Sample Collection Procedures for Insulating Fluid Samples



Similar documents
Electrical Maintenance Workshop

LAB 24 Transpiration

Atrium Pneumostat Chest Drain Valve. Discharge Instructions

For safety information, see the ABI PRISM 310 Genetic Analyzer User s Manual (PN or ).

Administration of Meropenem For Child

15CI and 25CI Reversing Motor Pumpset Owner's Manual

Standard Hydraulic Piping Flushing Procedure

Promoting safer use of injectable medicines

Ward 29 guide to the safe preparation and administration of intravenous (IV) antibiotics at home

Operator Quick Guide EC SENSOR

Blood Sampling in Sheep AS-557-W

Instructions for 24 hr Urine Collection

Rutgers Environmental Health and Safety

When Completed - Fax to (410)

ClikSTAR - Important facts about your new insulin delivery device.

Instructions for Use PROCRIT (PRO KRIT) (epoetin alfa)

Flushing and Cleaning the A/C System

NITROUS TRANSFER PUMP INSTRUCTIONS

Back Pack Sprayer. Operator's Manual MODELS MS - 40 MS - 50

The Molar Mass of a Gas

Care for your child s Central Venous Catheter (CVC)

Dissolved Oxygen Sensors

NIH Clinical Center Patient Education Materials Giving a subcutaneous injection

Biliary Drain. What is a biliary drain?

Scotchgard Multi-Layer Protective Film 1004

Determination of a Chemical Formula

STANDARDIZATION OF A SODIUM HYDROXIDE SOLUTION EXPERIMENT 14

Extraction: Separation of Acidic Substances

Tipping Bucket Rain Gauge Models 6011-A 6011-B

Model 1210C Battery Powered Pump Shown. Description

INSTITUTIONAL POLICY AND PROCEDURE (IPP) Department: Manual: Section:

Instructions for Drawing Blood Samples

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

MAGB HEALTH, SAFETY AND ENVIRONMENT GROUP POLLUTION INCIDENT RESPONSE PLAN

UNIVERSITY OF MINNESOTA DULUTH DEPARTMENT OF CHEMICAL ENGINEERING ChE ABSORPTION OF CARBON DIOXIDE INTO WATER

Section 6: Your Hemodialysis Catheter

Record Cleaning Machine

North Carolina State University Emergency Facilities Closure Checklist- Part I

The Analytical Balance

Calibration of Volumetric Glassware

Coating and Extraction of Honeycomb Denuders

Pressure. Curriculum for Excellence. Weather and Climate Cross-curricular project Section 2. Background Information:

VAPOR PRESSURE AS A FUNCTION OF TEMPERATURE. This laboratory covers material presented in section 11.8 of the 9 th Ed. of the Chang text.

How To Prepare and Give a Prefilled Syringe Injection

World-Class Oil Sampling It is Possible

Self Purging Liquid Trap (SPLT ) User s Manual

UNIVERSITY OF WISCONSIN MADISON

Ozone Generator Manual

Global Water Instrumentation, Inc.

Paper Chromatography: Separation and Identification of Five Metal Cations

CYTOTOXIC PRECAUTIONS A GUIDE FOR PATIENTS & FAMILIES

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

Standard Operating Procedure for a Chemical Spill

Caring for a Tenckhoff Catheter

Good practice for the preparation of injectable medicines in clinical areas

Tube Feeding at Home Gravity or Syringe Feeding

CHAPTER 9 SAMPLERS AND SAMPLING PROCEDURES

Chemistry 112 Laboratory Experiment 6: The Reaction of Aluminum and Zinc with Hydrochloric Acid

PATIENT GUIDE. Care and Maintenance Drainage Frequency: Max. Drainage Volume: Dressing Option: Clinician s Signature: Every drainage Weekly

Unit 24: Applications of Pneumatics and Hydraulics

What Can the OIL ANALYZERS Fluid Analysis Program Do For You?

Instructions for Use. Components of the GENOTROPIN PEN 12

Peripheral Venous Catheter Placement Simulator

Sampling Solutions. Fuel and Lube Oil sampling Equipment. Convenient, Representative, Approved.

I-140 Venipuncture for Blood Specimen Collection

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER...

