGY USING GROUND SOURCE HEAT PUMPS

Chilled Water HVAC Systems

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

TYPES OF ROCKS & THE ROCK CYCLE

Chapter 2 Practical Approach in Design of HVAC Systems Utilizing Geothermal Energy

Renewable Heat Pumps. A guide for the technically minded

Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

1. Base your answer to the following question on on the photographs and news article below. Old Man s Loss Felt in New Hampshire

Experimental Investigation of the Performance of a Ground Source Heat Pump System for Buildings Heating and Cooling

Residential Ground-Source Heat Pumps: In-Field System Performance and Energy Modeling

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Instructor: Ms. Terry J. Boroughs Geology 305 INTRODUCTION TO ROCKS AND THE ROCK CYCLE

Geothermal Energy. How it Works

7) A clastic sedimentary rock composed of rounded to subrounded gravel is called a A) coal. B) shale. C) breccia.

TWE+TTA TWE+TWA T.R.

BOREHOLE SEALING IN A COAXIAL HEAT EXCHANGER BY BENTONITE TREATMENT

Lower Energy Costs with Rooftop Air-Conditioning Package Units

Appendix C. Minimum Equipment Efficiency Standards

Closed-Loop/Geother mal Heat Pump Systems

Understanding Heating Seasonal Performance Factors for Heat Pumps

Metamorphic rocks are rocks changed from one form to another by intense heat, intense pressure, and/or the action of hot fluids.

Instructor: Ms. Terry J. Boroughs Geology 305 INTRODUCTION TO ROCKS AND THE ROCK CYCLE

Salt Lake County Water Pump Design and Installation Guideline

Three Main Types of Rocks Igneous Rocks. Sedimentary Rocks Metamorphic Rocks. Made by Liesl at The Homeschool Den

catalog Single Package Vertical Air Conditioners and Heat Pumps

Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems

Designing coaxial ground heat exchangers with a thermally enhanced outer pipe

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps

HP switch LP switch Discharge thermo Comp. Surface thermo

Sustainability: Geothermal Energy for Sherman Hospital

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

Native InDesign 2890 SaniTite Brochure 1/8" CMYK April 17, 07

To find out more about installing a heat pump call or visit energysavingtrust.org.uk

HVAC Basic Science - System Capacity

The next generation of geothermal systems for school buildings

HVAC Efficiency Definitions

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

All the latest news regarding Geothermal Heating and Cooling Systems. Residential geothermal tax credit now available

Questions & Answers Proposed for Exam #3

Name: Rocks & Minerals 1 Mark Place,

Geothermal Applications APPLYING GEOTHERMAL COMFORT TO RESIDENTIAL CONSTRUCTION

BACK TO PAGE ONE ANALYSIS OF SURVEY DATA

Calculating System Flow Requirements

The Most Advanced Name in Drainage Systems. Sanitary Sewer Pipe

Onsite Wastewater Concepts, Materials, Regulations & The Application Process Part I

Solar Thermal TECHNOLOGY. Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu

Transcription:

