Nokeval. User's Manual Models 301 / 302 / 305



Similar documents
Contents. Document information

TC-9102 Series Surface Mount Temperature Controllers

Digital Pressure Measuring Instrument MDR480

PRODUCT PROFILE FEATURES

Transmitter Interface Program

PIEZOMETER AIRFLOW MEASURING RING

Preliminary. Dual-line FLOW rate/totalizers. Pr ovu Model PD6200 Analog Input. Pr ovu Model PD6300 Pulse Input. Analog Inputs.

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Preset Counter signo 721

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

PK-01. Standalone door control module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

Short information Parameters are programmed via front-side membrane keypad

BROOKFIELD MODEL VTE250 ELECTRIC VISCOSEL PROCESS VISCOMETER. Installation, Operation, and Maintenance Instructions. Manual No.

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46

Virtual Measurements & Control. Flip/Flop Filler

Online Infrared Flue Gas Analyzer Gasboard 3000

INSTRUCTION MANUAL VRT-200. TECSYSTEM S.r.l. Via Cristoforo Colombo, 5/C Corsico (MI) phone / Fax:

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

Mode Switch. Fan Switch Menu button Program button

Installation and User Guide

CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13

Telefon (+45) Telefax (+45) Installation and operating manual

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

PD 100A. Printing data system

Product Information Sheet UH36 Hi Pot Tester

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

PART 1 PRODUCT (GENERAL)...1.

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

Modular I/O System Analog and Digital Interface Modules

Electronic Pressure Switch EDS 3000

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

Specifications - Installation and Operating Instructions Ø5 [127.00] 17/64 [6.91] 1-59/64 [48.89]

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

FAQ s on Siemens Magmeters

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

KCIEN KCIENSBP. Heavy Duty Stainless Steel Illuminated Keypads INSTALLATION MANUAL. Range: DIGICODE (Stand-Alone Keypad)

NC-12 Modbus Application

Wahl C50 Calibrator FEATURES

Duct Humidity Transmitter

Safety technique. Emergency stop module BO 5988 safemaster

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

FIREDEX Conventional Fire Panels

Digital display DA 48

GREISINGER electronic GmbH

Ordering Part Numbers: Universal Signal Converter: USC-CVB Universal Signal Converter with a 4-20mA input and +/- 10V output: USC-CVB225-B10V

4-Channel Thermometer / Datalogger

AIS750 Series Alarm Annunciator

magnetronic GmbH Kreuzhofstr München Tel.: 089/ Fax: 089/ Battery control system DCC 6000

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

TMO2D with Fault Alarm and Event Log. Software Version 4B (or Earlier) Using the Fault Alarm

Talon and Talon SR User Manual

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

SYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016)

RAINCONTROL LCD Special

SX460. Generator Automatic Voltage Regulator Operation Manual

Product Information Sheet UH28CS-12kV Hi Pot Tester

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Ground Resistance Clamp On Tester

KRONOS GA11 WEEKLY-PROGRAMMING DIGITAL CHRONOTHERMOSTAT FOR THE REMOTE CONTROL OF HOT AIR GENERATORS THROUGH BRAHMA INTERFACE BOARD APPLICATION

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

GST301. (Single Protection Zone) Operation Manual

DPI 260 SERIES: Digital Pressure Indicators

Operation Guide 3M-22

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval.

e-4 AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

SLIM LINE FUME HOOD MONITOR

WD-AMX Water Detection Controllers

Hand-held thermometer Model CTH7000

Mirror Mount Video Monitor/Recorder with Front and Rear View Night Cameras PLCMDVR5

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

OCS-S High Resolution Digital Crane Scale

BOS 73K... BOS 74K...

