INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)



Similar documents
Operating Instructions

Floodlight Range Installation Guide

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

Operating Instructions

Technical data sheet TDS0070

Oil and Coolant Circulating Heating System. Model - OCSM

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Safety instructions VEGADIS DIS81.CEIA/V****

SELECTION, APPLICATION AND MAINTENANCE

Rosemount 5300 and 5400 Series Terminal Compartment Spare Part Instruction

Frost Heave Protection System Installation and Operation Manual for Self-Regulating Heating Cable Systems

Installation & Maintenance Manual Type C350 Clear View Screen

Submersion/Insertion Toroidal Sensor

Instructions for Safe Use

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Terminal Box. Specifications TNCN

PBX Series Quick Fit Connector Bimetallic Steam Traps

Explosion proof enclosures

Maintenance Guide IM/AZ20M EN Rev. C. Endura AZ20 series probe Combustion oxygen monitor

Aquamax Australia Pty Ltd ABN

Installation, Operating and Servicing Instructions. Electric Auto-Fill Push Button Water Boilers EB3F/PB and EB3F/PBM

IMPORTANT SAFETY NOTICE

Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen. Series: LP Gas

SureSite Magnetic Liquid Level Indicator

Series 510 Submersible Level Transmitters

SINGLE STAGE INLINE FIRE PUMP

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Compact pressure switch Flameproof enclosure Ex d Model PCA

Design of intrinsically safe systems

5800 Temperature Sensor Cable Assembly

OPERATING INSTRUCTIONS

Mounting Instructions. Torque Transducer. A en

Colima Visco and Colima Viscorol Magnetic Level Indicators

Float and Thermostatic Traps Series H, C and X

Operators manual Basic water heater

Ambient Temperature Sensor TEMPSENSOR-AMBIENT

Instructions For SF 6 Refill Kit

SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths

Coolflo Safe Touch Shower Mixing Valve ST20015CP

Ducoterra Radiant Heating Panel Installation Manual

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

AquaMaster. Installation Manual

MIC-WKT and MIC-WKT-IR

Terminal Boxes in Glass Fiber Reinforced Polyester (GRP)

V94 BULK TAPE DEGAUSSER

Cleaning Instructions, Pilot Replacement and Valve Change. Model No.: Natural Gas


OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

SERVICE SERVICE COMPACT MANUAL. Mod X Mod X Mod X. Part 2

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. OT 020 BENCH TOP STEAM STERILIZER USER S MANUAL


SELECTION, APPLICATION & MAINTENANCE

SF15K SF05KSS, SF10KSS

AMERBRITE UNDERWATER WHITE LED POOL LAMP

Stainless Steel and Mild Steel Enclosures. Stainless Steel and Mild Steel Enclosures

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

Machine needle shut-off nozzle type-a

Fitting Instruction: Daytona 675 Street Triple from VIN , Street Triple R from VIN A

Record Cleaning Machine

MANDATORY SERVICE BULLETIN

DTS-HAZ DTS-HAZ-DC. Installation Instructions. for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Pet hair clipper. Model Diagrams within this manual may not be drawn proportionally.

Cylinder head gasket, replacement

Triac Printed Circuit Board Replacement

Instruction Manual. T3111 T3111L T3111P T3111Ex

Operator Mounting Kit

Artisan Thermostatic basin mixer. Fitting Instructions & Contents List

INFRARED QUARTZ WALL HEATER

Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions

Assembly and instructions

Acclaim III Recessed Fluorescent Luminaires ATEX

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer

Plastic tube flowmeters Series PT/PS

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

SHOT BLAST CABINET MODEL NO: CSB20B

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH7/2.2, AH10/2.2, AH15/2.2

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN

Isotemp Basic, Slim/B & Slim Square

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions

SELECTION, APPLICATION AND MAINTENANCE

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

Model 1756 Test Lead Kit

Operating Instructions

Cooling system components, removing and installing

ATS Overhead Table Shelf System INSTRUCTION MANUAL

Welding Reel ERA 4000 Service Manual

NELSON HEAT TRACING SYSTEMS

Toroidal Conductivity Sensor

KEEP FOR FUTURE REFERENCE MRTALP VERTICAL LIFT BAR READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT

David O Brien, CMP Products (David.OBrien@cmp-products.com)