GSHP Design Recommendations- Residential & Light Commercial These residential closed- loop ground source heat pump (a.k.a geothermal or groundcoupled heat pumps) design guidelines were developed in conjunction with a project sponsored by the Tennessee Valley Authority in conjunction with a TVA Ground Source Heat Pumps promotion. Previous guidelines were verified and adjusted according to data gathered during this effort and previous similar projects. A set of recommendations for loop sizing, piping guidelines, piping arrangements, and antifreeze precautions is provided. They attempt to balance the conflicting constraints of installation cost and efficiency. These guidelines have recently been extended to regions beyond the TVA service territory. Loop Lengths Table 1 provides recommendations for ground loops in the Tennessee Valley Authority service area and beyond. The values use results from this TVA sponsored project coupled with a previous Alabama Power project and the resulting recommendations for Alabama (Kavanaugh, 1991). The length of the trench or bore must be based on the amount of pipe in the trench, burial depth, and average ground temperature and conductivity. The table provides extremes of pipe length per length of trench from 10 ft/ft (i.e. 1000 ft. of pipe in a 100 ft. long trench) to 2 ft/ft. The table was developed for an average burial depth of 5 ft. and ¾ high-density polyethylene (HDPE) pipe. The extremes of normal ground temperature are 44 o F for the northern continental US and 70 o in southern USA (not including southern Florida and Texas and all of Hawaii). These lengths should provide a maximum loop temperature of 90 o F entering the heat pump in normal applications. In homes with excessive run times this temperature will be 3 o to 5 o F higher. The table also includes recommendations for vertical ground loops in ft. of bore per ton for ¾ and 1-1/4 HDPE, which will operate about 5 o F cooler than the horizontal loops. Table 1. Recommended Lengths of Trench or Bore Per Ton For GCHPs Multiply length of trench by pitch to find required length of pipe. See Tables 4 and 5 for Thermal Conductivity of Soils and Rocks. Pitch Ground Temperature - o F Coil Type (See Figure 1 for Details) Ft. of Pipe per Ft. Trench (or Bore) 44 to 47 o F 48 to 51 o F 52 to 55 o F 56 to 59 o F 60 to 63 o F 64 to 67 o F 68 to 70 o F Horz. 10-Pitch Slinky 10 125 120 115 120 125 150 180 Horz. 6-Pipe/6-Pitch Slinky 6 180 160 150 160 180 200 230 Horz. 4-Pipe/4-Pitch Slinky 4 190 180 170 180 190 220 260 Horz. 2-Pipe 2 300 280 250 280 300 340 400 Vertical U-tube (3/4 Pipe) 2 180 170 155 170 180 200 230 Vertical U-tube (1 Pipe) 2 170 160 150 160 170 190 215 Vertical U-tube (1¼ Pipe) 2 160 150 145 150 160 175 200 Table 1 based on k=0.6 Btu/hr-ft- o F for horizontal loops and k=1.2 Btu/hr-ft- o F for vertical loops and an annular fill/grout conductivity of 0.85 in vertical loops. For other conditions: L/Ton(Corrected) = L/Ton (Table 1) CF(k -ground) CF(k-annulus) Ground Therm. Cond. (Btu/hr-ft- o F) 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 Horz. Loop, CF(k-ground) 1.22 1.0 0.89 0.82 --- --- --- --- --- Vert. Loop, CF(k-ground) --- --- 1.23 1.10 1.0 0.93 0.87 0.83 0.79 Annulus Ther. Cond. (Btu/hr-ft- o F) 0.4 0.6 0.8 0.85 1.0 1.2 1.4 Vert. Loop, CF(k-annulus) 1.2 1.08 1.01 1.0.98.93 0.91 No Correction for Horz. Loop

HEADERS BACKHOE INSTALLATION 4' 6' Two-Pipe 5' Min. 3/4" TO 1-1/2" HDPE TUBING Four-Pipe CONVENTIONAL HORIZONTAL GROUND- Two-Pipe 6' COUPLED HEAT PUMP SYSTEM Trencher Installation 4' 6' Six-Pipe 4' 15 TO 20' HDPE U-BENDS 3/4" TO 1-1/2" DIA. VERTICAL GROUND-COUPLED HEAT PUMP SYSTEM BACKHOE INSTALLATION TRENCHER INSTALLATION 5' 3/4" HDPE COILS 6' 10 Pitch Slinky 6 Pitch Slinky SLINKY COIL GROUND-COUPLED HEAT PUMP SYSTEM Figure 1. Ground-Coupled (Geothermal) Heat Pump Types (Groundwater and Surface Water Systems Not Shown) Heat Pumps The minimum efficiency for air heat pumps rated under ARI Standard 210/240 is 10 Btu/whr. Since water-to-air heat pumps appear to cost more according to the results of the TVA GSHP promotional and the NRECA/UA study, an efficiency equivalent to a 10 SEER should at the very least be the minimum required. In order to arrive at a minimum recommended EER, the performance of a line of compressor is used as the basis for the design of a 3 ton heat pump. The Appendix A contains the performance data of a nominal 2.5 and 3.0 ton Copeland reciprocating compressor. The Appendix A also contains the details of a computation that results in an SEER of 10.2 and a cooling capacity of 37,300 Btu/h for the 3.0 ton compressor at ARI 210/240 conditions. The indoor fan is 1/3 hp and outdoor is ¼ hp, both have 60% efficiency. Using a 2.5 ton compressor from the same series, a water-to-air heat pump is able to achieve an EER of 13.7 at ARI 330 ( 14.5 @ ISO 13256-1/GLHP) conditions using the identical indoor fan motor. Calculations also include the ARE 330 pump penalty at 9 gpm with a 12 ft. head loss through the water coil. To be consistant, the minimum EER is adjusted down to 13.5 since the air heat pump SEER was 10.2 rather than the minimum or 10. The heat pump should have the capability to operate at the extended low range of 32 o F called for by ARI 330 or ISO 13256-1. The recommendations for the heat pump are:

