Eksplosjonsrisiko, værbeskyttelse og optimalisering av design



Similar documents
Using CFD in Platform Design

Norsk Olje og gass Selbusjøen

Assessment of Hydrocarbon Explosion and Fire Risks. Professor Jeom Paik. The LRET Research Collegium Southampton, 11 July 2 September 2011

Marin Ising (sjøsprøyt) på fartøyer, MARICE prosjektet

Risk Analysis of Gas Explosions on Oil Platforms

Managing risks for lay-up of OSVs and Rigs

CFD Computational Fluid Dynamics

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

Risk Assessment Data Directory. Report No March Ignition probabilities

Lessons Learned, Best Practices and Observations Plant Winterization Visits

ROOFS, SNOW AND ICE DAMS

Mechanical and Natural Ventilation

Safety Challenges in the Arctic

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Enclosures DuraSystems Barriers, Inc. The Passive Fire Protection Specialists

HOW MUCH FUEL DOES A GAS STOVE CONSUME AND HOW MUCH DOES IT COST TO OPERATE?

GAS DISPERSION WITH OPENFOAM

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

TOXIC AND FLAMMABLE GAS CLOUD DETECTORS LAYOUT OPTIMIZATION USING CFD

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1

Nitrogen Blanketing for Methanol Storage and Transportation

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Condensing Boiler Efficiency

NORSOK STANDARD H-001 Rev. 4, Nov Heating, ventilation and air-conditioning

Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere

Radiant Panels and Chilled Sails.

Onshore Explosion Studies Benefits of CFD-Modelling

Preventing Ice Dams on Roofs

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

Energy efficient home design

A Response Surface Model to Predict Flammable Gas Cloud Volume in Offshore Modules. Tatiele Dalfior Ferreira Sávio Souza Venâncio Vianna

Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels. W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd.

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

From WorldWide to Arctic, challenges and risk

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

DET NORSKE VERITAS TM

LNG SAFETY MYTHS and LEGENDS

RESPONSE TIME INDEX OF SPRINKLERS

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING

Seasonal & Daily Temperatures. Seasons & Sun's Distance. Solstice & Equinox. Seasons & Solar Intensity

Diesel fuel in winter The effect of cold weather on fuel systems

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A.

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Defining and operationalizing the barrier concept

BRUNS-PAK Presents MARK S. EVANKO, Principal

Risk Assessment Data Directory. Report No March Consequence modelling

Ultrasonic Gas Leak Detection

Commercial Roof Management

Ammonia Detection System Codes and Design Specifications

University of Tennessee Safety Guidelines

INTERNATIONAL STANDARD

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

ASTACEA4 Inspect complex/central air conditioning systems

INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

2.1 The performance of bus air conditioning system is evaluated in the following operating conditions

Data Center Power Consumption

NOTE: Additional user information for your printer may be available in the "Manuals" section at support.dell.com.

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

HSE Information Sheet. Advice on acceptance criteria for damaged Passive Fire Protection (PFP) Coatings. Offshore Information Sheet No.

A Code Review for Emergency Generators and Indoor Use of Portable Generators

Darchem Thermal Protection

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

The Orange County Farmers Museum Emergency Preparedness Plan

Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay

Benefits of Cold Aisle Containment During Cooling Failure

Application of Nuclear and Aerospace Industry Experience to Offshore Barrier Integrity Management

Fire Hazard Calculations for Hydrocarbon Pool Fires Application of Fire Dynamics Simulator FDS to the Risk Assessment of an Oil Extraction Platform

Advice to consumer Reference 50.1 May Condensation. Some causes, some advice.

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000

Passive Cooling Systems Air Conditioning Without the Need of Energy

EMERGENCY VESSELS BLOWDOWN SIMULATIONS

Safety Storage Cabinets

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

CONFINED SPACE ENTRY WORK STANDARD

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

Managing Extreme Weather at Transport for London. ARCC Assembly - 12 June 2014 Helen Woolston, Transport for London Sustainability Coordinator

Guidelines the DNV way

EVALUATION OF THE PMV THERMAL COMFORT INDEX IN OUTDOOR WEATHER CONDITIONS JuYoun Kwon and Ken Parsons

Page 1. Weather Unit Exam Pre-Test Questions

Energy Saving Fact Sheet Boilers

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Near shore and shoreline oil spill response Current status and need for future development

HEALTH, SAFETY AND ENVIRONMENT HANDBOOK HSE

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

13. FPSO Operational Problems Don Smith, OGP

Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before Don Osias Jim Thompson

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Installation Instructions

A practical guide to restrictive flow orifices

Transcription:

