R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power



Similar documents
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

PANASONIC TROUBLE SHOOTING GUIDE

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Failure code manual. content

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

10.1 Indoor Unit Error Display

Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

, User s Manual

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

14. Troubleshooting Guide

MP-4000 Alarm List (Software version or later)

Haier Air conditioner

Split and Multi Split air conditioners Service information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O

A/C-HEATER SYSTEM - AUTOMATIC

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7

Air conditioning, electrical testing

Instruction manual for Firstline FCS12000CH

Technical service manual

york air-conditioning products Residential & VRF News 2015

SERVICE MANUAL REFRIGERATION

HEAT SIPHON ANSWERBOOK

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Technical service manual 2009

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved


4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No

Technical data. Danfoss DHP-A

SYSTEM 45. C R H Electronics Design

Pioneer in sustainability

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

ECOCIAT. Domestic hot water heat recovery unit

Contents. Part 1 General Information Part 2 Outdoor Units Part 3 Installation Part 4 Troubleshooting 73

*.ppt 11/2/ :48 PM 1

Operating Instructions Air Conditioner

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

DTC B1423/23 Pressure Sensor Circuit

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

How To Power A Car With A Fan And A Fan (Power)

Table of Contents. 1 - Specifications Installation Wiring User controls...7

HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS

INSTALLATION AND OPERATION MANUAL

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

Operating Instructions Air Conditioner

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

AIR CONDITIONING & HEAT PUMP SYSTEMS

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

USER S MANUAL HSC-24A

Pro Logic Version Diagnostics Manual

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

MAKING MODERN LIVING POSSIBLE. Wiring Diagram DHP-R.

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE

Air Source Heat Pump Installation and Maintenance Manual

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

Q1-750 Q Q Q Q2-200 Q4-90 Q4-120 HIGH PERFORMANCE AMPLIFIER

1116, Suenaga, Takatsu-ku, Kawasaki , Japan

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

WALL MOUNTED SPLIT TYPE AIR CONDITIONER

Nordic Heat Pump Product Guide

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

User Manual for CH-PFC76810

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331)

Fault Code Check List

February 1, Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure

Electronically Controlled Clutchless or Variable Drive Compressors

Technical Information

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

SiBE D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump

FTQ. Daikin Inverter Ducted Heat Pump


Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Tankless Gas Water Heaters Second Generation Indoor, Outdoor and Direct Vent Up to 199,000 BTU

Air Conditioning System

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

AIR CONDITIONING SYSTEM (FOR AUTOMATIC AIR CONDITIONING SYSTEM)

CARING FOR YOUR WATER HEATER

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

SERVICE & MAINTENANCE MANUAL

HVAC. (w) HVAC SYSTEM. Blower unit. (See BLOWER UNIT REMOVAL/INSTALLATION.) (See BLOWER UNIT DISASSEMBLY/ASSEMBLY.) Air filter

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Operating Instructions Split System Air Conditioner

Split Air Conditioner

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Split System Air Conditioners SkyAir Inverter

Troubleshooting Your Refrigerator

Transcription:

R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters

R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor Unit Heat Pump Horse Power Phase. (V=Single Y=Three) Control

Compatibility notes. There are three kinds of control. These are as follows. G (eg: PLH 3 AGH) K (eg: PLH 3 KKHB) A (eg: PLA P 3 KAH) These are not compatible with each other.

Compatibility notes. There are numerous styles of unit. These are as follows PC Under Ceiling PE Ducted PK Wall Mounted PL Four Way BlowCassette PM Corner (One Way Blow) Cassette PS Floor Standing Console

Compatibility notes. Horsepower indicates the duty of the unit. This is a basic guideline 1.6 HP = 4.5Kw 2 HP = 5.5Kw 2.5HP = 6.3Kw 3HP = 7.7Kw 4HP = 9.5Kw 5HP = 12.4Kw 6HP = 14.5Kw 8HP = 22.2Kw 10HP = 27.3Kw

K Control Fault Code Diagnostics / Flow Charts Abnormality of Return Air Sensor - Short or Open Circuit Run system in Test Run. This will bypass all thermistors Check thermistor is positioned correctly. NO Replace in holder Remove thermistor from PCB and check resistance. 6.4k at 20 C (Room Temp). NO Replace thermistor YES Replace Indoor PCB. P1 Fault Code Diagnostics

K Control Fault Code Diagnostics / Flow Charts Abnormality of Indoor Coil Sensor - Short or Open Circuit Run system in Test Run. This will bypass all thermistors Check thermistor is positioned correctly. NO Replace in holder Remove thermistor from PCB and check resistance. 6.4k at 20 C (Room Temp). NO Replace thermistor YES Replace Indoor PCB. P2 Fault Code Diagnostics

Component Part Testing Room temperature thermistor (RT1) Pipe temperature thermistor (RT2) Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10 30 C) (Refer to the thermistor graph) Normal 4.3kohm~9.6kohm Abnormal Open or short P1 and P2 Fault Code Diagnostics - Thermistors

