Explosion proof enclosures



Similar documents
Terminal Box. Specifications TNCN

David O Brien, CMP Products (David.OBrien@cmp-products.com)

SEISMIC VELOCITY TRANSDUCER T1-40

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

IIB+H2 Flameproof Ex d enclosures EJB Aluminium & Stainless steel

Compact pressure switch Flameproof enclosure Ex d Model PCA

Terminal Boxes in Glass Fiber Reinforced Polyester (GRP)

Operating Instructions

Series 8146/5-V37 and Series 8150/5-V37

Instructions for Safe Use

Linear Luminaire with LED Series EXLUX 6402/2

Terminal Boxes Series 8146

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Operating Instructions

Technical data sheet TDS0070

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. Dimensions

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design

Control and Distribution Boxes made of Stainless Steel Series 8150

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Product Brochure. Certified Mining Motors

Technical Data. Dimensions

Inductive sensor NI10-M18-Y1X-H1141

Plug and Socket Devices CES 63 A Series 8579

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Series 510 Submersible Level Transmitters

Safety instructions VEGADIS DIS81.CEIA/V****

MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

Worcester DS/DM Series UltraSwitch Switch box

Floodlight Range Installation Guide

CUSTOMS UNION. CUSTOMS UNION CERTIFICATE OF CONFORMANCE No. RU C-DE.ГБ05.В Series RU No

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Air Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB

Threaded Resistance Thermometers Model TR10-D, Miniature Design

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

2.12. page Products for Explosion hazardous Environment

EXPLOSION-PROOF EMERGENCY LIGHTING FIXTURE FOR FLUORESCENT LAMP EVF-..-EL SERIES

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Installation Guide of Sunrise Solartech PV Modules. Term Contents. Purpose of this guide. General. Safety precaution for installing a solar

Magnetic field sensor for pneumatic cylinders BIM-INT-Y1X-H1141

Stainless Steel and Mild Steel Enclosures. Stainless Steel and Mild Steel Enclosures

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Rosemount 752 FOUNDATION fieldbus Remote Indicator

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)

Flameproof Audible Signal 115 db (A) Series YA90

Components for System Solutions E9/5. Ex d Enclosure System Made of Light Metal or Stainless Steel, "Flameproof Enclosure" Series

How To Read A Pipe From A Sensor

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

Inductive slot sensor

Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****

Toroidal Conductivity Sensor

Guide to enclosures for potentially explosive atmospheres

Safety instructions VEGAPULS PS62/63/66/67/68.GI/RI(*)****** IECEx BVS Ex t IIIC T Da, Da/Db, Db IP 66

3/2, 5/2, 5/2 bistable and 5/3 way pneumatic solenoid valve

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

Instruction Manual Differential Pressure Transmitter

Control Stations Made of Polyester Resin Series 8146

din din-s 90Ah/plate 155Ah/plate 115Ah/plate 140Ah/plate

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL

distributing & controlling system solutions

Material: Weight: Bearing Life: Shaft Loads: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

3/2- and 2/2-way cartridge valve type BVE

3/2, 5/2, 5/2 bistable and 5/3 way pneumatic solenoid valve

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

FAQs-Main switchboard design criteria

FGM 160 ATEX EC type examination certificate

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

Rosemount 751 Field Signal Indicator

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

Machine needle shut-off nozzle type HP

Cross-beam scanning system to detect slim objects. 100 mm in

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

Explosion-Proof Electric Unit Heaters

Control- and feedback head for integrated mounting on Robolux valves Type 2036

Reliance DuraStar ORDINARY LOCATION INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS

Rosemount DIN-Style Temperature Sensors and Thermowells (Metric)

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

HL Economical, Miniature Limit Switch Boasting Rigid Construction. General-purpose Limit Switch. Model Number Structure.

Variable speed drives for synchronous and asynchronous motors

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

Instruction Manual. T3111 T3111L T3111P T3111Ex

R.C.C.B. s two-pole LEXIC

Directions for use : Dosing chutes type DSX.

Inrush Apparent power (VA) Flow Characteristics/Weight. Port size Rc. Valve model VS VS VS VS VS

TEIP11 I/P signal converter for standard signals. Measurement made easy

A good connection. International approvals.

