Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions



Similar documents
Research on the Air Conditioning Water Heater System

Final Report by Air Conditioner Evaluation Standard Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Standards & Labeling System for Air-conditioning Equipment in US, Europe and Japan

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

LG Electronics AE Company, Commercial Air Conditioning

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Research on annual energy consumption of packaged air-conditioning units

How to choose a heat pump and use it wisely

1116, Suenaga, Takatsu-ku, Kawasaki , Japan

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

Commercial Gas Heat Pump - VRF

The Development of a Frost-Less Heat Pump

york air-conditioning products Residential & VRF News 2015

Failure code manual. content

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

Creating Efficient HVAC Systems

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Air Conditioner Cooling Capacity Test AS/NZS :1998

ROTEX gas hybrid heat pump. A strong team.

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Waste Heat Recovery through Air Conditioning System

Heating & Cooling Efficiency

ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM

HVAC Efficiency Definitions

Development and testing of a multi-type air conditioner without using AC inverters

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM

EnergyPro Building Energy Analysis. Assisted Living Building

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Lesson 36 Selection Of Air Conditioning Systems

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Federation of European Heating, Ventilation and Air-conditioning Associations

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates

Domestic air-conditioner and integrated water heater for subtropical climate

Absolute and relative humidity Precise and comfort air-conditioning

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Glossary of Heating, Ventilation and Air Conditioning Terms

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump

Testing methods applicable to refrigeration components and systems

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut John F. Sima III P.E.

Poor Performing AC? High Electric Bills? High Humidity?

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

Greenhouse and Energy Minimum Standards (Air Conditioners and Heat Pumps) Determination

Energy Efficient HVAC-system and Building Design

REFRIGERATOR AND AIR-CONDITIONER TESTING IN THE REPUBLIC OF KOREA

Hybrid heat pumps. saving energy and reducing carbon emissions

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

The Benefits Really Add Up

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

FULL DC INVERTER SYSTEMS

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

Emerging End Use Technologies

HVAC Systems: Overview

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

HP switch LP switch Discharge thermo Comp. Surface thermo

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

SECTION MORTUARY REFRIGERATORS

GREE, MAKING BETTER AIR CONDITIONERS

Selection Tips For Air-Conditioning Cooling Systems

BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad

your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction

Air-Conditioning Buying Guide

Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Ductless Heat Pumps. Gary Nordeen January

Natural geothermal energy.

Experimental Evaluation Of The Frost Formation

An Overview of Solar Assisted Air-Conditioning System Application in Small Office Buildings in Malaysia

HVAC Basic Science - System Capacity

HEAT TRANSFER ANALYSIS OF COLD STORAGE

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE

AIR CONDITIONING - ENERGY CONSUMPTION AND ENVIRONMENTAL QUALITY

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Building HVAC Load Profiling Using EnergyPlus

air conditioners how to choose a cooling system

GEOTHERMAL HEATING AND COOLING INTRODUCTION

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps

Get the FACTS about SEER and Deliver Better Customer Value

ENHANCED LABORATORY HVAC SYSTEM

Introduction To VRF: System Overview, Applications, & Savings Opportunities

Heat Pumps for Swimming Pools

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions Yoshiaki Yumoto Tokyo University of Marine Science and Technology Toru Ichikawa Tokyo Gas Co. Tatsuo Nobe Kogakuin University Shigeki Kametani Tokyo University of Marine Science and Technology Follow this and additional works at: http://docs.lib.purdue.edu/iracc Yumoto, Yoshiaki; Ichikawa, Toru; Nobe, Tatsuo; and Kametani, Shigeki, "Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions" (2006). International Refrigeration and Air Conditioning Conference. Paper 757. http://docs.lib.purdue.edu/iracc/757 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R067, Page 1 Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions *Yoshiaki Yumoto 1, Toru Ichikawa 2, Tatsuo Nobe 3, Shigeki Kametani 4 1 Tokyo University of Marine Science and Technology, Graduate school 4-5-7, Konan, Minato, 108-8477 Tokyo, Japan * (81-3-5463-0492, 81-3-5463-0492, m054008@edu.s.kaiyodai.ac.jp) 2 Tokyo Gas Co., Ltd., Department of gas energy 3-7-1, Nishi-Shinjuku, Shinjuku, 163-1059 Tokyo, Japan (81-3-5322-7715, 81-3-5322-7714, toithi@tokyogas.co.jp) 3 Kogakuin University, Department of Architecture, Faculty of Engineering 1-24-2, Nishi-Shinjuku, Shinjuku, 163-8677 Tokyo, Japan (81-3-3340-3438, 81-3-3340-3438, nobe@cc.kogakuin.ac.jp) 4 Tokyo University of Marine Science and Technology, Faculty of Marine Science 4-5-7, Konan, Minato, 108-8477 Tokyo, Japan (81-3-5463-0491, 81-3-5463-0491, kametani@s.kaiyodai.ac.jp) ABSTRACT This paper deals with an actual performance of split air conditioning systems. In recent years, the split air conditioning system is installed in a building more than 100000 square meters in Japan. The performance of these units is evaluated by JIS (Japan Industry Standard) rules, however these tests is done in static condition, and the actual performance is not evaluated. These false estimates produce a different anticipation of future energy consumption or waste heat contamination. Setting various weather conditions, the experiment that assumed the actual operating condition is done. As the experimental results, performance characteristics and thermal characteristics of the system have been estimated, and influences of the weather conditions and thermal load have also been investigated. 1. INTRODUCTION The market share of a split air conditioning system has been growing rapidly, because of high cost performance and easy installation, and it goes to be replaced by central air conditioning systems. JIS rules on the performance of split air conditioning systems, an air-enthalpy method using a room type calorimeter is used widely in order to evaluate it. But, in this air-enthalpy method, a performance test is done in static condition and it is so difficult that it indicates an actual operating condition. Also, on the rating test, for a test conditions, only temperature and humidity are defined by JIS rules and not required to operation conditions of test unit. The actual performance receives a large influence by environmental factors such as temperature, humidity, SHF and thermal load etc. Therefore, the ratings performance was completely different from actual performance. The clarification of actual performance is so useful for the design of conventional air conditioning facilities. In this paper, fluctuating condition tests and starting performance tests are done to clarify actual performance that assumed actual operating conditions.

