Alarm Systems Using Wireless or Other Transmission Technology as a Single Path of Communication. Purpose. References. Description of Code Reference

Similar documents
White Paper. Why Cellular as a Single Transmission Path meets the Requirements of NFPA 72. The Gradual Demise of POTS

Loop Start or Ground Start?

UL s Perspective on IP Signaling Larry Shudak Principal Engineer Signaling and Security Control Equipment Underwriters Laboratories Inc.

The Evolution of Requirements for Supervising Station Alarm Systems

Fire Alarm System Monitoring - CAN/ULC-S561-03

January 1, RE: TG-7FS Sole Path Cellular Alarm Communicator. To whom it may concern:

CAN/ULC-S Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013

Module 4, Lesson 12 Fire Alarm Systems

From Tyco Security Products. Commercial Fire Monitoring Solutions. Dsc -- The Most Trusted Name In Fire Monitoring

Fire Prevention Coffee Break Training. November 2015

New UL 864 & NFPA th Edition Fire Alarm Control Panel (FACP) AND. Cellular Communication Regulation Advancements

OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

AlarmNet Commercial Fire. We ve Got You Covered

Central Station Interface with Fire Alarm and the Relevant Codes & Standards

Internet/Intranet Alarm Communications. Maximize security and convenience with Internet/Intranet alarm communications

Voice Over IP Digital Phone Concerns with Security and Fire Alarm Communications Systems

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

Wireless Mesh Networks and Applications in the Alarm Industry. A Technology Overview. Presented by

Security Alarm Systems

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

AlarmNet Network Overview

Before the FEDERAL COMMUNICATIONS COMMISSION Washington, DC 20554

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

How To Install A Carbon Monoxide Detector

SECTION DETECTION AND ALARM

Common Questions & Answers

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

Overview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products

Fire Alarm Systems Certification

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

Fire Alarm Log Book. Any activity regarding this system must be documented in writing.

Phone Company or Phony Company? Part 2 by Dean K. Wilson, P.E.

FIRE ALARM SYSTEM RECORD OF COMPLETION

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

FIRE ALARM SYSTEM RECORD OF COMPLETION

BASIC FIRE ALARM TRAINING

Application Note AN-00125

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

NATIONAL FIRE ALARM AND SIGNALING CODE

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

SOLUTION BRIEF. Motorola FSA4000. How to Achieve Near 100% Fire Station Alerting Reliability

CHAPTER 8. Village of Caledonia Alarm Systems Ordinance ( /01/13)

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

Sam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

rpsa FIRE PROTECTION ENGINEERS

Chapter 4. Regulation of Alarm Systems

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

Simon XTi Installation Guide

TOWN OF SIDNEY BYLAW NO A BYLAW TO REGULATE THE USE AND POSSESSION OF SECURITY ALARM SYSTEMS IN THE TOWN OF SIDNEY

Alarm over IP. What is Alarm over IP? How does Alarm over IP work? Intrusion Systems White Paper Series Alarm over IP

Overview of Standards for CO Detection Products

What Should I Expect From My Alarm Monitoring Station?

Safety & Performance in the Wire and Cable Industry

Fire Station IP Alerting System

Infant & Pediatric Security Solutions

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE

NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. Level III Content Outline

POSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008

Before the FEDERAL COMMUNICATIONS COMMISSION Washington, DC 20554

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL

CLASS TITLE: Two-Way Wired Emergency Communication Systems (ECS), and Wireless Emergency Responders Radio Coverage Systems (ERRCS)

THE TOWN OF GROTON IS REQUESTING PROPOSALS FOR A WIRELESS ALARM MONITORING AND CONTROL SYSTEM WITH INTERNET BASED DATA ACCESS

Effective June 27, TEXT (CO Detection Commercial Buildings)

University Design Standard. Fire Alarm Systems

IP Alarm System Resiliency on Disaster Recovery and ISP changes. A better alternative to DNS-based solutions

UNIFIED FACILITIES GUIDE SPECIFICATIONS

A new radio system for the German coast

TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section , to read as follows:

AlarmNet-i. Are you ready for Internet monitoring?

Comprehensive Security with one Powerful System. G Series integrated security, fire and access control panels

ORDINANCE RELATIVE TO FALSE ALARMS

Rolling Meadows, Illinois: Code of Ordinances

HIPAA Security Considerations for Broadband Fixed Wireless Access Systems White Paper

HERNANDO COUNTY FIRE ALARM GUIDELINES

The Mission Critical Fire Protection Experts

Definitions for KRS , , , and As used in KRS , , , and : (1) "Ancillary services"

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

Business Account -- Service Takeover Authorization Form

White Papers: Delayed Egress Hardware

Security Enhancements through Industrial Wireless Networking. Prepared by Microwave Data Systems Rochester, New York June 2002

Network Neutrality Statement

Complete Security One Powerful Solution. GV4 Series integrated security, fire and access control panels D7212GV4, D7412GV4, D9412GV4

