Hilton Bayfront Guestroom HVAC Energy Management System Evaluation



Similar documents
Energy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat

Hotel System Management The Hotel Smartest Solution

Example Retrocommissioning Measure: Opening Throttled Discharge Valves


Best Practices in HVAC Design/Retrofit

Building Energy Analysis Report

AircoSaver Energy Savings for At&t Mobility San Diego

CODES AND STANDARDS ENHANCEMENT INITIATIVE (CASE)

Guest Room HVAC Occupancy-Based Control Technology Demonstration

T5000 T000 LCD Digital Fan Coil Thermostat

HEATING, VENTILATION & AIR CONDITIONING

The THERMOSTAT THE EVOLUTION OF CAPABILITIES INTO A PLATFORM FOR ENERGY MANAGEMENT

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Controls for fan coil units and cassettes

Applying Schedules and Profiles in HAP

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Smart Ideas for Your Business. Energy Saving Opportunities for Hospitals

Case Studies: Infrared Heating in Industrial Applications

What s the Difference? 2 Pipe vs 4 Pipe Fan Coil

RELAX IT DOES THE REST GUEST ROOM CONTROL SYSTEM FOR HOSPITALITY BUILDINGS GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014

EP A1 (19) (11) EP A1 (12) EUROPEAN PATENT APPLICATION. (43) Date of publication: Bulletin 2012/21

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Energy Efficiency HOSPITALITY.

Tips on Saving Energy in Your Business

Aurora UPC ZS Zone Sensors User Guide

Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

EnergyPro Building Energy Analysis. Assisted Living Building

Room thermostats wide variety and high energy efficiency

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

Modular Room Control (MRC) Series Digital Thermostat

Operation Guide 3M-22

Commercial/Office Space

Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Inwall Room Temperature Unit

HVAC Systems in Schools & Commercial Buildings and Radon

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering

2006 Delta T Corporation dba Big Ass Fan Company

Catalyst RTU Controller Study Report

With colder weather approaching and heating costs continuing to skyrocket, ASHRAE is offering some simple ways to save energy and keep you and your

Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013

Retail & Commercial Solutions. Siemens EcoView. Energy Management Made Easier.

ABB i-bus KNX. Room Solutions. ABB STOTZ-KONTAKT GmbH - 2CDC N0202, page 1

Trinchero Family Estates Building: Operation User s Guide

CONTROL STRATEGIES FOR HVAC SYSTEMS

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

By Tom Brooke PE, CEM

HVAC and Lighting Control Products for Open Building Automation Systems

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Energy Efficiency. Bars & RestauRants.

Impact of Control System Technologies on Industrial Energy Savings

ENERGY AUDITS AND RETRO- COMMISSIONING Local Law 87

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Heating, Ventilation & Air Conditioning Equipment

Data Center Energy Profiler Questions Checklist

Early Retirement Using Preponderance of Evidence

Starting Current Reduction of Residential HVAC System and Peak-Load Impact of Power System: A Case Study

Workshop 7 PC Software - Tracker

Central Monitoring and Control Software for GRMS & Access Control

Smart Thermostat page 1

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

HOTEL INFORMATION SYSTEMS. Chapter 6

Lighting Management solutions

Commercial Refrigeration Temperature and Defrost Controls

T7560A,B,C Digital Wall Module

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

Heating, Ventilation & Air Conditioning Equipment

Using Time-of-Day Scheduling To Save Energy

Data Centre Testing and Commissioning

KNX for building and room automation simple and efficient

Variable Air Volume - VAV

HVAC Processes. Lecture 7

Center for Energy Education Laboratory

Building Technologies

Cx for Enhanced Healthcare Project Delivery. Presentation Format. Project features and timeline

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers

Continuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013

R001. Room Control Unit TG650. Summary. Control functions. Orders. Planning. Installation

Small Business Energy Efficiency and Specialty Equipment

Florida Energy Efficiency Code For Building Construction

Creating Credible, Actionable Energy Audits

New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

General Information. Do programmable thermostats really save energy?