K Control Fault Code Diagnostics / Flow Charts Signal Transmission Error Check transmission wire to remote controller. Check for continuity, cable length and type (2 core, min 0.69mm) Check for potential interference from other equipment such as lighting, batteries, UPS and wireless communications. OK Potential Problem Replace standard 2 core with shielded cable Check with another remote controller P3 Fault Code Diagnostics P3 still shows P3 goes Replace PCB Replace controller

K Control Fault Code Diagnostics / Flow Charts Abnormality of Drain Sensor - Short or Open Circuit Run system in Test Run. This will bypass all thermistors Check thermistor is positioned correctly. NO Replace in holder Remove thermistor from PCB and check resistance. 6.4k at 20 C (Room Temp). NO Replace thermistor YES Replace Indoor PCB. P4 Fault Code Diagnostics

Component Part Testing Drain sensor Measure the resistance between the terminals using a tester. Measure the resistance after 3 minutes have passed since the power supply was intercepted. (Surrounding temperature 0 C 60 C) Normal 0.6-6.0 kohms (Refer to the thermistor graph) Abnormal Open or short P4 Fault Code Diagnostics - Drain Sensor

K Control Fault Code Diagnostics / Flow Charts Malfunction of Drain Sensor and / or Drain Pump Check drain fall / rise. Rise must not exceed 500mm. Check that inspection cover is in place. Cold airflow across the drain will cause the unit to fault. Measure resistance of drain sensor heater. Remove from PCB and test for 82. NO Replace Drain Sensor / Heater Is there 240 volts at PCB on Drain Pump connector CNP YES NO Replace Drain Sensor / Heater Replace Indoor PCB. P5 Fault Code Diagnostics

K Control. Drain Pump Operation. Drain pump control The drain pump works in COOL or DRY operation. When operation stops or changes to HEAT mode, the drain pump continues to operate for 3 more minutes. The drain pump does not work in check mode. <Drain sensor> When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due to a drain pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code P5 on the remote controller will display this occurrence. P5 Fault Code Diagnostics - Drain Pump

K Control. Service Notes. P5 500mm Max Lift 150mm Max P5 Fault Code Diagnostics - Drain Pump

Component Part Testing Drain pump Measure the resistance between the terminals using a tester. (Surrounding temperature 20 C) Normal 290 ohms Abnormal Open or short P5 Fault Code Diagnostics - Drain Pump

K Control Fault Code Diagnostics / Flow Charts Coil Frost Prevention / Short Cycling Remove thermistor from PCB and check resistance. 6.4k at 20 C (Room Temp). NO Replace Thermistor Check for dryer or sight glass Check for Short Cycling of air around evaporator Check for Dirty Filter, obstructions at Outdoor Unit or damaged fan motor YES YES Remove component as is expansion line and may be the cause of previous overcharging Correct Air Flow If NO to any of these then the system is likely to have an incorrect refrigerant charge. P6 Fault Code Diagnostics

K Control. Coil Frost Prevention. Coil frost prevention To prevent indoor coil frost, the compressor will stop when the pipe thermistor (RT2) reads 1 C or below after the compressor has been continuously operated for at least 16 minutes or more. When the pipe temperature rises to 10 C or above, the compressor will start in a 3- minute(w2) time delay. When the pipe temperature is -1 C or less, the compressor starts in 6 minutes. NOTE : By turning OFF the dip switch SW1-3 on indoor controller board, the start temperature of coil frost prevention changes from 1 C to -3 C. P6 Fault Code Diagnostics

K Control Fault Code Diagnostics / Flow Charts System Addressing Error Error on dipswitch setting of Indoor Unit or Remote Controller. Check SW2 and SW6 setting. SW2 - Group Control. SW6 - Twin/Triple Split NO Check SW17 1-6 on RC. These should be OFF unless controlled from third party. NO Malfunction of the transmitting receiving circuit. The Remote Controller power supply is faulty Check for 12 volts DC at terminals of Remote Controller. Try with different controller! Replace Indoor Controller Board P7 Fault Code Diagnostics

K Control. Dip Switch Configuration (CN40 Plug). CN40 The CN40 plug is found on the Indoor Control Board of a P series split system. Its use is to provide power to the Remote Controller. If the plug is removed, the Remote Controller will not receive a signal from the Indoor Unit. This plug is often removed in Group Control and Multi- Split operation. P7 Fault Code Diagnostics

K Control. Dip Switch Configuration Indoor Unit - SW2 ON OFF ON OFF ON OFF CN40 1 2 3 4 CN40 1 2 3 4 CN40 1 2 3 4 Master Unit Unit 1 Unit 2 P7 Fault Code Diagnostics - Group Control Individual Condensers

K Control. Dip Switch Configuration Indoor Unit - SW6 ON ON OFF OFF CN40 1 2 3 4 1 2 3 4 CN40 Master Unit Slave Unit P7 Fault Code Diagnostics - Twin Split System One Condenser