OIL & GAS Eksplosjonsrisiko, værbeskyttelse og optimalisering av design HMS utfordringer i Nordområdene Arbeidsseminar 4 Asmund Huser 20 May 2014 1 DNV GL 2013 20 May 2014 SAFER, SMARTER, GREENER

Content Challenges and Objectives Explosion risk analysis as decision making tool Explosion theory Example FPSO in arctic Wind chill and outdoor operations Theory and principles Typical scope ERA and Wind Chill Analysis Optimization of design Improving ventilation with passive and active systems Mitigating explosions Summary and recommendations 2

Main safety challenges in arctic Ensure safe design wrt process safety and working environment Objectives: Give recommendations and decision support in order to optimize working environment AND safety Comply with regulations 3

Explosion risk analysis as decision making tool 4

Overall risk analysis and risk based design procedure Break down and organize consequences and frequencies Examination Simulate all events Risk Analysis Start Establish Scenarios Consequences CFD Frequencies LEAK Point at risk drivers Diagnosis Deliver design improvements Find solutions together with contractor Mitigate Risk assessment e.g. EXPRESS Escalation? Yes Stop No 5

Explosion Risk Analysis approach EXPLOSION ANALYSIS: Geometry modeling Ventilation Dispersion Explosion Probabilistic analysis: DNV program EXPRESS Response surfaces JIP Ignition model Monte Carlo simulations Sensitivities? Design effects and recommendations Explosion Design Accidental Loads Pressure frequency exceedance curves Ignition probabilities 6

Large semi-sub Det Norske Veritas AS. All rights 20 May 2014 Slide 7

Gas leak starts, t = 0 s 1 Wind direction Gas leak starts Above UEL Side view Below LEL Top view 8

Gas leak dispersion simulation, t = 5 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 9

Gas leak dispersion simulation, t = 10 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 10

Gas leak dispersion simulation, t = 15 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 11

Gas leak dispersion simulation, t = 20 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 12

Gas leak dispersion simulation, t = 25 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 13

Gas leak dispersion simulation, t = 30 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 14

Gas leak dispersion simulation, t = 35 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 15

Gas leak dispersion simulation, t = 40 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 16

Gas leak dispersion simulation, t = 45 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 17

Gas leak dispersion simulation, t = 50 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 18

Gas leak dispersion simulation, t = 55 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 19

Gas leak dispersion simulation, t = 60 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 20

Gas leak dispersion simulation, t = 65 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 21

Gas leak dispersion simulation, t = 70 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 22

Gas leak dispersion simulation, t = 75 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 23

Gas leak dispersion simulation, t = 80 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 24

Gas leak dispersion simulation, t = 85 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 25

Gas leak dispersion simulation, t = 90 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 26

Gas leak dispersion simulation, t = 95 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 27

Gas leak dispersion simulation, t = 100 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 28

Gas leak dispersion simulation, t = 105 s 2 Wind direction Leak location Above UEL Side view Below LEL Top view 29

Gas leak dispersion simulation, t = 110 s 2 Wind direction Leak ends Above UEL Side view Below LEL Top view 30

2 Gas leak dispersion simulation, t = 115 s Wind direction Above UEL Side view Below LEL Top view 31

2 Gas leak dispersion simulation, t = 120 s Wind direction Above UEL Side view Below LEL Top view 32

2 Gas leak dispersion simulation, t = 125 s Ignition Above UEL Side view Below LEL Top view 33

2 Explosion pressure wave starts, t = 0 s Ignition Above 0.5 barg Side view 0 barg Top view 34

2 Explosion pressure wave starts, t = 1.15 s Above 0.5 barg Side view 0 barg Top view 35

Explosion pressure wave, t = 1.2 s 2 Above 0.5 barg Side view 0 barg Top view 36

Explosion pressure wave, t = 1.22 s 2 Above 0.5 barg Side view 0 barg Top view 37

Explosion pressure wave, t = 1.23 s 2 Above 0.5 barg Side view 0 barg Top view 38

Explosion pressure wave, t = 1.24 s 2 Above 0.5 barg Side view 0 barg Top view 39

Explosion pressure wave, t = 1.25 s 2 Above 0.5 barg Side view 0 barg Top view 40

Explosion pressure wave, t = 1.253 s 2 Above 0.5 barg Side view 0 barg Top view 41

Explosion pressure wave, t = 1.26 s 2 Above 0.5 barg Side view 0 barg Top view 42

Explosion pressure wave, t = 1.27 s 2 Above 0.5 barg Side view 0 barg Top view 43

Explosion pressure wave, t = 1.28 s 2 Above 0.5 barg Side view 0 barg Top view 44

Explosion pressure wave, t = 1.29 s 2 Above 0.5 barg Side view 0 barg Top view 45