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331)

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

Transcription:

Hilton Bayfront Guestroom HVAC Energy Presented to: Presented by: September 14, 2012

1) Contacts Hilton San Diego Bayfront Hotel 1 Park Boulevard San Diego, CA 92101 Tibor Tip Jozsa Director Property Operations t. 619.564.3333 tibor.jozsa@hilton.com Sunstone Hotel Investors, Inc. 120 Vantis, Suite 350 Aliso Viejo, CA 92656-2686 Marc Hoffman, Chief Operating Officer t: 949.382.3030 mhoffman@sunstonehotels.com Scott Broder, Analyst, Asset Management t. 949.382.3044 sbroder@sunstonehotels.com Willdan Energy Solutions 3750 Convoy St, Suite 175 San Diego, CA 92111 Chikezie Nzewi, P.E., CEM, CBCP, LEED AP Sr. Mechanical Engineer t. 925.556.2600 x1719 c. 925.785.5119 cnzewi@willdan.com Gwen Strickland Senior Program Manager t: 858. 292.1840 ext 1880 c: 31.386.4703 gstrickland@willdan.com Joe Huff Project Engineer t: 858.292.1840 ext 1885 c: 858.880.5045 jhuff@willdan.com 1

2) Summary of Analysis Performed Willdan Energy Solutions performed a detailed study to compare the energy savings from implementing occupancy-based thermostats to control the fancoil units (FCU) providing space conditioning at the guestrooms. The guestrooms are currently served by a floor-mounted fancoil unit recessed within a wall in the guestroom near the building exterior and window. See Picture 1. Each FCU has a three (3) speed fan and chilled water coils for cooling and hot water coils for heating. The existing wall thermostat controls the fan speed whether the fancoil is operating in cooling or heating mode. See Picture 2. Picture 1: Floor-mounted fancoil unit Picture 2: Existing thermostat In this study, the following thermostat control options and technologies were tested: Existing room thermostat (Inncom model E528) Telkonet room thermostat with ceiling mounted occupancy sensor Inncom occupancy based room thermostat with auxiliary door switch Pictures of the tested technologies are shown below. Picture 3: Telkonet Thermostat Picture 4: Telkonet ceiling mounted occupancy sensor 2

Picture 5: Inncom Thermostat Picture 6: Inncom door switch For each of the three options above, three guest rooms on identical orientations/exposures of the building were studied. The Hotel ensured that the tested rooms given priority for occupancy. The performance of the fancoil serving these guestrooms was tracked over a period of two (2) weeks. The following parameters were tracked: Fancoil fan energy use Chilled water cooling energy use Hot water heating energy use Independent monitoring devices were installed at each guestroom fancoil unit to measure fan power at low speed, medium speed and high speed. Cooling chilled water supply and return temperature from each FCU was measured and recorded. Heating hot water supply and return temperatures for each FCU were also measured. To achieve this, a number of sensors with attached data loggers were installed in each FCU cabinet. See Picture 7 & 8. Picture 7: FCU Fan Power Logger and Sensors Picture 8: FCU Chilled & Hot Water Temp Logger and Sensors 3

The following data was monitored with the given intervals: Chilled water supply temperature every minute Chilled water return temperature every minute Hot water supply temperature every minute Hot water return temperature every minute Fan low speed current and voltage, every 30 seconds Fan medium speed current and voltage, every 30 seconds Fan high speed current and voltage, every 30 seconds From this data, the energy use for cooling, heating and fan operation was calculated; results are summarized in the next section. 3) Hotel Occupancy During Test To obtain actionable test data, Willdan instructed the Hotel reservation personnel to ensure that the none (9) rooms selected for this test were always rented and continuously occupied. This ensured that none of the rooms remained unrented and unoccupied and therefore would show significantly greater savings that the rented and occupied rooms. Keeping all the rooms rented during the period of the test ensured that the comparison utilized similar conditions across the various technologies. During typical hotel operation, a percentage of the guestrooms are unoccupied and the energy savings that can be realized from having active occupancy based temperature controls in these rooms will be significant. 4) Utility Incentive Calculations It is critical to note that the current incentive calculations for San Diego Gas and Electric are based on an established White Paper that quantified typical energy savings for occupancy based temperature controls in hotel guestrooms. The energy use of the typical guestroom with no occupancy based thermostat controls will be similar to the energy usage numbers below as in this scenario, the HVAC system remains activated and maintaining an occupied space temperature setpoint. However, the energy use of the guestrooms with occupancy based thermostats installed will be significantly lower, resulting in savings values that will be greater than shown in this study. 4