R067, Page 2 2. EXPERIMENTAL EQUIPMENTS AND METHODS The two different experiments are done in this paper. One is a measurement of total energy consumption under the fluctuating conditions. And another one is for starting performance. The thermal load assumed the actual weather condition is supplied to a room type calorimeter chamber and the temperature and humidity of outside (condenser side) and inside (evaporator side) room is controlled. 2.1 Experimental Apparatus In this experiment, the room type calorimeter chamber which own Kogakuin University is used. This chamber has been used for evaluation of building environment and designed for architecture environment system, and it has a pair of chambers for comparative experiments. We installed an outdoor unit (condenser in cooling cycle) and an indoor unit (evaporator in cooling cycle) in each chamber. The floor plan of experimental unit is shown in figure 1 and the specification of a calorimeter chamber is shown in Table 1. Thermal load of chambers is controlled by supply air conditions (e.g., temperature, humidity and air volume). The air conditioning system of this chamber has cooling and heating coil, steam generator and VAV (Variable Air Volume) system as shown fig. 2. As this chamber is not able to set a freezing condition, a refrigerating machine is attached to compensate it. The test unit is general marketing air conditioning system which is inverter controlled and split type. The specification of a test unit is shown in Table 2. Figure 3 shows a deification of supplied thermal load to a test chamber. The generated available heat of test units is defined as supplied thermal load to chamber for measurement term. Table 1: Specification of a calorimeter chamber Designation Specifications Refrigerator Air cooling chiller (45kW) Heater Electric heater (40kW) Cool bath FRP sandwich panel (3m 3 ) Heat bath Monocoque steel (2m 3 ) Outdoor air conditioning unit Air volume (1000m 3 /h) Air conditioning system for chambers Air volume (1000m 3 /h) Package air conditioner for thermal buffer zone Multi type, 8 indoor units (5Hp) Controllable temp. -5 to 50 ( C) Controllable humidity value 10 to 100 (%) Chamber size 5.9 (L) 4.1 (W) 5.5 (H) Wall heat transfer coefficient Under 0.2W/m 2 K Thermal insulation Polystyrene foam (200mm) Table 2: Specification of a test unit Electric Source Refrigerant Cooling capacity Heating capacity Rated COP Indoor unit Designation Specifications 3Φ 200V R - 410A 3.60 kw 0 kw Cooling 4.13 Heating 4.26 Ceiling suspended type

R067, Page 3 N 10780 2380 5860 2540 ThermalBuffer Zone Outdoor Un it In doo r U n it Outdoor S ide Indoo r S ide Balcony VAV Un its Supp ly A ir Return A ir The Chamber Room AirHandringUnit Heating Coil Hum idifier Cooling Coil 1500 4070 2260 4070 1500 13400 (m m ) Fig. 1: Floor plan of calorimeter chamber Fig. 2: Piping diagram of heat source 8 Measurement term (kw) 7 6 5 4 3 2 1 Start a test unit Supplied thermal load to chamber = Generated available heat of units Base energy level of chamber 0 0:00 0:30 1:00 1:30 2:00 2:30 Time Fig. 3: Definition of supplied thermal load 2.2 Experimental Method (1) Fluctuating Condition Test In a calorimeter chambers, it is difficult to reproduce an actual thermal load pattern exactly. So, we arranged simply thermal load pattern using CASCADE3 (Computer Aided Simulation for Cogeneration Assessment & design) which is typical office building load pattern in Japan. The simulated operating term is 8:00 to 19:00. The thermal load and weather data assumed actual condition by CASCADE3 are shown in Fig. 4(winter) and Fig. 5(summer).