Explosion pressure wave, t = 1.295 s 2 Above 0.5 barg Side view 0 barg Top view 46

Explosion pressure wave, t = 1.3 s 2 Above 0.5 barg Side view 0 barg Top view 47

Explosion pressure wave, t = 1.32 s 2 Above 0.5 barg Side view 0 barg Top view 48

Physics highlights Ventilation should be good before leak starts to dilute the gas Gas cloud develops fast, within 30-60 s for large leaks. Light gas collects under roofs Heavy gas spreads along deck Explosion starts slow and then boom! Effects that decides when it takes off and how high it gets: Size (distance) of combustible gas cloud Congestion Confinement 49

Example FPSO in arctic Turret moored FPSO Winterized process area 50

15 deg wind heading 20 May 2014 Slide 51 Det Norske Veritas AS.

Wind sped inside process area, 15 deg heading 20 May 2014 Slide 52 Det Norske Veritas AS.

Velocity vectors, 15 deg heading Det Norske Veritas AS. 20 May 2014 Slide 53

Velocity vectors transverse planne, 15 deg heading 20 May 2014 Slide 54 Det Norske Veritas AS.

Example dispersion simulations. Gas under roof light gas 20 May 2014 Slide 55 Det Norske Veritas AS.

Example dispersion simulations. Gas under roof 20 May 2014 Slide 56 Det Norske Veritas AS.

Applied designs that prevents and mitigates explosions ignition Prevent: Ventilation Dispersion Mitigate: Venting Explosion Fire Preventive effects are preferred over mitigating effects Reduces both explosion and fire risk Focus on improving ventilation and dispersion Inherent safe design Active ventilation control Active weather panels Platform orientation 57

Wind Chill and Outdoor Operations Theory and principles 58

Theory and Principles - Cold Challenges Cold stress factors Wind Precipitation and moisture Low temperatures Direct exposure to cold surfaces Activity Work clothing Wind chill and outdoor operations Wind chill temperature ( o C) Radiation Evaporation Respiration Convection Conduction Effective Heat Loss per time, WCI (W/m2) (ISO/TR 11079 ) I WC 1 2 1.16 u u 10.45 10 33 T 59

Effective temperatures considering wind chill Effective temperature as function of wind and ambient temperature (ISO11079:2007 / ISO 15743; Ergonomics of the thermal environmet. Cold workplaces Risk assessment and management) 60

NORSOK and US limitations Det Norske Veritas AS. 20 May 2014 Slide 61

Effective Heat Loss per time (ISO/TR 11079 - NORSOK S-002, 2004 reference) I WC 1 2 1.16 u u 10.45 10 33 T 62

Other influences Night work increased heat loss Age Lowered tolerance Sex Men tolerate cold better Ethnical differences Polars benefit Medical conditions heart, Reynaud (likfingre) Work intervals 63

Opimize design: Wind walls and enclosures to provide weather protection Optimal design related to weather protection Potenital explosion risks due to confinement and enclosures: Gas cloud build-up No explosion relief Balancing Process safety vs Working environment Requirements: - NORSOK S-002, Section 4.4.9/5.8 - NORSOK S-001, Section 15.4.1 Practice - NORSOK Z013 annex F 64

TYPICAL SCOPE ERA and Wind Chill Analysis 65

ERA and ACH Assessment Obtain DAL pressures from ERA. Assess if DAL is acceptable - NORSOK Z013 Annex F is followed - Use same geometry model for WCI sims Assess if minimum required ventilation rate is obtained - Assess NORSOK S001 criteria of minimum 12 ACH 95% of the time - ACH exceedance curve found by combining wind rose with ventilation simulation results - The upper 95% ACH percentile read off the curve Geometry Ventilation simulations ERA WCI assessment DAL and Outdoor operations workshop 66

Work area Availability (%) WCI distribution calculations: Unavailability WCI distribution for work areas calculated and assessed towards criteria Unavailability calculations considering Distribution of WCI levels Availability per WCI level Work area distribution Criteria: Yearly unavailability < 2% Geometry Ventilation simulations ERA WCI assessment Outdoor operations workshop 67

Outdoor Operation and safety Workshop Identification, discussion and measures - Different disciplines including operational personnel attending - Use ERA and WCI assessment to point at: - explosion risk drivers and - Challenging work areas wrt wind - Identify improvement measures - Find solutions that works and is possible - Design - Operation - Further work Geometry Ventilation simulations ERA WCI assessment DAL and Outdoor operations workshop 68