Transcription:

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF) Please read these instructions thoroughly before installation and ensure they are passed on to the end-user. 1

1.0 GENERAL 1.1 All work should be carried out by suitable qualified personnel. 1.2 Heaters must be handled with care and stored in dry conditions. 1.3 Adequate withdrawal space must be provided to allow the removal of the heater assembly. 1.4 Carefully remove all protective packaging and visually inspect unit for any transit damage. 1.5 All prevailing rules, regulations and bylaws in force at the time and place of installation must be observed. 1.6 Heaters must only be immersed in the fluid they are designed to heat. 1.7 The introduction of alternative fluids even in small concentrations for purposes such as sterilising may cause serious damage to the heater and will invalidate the warranty. 1.8 Any modification not carried out by Exheat Limited or its approved agent will invalidate certification and warranty. 1.9 Precautions must be taken to prevent damage to enclosure seals. 1.10 For flameproof heaters reference must be made to IEC / EN 60079-17. 1.11 All electrical testing must be carried out in a non-hazardous area. 1.12 Precautions must be taken to prevent damage to machined surfaces and threads of flameproof enclosures. 1.13 Any special conditions for safe use detailed on the hazardous area certification for flameproof heaters must be complied with. 2.0 INSTALLATION 2.1 The heater should be securely fixed in position and all terminal connections checked for tightness before energising. 2.2 The heater must be installed horizontally unless it has been specified and manufactured for use in a vertical orientation. 2.3 The installed orientation of horizontally mounted heaters must be such that any thermostats or other temperature sensors are uppermost. 2.4 Sealing gaskets must be undamaged. 2.5 The terminal box must not be used for tightening heater into tank or vessel. 3.0 ELECTRICAL SUPPLY CONNECTION 3.1 Refer to wiring diagram (inside the cover non-flameproof heaters only). 3.2 The cable entry is positioned on the side of the terminal box. 3.3 Before connection ensure that the supply corresponds with that specified on the rating label. 3.4 Ensure that the sizes and types of cables to be used are suitably rated for the load and temperature of the unit. 3.5 Each heater must be protected by a suitably rated over current device. 3.6 Cables must enter the terminal box via a suitable cable gland to maintain the IP rating and be fitted by a qualified person. 3.7 For flameproof heaters, cables must enter the heater terminal box via ATEX certified Ex d (for ATEX certified heaters) or IECEx certified Ex d (for IECEx certified heaters) cable glands (not supplied) and be fitted by a qualified person. 3.8 The cover (and body where applicable) of FP and RF series terminal boxes are unscrewed after slackening a locking grub screw using a 3mm A/F hex key. When re-fitting ensure that the o ring seal is in good condition and correctly located. The main cover threads MUST be kept clean and free from any debris at all times. 3.9 The installer or end user must connect to the Exheat supplied terminals within the terminal box - DO NOT connect to or disturb factory fitted heating element wiring. 2

4.0 EARTH CONNECTION 4.1 WARNING these heaters MUST BE EARTHED. 4.2 An internal earth connection is provided inside the terminal box. 4.3 An external earth connection (flameproof heaters only) is located adjacent to one of the terminal box cable entries. 5.0 OPERATION 5.1 Ensure that the active section of all the heating elements are fully immersed in the fluid to be heated at all times whilst energized. 5.2 Heat is transferred by means of electric heating elements. 5.3 Control of the heater is facilitated by thermostats, thermocouples or RTD s and reference should be made to the wiring diagram (inside the cover non-flameproof heaters only) to ensure that these are correctly connected and set prior to energising the heater. 5.4 Where a manual reset thermostat or cut-out is installed, the terminal box cover will have to be removed to enable a reset to be carried out. 6.0 MAINTENANCE 6.1 All prevailing site safety regulations shall be adhered to at all times. 6.2 Any damage or faults should be notified to Exheat Limited immediately 6.3 Equipment must be fully isolated from the electrical supply before and whilst any work is being carried out. 6.4 Before and whilst any maintenance activity is carried out, it must be ensured that there are no hazardous gases present. 6.5 Replacement of core type heating elements may be carried out without removing the heater by disconnecting the element and withdrawing it from its tube CAUTION: hazardous area core heaters must NOT be energised with any core elements missing from their respective tubes. 6.6 For flameproof heaters reference should be made to IEC / EN60079-17 (especially table 1) in addition to the following recommendations. 6.7 Any replacement parts required must be obtained directly from Exheat. The use of any other parts will void any certification and warranty. 6.6.1 3 Monthly a. Generally inspect the equipment for external damage or leaks. 6.6.2 6 Monthly a. Isolate the electrical supply and remove the cover (after releasing locking grub screw using a 3mm A/F hex key flameproof heaters only). b. Check that the terminal box is clean and dry internally. c. Check that the electrical terminals are intact and secure. d. Check that the heating element insulation resistance is at least 2 megohm. e. Check the continuity of all heating elements. f. Refit cover with new gasket or o ring if required (and re-tighten locking grub screw flameproof heaters only). g. Check that earth continuity is maintained between all exposed conductive material and main structure. 3

