M-Bus Network Installation Notes



Similar documents
Documentation. M-Bus 130-mbx

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference :

s!nus-elektrotechnikai bt. Industrial IT & Automation

s!nus-elektrotechnikai bt. Industrial IT & Automation

Electronics. Discrete assembly of an operational amplifier as a transistor circuit. LD Physics Leaflets P

RS485 & RS422 Basics

Meter Communication. Twisted Pair Baseband (M-Bus) Physical and Link Layer CEN TC 294. Date: TC 294 WI 006 CEN TC 294. Secretariat: AFNOR

BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION

Elettronica dei Sistemi Digitali Costantino Giaconia SERIAL I/O COMMON PROTOCOLS

Contents. Document information

Network Design. Yiannos Mylonas

What are the Requirements for an Accurate DSL Line Simulator? Paradyne International, France

Technical Data Sheet. 3DLevelScanner

We hope that every customer sets up CC-Link system easily by reading this documentation.

Installation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable

M-Bus-Logger Data Logger

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

RS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: / 97 / 98 (M)

1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0

Current Loop Application Note 1495

Practical steps for a successful. PROFIBUS Project. Presented by Dr. Xiu Ji Manchester Metropolitan University

HSG Engineering Tech Bulletin

ATS Communication Overview

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

HARTING econ 3000 Introduction and features

ELCOMPONENT LTD. User Manual

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

Technical Description U00980 Revision 2

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

FlexPoint T1/E1 Copper to Fiber Line Driver

ADACSNET USB Control Module

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

KNX. Siemens Building Technologies HVAC Products. Synco Konnex bus. For devices of the Synco 700 / RXB ranges

WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications

PROFIBUS. Design and. Good Practices

Modular I/O System Analog and Digital Interface Modules

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

DSX Master Communications

If you want to get an official version of this User Network Interface Specification, please order it by sending your request to:

Application/Connection Examples

Contents. : AEOS Blue cabling and technical aspects. NEDAP N.V. IDEAS Information Bulletin No: H032. Date : 12 January 2016

Crosstalk effects of shielded twisted pairs

How To Use A Multi-Line Calculator With A Power Supply And Power Supply (Kamstrup)

Customer Interface Publication: KCH CIP002. Public Switched Telephone Network (PSTN)

EDI Distributor Control Interface Wiring and Setup Instructions

Total solder points: 67 Difficulty level: beginner advanced UNIVERSAL TEMPERATURE SENSOR K8067 ILLUSTRATED ASSEMBLY MANUAL

Installation manual. Version

GPS NTP TIME SERVER Rack Version V2.2x

RS-422 and RS-485 Application Note

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

Dynamic Pressure Charge Amplifier

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3

CANtrol EC Modular Control System Powerful and versatile

1 Which network type is a specifically designed configuration of computers and other devices located within a confined area? A Peer-to-peer network

WEB log. Device connection plans

Bus modules systron PM

SICK AG WHITEPAPER. Information for cable manufacturers Note-2_03

TO-PASS. TO-PASS -FAQ- Remote Monitoring. What is TO-PASS used for? What are the special functions of TO-PASS?

Cabling Specifications

Features. Picture. Specifications

TIMING SIGNALS, IRIG-B AND PULSES

VE02AL / VE05AL / VE02ALR VGA & Stereo Audio CAT5 Extender with Chainable Output

Document Revision History: Network Guide 05DI-UGBACNG-12 Copyright Distech Controls Inc. First printing June Printed in Canada.

DAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite:

Industrial Networks & Databases

Model CFA-24 Transparent Cable Farm Automation Switch

User Manual Revision English

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

How To Fix A Cbus Network From A Power Supply To A Power Source

CB Svendsen A/S PS / rev. 1.5

Lab 1: DC Circuits. Student 1, Partner : Student 2, student2@ufl.edu

Temp-485-Pt100. A temperature sensor (Pt100 or Pt1000) communicating over the RS-485 bus with a simple communication protocol

HARTING mcon 3000 Introduction and features

Termination Resistors:

Tristan s Guide to: Solving Series Circuits. Version: 1.0 Written in Written By: Tristan Miller Tristan@CatherineNorth.com

DSL Calculator. 2. Starting the DSL Calculator

Magnet field- and Radiation Tolerant New Power Supply System MARATON - Technical Overview. 22-Sep-03 1

UCC 1 USB-CAN CONVERTER

Quantec Wiring Instructions

Planning BACnet networks

Using installed Fieldbus Wiring to carry Ethernet Communications

INSTRUCTION MANUAL. SIGNAL AMPLIFIER 4-20 ma

3 Slot Payphone Controller

What is BACnet MS/TP?

EVOline Multimedia Modules

User Manual IC-485AI

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

The multi-functional integrator Supercal 531

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions

Grounding Demystified

Flexible Counter Series in DIN size 24 x 48 mm

Type max. stroke length el. stiffness resonance

Rutenbeck Network Connection Box Cat. 5, shielded. Cable installation. UAE Connection Box Cat. 5 Operating Instructions.