Reference Documents and Standards Relevant standards NORSOK S-002 Working Environment, Rev. 4, August 2004 NORSOK S-001 Technical Safety, Rev. 4, February 2008 NORSOK Z013 Annex F Procedure for Probabilistic Explosion Simulations 2010 ISO 15743:2008. Ergonomics of the thermal environment - Cold workplaces - Risk assessment and management, Edition 1, November 2008 ISO 11079:2007. Ergonomics of the thermal environment - Determination and interpretation of cold stress when using required clothing insulation (IREQ) and local cooling effects, Edition 1, December 2007 ISO 19906:2010. Petroleum and natural gas industries - Arctic offshore structures, Edition 1, December 2010 Reference Reports Health Aspects of Work in Extreme climates, A guide for oil and gas industry managers and supervisors. OGP Report Number 398, 2008 Kalde utfordringer. PSA Report number 10-31, ISBN 978-8032-024-7, May 2010, 69

DESIGN OPTIMIZATION 70

Applied designs that reduce explosions and improve working areas ignition Prevent by: Ventilation Dispersion Plus avoid high wind Mitigate by: Venting Explosion reduction Fire reduction Preventive effects are preferred over mitigating effects Reduces both explosion and fire risk Focus on improving ventilation and dispersion Inherent safe and work place friendly design Active ventilation control Active weather panels Platform orientation 71

Prevention by inherent safe ventilation design Main air comes in through wall openings and in arctic the openings are reduced significantly Optimize WCI vs. dispersion Open as much as possible without breaching WCI requirements Avoid gas accumulation under roof More openings high up on the walls Roof openings 72

Openings along upper parts Slide 73

Roof design Important to get the gas out quickly Permanent openings best Open all along roof is best Chimneys not sufficient openings Snow and ice challenge Causes build-up of weight which stops explosion release panels Snow can come into the process Separate snow simulations can be performed Heat tracing becomes very extensive 3m 4m 1m 16m 13m Upper Process Deck: EL 47.1 Main Process Deck: EL 38.1 Slide 74

Prevention by inherent safe ventilation design Avoid re-circulation flow in process areas FPSO Safety gaps show benefits Blast walls upwind gives re-circulation and poor ventilation Limit size of explosion areas Process areas, use plated decks between modules FPSO, use plated 1 st process deck Minimize blocking by equipment of module air inlets 75

Prevention by active ventilation control Active weather panels in walls Opens when gas is detected Opens when temperature is higher Opens when areas are unmanned New technology ice and snow challenge Roof panels Can open when temperature is higher Snow and ice challenge Ventilated and heated rooms where most of work is performed Challenge with leak sources inside FPSO active thrusters to improve ventilation Fans to improve ventilation: last resort Requires large fans Represent ignition source 76

Mitigation of explosions Leak/ignition Mitigate Congested equipment and piping away from walls and decks Avoid corners in walls Reduce congestion by more space Minimize blocking of module venting openings Use explosion panels in walls and ceilings 77

Preventive and/or mitigating measures Process: Smaller segments Automatic blowdown Quick ESD valves Shutdown of ignition sources Good gas detection Fire protection Optimize blowdown vs PFP Use quick blowdown instead of PFP Internal escape route Avoid trapping of smoke by large items 78

Arctic weather protection options Passive Windwalls typically used in the North Sea Wind cladding Porous windwalls Louvres Explosion release panels Active weather panels Roof design 79

Active Panel Geometry Part of wall has AWP Total opening degree is important Combination of open, closed and AWP

How AWP can operate / different strategies Open on gas detection Often too late to reduce gas cloud Automatic operated based on wind and temperature, snow and ice: Open at good weather Close when people are present and weather is bad 81

Recommendations Wall designs Additional Ventilation where required Higher levels where buoyant release accumulates Alteration to roof opening design to allow more gas to escape Not frequently manned areas More Control where required Active weather panels positioned at working heights on lower and upper deck Allows control of wind speed where people will be working Automatic opening during low wind speeds and high temperatures Pop Out blast panels Can significantly reduce explosion pressures

LQ, helideck, utility and process location on FPSO LQ and helideck upwind to avoid Smoke Exhaust Turbulence Gives poor ventilation to process LQ and Helideck downwind Gives better ventilation to process modules Must ensure long enough distance from process to LQ Conflicts with aft offloading Slide 83

SUMMARY AND RECOMMENDATIONS 84

Recommended measures Layout and process recommendations Personal protective wear and equipment Temporary windbreaks or active wind walls Procedures and operation Work restrictions, Cold permit Information, coursing and medical preparedness Access to heated shelters close to cold working areas 85

Benefits of combined explosion and wind chill analyses Wind chill and explosion challenges identified in early project phase, and not later based on bad experiences Difficult or costly to implement improvement measures after early design phases Decision support for a safe and sustainable design and operation 86