6.6.3 Annually a. Carry out all 3 monthly and 6 monthly checks as above. b. Check for element failure or low insulation resistance. 6.7 Only Exheat Ltd or its approved agent to carry out rod type element replacement in flameproof heaters otherwise the certification will be invalidated. 6.8 If heaters are being left unused for a period greater than 3 months, carry out 6 monthly maintenance before energizing. 6.9 IR Low Insulation / Earth Leakage Prevention 6.9.1 Heaters must be handled carefully and stored in a clean and dry environment. 6.9.2 The storage period should not exceed 12 months. 6.9.3 The silica gel bags must remain within the terminal box and replaced as required. 6.9.4 The cable entries must be plugged at all times. 6.9.5 The terminal box lid must be replaced immediately after any installation work has been carried out. 6.10 Removal and Replacement of Ceramic Core Type Heating Elements (core-type heaters only) 6.10.1 Replacement of this type of heating element may be carried out without removing the heater assembly from its tank or vessel and without draining it down. 6.10.2 Isolate the electrical supply and remove the cover (after releasing locking grub screw using a 3mm A/F hex key flameproof heaters only). 6.10.3 Disconnect electrical connections and remove cables to heater (single core flameproof heaters only). 6.10.4 Slacken base locking grub screw then unscrew and remove terminal box body (single core flameproof heaters only). 6.10.5 Release clamps securing heating element. 6.10.6 Carefully withdraw heating element from its tube. 6.10.7 Check element tube is clean and dry internally. 6.10.8 Carefully fit replacement healing element through a new sealing gasket and into tube whilst preventing it from bending and protecting it from mechanical shock. 6.10.9 Re-assemble heater and re-connect wiring (reverse of 6.9.2 to 6.9.5 above). 6.10.10 Carry out 6 monthly checks as above. 4

7.0 Marking 7.1 RFA Type: II 2 G (ATEX certified heaters only) Ex d IIC T6 to T3 7.2 RFA Type (Externally adjustable version): II 2 G/D( ATEX certified heaters only) Ex d IIC T6 to T3 Ex td A21 IP6X T C 7.3 RFA-C Type: II 2 G (ATEX certified heaters only) Ex d IIC T6 7.4 FP Type: II 2 G/D (ATEX certified heaters only) Ex d (or de) IIC T6 to T1 Ex td A21 IP66 T C 8.0 Certification references: 8.1 RFA Type LCIE 99 ATEX 6006 X 8.2 RFA-C Type LCIE 99 ATEX 6011 X 8.3 FP Type LCIE 01 ATEX 6056 X IECEx LCI 06.0006X 5

This Page Intentionally Left Blank 6

This Page Intentionally Left Blank 7

EXHEAT LTD Threxton Road Industrial Estate Watton, Thetford, IP25 6NG Tel: +44 (0)1953 886200 Fax: +44 (0)1953 886222 For sales, spares and new product information see our website www.exheat.com 2006/95/EC 89/336/EEC (As amended by 92/31/EEC & 93/68/EEC 94/9/EC (ATEX Certified Flameproof heaters only) Stock Code S090.00.0000.0008 Issue J 8