ACL 395 Resistivity Meter

Mini USB and USB 2.0-IP67 Connector System

AMERBRITE UNDERWATER WHITE LED POOL LAMP

TEIP11-PS I/P signal converter for standard signals. Measurement made easy

Mounting Instructions for SP4 Power Modules

12 Volt 30 Amp Digital Solar Charge Controller

Transcription:

1 of 7 Explosion proof enclosures DE8 C

2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without Intrinsic safety Ex d II T4 to T6 Gb Or Ex d II + H2 T4 to T6 Gb ( Except for DE8-C148 ) Ex tb IIIC IP65-66 T85 C to T135 C Db With Intrinsic safety Ex d[ia] or [ib] II T6 Gb Or Ex d[ia] or [ib] II + H2 T4 to T6 Gb ( Except for DE8-C148 Ex tb IIIC IP65-66 T85 C Db They are designed for use in potentially explosive atmospheres and certified according to the latest requirements of the ATEX Directive and the latest IEC Ex requirements. The enclosures listed in this manual are certified: II 2 GD The certificate numbers are : INERIS 09ATEX0061X IECEx INE 13.0088X They are made in accordance with the following standards: Zones due to gases, vapors and fumes EN 60079-0 : 2009 IEC 60079-0 : 2007 EN 60079-1 : 2007 IEC 60079-1 : 2007 EN 60079-11: 2007 IEC 60079-11: 2006 Zones for dusts EN 60079-31: 2009 IEC 60079-31: 2008 Description Our range of explosion proof enclosures is available in many sizes. They are machined and painted in steel or stainless steel 316L. Each is expected to receive electrical components inside, making it easy replacement or maintenance. They can also be customized to meet each individual specific need. If necessary, multiple enclosures can be assembled on a frame with junction boxes and / or switching coupled or separated. Enclosures can be delivered fully equipped according to customer requirements or EMPTY with a partial certification (certificate with U extension) to be used as basis for certification of an Equipment or Protective system.

3 of 7 Safety instructions The device must be installed, used and maintained in accordance with the following standards: NF C 15 100 EN/IEC 60079-14 (electrical installations in explosive gas atmosphere) EN/IEC 60079-17 (inspection and maintenance in hazardous areas) EN/IEC 60079-31 (protection of equipment against dust ignition by enclosure "t") Decrees, orders, laws, directives, circulars, applications, standards, state of art and other documentation relating to its installation site It is forbidden to change anything (components, installation, wiring...) without the prior consent of artec Technor. Meaning of symbols This symbol means a hazard or precaution to be taken We cannot accept any responsibility for failure to observe these regulations Make sure of the compatibility between the information on the nameplate, the explosive atmosphere present, the area of use and ambient temperatures and surfaces. Any damage of the device can have for consequence to make ineffective the explosion-proof protection. The installation of the enclosure must be done in the state of the art in the technical domains and only by qualified, competent and empowered personnel. A defective or abnormal use as well as the non compliance with the instructions of the present document exclude any clause of guarantee and do not engage our responsibility The use of the device in case of excessive deposits of dusts superior at 50mm according to EN / IEC 60079-31 is not authorized. Liability for manufacturer traceability is ensured only at the first known delivery destination (serial number specified on the certification label) It is also required to observe the regulations of the country of use Transport, storage Check it the product has not been damaged during transport. If any, do the statutory reserves to the carrier Do not put into service damaged products Packaging Location storage Duration storage Open In a covered location, clean (without contact with external substances) and closed with temperature a constant humidity (-40 C < T < +70 C). Shielded from important temperature variations 2 years and more with regular inspection (cleanness and mechanical damage)

4 of 7 Putting into service Verify that the information on the label of the product are in accordance with the permissible conditions for the Ex area of the site of use (Group II: Surface Industries - Category 2: high level of protection for ATEX G = for Gas / D = for Dusts for IEC Ex GPL - G = for Gas / D = for Dusts - IPxx: IP rating (waterproofness for solids and liquids) Check if there is a specific position of mounting The wiring of the cable conductors must be made with a particular care The conductor insulation must reach the terminal. The conductive soul must not be damaged Not to exceed the authorized maximal temperature, it is advisable to choose the appropriate cables and take a particular care in installing them Follow the instructions contained in the specifications Installation of intrinsic safety elements: The installation of the intrinsic safety circuits (IS) inside the enclosure is subordinated to the respect of the requirements of their documents of certification, their certificates and with that after: Circuits IS are cabled with connection wires of which the thickness of insulator is 0,5 mm and the section 0,5 mm ². The connection wires support a dielectric test of 500 V effective. The air gap between the active parts under voltage of the connection elements of the intrinsic safety circuit compared to connection elements of an non intrinsic safety circuit is higher or equal to 50 millimeters The air gap and creepage distances in the air between the active parts under voltage of the intrinsic safety circuit compared to an intrinsic safety circuit close are higher or equal to 6 millimeters The air gap and creepage distances in the air between the active parts under voltage of the intrinsic safety circuit compared to the metal parts which can be with the ground are higher or equal to 3 millimeters. The active parts of the intrinsic safety circuits support a dielectric test of rigidity under an effective alternating voltage of 500 Volts compared to the metal mass The active parts of an intrinsic safety circuit support a dielectric test of rigidity under an effective alternating voltage of 500 Volts compared to an intrinsic safety circuit close. Circuits NIS are cabled with conductive wires whose insulation is such as they can support a dielectric test of 2 U + 1000 V effective, U being the sum of the tensions of the IS and NIS circuits, with a minimum of 1500 V