IS3016A Passive Infrared Motion Sensor with Anti-Mask - Installation Instructions

LOXONE 12 Channel Amplifier

Controller Automation, Model II+

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

Multi-Range Programmable DC Power Supplies 9115 Series

PD6000 Analog Input Process Meter Instruction Manual

IO-RM3 3-Stage Relay Module

Drayton Digistat +2RF/+3RF

Product Name LED Panel light Product Models

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

SATEX SA Manual. Weegtechniek holland b.v. PRECISION BALANCE. Patroonsweg DA Zeewolde HOLLAND

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Multi-Range Programmable DC Power Supplies 9115 Series

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Light Meter (Foot Candles)

Section D..General Auto Electrical Corporation

Transcription:

Nokeval User's Manual Models 301 / 302 / 305 No 16042010 1

Contents Contents... 2 General description... 3 Disabling front panel keys... 4 Front panel buttons and indicators... 5 Configuration mode... 5 Resetting configuration parameters... 5 Alarm level setting... 5 Alarm functions... 5 Disable alarms... 5 Manual reset... 5 Configuration... 6 Enter configuration mode... 6 Access code for configuration... 6 Description... 7 Input terminals... 7 Alarm connections, only with model 302... 7 Measuring mode... 7 Configuration mode... 7 Alarms off... 7 Calibration mode... 8 : Nokeval Nokeval Oy, Yrittäjäkatu 12, 37100 Nokia, Finland Tel. +358 3 342 4800, fax.+358 3 342 2066, www.nokeval.com, sales@nokeval.com 2

Loop powered LED displays Alarm 1 (low level) Alarm 2 (high level) Transmitter 4-20 ma 4-20 ma For process input 4-20 ma Without external power supply Loop resistance 240 ohm only Scaling on front panel 2 settable alarms (option) Passwords for configuration Field enclosure rating IP 65 4-20 ma Polarity protected Resettable PTC fuse Z1= 4,8 V 2500 10 ohm General description Autopowered bright red LED displays need no external power supply. Current signal 4-20 ma provides the necessary energy. Therefore, it is possible to install the meter in places having no auxiliary power available. You can now replace the autopowered LCD displays, having very poor visibility, by bright red LED displays. There are four models according to optional alarms and plastic case (ABS) IP65 size: 100 x 100 mm basic model 301 without alarms and model 302 with two alarm contacts. Correspondingly model 305 is in 82 x 80 x 57 mm case. Both size versions have the same functions. Display scaling and configuration by front panel buttons. Unit has digital filter for stabilizing the 4-digit display. In models 302 You may configure two optional alarms, high and low. More versatile alarm settings and alternative alarm modes offers our powered models 2012 and 2021. Password is settable for entering configuration. Tampering the configuration can be prevented with a password or with a jumper inside the case. 3

Technical specifications: Input 4..20 ma Max. display scaling -999...+9999 at 23 C, 100ppm/ C Accuracy 0.05% of span Input voltage drop 301, 305 continuous 4,8 V = 4-20 ma (comparable 240 Ω, non resistive) 302 continuous 7,3 V = 4-20 ma (comparable 340 Ω, non resistive) with alarms Alarm relays (option) 2 solid state relays (SSR), max. 250 VAC, 150 ma Alarm reset automatic or manual (hold) via front panel key Alarm mode High and low level Hysteresis Selectable 0..100 % Display 4-digit red LED, 14.5 mm, adjustable brightness Push buttons Switches under front panel surface Case protection IP65 Case material and color ABS-plastic, grey Case dimensions: 301/302 100 x 100 x 57 mm 305 82 x 80 x 57 mm Ambient temperature 0...+60 C Terminals Detachable 2.5 mm² (models 305 and 306 1.5 mm²) Weight 200 g Order codes: Model 301-4/20 ma Model 302-4/20 ma Model 305-4/20 ma 4-digit 4-20 ma loop powered indicator With optional 2 alarms Smaller case 82 x 80 x 57mm Connections: Relays max. 250 VAC, 150 ma Alarm only in models 302 Model 301/302 High level Low level 4 5 6 7 Disabling front panel keys Use of front panel keys can be enabled/ disabled with short cut jumper. When short cut jumper is installed keys can be used to configure and set alarm levels. Keylock A2 A1 Input 4-20 ma - + 3 2 1 Terminal 3 has no internal connection. It can be used freely. Case dimensions (mm): 100 (80) 57 (57) Inlets 2 x 11 mm PG11 Case protection IP65 Case material ABS. Model 305 dimensions are in brackets. This small size enclosure has only one PG11 inlet. 100 (82) 4