Bydureon 2 mg powder and solvent for prolonged-release suspension for injection

Calibration of Volumetric Glassware

DryWeight BulkVolume

SPILLS & SPILL KITS. Spills -General Guidelines:

Submersion/Insertion Toroidal Sensor

Aseptic Technique. A GMP/GTP Training Module

Support Cleaning Apparatus. Operation, Cleaning, & Safety Manual

Trace Dissolved Oxygen Sensor

Introduction A JP Drain is a soft tube and container used to drain fluids that build up under the skin after surgery.

Steam Sterilization Cycles for Lab Applications

Proper Segregation and Disposal of Low-Level Radioactive Waste (LLRW) at Wayne State University

INSTRUCTIONS FOR USE HUMIRA 40 MG/0.8 ML, 20 MG/0.4 ML AND 10 MG/0.2 ML SINGLE-USE PREFILLED SYRINGE

Private Water Supplies Sampling Manual. A Field Guide

Removing a Clog. Before you begin:

Particularly Hazardous Substances (PHS) Standard Operating Procedure (SOP)

ANALYSIS OF FOOD AND NATURAL PRODUCTS LABORATORY EXERCISE

UNIVERSITY OF RICHMOND REGULATED MEDICAL WASTE MANAGEMENT GUIDELINES

User Manual Important: First read the Medication Guide that comes inside your FORTEO carton.

Policies and Procedures Manual Waste Management Plan Policy No. 06:04:00 Page 1 of 12

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

ENGINE COOLING SYSTEM

FOREWORD. The Plastics Pipe Institute. This Technical Note, TN-30, was first issued in January 2006 and was revised and republished in September 2013.

Policy and Procedure Flushing and / or Blood withdrawal Aspiration Procedure For PICC Line and Midline Catheters

AIRFREE TECHNIQUE AND SENSITIVE REAGENTS S ECTI O N 1: GLASS W ARE A ND E Q UIP M ENT. A. Using a manifold

COMMON LABORATORY APPARATUS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Berea College Chemical waste/product Management Guide. October 2014

IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1

INGROUND, ROPED, AND HOLELESS JACK SEAL REPLACEMENT

Insulin and Diabetes

The Enbrel SureClick autoinjector is a single-use prefilled autoinjector. It contains one 50-mg dose of Enbrel.

Transcription:

Sample Collection Procedures for Insulating Fluid Samples GENERAL Sampling electrical insulating oil for laboratory analysis requires care to ensure that the sample is representative of the product being sampled. Attention to cleanliness is the key to success. Before attempting to draw the sample identify the type of cooling liquid in the transformer. Normally, mineral oil not contaminated by PCBs, mineral oil with unknown values of PCBs, and silicone fluids will be sampled. If the fluid is other than conventional mineral oil, identify the fluid on the insulating test report under samplers comments. It is not recommended to draw samples of Askarel type liquids or mineral oils with a PCB contaminant level greater than five hundred ppm. If the transformer has been sampled for PCB fluid contamination, it should contain a label indicating the level of contamination. Since it is possible that an oil sample can be contaminated with trace amounts of PCB, do not pour waste oil on the ground. If the device is not labeled as a PCB transformer and has never had a PCB determination made, indicate on the data sheet to instruct the laboratory to perform this test. When sampling a unit with no PCB label present, treat the unit as having contaminated fluid. This is to protect the sampler. PROCEDURE While reviewing the following procedures, please refer to Figure 1, illustrating the sample valve connections on a typical transformer, and Figures 2 and 3 demonstrating the syringe valve positions. The apparatus to be sampled should be under positive pressure. For transformers sealed with an inert gas, check the pressure gauge to make sure it

does not indicate a negative pressure. The head of oil in the transformer may be enough to overcome a partial vacuum and allow the sample to be taken. To ensure that the vacuum will not draw air into the transformer, attach a length of Tygon tubing, filled with clean oil, to the sampling valve before cracking the valve open. Carefully observe the direction of oil movement in the tube and close the valve immediately if the oil flow is towards the transformer. Do not allow air to be drawn into the transformer! Air can only enter the transformer when it is under a vacuum. The valve through which the sample is to be taken should be flushed by allowing about half of a gallon of oil to flow to a waste container. Figure 1