5) Test Results Data from the two-week test was normalized to report energy savings for a one year period. It is important to note that the Hotel gave significant priority to selling the nine test rooms, thus realized energy and cost savings will be greater based on typical occupancy of 78% (as reported by Sunstone). Control Telkonet Inncom Annual Fan Energy Use Per Room (kwh) 930 548 484 Annual Fan Energy Use All Rooms (kwh) 1,106,998 652,122 575,744 Annual Fan Energy Savings (kwh) N/A 454,875 531,254 Annual Fan Energy Savings (%) N/A 41.1% 48.0% Annual Cooling Energy Use Per Room (kwh) 1,163 913 898 Annual Cooling Energy Use All Rooms (kwh) 1,384,483 1,085,993 1,068,643 Annual Cooling Energy Savings (kwh) N/A 298,490 315,840 Annual Cooling Energy Savings (%) N/A 21.6% 22.8% Annual Heating Energy Use Per Room (Therms) 37 21 32 Annual Heating Energy Use All Rooms (Therms) 44,613 25,010 38,077 Annual Heating Energy Savings (Therms) N/A 19,603 6,535 Annual Heating Energy Savings (%) N/A 43.9% 14.6% Total Electric Energy Savings (kwh) N/A 753,365 891,584 Total Electric Energy Savings Per Room (kwh) N/A 633 749 Total Natural Gas Savings (Therms) N/A 19,603 6,535 Total Natural Gas Savings Per Room (Therms) N/A 16.5 5.5 N/A Total Electric Savings Cost ($) N/A $113,381 $134,183 Total Natural Gas Savings Cost ($) N/A $16,809 $5,604 Total Energy Cost Savings ($) N/A $130,191 $139,787 N/A 31.5% 33.8% 1,190 Total Guest Rooms $0.1505 Electricity Virtual Rate $0.8575 Natural Gas Virtual Rate The energy savings from installing each technology have been quantified for both electricity and natural gas, and are tabulated in the table above. The study shows that the technology can deliver an annual energy cost savings of over 31% for Telkonet and 33% for the Inncom system. 5

6) Product Comparison SYSTEM PROPOSED & TESTED EcoAir SS6550, EcoView Ceiling Sensor, Zigbee Network Wireless E529 X07 HVAC Control, Door Sensor, CI Network EQUIPMENT PHOTOS EQUIPMENT COMPARISON Customizable Display YES YES Night Occupancy Mode YES YES Built-in Occupancy Sensor YES YES Demand-Response Ready YES YES Electronic Door Lock Networking Capable NO YES Minibar Networking Capable NO YES QUANTITY (Per Proposal) 1200 Property has 1,190 guestrooms 1211 GROSS PROPOSED COST $497,444 w/ceiling mounted sensor $540,372 w/door sensor GROSS COST PER ROOM $415 $446 COST REDUCTIONS Estimated SDG&E Incentive 1 ($162,233) ($162,233) Buyback of Existing Thermostats $0 ($72,660) Additional Credit for Returned Thermostats $0 ($17,000) NET INSTALLED COST $335,212 $288,479 NET INSTALLED COST PER ROOM $279 $238 Test Rooms 748 / 750 / 752 850 / 852 / 854 Control Rooms: 746 / 754 / 844 [1] Incentive is estimated and subject to chage pending review and approval from the CPUC (California Public Utilities Commission) 6