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE

Current Transformer (CT) Selection Guide

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel vc@valcontrols.com

ROLINE THE Difference

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Current Probes. User Manual

Transcription:

M-Bus Network Installation Notes 1 M-Bus Network Installation Notes This manual explains how to calculate the maximum M-Bus cable length depends on technical parameters of used cable and number of M-Bus slave devices. It can be used for calculation if one or more M-Bus-LC-10 or M-Bus-LC-60 master M-Bus level converter is used. On slave side any M-Bus slave device can be used like: energy meters, PLC,..., etc. 1.1 Topology The topology of the M-Bus network is (almost) arbitrary. Only the ring topology as shown beneath should be avoided. In general the length of the cables should be minimized. Usually a mixture between star and bus topology should be used. 1.2 M-Bus Cable The M-Bus uses two wire cables which are going from the M-Bus Master / Repeater to each M-Bus device (bus structure). The M-Bus is polarity independent and needs no line termination resistors at the end of the cables. Page 1/5

Any cable type may be used as long as the cable is suitable for 42 V / 500 ma. Shielding is not necessary and not recommended since the capacity of the cable should be minimized. In most cases a standard telephone cable is used which is a twisted pair wire with a diameter of 0.8 mm each (2 x 0.8 mm). This type of cable should be used for the main wiring. For the wiring to the meters from the main wiring (last 1.. 5 m to the meter) a cable with smaller diameter may be used. 1.3 Maximum Cable Length in M-Bus Networks The question for the maximum possible cable length in M-Bus networks is not easy to answer since several parameters are critical. However, an example calculation is shown here to give an estimation. Cable Type: 2 x 0.8 mm (JYStY N*2*0.8 mm) The limiting parameters in M-Bus networks are mainly the cable resistance and the cable capacity plus the capacity of the devices (= bus capacity). The cable resistance causes, depending on the bus current, a bus voltage drop. The maximum bus voltage drop may not be more than 16 V.. 18 V since the minimum bus voltage at any device must not be lower than 24 V (40 V 24 V = 16 V). R = U / I R: Cable Resistance U: Voltage Drop over Cable Length I: Bus Current N: connected M-Bus Umax = 16 V I = N * R= 16 / (1.5 * N) Ohm The cable resistance, therefore, limits the maximum possible cable length from the M-Bus Master / Repeater to the device with the largest distance away from it (largest cable segment). The table beneath shows an estimation of the maximum cable segment length: Page 2/5

Number M-Bus Resistance Length () 1 10.7 kohm 142 km 10 1.1 kohm 14.7 km 50 213 Ohm 2.8 km 100 106 Ohm 1.4 km 150 71 Ohm 0.95 km 200 53 Ohm 0.71 km 250 43 Ohm 0.57 km The cable segment length is the distance from the M-Bus Master to the M-Bus device furthest away. NOTE: The given maximum cable segment length takes into account only the bus resistance and not the bus capacity. Therefore, some of the cable lengths in the table may not be possible in reality. At the end of the chapter is a table with real example configurations. The cable capacity plus the capacity of the M-Bus devices (= bus capacity) is responsible for sloppy signal edges. Therefore, the bus capacity limits the maximum data transfer rate of the M-Bus. The M-Bus Master is able to drive approx. 1 µf at a baudrate of 300 baud. The table beneath gives an estimation of the bus capacity / baudrate relationship: Baudrate Max. Bus Capacity Example Configuration 300 Baud 1000 nf 1 Device + 20 km Cable (1 * + 20 * 50 nf) 50 + 19 km Cable (50 * + 19 * 50 nf) 250 + 14 km Cable (250 * + 14 * 50 nf) 2400 Baud 300 nf 1 Device + 6 km Cable (1 * + 6 * 50 nf) 50 + 5 km Cable (50 * + 5 * 50 nf) 250 + 1 km Cable (250 * + 1 * 50 nf) 9600 Baud 100 nf 1 Device + 2 km Cable (1 * + 2 * 50 nf) 50 + 1 km Cable (50 * + 1 * 50 nf) The given cable length is the sum over all cables attached to one M-Bus Master / Repeater. NOTE: The mentioned example configurations are taking into account only the bus capacity but not the bus resistance. Therefore, some of the cable lengths in the table may not be possible in reality. At the end of the chapter is a table with real example configurations. The tables beneath are showing some example configurations depending on bus resistance and capacity. In general the following topology is taken: Page 3/5

NOTE: The table values are theoretical maximum values. Usually the M-Bus devices are connected to the cable with varying distances from the M-Bus Master / Repeater. Therefore, larger cable length can be achieved in reality. However, for very large cable length additional parameters must be taken into account (e.g noise) and, therefore, cable length larger than approx. 10 km should not be used without amplification. 300 Baud 1 20 km 142 km 20 km 50 19 km 14.7 km 14.7 km 250 14 km 0.57 km 0.57 km Page 4/5

2400 Baud 1 6 km 142 km 6 km 50 5 km 14.7 km 5 km 250 1 km 0.57 km 0.57 km 9600 Baud 1 2 km 142 km 2 km 50 1 km 14.7 km 1 km Page 5/5