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

INTRUSION DETECTION SYSTEM Section

ARTICLE 735. Emergency Alarm System

COMBINE BURGLARY AND FIRE PROTECTION WITH ACCESS CONTROL IN A SINGLE,

Transcription:

TOWN OF BRIGHTON Office of the Fire Marshal 2300 Elmwood Avenue Rochester, New York 14618 (585) 784-5220 Office (585) 784-5207 Fax Alarm Systems Using Wireless or Other Transmission Technology as a Single Path of Communication The NYS Division of Code Enforcement Technical Bulletin permits the reference of Annex A.3.3.141 of NFPA 72-2010 Edition, pertaining to acceptable fire alarm signal transmission paths. Additionally the signal transmission paths must utilize an approved method which is listed and tested in accordance with UL 864 for fire alarm signal transmissions. Purpose To clarify the requirements where the NFPA 72-2007 Edition, Section 8.5.4 currently requires the common DACT, which traditionally utilizes two hard-wired phone lines (POTS lines) for signal transmission; whereas, NFPA 72-2010 Edition permits the use of other technology for communication between alarm panels and References NFPA 72 2010 National Fire Alarm and Signaling Code (not yet adopted) NFPA 72 2007 National Fire Alarm Code 72-6.16.2.7, 72. - 8.6.3.2.1.1, Fire Code of New York State 2010 Sections 907.15, 903.4.1 Description of Code Reference IP monitoring doesn t have its own section heading in the 2007 edition of NFPA 72; instead, it is generically addressed in Section 8.6.4, Other Transmission Technologies. This section stipulates that the AHJ must allow IP monitoring when it is in conformance with this section: 8.6.4.1 Conformance. 1.6 New Technology. 1.6.1 Nothing in this standard shall be intended to restrict new technologies or alternate arrangements, provided the level of safety prescribed by this standard is not lowered. NFPA 72-2007 Edition - Section 8.6.4, Other Transmission Technologies, provides guidance as to the requirements with which IP Communicators must comply. NFPA 72 2007 Edition - 8.6.4 Other Transmission Technologies. 8.6.4.1 Conformance. Other transmission technologies shall include those transmission technologies that operate on principles different from specific transmission technologies covered by this chapter and shall be permitted to be installed if they conform to the requirements of this subsection and to all other applicable requirements of this Code. Other transmission technologies shall include those transmission technologies that operate on principles different from specific transmission technologies covered by this chapter and shall be permitted to be installed if they conform to the requirements of this subsection and to all other applicable requirements of this Code.

Conformance simply entails mounting, wiring and programming the equipment in strict accordance with the manufacturer s printed instructions packed with the equipment. NFPA 72-2010 Edition - Chapter 26 provides further clarification with respect to this emerging technology and more specifically speaks to the reliability of the transmission methods and power supplies. Communication Methods Supervising station systems shall have communication methods that are approved. The 2010 edition of NFPA 72 provides general requirements for transmission methods used by supervising station systems. In general, all transmission methods shall meet the requirements of Sections 26.6.3.1.1 through 26.6.3.1.13, in addition to these requirements digital alarm communicator (DACT) systems and radio systems shall meet the requirements of 26.6.3.2 and 26.6.3.3 respectively. Digital Alarm Communicator Transmitters (DACT) shall continue to be installed according to their listing with an approved phone line and approved secondary means of communication in accordance with NFPA 72-2007 Edition - Section 8.6.3.2.1.4. Other Transmission Channels or alternative means proven to meet the exception given for a dedicated derived channel are acceptable. Besides the common DACT, which traditionally utilizes two hard-wired phone lines for signal transmission, 2010 Edition - NFPA 72 permits the use of other technology for communication between alarm panels and Unless prohibited by the enforcing authority, governing laws, codes, or standards, a single transmission path shall be permitted, and the path shall be supervised at an interval of not more than 60 minutes. A failure of the path shall be annunciated at the supervising station within not more than 60 minutes. The failure to complete a signal transmission shall be annunciated at the protected premises in accordance with 10.12. NFPA 72-2010 Edition - Section 26.6.3.1.5 Single Communications Path. NFPA 72-2010 Edition - Section 26.6.3.2.1.4 Transmission Channels. (A) A system employing a DACT shall employ one telephone line (number). In addition, one of the following transmission means shall be employed: (1) A second telephone line (number) (2) A cellular telephone connection (3) A one-way radio system (4) A one-way private radio alarm system (5) A private microwave radio system (6) A two-way RF multiplex system (7) A transmission means complying with new technologies section