A minimum EER of 14 Btu/whr at ISO 13256-1 GLHP conditions (77ºF/25ºC Entering Water Temperature). Data should be in ARI Directory not in manufacturer s literature. A maximum head loss of 12 ft. of water at 3 gpm per nominal ton. Extended range capability to operate with an entering liquid temperature of 100 o F in cooling and in heating at 32 o F. Pumps, Piping and Antifreeze This project revealed that contractors were prone to installing excessive numbers of pumps. This may be a result of undersized piping, excessive amounts of viscous antifreeze solutions, or added insurance. Since a 15 EER, 3-ton heat pump will only require a total power (compressor and fan) of 2400 watts, the addition of a second 1/6 hp pump (which draws 200 watts) will reduce system efficiency by 8%. Table 2 is provided as a guideline to insure adequate liquid flow rate with the least possible number of pumps. The table is to be used in conjunction with Table 1 and applies to loops with 0 to 15% propylene glycol solutions (by volume). This solution has the reputation of being the most difficult of the commonly used solutions to pump. However, it is no more difficult to pump than ethyl alcohol and pumping penalties can be mitigated by adding only the required levels. Table 3 gives recommended levels of antifreeze solutions for loops installed according to Table 1 assuming all lines are located below grade. Shorter loops may require higher levels of antifreeze solutions. See ASHRAE 1999 Applications Handbook, p. 31.25 for more details regarding antifreeze recommendations. Any exposed piping above the frost line must be insulated with a close cell insulation with Ultraviolet (UV) protection (paint or wrap). Table 2 RECOMMENDED GCHP PIPING ARRANGEMENTS AND PUMPS Nominal Heat Pump Capacity (Tons) 2 3 4 5 6 Required Flow Rate In GPM 5-6 7-9 10-12 12-15 15-18 Coil Type Number of Parallel Loops Slinky (10 pitch) 3-4 4-6 6-9 8-10 8-10 6-Pipe 3-4 4-6 6-9 8-10 8-10 4-Pipe 2-3 4-6 5-8 6-9 6-10 2-Pipe 2-4 3-5 4-6 5-8 6-10 Vert.-3/4 PE 2-3 3-5 4-6 5-8 6-10 Vert.-1 PE 2-3 2-4 3-5 4-6 4-6 Vert.-1-¼ PE 1-2 1-2 2-3 2-3 2-4 Trench Ft. Header Diameter HDPE, DR 11 Pipe Less 100 1 ¼ 1 ¼ 1 ¼ 1 ½ 1 ½ 100-200 1 ¼ 1 ¼ 1 ½ 1 ½ 1 ½ - 2 Number & Size Of Pumps Required 1-1/12 hp 1-1/6 hp 1-1/6 hp (1½ hdrs.) 2-1/6 hp 2-1/6 hp 2-1/12 hp (1¼ hdrs.) Pipe sizing assumes 20% antifreeze solutions and heat pump water coil head loss < 12 ft.