5 of 7 efore starting Make sure the unit has been correctly settled and not damaged Make sure the wiring and the tightening of the terminal screws have been performed properly (see descriptive tightening torque) The device may include any foreign body and no part is damaged The cable gland must be tightened (see description of the gland torque) Maintenance The maintenance and repairs works on devices must be made only by authorized and trained persons for that purpose. efore any work the devices must be switched off. In addition: Prevent and avoid any formation of layers of dusts: make a periodic cleaning with a wet cloth Do not take apart the command and control units (push buttons, pilot light, etc.) The following checks must be made at least once a year: The outdoor equipment and surfaces must not be damaged The cable entries and blanking plugs must be threaded Check tightness of the connections, rewiring if necessary Prior to closing, check the cleanliness of the flame path (machined part of the cover in contact the machined part of the box). Grease these 2 parts with a grease resistant to oxidation (OPAL - Siberia, for example) Screw the cover on the box using the stainless steel bolts A4-70 minimum. Ensure that all the bolts are screwed. After tightening the bolts, check with a shim of 15/100 mm (4/100mm for II + H2)all around the flam path that the shim cannot penetrate the enclosure. Its non-penetration on full is the insurance of the conformity of the product with the standards Dimensions Technical features External dimensions (mm) References A C Internal volume dm 3 / liters Maximum power whatever the content is Dimensions of mounting plate (mm) Fixing (mm) W Max. H L Int c H1 L1 ØD holes olts in stainless steel INOX A4-70 (min.) Qty x Ø-L DE8C 32 334 434 240 17,5 250 300 200 166 234 326 Ø12 12 x M12-35 59 DE8C 351 354 474 240 21,06 250 350 225 166 274 346 Ø12 14 x M12-35 59 DE8C 43 434 534 290 40,95 380 400 300 226 334 526 Ø12 14 x M12-35 59 DE8C 44 544 544 295 52,65 380 400 400 226 334 526 Ø12 16 x M14-40 95 DE8C 54 544 644 305 64,35 410 500 400 226 414 526 Ø20 18 x M14-40 95 DE8C 64 544 744 310 76,05 470 600 400 226 514 526 Ø20 20 x M14-40 95 DE8C 75 664 864 320 109,31 600 700 500 231 614 630 Ø20 24 x M14-45 95 Tightening torque DE8C 86 764 964 365 168,51 600 800 600 271 714 734 Ø20 26 x M16-40 148 DE8C 107 864 1164 380 240,18 1200 1000 700 251 908 868 Ø20 30 x M16-40 148 DE8C 108 864 1164 425 275,62 1400 1000 700 300 908 868 Ø20 30 x M16-40 148 DE8C 148 940 1590 510 448 2000 1450 800 425 1200 900 Ø20 40 x M16-60 148 Nm

and D and D and D and D and D and D Scope : 6 of 7 Side C Side A Side D Side Number of cable entries: Any type of cable or conduit entry certified Ex d can be used and installed according to EN / IEC 60079-14 Different types of threads can be used but minimum five threads by bolt must always been engaged ½ NPT ¾ NPT M20 ISO 1 NPT M25 ISO 1 ½NPT 1 ¼NPT M32 M40 M42 ISO 2 NPT (with welded ring) M50 ISO 2 ½ NPT (with welded ring) M63 ISO 3 NPT (with welded ring) M75 ISO References DE8C 32 12 12 32 8 8 20 3 3 12 1 1 4 DE8C 351 12 12 24 8 8 18 3 3 8 1 1 4 DE8C 43 18 18 36 14 14 28 4 4 16 2 2 5 1 1 2 DE8C 44 20 20 40 16 16 30 5 5 20 3 3 6 1 1 3 DE8C 54 20 20 40 15 15 30 5 5 20 3 3 6 1 1 3 DE8C 64 28 28 60 18 18 50 7 7 28 4 4 9 1 1 4 DE8C 75 28 28 72 24 24 72 10 10 40 4 4 11 2 2 7 DE8C 86 32 32 112 28 28 100 20 20 80 5 5 17 2 2 8 1 1 4 DE8C 107 36 36 112 32 32 100 20 20 80 5 5 17 3 3 10 1 1 4 DE8C 108 36 36 112 32 32 100 20 20 80 5 5 17 3 3 10 1 1 4 DE8C 148 72 72 224 64 64 200 40 40 160 10 10 34 6 6 20 2 2 8

7 of 7 Special Conditions for safe use (X): When the enclosure is equipped with intrinsic safety elements, a temperature probe must also be fitted inside and be connected to a system that can switch off the supply when the inner temperature raises the maximum ambient temperature indicated in the certificates of the IS elements. The products that can be connected to the IS elements installed inside the enclosure must be certified type and association must be compatible in regards of intrinsic safety. The content of the DE8-C enclosure may be placed in any arrangement provided that an area of at least. - 20 % of each cross-sectional area remains free for groupii - 40 % of each cross-sectional area remains free for group II + H2