DRAWING THE SAMPLES I. Bottle Samples for Screen Tests: After having flushed the valve, rinse the bottle by partially filling and gently swirling and emptying the oil into the waste container. Fill bottle to within an inch or so of the top. Do not over fill to allow for expansion. Visually examine the fluid for water droplets or foreign particles. If present, resampling is required. If the sample is clear, attach the cap securely, identify the sampled unit on the bottle s label, and prepare for shipment. Do not tape the cap. II. Syringe Samples for Dissolved Gas Analysis: The plastic stopcock (Figure 2 and Figure 3), which comes with the syringe, must remain firmly affixed to the syringe at all times to prevent leaks and to securely close the syringe for shipment. When obtaining oil samples for gas analysis, it is important that the sample never be subjected to a vacuum, which would tend to degas the oil and lead to inaccurate test results. This means that the syringe should be filled without pulling on the plunger. It will help to follow the sampling procedure if you remember that the handle of the plastic stopcock points to the closed port of the stopcock (Figure 2 and Figure 3). The stopcock handle hereafter is referred to as the handle. A. Syringe step by step sample instructions: 1. Attach the syringe to the sampling valve located on the side of the drain valve using a short length of Tygon tubing (available at any hardware store) as an adapter. If there is no sampling valve, see step (e) described below.

Figure 2 Figure 3

2. Flush the system as follows: a) Move the handle toward the sampling valve, b) Open sampling valve and move the handle towards the syringe allowing the oil to flush the tube and stopcock. c) Move the handle towards the side port, allowing oil pressure to enter the syringe barrel, forcing the plunger out. Until the inside of syringe has been wetted with oil, it may be necessary to pull on the plunger. d) When the oil reaches the 50 cc mark, move the handle towards the sampling valve and eject oil from syringe by pushing in the plunger. Catch this ejected oil in a waste container to avoid spilling it on the ground. 3. Draw the sample by moving the handle towards the side port and allow the oil pressure to fill the syringe. Do not pull on the plunger! When the oil reaches the 40 to 45 cc mark, move the handle towards the syringe. Do not over fill since the shipping container was designed to protect the syringe with the plunger extended no further than 50 cc. 4. Examine the sample to see that there are no foreign particles or bubbles present. If the sample is clear, move the handle towards the syringe, close the sampling valve and remove the syringe with the stopcock still firmly attached to the syringe. If the sample was not clear, repeat steps (a) and (b). If you are unable to obtain a bubble-free sample after two or three attempts, fill the syringe to above the 50 cc mark, move the handle towards the syringe, close the sampling valve and remove the Tygon tube (with the syringe still attached) from the sampling valve. Hold the syringe upright and allow bubbles to rise towards the stopcock. Move the handle towards the side-port and gently push the plunger to eject any bubbles. Close the valve (handle toward the stopcock) when the volume reaches 40-45 cc. Remove the Tygon tubing from the syringe. Wipe off surface oil and prepare for shipment to the laboratory.

Note: The stopcock must be firmly attached to the syringe and the handle must point to the syringe. When there isn't a sampling valve, a sample can be obtained by removing the syringe plunger and gravity filling the syringe after having flushed the drain valve and syringe. Remove any bubbles as instructed in step 4. Please note on the test form the fact that the sample was drawn using gravity fill so that proper allowances can be made in the data analysis. AFTER THE SAMPLE 1. Complete the Sample Data Sheet as thoroughly as possible. 2. Wipe any oil from outer surface of the sample container and place in the shipping container. Place the Sample Data Sheet(s) in a plastic bag and enclose it in the shipping container. 3. Seal the shipping container and affix the gummed address label supplied by TJ/H2b Analytical Services, Inc. If no label was supplied, please ship the sample to the TJ/H2b location nearest you. 3123 Fite Circle, Sacramento, CA 95827 4927 Jefferson Highway, Jefferson, LA 70121 3098 Happy Valley Road, Sun Prairie, WI 53590 204 Gale Lane, Kennett Square, PA 19348 335 25 th Street S.E., Calgary, AB, Canada T2A 7H8 FINDINGS: The results of the test analysis are prepared in a written report and mailed to the contact address entered on the Sample Data Sheet. You will be notified of critical results by fax/telephone. Permission to provide this information has been granted by TJ/H2B (http://www.tjh2b.com/).