Front panel buttons and indicators Conf led indicates configuration mode Alarm indicator LED's A1..A2. ^v arrow buttons are used to change numerical value and for moving on configuration menu. Nokeval 5620 * Conf Place for unit (301 and 302) Configuration mode Exit from selected configuration stage Alarm functions Enter selections in configuration stage Configuration can be started by pressing and holding *- and ^-keys simultaneously for 2 seconds. Configuration stage is for selecting input, display scaling and alarm function. Specified instructions on pages 6-7 section Configuration. Resetting configuration parameters Some times it is necessary to return indicator parameters to factory defaults, e.g. if secret access code is missed. Resetting can be done by pressing and holding * and > buttons simultaneously for 2 seconds when connecting input signal 4..20 ma. Prosedure will reset all settings to factory defaults. Alarms can be viewed in configuration mode. Special instructions on pages 6-7, section configuration. Disable alarms Negative hysteresis value disables alarm function. Manual reset Auto reset is a standard function. Manual reset with front panel v button can be selected by choosing wider hysteresis than full span (Hi -Lo). For example: Input scaling is 0..100,0 i.e. full span is 100. Select hysteresis larger than 100 (9999) and You will have manual reset. Changing value Value is selected with ^v-buttons, one number at a time. Changing begins from the most signifigant digit on the left. Next digit to right is selected with >-button. Accept and exit with *-button. Value selection Selecting next digit 400.0 400.0 Numbers 0...9 Desimal point selection with -keys before number selection 5

Configuration Entering the configuration mode Configuration can be started by pressing and holding * and ^ buttons simultaneously for 2 seconds. Arrow keys ^ and v will move up and down in the main menu. Desired function is selected with > button. Save mode can be selected directly by pushing * button in the main menu. Alarm values and hysteresis are selected in configuration mode. Changes can be restored by selecting text UnDO into display and pressing > button. Note! Detailed configuration stage description on next page. Access code for configuration Configuration mode can be secured with pass word. If function is selected unit asks CODE. Enter required key combination as shown on page 7 section CFCo. Save and Exit Start Return (*) Low level alarm setting. High alarm setting, same routine as low level setting. Undo changes and exit Hysteresis setting. Negative value disables alarm function. Manual reset with front panel keys can be selected by choosing wider hysteresis than full span (Hi -Lo). Decimals 0-3 (^v) Return (*) Display scaling for 20 ma (e.g. 20 ma=1000). Dead zone around zero. If dead is set 0, only negative readings are forcet to 0. Value -1.0 = disabled. D Digital filter, factory default 0,5. Value 0 means no filter Display intensity 1-15. 15 = brightest LIN = linear display Sqrt = square root display Poly = factory setting Can be seen only if TrF=Poly LO and HI Display scaling for 4 ma. Point selects number of digits (not decimals) (^v) and then select minmum scale value with arrow buttons (>) (^v). Number of decimals is selected in section DEC. When exiting with * button, display show selected value with decimals. Alarm relays: LoHi = low alarm, only one of relays can be set for low alarm HiHi = high alarm, both of relays can set for high alarms Password for configuration mode 6