This policy is not an adoption of the 2010 Edition of NFPA 72 in its entirety, any other use of NFPA 72-2010 edition that is an alternative to accepted methods in the 2007 Edition - NFPA 72, other than the monitoring options, shall be subject to an appeal or variance. Besides the common DACT, which traditionally utilizes two hard-wired phone lines for signal transmission, 2010 Edition - NFPA 72 permits the use of other technology for communication between alarm panels and The NFPA does not play the role of certifying specific products for use in NFPA 72-compliant systems. Instead that task has been assigned to Underwriters Laboratories, which conducts tests to confirm that products meet specified performance requirements and that the products include instructions that clearly specify requirements for installation in a manner compliant with NFPA 72. Like the NFPA, Underwriters Laboratories also updates its requirements from time to time. When a particular UL standard is updated, a date is established for when the new requirements will go into effect. Products manufactured after that date must conform to the requirements of the new version. (Although AHJs have flexibility in determining when and if they want to implement new versions of the NFPA 72 code, manufacturers do not have the same flexibility in meeting UL requirements. After a certain date, all products manufactured must meet the requirements for the latest version of the standard). The ANSI/UL 864 standard covers control units and accessories for fire alarm systems. ANSI/UL 864, 9 th edition is the version of the standard that fire alarm control panels and communicators manufactured today must obtain for use in systems requiring compliance with NFPA 72, regardless of which version of NFPA 72 an AHJ is using. Reliability of the communications link One important goal of NFPA 72 is to help ensure the integrity of the communications link between the fire alarm system installed at the customer premises and the central monitoring station. Older versions of NFPA 72 require a customer to have two dedicated phone lines for commercial fire alarm systems. The idea behind this approach is that if one phone line should fail, the other likely would still be functional. But redundant phone lines are costly, requiring commercial accounts to pay as much as $700 to $1200 per year in phone charges for every one of their locations. In addition, redundant phone lines can and sometimes do fail simultaneously. Fire systems that rely on redundant phone lines for communication are required to send test messages to the central station once every 24 hours to confirm that the system is capable of transmitting an alarm. If the central station does not receive a signal from the system at the expected time, the business is alerted so that the problem can be addressed. The downside of this approach, however, is that if a problem were to occur shortly after a test message, it would not be detected for nearly 24 hours. Over the last 10 to 20 years, alternative communications technologies using wired or wireless digital data communications have been developed and increasingly these technologies are being used in security and fire alarm systems. The availability of these alternative communications methods for fire systems caused the NFPA to rethink its requirements for commercial fire systems. One option that the NFPA has allowed in the most recent versions of the NFPA 72 code is to use a combination of two technologies, such as a cellular network and a networked data connection as long as both connections are verified once every 24 hours.

In addition, the most recent versions of NFPA 72 allows a single communications link to the central station to be used if the integrity of the entire communications path is verified more frequently once every five minutes instead of once every 24 hours. The relevant section of the 2007 code is 8.6.4.4. The relevant section of the NFPA 72 2010 code is 26.6.3.1.4.1. When technicians install the system, they establish a connection with the central monitoring station by programming the IP address of the central station receiver and obtaining an account number from the central station, which is also programmed into the system. As part of the programming process, the system prompts technicians to enter the number of minutes for check-in and fail time. Both settings should be programmed for five minutes. When the initial communication from the system is sent to the central station, the central station receiver records the check-in and fail times for the account number. Those settings trigger the receiver to automatically look for a check-in from the system every five minutes and if the receiver does not receive an check-in message from the communicator, an alert signal is sent to the commercial account through the central station personnel. The net result is a higher level of system reliability in comparison with traditional systems that rely on redundant phone and the substantially less frequent 24-hour supervision reports associated with that approach. Today s cellular networks support voice and data communications using digital technology and do not rely on a wired connection to the customer premises that can be damaged or sabotaged. Cellular networks operated by wireless service providers are designed and built to high reliability standards, with proactive monitoring and redundancy provided by the wireless carrier. Because the cellular connection to the customer premises is fixed, unlike with mobile cellular network connections, no hand-offs are involved, minimizing the occurrence of dropped connections. And because the size of the data messages sent between the cellular communicator and the central station require relatively low bandwidth, the likelihood of communications not going through because of congestion also is minimized. Ruling Understanding that the traditional POTS lines are being phased out in favor of other transmission technologies, increased reliability of the internet and the inherent multiple pathways to the Central Station Monitoring Center, the Office of the Fire Marshal will permit the use of a IP Communication method under the following conditions. 1. The secondary power supply for all equipment necessary for the transmission and reception of signals to the central station (internet gateway, router, etc.) shall meet the same battery backup requirements as the fire alarm system, either 24 hours or 60 hours. 2. If the central station will be employing new technology or equipment beyond the scope of its current certificate, provide a new UL certificate showing that it is listed for the new technology. 3. The IP communication device shall have the capability to transmit all signals in full addressability. (i.e Point ID / Contact ID Format) 4. All IP communication devices shall be UL 864 OT listed.

5. All other requirement of the 2010 Fire Code of New York State, 2007 Edition of NFPA 72 and Town of Brighton - Office of the Fire Marshal requirements shall be met. Systems listed for other than phone line transmission shall be installed and tested in accordance with all requirements of the listing and NFPA 72 National Fire Alarm and Signaling Code, 2010 Edition and their current listing.