SWITCH YARD OPERATION IN THERMAL POWER PLANT(KaTPP Jhalawar Rajasthan)



Similar documents
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Unified requirements for systems with voltages above 1 kv up to 15 kv

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Chapter 1. Network Structures

Electronic overload relay EF65, EF96 and EF146

Hyperlinks are Inactive

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Electronic overload relay EF19 and EF45

Power transformers. Special transformers Railway

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

CAPACITOR BANK TESTING SWP

Technical Specification Of Substation Protection & Control System with IEC BHEL s Perspective

Safety technique. Emergency stop module BO 5988 safemaster

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation

Secondary Unit Substations

SURGE PROTECTIVE DEVICES

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Engineering Specification

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

HIGH VOLTAGE SHORE CONNECTION

How To Choose A Transformer

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Circulating Current Relay. Type IRXm

Typical Data Requirements Data Required for Power System Evaluation

R.C.C.B. s two-pole LEXIC

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Permissible ambient temperature Operation Storage, transport

Power surges can also be generated by equipment in your facility such as:

SCOPE OF WORK - SUBSTATION

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

EARTHING SYSTEM CALCULATION

Intersection Preassembled 19-inch Rack

TROUBLESHOOTING PRELIMINARY

Arc Terminator Active Arc-Resistant Switchgear

Transformer Design & Design Parameters

Power Quality for Information Technology System

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Customer Substation Manual 08/05/02

Future grid infrastructure Field tests of LVDC distribution

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Applications. Remote Display Mounting Kits

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

Bus differential relay REB phase 1MRK BEN Page 1 Issued: September 2006 Revision: C Data subject to change without notice

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Residual Current Circuit Breaker

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

HIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Electrical Shore Connections / Cold Ironing

Digital Pressure Measuring Instrument MDR480

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

When power interruptions happen.

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Step Voltage Regulators

Electrical Predictive and Preventative Maintenance

Trip circuit supervision relay. Type RXTCS

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

Table of Contents. TransformerIQ FAQs 1

Advantages of Fixed Circuit Breaker Switchgear

Part 1 System Modeling & Studies for Existing Systems

BASIC NEC CODE RULES AND DESIGN PRACTICE

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

ESCOM BY G.KALINDE SUBSTATIONS ENGINEER

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

High-Voltage GIS yesterday - today - tomorrow

Three-phase monitoring relay CM-PFE

How To Understand The Electrical Power Supply Of A Power Supply System

How to design SMPS to Pass Common Mode Lightning Surge Test

Transcription:

From the SelectedWorks of Radhey Shyam Meena Winter July 12, 2012 SWITCH YARD OPERATION IN THERMAL POWER PLANT(KaTPP Jhalawar Rajasthan) RADHEY SHYAM MEENA, Er. Available at: http://works.bepress.com/radhey_meena/5/

PHASE-I PHASE-II 600MW 600MW 650MW 650MW

LOCATION COAL Nimoda, Undal, Motipura, Singharia and Devri villages of Tehsil Jhalarapatan, Distt. Jhalawar LAND The GOR has alloted 842 bigha Government land and aquired 1388 bigha private khatedari land for the thermal project. WATER The state irrigation department has alloted 1200 mcft water for the project from proposed Kalisindh dam Ministry of coal, Govt. of India has alloted Paras east and Kanta basin coal blocks to RVUN in Chhatisgarh state. under joined venture with M/s. Adani Enterprises

KaTPP JHALAWAR, 22KV 1200MW 400KV BTAWDA GT 400KV 400KV BTAWDA GEN. 22 KV UT 22/11 KV GCB 22KV UAT 11/3.3 KV GT GT C&I 3.3KV, 220V SWITCHY ARD ICT 400/ 220 KV 220KV JWR 220KV 220KV JWR

. BUS BAR LIGHTING ARRESTER CIRCUIT BREAKER ISOLATOR CURRENT TRANSFORMER CAPCITIVE VOLTAGE TRANSFORMER WAVE TRAPER

The whole switchyard is grounded with MAT Grounding. In MAT grounding,5 Conductors are placed Horizontally & 8 Conductors are Placed Vertically. All Switchyard equipment are grounded by two Earthing Connection. In switchyard grounding,32mm earthing conductor is used & 75/2 GI earth Sheet is used. All switchyard are gravelled to make the tower footing resistance high.

BUSBAR SCHEME GT feeder Line feeder 2000A 2000A IPS tube of minimum 4.5 inch size IPS tube of minimum 4.5 inch size

GENERATOR BAY 17

Bus Sectionaliser Bay. Bus Coupler Bay 18

ST back charging Bay CLEARANCES 19

LIGHTNING ARRESTORS These are equipments designed to protect insulators of power lines and electrical installations from lightening surges by diverting the surge to earth and instantly restoring the circuit insulation to its normal strength with respect to earth.

CIRCUIT BREAKER A circuit breaker is an automatically operated electric switch designed to protect an electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and, by interrupting continuity, to immediately discontinue electrical flow. Unlike a fuse, which operates once and then has to be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.

SYSTEM ISOLATORS 400KV, 2000A, 40KA for 3.0 sec isolators for GT, lines, ICT bays shall be provided. The Isolator used in this plant is of two types. Single pole double break isolator. Double pole single break isolator.

CURRENT TRANSFORMERS When current in a circuit is too high to directly apply to measuring instruments, a current transformer produces a reduced current accurately proportional to the current in the circuit, which can be conveniently connected to measuring and recording instruments 400KV oil filled live tank type hermetically sealed single phase current transformers will be used. Multi-ratio CT tapping shall be provided on the secondary side to obtain different ratios in order to different ratios In order to permit different ratios on each core, as desired.

C V T capacitor voltage transformer (CVT) is a transformer used to step down extra high voltage signals and provide a low voltage signal, for measurement or to operate a protective relay. Nominal/highest system voltage 400/420 KV Rated primary voltage 400 KV/1.732 Rated secondary voltage 110 V/1.732

An electronic filtering device designed to exclude unwanted signals or interference. It blocks the high frequency carrier waves (24 khz to 500 khz) and let power waves (50 Hz - 60 Hz) to pass through. It is basically an inductor of rating in milli henry.

Purpose of ICT is simply interconnection between 400KV and 220KV Switchyard. 315MVA,400/220/33 KV ONAN ONAF ODAF HV 189 252 315 LV 189 252 315 TV 63 84 109

400KV 400KV BTAWADA 220KV JHALAWAR 220KV BTAWDA KaTPP SWITCHYARD JHALAWAR

Interlocks When Circuit breaker is ON, Isolator should not operate. When Isolator is CLOSE, Earth switch should be OPEN. When Both the Bus are charged, Bus coupler should not become CLOSE. When DC supply if not available, alarm should be raised. When gas pressure inside the Breaker is reduced to 5Kg/cm2,the alarm should be raised. When the oil pressure inside the current transformer is low, then alarm should be raised. When the Nitrogen gas pressure is low at the Current Transformer, then alarm should be raised. 31

RADHEY SHYAM MEENA Student Member Of The Institute Of Engineering & Technology (IET) International Electrotechnical Commission (IEC) Institute Of Electrical & Electronics Engineers (IEEE) The South African Institute Of Electrical Engineers(SAIEE) Universal Association Of Computer & Electronica Engineers(UACEE) Coordinator:-Disha Gyan Sanstha(Rural Education Devlopment Technology)