35 30 WET ROTOR CIRCULATOR PUMP CURVES Head - Feet of Water 25 20 15 10 1/25 HP 1/12 HP 1/6 HP 5 0 0 5 10 15 20 25 30 Flow Rate - GPM Coil Type Figure 2. Grundfos Circulator Pump Curves (Other Manufacturers have similar products) Table 3 RECOMMENDED LEVELS OF ANTIFREEZE SOLUTIONS FOR GCHP SYSTEMS Recommended % Volume of Propylene Solutions Pitch Ft. pipe/ft.trench % by Volume 60 to 63 o F Ground % by Volume 52 to 59 o F Ground % by Volume 44 to 51 o F Ground Slinky 10 10 15 20 6-Pipe or Eqv. Slinky 6 10 15 20 2-Pipe 2 10 15 20 Vertical (3/4 Pipe) 2 0 10 20 Vertical (1 ¼ Pipe) 2 0 10 20 Warning more antifreeze will be required if loops are shorter than those recommended in Tables 1 and 2. Example Design: Design the vertical ground coupling grid and the pumping loop for a four-ton (48,000 Btu/hr) heat pump system. The home is located in Nashville and the header pipes can be brought into the equipment room where the unit will be located. The driller can bore 4.5-inch holes to a depth of 175 feet in the light limestone and clay at the site. The owner wants the drilling site to be located 75 feet from the house. Thermally enhanced grout with of thermal conductivity or 0.85 Btu/hr-ft-F is used to fill the annular region between the U-tubes and borehole walls.

Solution: The soil temperature is estimated to be 58ºF in Nashville (See Figure 5). Table 1 suggests bore lengths of 170 ft/ton for ¾ inch U-bends, 160 ft/ton for 1 inch, and 150 ft/ton for 1-1/4 in. (bores will be deep-greater than 100 feet). However, 1-1/4 inch U-bends will be very difficult to install into a 4.5 inch bore hole and are eliminated from consideration. Therefore, either 680 feet (170 ft/ton x 4 tons) of ¾ inch U-bend coupling or 640 (160 x 4 tons) feet of 1-inch coupling is required. One inch will be used in this example. Also, Table 1 is based on a soil conductivity of 1.2 Btu/hr-ft-F, which is an approximate average between limestone and clay, and a bore fill (or grout) conductivity of 0.85 Btu/hr-ft-F. If the ground conductivity is higher (i.e. more limestone than clay), the loops should be reduced as noted in the footnote for Table 1 or lengthened if the ground conductivity was lower than 1.2 Btu/hr-ft-F. Also, the loop lengths would need to be lengthened if the bore fill (or grout) conductivity is lower than 0.85 Btu/hr-ft-F as noted in the lower footnote of Table 1. The layout will be dictated by drilling conditions. The total length of 640 feet requires four bores since the driller can only drill to 175 feet. This can be accomplished with four 160 to 165 feet holes. Table 2 suggests either 3, 4 or 5 parallel circuits for the grid. Three and five circuits will not divide evenly into the four U-bends. Therefore, four circuits (one per U-bend) will be used in an arrangement similar to Figure 3. Example Four Ton Vertical GCHP System Extended Range ( EWT = 25 to 105 F) High Efficiency (ARI 330 EER = 13+) Water-to-Air Heat Pump P/T Tap Pump 3-Way Purge Valves (Lengths Vary - See Table for Other Applications and Climates Design) 1-1/2" HDPE Headers Close Header 1", DR 11 HDPE U-Tubes 15 to 20 ft. Minimum 165 ft. Figure 3. Four Ton Vertical GCHP Four Circuits - Four Bores

Figure 4. Groundwater Temperature Profiles for Alabama (Chandler) Figure 5 Approximate Groundwater Temperatures in the USA (NGWA)

Annual Ground Temperature Swing (F) Variation from Average (F) 20 15 10 5 0-5 -10-15 -20 0 90 180 270 360 Days of the Year Shallow Ground Temp. = Deep Ground Temp. + Swing 2 Feet 5 Feet 10 Feet 30 Feet Figure 6 Ground Temperature Variation in Average Soil with Depth and Season (Note: To find the soil temperature at any depth and time of the year, add the values in Figure 5, to temperatures shown in Figures 4 (Alabama) or 5 (USA).