R067, Page 4 Fig. 6 shows the supplied heating load and whether setting and also, Fig. 7 shows the supplied cooling load and whether setting. The experimental condition has 4 term patterns. The outside weather conditions are used the AMeDAS (Automated Meteorological Data Acquisition System) data in Otemachi, Tokyo. As for the temperature and humidity, calculated mean value in July and January are used. The recommended setting temperature of air conditioning system is 20 C (Heating) and 28 C (Cooling) in Japan. But, according to our research, indoor setting temperatures is higher in winter and lower in summer than it, and set the experimental conditions as shown in table 4 and table 5. Fig. 4: Weather condition and thermal Load (Winter, January) Fig. 5: Weather condition and thermal Load (Summer, July) Fig. 6: Supplied heating load and whether setting Fig. 7: Supplied cooling load and whether setting Table 4: Test setting condition (winter) Table 5: Test setting condition (summer) Indoor Side Outdoor Side Indoor Side Outdoor Side DB ( C) RH (%) Load (kw) DB ( C) RH (%) DB ( C) RH (%) Load (kw) DB ( C) RH (%) 2 2 3.4 5.3 42.8 2.3 29.0 59.2 2.3 8.1 34.5 3.2 31.4 50.6 5 2.1 9.1 32.9 3.4 31.1 51.7 1.2 7.8 39.2 2.8 29.5 57.8 (2) Starting Performance test The starting performance test is done under the conditions which are given in Table 6. The test unit is operated in original control logic till the conditions of chamber reaches the targeted value. On the summer term in Japan, a short circuit phenomenon by waste heat from condenser occurs, because of the outdoor units are equipped in small area on the top of the building. Then, the efficiency of a heat exchanger on

R067, Page 5 condenser deteriorates remarkably. Therefore, we set the high temperature condition assumed its phenomenon. On the middle season between summer and winter, the cooling demands are higher than the heating one. The outside temperature is set to 20 C as a representative of this term. On the winter term, parameters in the table are typical values in Japan. Table 6: Test conditions for performance test including start period Indoor side DB ( C) RH (%) *T.L.F (%) Outdoor side DB ( C) RH (%) Summer 4 2 5 Middle 2 4 100,50 5 Winter 2 4 2 *T.L.F: Factor 3. EXPERIMENTAL RESULTS 3.1 Fluctuating Condition Tests The experiment results of a fluctuating condition test are shown in Fig. 8 and Fig. 9. At the winter condition test, the test units frequently repeat start and stop following a defrosting, and indoor temperature changed less than 3 degrees Celsius. Also, because the control of attached refrigerating machine is not good, the outside temperature is changed remarkably. At a summer condition tests, as a thermal heat load is high, a compressor is running continually. For this reason, the test result is comparatively good. (Thermal load: kw) Power Consumption Inside Temp Outside Temp 3 (: kw) 4 3 2 1 2 1 1 Power Consumption Inside Temp. Outside Temp. 00:00 00:30 01:00 01:30 02:00 02:30 03:00 03:30 04:00 04:30 Fig. 8: Performance on winter condition test 00:00 00:30 01:00 01:30 02:00 02:30 03:00 03:30 04:00 04:30 05:00 05:30 Fig. 9: Performance on summer condition test

R067, Page 6 Table 7: Results of fluctuating condition test Total power consumption (kwh) Supplied thermal load (kwh) Measured COP COP Ratio (%) Summer 4.28 13.16 7 74.45 Winter 4.43 8.29 1.87 43.93 Table 7 shows results of fluctuating condition test. By the test that assumed a summer week day in an office building, the average of measured COP is 7. This value is equivalent to about 75% of a rated COP (catalogue) value. In the same way, the test results that assumed winter week day is 1.87 and this one is equivalent to about 44% of a rated COP. In this way, a result of the winter season is particularly different from its rated COP value. 3.2 Starting Performance test The total energy efficiency including starting period is measured. Fig.10 to Fig. 15 shows each starting performance results with 100% and 50% thermal load in the winter, middle and summer season. On the winter condition with 50% thermal load, as the test units frequently repeat start and stop following a defrosting, the energy consumption efficiency is getting lower. Test unit has this operation mode for refrigerant circuit and hardware protection. At the summer condition, power consumption is twice as high by comparison rated power consumption. Indoorside Temp. (: kw) 3 2 1 1 (: kw) Power Comsumption Outside Temp. (Temp : ) 3 2 1 1 Indoor Temp. Energy consumption Outdoor Temp. 00:00 00:10 00:20 00:30 00:40 00:50 01:00 01:10 00:00 00:10 00:20 00:30 00:40 00:50 01:00 Fig. 10: Starting performance on winter condition Fig. 11: Starting performance on winter condition (100% thermal load) (50% thermal load) (: kw) 3 3 (: kw) 3 3 2 2 Energy consumption Indoor Temp. Outdoot Temp. 1 1 Energy Consumption Indoor Temp. Outdoor Temp. 1 1 00:00 00:10 00:20 00:30 00:40 00:50 01:00 01:10 00:00 00:10 00:20 00:30 00:40 00:50 01:00 01:10 Fig. 12: Starting performance on middle condition Fig. 13: Starting performance on middle condition (100% thermal load) (50% thermal load)