Description Input terminals 1 (+) signal loop (4 20mA) 2 (-) signal loop 3 Not used, can be used as a spare terminal Voltage drop in 4..20 ma input loop is max 4.8 V. This corresponds 240 ohm loop resistance. When alarms are used (optional) voltage drop is max 7,3 V. Input is secured for reversed polarity and over current tolerance is 100 ma. Alarm connections, only models 302 6, 7 Low level alarm, display is lower than alarm level 4, 5 High level alarm, display is higher than alarm level Solid state relays,ssr: max. 250 V ±DC/AC, 150 ma, 12 ohm. Isolation between input loop 4 kv. Alarms can be taken into use by removing jumper inside the case. Voltage drop will increase to 7,3 V. Measuring mode This is normal operating mode. Scaled input signal is in display. LED indicator functions are: A1 = Low level alarm A2 = High level alarm Conf = Unit in configuration or calibration mode Measuring mode can be changed to Configuration mode by pressing simutaneously ^* buttons. If access code is used it must be entered when display shows Code. Configuration mode Undo, Save > Exit from configuration mode. SAVE saves new configuration and Undo exits without saving. AL L, AL H > Alarm levels (L=low, H=high). Both alarms cannot be energized at the same time. Therefore low level cannot have higher value than high alarm and vice versa.if input signal is under 3 ma relays will be deenergized. (Normal open 'NO' relays need energy to be closed). ALHy > Alarm hysteresis is number of digits below or above selected alarm level (both sides have same value). Normally alarm relays are enegized when display value goes to alarm level and de-energized when it goes over hysteresis value. Alarms can also have manual reset when hysteresis value is set larger than measuring range (full span). Manual reset is done with -key from front panel. An example of Manual reset / hold function: High level alarm is 100 C and low level -5 C. When input is over 100 C, LED A2 lits (relay A2 energized) and it don't go off even if the input goes below 100 C. It must be resetted manually with front panel key. Alarm will be resetted also if input goes below selected low level (-5 C). That is because both relays cannot be energized at the same time. If You do not want to use this possibility given by the other alarm, select it's value outside that the scaled range (not in use). Alarms off Negative hysteresis value disables alarm function. Dec > Decimal selection 0..3, i.e. 0.9, 0.99 or 0.999 Lo, Hi > Lo and Hi scales display to input signal 4..20 ma. Lo value is selected for input 4 ma and correspondingly Hi value is for 20 ma input. e.g. 4..20 ma = display Lo -100.. Hi +200 LoPa > Display Filter. This fucntion stabilizes display value when wide measuring range is used. Filter value can be set in seconds. 0= no filter Inte > Display intesity (brightness). You can change the intensity with ^v buttons. Hold v button to decrease intensity and vice versa. In measuring mode intensity decreases automatically when input is under 6 ma. TrF > Transfer function selection. Lin = normal fnction Sqrt = square root function Poly=for special factory setting ALCF > Access code (password) for configuration mode. Access code is formed with ^v*> buttons. Code is formed with six pushes of front panel buttons. Not in use when code is set to (******) (factory default). If configuration access code is forgotten, all the settings can be returned to factory defaults (not calibration) by holding down buttons * and > while connecting input signal 4..20 ma. 7

Calibration When calibrating, accurate 4 ma and 20 ma signals are needed. The device is factory supplied calibrated, and it is scaled to display 0-100.0 unless ordered differently. CAL > If the device displays incorrect readings (more than 0.05% of range), it should be recalibrated. Before doing that, ensure that the input signal is correct (using a separate ma meter) and that the scaling (Lo, Hi) is appropriate. Press ^v* buttons simultaneously and then select CAL and press > button. Enter calibration password 112213 =^^vv^*, 4 ma is displayed. Feed a precise 4.000 ma signal to the device and press > button, calibration factor value is displayed. Accept value by pressing * button and then press v button, 20 ma is displayed. Feed a precise 20.000 ma signal to the device and press > button, calibration factor value is displayed. Accept value by pressing * button. Finally exit to the configuration menu with * button, SAVE is displayed. Accept saving by pressing > button. Exit to the measuring display by pressing * button. : Nokeval Nokeval Oy, Yrittäjäkatu 12, 37100 Nokia, Finland Tel. +358 3 342 4800, fax.+358 3 342 2066, www.nokeval.com, sales@nokeval.com 8