TABLE 4 Thermal Conductivity and Diffusivity of Sand and Clay Soils Thermal Conductivity (k) - Btu/hr- F-ft and Thermal Diffusivity (a) - ft 2 /day Dry 5% Moist 10% Moist 15% Moist 20% Moist Soil Type Density k a k a k a k a Coarse 120 lb/ft 3 1.2-1.9 0.96-1.5 1.4-2.0 0.93-1.3 1.6-2.2 0.91-1.2 - - 100% Sand 100 lb/ft 3 0.8-1.4 0.77-1.3 1.2-1.5 0.96-1.2 1.3-1.6 0.89-1.1 1.4-1.7 0.84-1.0 80 lb/ft 3 0.5-1.1 0.60-1.3 0.6-1.1 0.60-1.1 0.6-1.2 0.51-1.0 0.7-1.2 0.52-0.90 Fine Grain 120 lb/ft 3 0.6-0.8 0.48-0.64 0.6-0.8 0.4-0.53 0.8-1.1 0.46-0.63 - - 100% Clay 100 lb/ft 3 0.5-0.6 0.48-0.58 0.5-0.6 0.4-0.48 0.6-0.7 0.37-0.48 0.6-0.8 0.41-0.55 80 lb/ft 3 0.3-0.5 0.36-0.6 0.35-0.5 0.35-0.5 0.4-0.55 0.34-0.47 0.4-0.6 0.30-0.45 Coarse grain = 0.075 to 5 mm - Fine Grain less than 0.075 mm Rock Type TABLE 5 Thermal Properties of Rocks @ 77 F Thermal Conductivity (k) - Btu/hr- F-ft and Thermal Diffusivity (a) - ft 2 /day % 1 Occurance in Earth s Crust k - All 2 Ther. Con. Btu/h-ft-F k - 80% 3 Ther. Con. Btu/h-ft-F c p Spec. Heat Btu/lb-F r Density lb/ft 3 a (k/ρc p ) Ther. Diff. ft 2 /day Igneous Rocks Granite (10% Quartz) 10.4 1.1-3.0 1.3-1.9 0.21 165 0.9-1.3 Granite (25% Quartz) 1.5-2.1 1.0-1.4 Amphibolite 1.1-2.7 1.5-2.2 175-195 Andesite 0.8-2.8 0.9-1.4 0.12 160 1.1-1.7 Basalt 42.8 1.2-1.4 0.17-0.21 180 0.7-0.9 Gabbro (Cen. Plains) 0.9-1.6 0.18 185 0.65-1.15 Gabbro (Rocky Mtns.) 1.2-2.1 0.85-1.5 Diorites 11.2 1.2-1.9 1.2-1.7 0.22 180 0.7-1.0 Grandiorites 1.2-2.0 0.21 170 0.8-1.3 Sedimentary Rocks Claystone 1.1-1.7 Dolomite 0.9-3.6 1.6-3.6 0.21 170-175 1.1-2.3 Limestone 0.8-3.6 1.4-2.2 0.22 150-175 1.0-1.4 Rock Salt 3.7 0.20 130-135 Sandstone 1.7 1.2-2.0 0.24 160-170 0.7-1.2 Siltstone 0.8-1.4 Wet Shale (25% Qrtz.) 1.0-1.8 0.9-1.2 Wet Shale (No Qrtz.) 4.2 0.6-2.3 0.6-0.9 0.21 130-165 0.5-0.6 Dry Shale (25% Qrtz.) 0.8-1.4 0.7-1.0 Dry Shale (No Qrtz.) 0.5-0.8 0.45-0.55 Metamorphic Rocks Gneiss 21.4 1.0-3.3 1.3-2.0 0.22 160-175 0.9-1.2 Marble 0.9 1.2-3.2 1.2-1.9 0.22 170 0.8-1.2 Quarzite 3.0-4.0 0.20 160 2.2-3.0 Schist 5.1 1.2-2.6 1.4-2.2 170-200 Slate 0.9-1.5 0.22 170-175 0.6-0.9 1 Percentage of sedimentary rocks is higher near the surface. 2 All represents the conductivity range of all samples tested. 3 80% represents the mid-range for samples of rock.