K Control. Dip Switch Configuration Indoor Unit - SW6 ON OFF ON OFF ON OFF 1 2 3 4 1 2 3 4 1 2 3 4 CN40 CN40 CN40 Master Unit Slave 1 Slave 2 P7 Fault Code Diagnostics - Triple Split System One Condenser

K Control. Dip Switch Configuration ON ON OFF OFF CN40 1 2 3 4 1 2 3 4 CN40 1 2 3 4 1 2 3 4 ON OFF SW2 System One, Master SW6 ON OFF SW2 System One, Slave SW6 CN40 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 CN40 SW2 System Two, Master SW6 SW2 System Two, Slave SW6 P7 Fault Code Diagnostics - Group Control and Twin Split Configuration

K Control. Detecting abnormalities in the Outdoor Unit. Detecting abnormalities in the outdoor unit After the compressor has been continuously operated for 3 minutes, if the difference between the pipe temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code P8 appears on remote controller. RANGE A : Pipe temperature is more than 5 degrees above the room temperature. RANGE B : Pipe temperature is within 5 degrees either way of the room temperature. RANGE C : Pipe temperature is more than 5 degrees below the room temperature. P8 Fault Code Diagnostics Explanation of system logic

K Control. Detecting abnormalities in the Outdoor Unit. P8 Fault Code Diagnostics Explanation of system logic

K Control Fault Code Diagnostics / Flow Charts P8 Fault Codes Explanation of system logic The Indoor Unit will detect an abnormality in the Outdoor Unit when the difference in temperature between the coil sensor and the return air sensor does not exceed 5 C after a running period of eight minutes. Further interrogation of the Outdoor Unit When The Indoor Unit detects a fault at the Outdoor Unit P8 will flash on the Remote Controller. The Outdoor Unit LED diagnostics need to be interrogated. Blinking LED - Fault Static LED - Output state P8 Fault Code Diagnostics Explanation of system logic

K Control Fault Code Diagnostics / Flow Charts SW1 Erase past check code contents SW2 Display existing / last reported check code contents Fault Code Diagnostics SW1 and SW2 Functions

K Control Fault Code Diagnostics / Flow Charts SW2 SW2 With SW3-1+2 off will alternate between fault and operation status output With SW3-1 off +2 on will initiate compulsory defrost ON OFF SW3 Fault Code Diagnostics SW3 Functions

K Control Fault Code Diagnostics / Flow Charts Reverse Phase Protection Activated Check Phase of power supply Exchange any two of the Red, Yellow and Blue phases Check RST Plugs. Check PCB. Three phase PCB on single phase unit? LED 1 Fault Code Diagnostics

K Control Fault Code Diagnostics / Flow Charts PCB R S T A1 A2 A3 N The RST Plugs check the incoming phase rotation and also check for missing phases. LED 1 Fault Code Diagnostics RST Plugs

K Control Fault Code Diagnostics / Flow Charts Open Phase Detected Check for 415 volts between Red, Yellow and Blue Phases OK Protector may be open circuit when power switched on Check for 240 volts between each Phase and Neutral NO Reconnect missing phase. Check fuses, wiring etc. Check the following for Open Circuit. 63H1 (HP Control) 63H2 (HP Protect) 26C (Thermal Switch) Check RST Plugs. LED 2 Fault Code Diagnostics

K Control Fault Code Diagnostics / Flow Charts Pipe sensor short or open circuit Check for poor contact or disconnected sensor plug. NO Check plug and contact on PCB. (CN2) Measure resistance of pipe thermistor. NO Replace thermistor Replace PCB LED 3 Fault Code Diagnostics

K Control Fault Code Diagnostics / Flow Charts High Pressure Switch Fault Check with HP Gauge. Does this read over 300 psi? NO YES Check to see if 63H2 Plug is connected. This should only be connected if the compressor is a Copeland. Check connection of 63H2 Check for open circuit of 63H2 Replace HP Switch Fan Motor runs fast Check Airflow of Condenser and clean coils if required Link pins on CN22 at Outdoor to run fans at full speed Check resistance of thermistor Replace PCB Fan Motor runs slow Replace Motor LED 4 Fault Code Diagnostics

K Control Fault Code Diagnostics (Thermistor Readings). Actual temp Resistance Actual temp Resistance Actual temp Resistance 1 14.32 16 7.41 31 4.09 2 13.67 17 7.10 32 3.94 3 13.06 18 6.82 33 3.79 4 12.48 19 6.54 34 3.66 5 11.93 20 6.28 35 3.52 6 11.40 21 6.03 36 3.40 7 10.91 22 5.80 37 3.28 8 10.43 23 5.57 38 3.16 9 9.99 24 5.35 39 3.05 10 9.56 25 5.15 40 2.94 11 9.16 26 4.95 41 2.84 12 8.77 27 4.76 42 2.74 13 8.40 28 4.58 43 2.65 14 8.05 29 4.41 44 2.56 15 7.72 30 4.25 45 2.47