R067, Page 7 (: kw) (Temp: ) 4 (: kw) 4 4 3 3 Energy Consumption Indoor Temp. Outdoor Temp. 4 3 3 2 2 indoor Temp. Power Consumption Outdoor Temp. 00:00 00:10 00:20 00:30 00:40 00:50 01:00 01:10 00:00 00:10 00:20 00:30 00:40 00:50 01:00 01:10 01:20 Fig. 14: Starting performance on summer condition Fig. 15: Starting performance on summer condition (100% thermal load) (50% thermal load) At the starting period, the unit demands many power resources, so the energy efficiency is getting lower. The COP ratio is about 50%. The fluctuation of room temperature with the defrost operation at heating. On the summer condition test, test unit is following to the change of the condition. It shows the inverter control has much influence to the energy saving. The performance including start period is lower than rated value. The rush current is characteristic phenomenon at start period, but arrow for that, lowers performance at the winter conditions. On a winter condition, on-off operation for defrost is observed. Because of that, the total energy consumption efficiency is lower than summer condition. The performance of middle season is favorable. It is thought of as the designing concept of air conditioner matches this range. Table 8: Results of start performance test Condition Summer Middle Winter Factor (%) Total Energy Consumption (kwh) Supplied (kwh) Measured COP COP Ratio (%) 100 1.76 2.34 1.33 32.19 50 0.97 0.78 0.80 19.47 100 0.93 1.90 4 49.47 50 0.55 1.60 2.91 70.44 100 1.96 3.19 1.63 38.21 50 9 1.42 1.30 30.62

R067, Page 8 4. CONCLUSION and DISCUSSION In this experiment, we obtained following conclusions. In the fluctuating condition tests, the measurement performance does not reach to the rated performance. The performance of test unit is received large influence with circumstance conditions. Therefore, By a current test method, i.e. air-enthalpy method with static conditions, it is difficult that estimate an actual performance. The evaluation of actual performance is important for air conditioning facility designs. On the basis of these results, we suggest that it is necessity to establish the evaluation method under actual conditions. The split air conditioning system will become the mainstream of it in the next generation. In addition, an estimate of generated effective thermal capacity based on a rating test is not clear. It is important that we know the generated effective thermal capacity in a real use, if we design an air conditioning. Rating test is necessary for indication of product design. The problem what standards should be applied on the product design. The split air conditioning system is respond to the demands of the times. The requirement of air conditioner involves the amenity and energy-saving. Rated test result but also actual evaluations are draw attention as quality production. So, we suggest that the evaluating actual performance is the most important thing for the developing air conditioning system as one of building equipments. As for the air conditioner, it should be done evaluation from a user side. This is the item which is so important in a design of an air conditioner. The false estimates produce a different anticipation of future energy consumption or waste heat contamination. Therefore, establishment of immediate evaluation technique is expected. REFERENCES Japanese Standards Association, 1999, Ducted air-conditioners and air-to-air heat pumps Testing and rating for performance JIS B 8615-1, Japanese Standard Association: p.2-42. Japanese Standards Association, 1999, Ducted air-conditioners and air-to-air heat pumps Testing and rating for performance JIS B 8615-2, Japanese Standard Association: p.2-42. The Japan Refrigeration and Air Conditioning Industry Association, 1995, Package Air Conditioners JRA 4002, Japanese Standard Association: p.1-70. The Japan Refrigeration and Air Conditioning Industry Association, 2001, Calculating method of annual power consumption for package air conditioners JRA4048, Japanese Standard Association: p.5-30. International Organization for Standardization, 1994, Non-Ducted air conditioners and heat pumps - Testing and rating for Performance, International Organization for Standardization, Geneve Switzerland: p.1-19. Naho,W., Kousuke,T., Eiji,H., 2004, Research on Annual Energy Consumption of Air Conditioning Equipment, Trans. of the JSRAE., vlo.21, no. 2: p. 157-165. The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan, 2003, Computer Aided Simulation for Cogeneration Assessment & design Ver.3.1, The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan