APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Similar documents
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

3/29/2012 INTRODUCTION HVAC BASICS

Dedicated Outdoor Air Systems (D.O.A.S.)

HVAC Systems: Overview

How To Buy A Lennox Power System

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

How To Design A Building In New Delhi

Defining Quality. Building Comfort. Precision. Air Conditioning

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

By Tom Brooke PE, CEM

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH%

Lesson 36 Selection Of Air Conditioning Systems

Dehumidification Frequently Asked Questions

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

School HVAC Design Guide

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Preliminary Final Proposal

Bring the fresh in. Dedicated Outside Air Systems

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

School HVAC. Design Manual. Application Guide AG Air Cooled Chiller. Chilled Water Pumps. Expansion Tank CHWR CHWS. Make up Water Line Boiler

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Lower Energy Costs with Rooftop Air-Conditioning Package Units

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Mechanical Rooftop Custom Capabilities

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

Role of Economizers in Dedicated Outdoor Air Systems

Flexibility, Efficiency In San Antonio Arena

DOAS UNITS. MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR. Kitchens Hotel Corridors Laboratories. Paint Booths. Capacities Tons MBH

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

Ductless Heat Pumps. Gary Nordeen January

Pool Dehumidification Basics

Energy Efficiency in Industrial HVAC Systems

HVAC Efficiency Definitions

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord

Whole House Dehumidification for Occupant Comfort and Energy Savings

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

HVAC Calculations and Duct Sizing

Innovent LASER Packaged Fresh Air Conditioning Units

To provide good indoor air quality


Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Air Conditioning Clinic

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment

Active Chilled Beam System Design & Layout

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Energy Efficient HVAC-system and Building Design

HVAC Basic Science - System Capacity

EnergyPro Building Energy Analysis. Assisted Living Building

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

MULTIZONE APPLICATION OF SOLUTION UNITS

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE ? SLIDE 1

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Glossary of Heating, Ventilation and Air Conditioning Terms

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

CHAPTER 5 Energy Efficient HVAC Design

Why Do I Need Precision Air Conditioning?

york air-conditioning products Residential & VRF News 2015

KANSAS STATE UNIVERSITY Department of Architectural Engineering and Construction Science 240 Seaton Hall Manhattan, KS PREPARED BY:

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products. Richard Lord

What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere

Commissioning - Construction Documents (Page 1 of 6)

Introduction To VRF: System Overview, Applications, & Savings Opportunities

STULZ Water-Side Economizer Solutions

Residential HVAC System Sizing

HVAC Checklist - Long Form

for Plans Examiners and Building Inspectors

Improving Data Center Energy Efficiency Through Environmental Optimization

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Air Conditioning Contractors of America

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

Element D Services Heating, Ventilating, and Air Conditioning

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Failure code manual. content

HVAC Processes. Lecture 7

Variable Refrigerant Flow Systems vs. Geothermal Water Source Heat Pump Systems

HVAC Simplified Approach Option

Development and testing of a multi-type air conditioner without using AC inverters

MEETING AGENDA. Project Administrator:

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

Transcription:

APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems do not have direct acting dehumidification capability. Instead, the equipment is sized to meet the design latent (dehumidification) load but is operated to meet the real-time sensible cooling load. How well these systems actually meet the latent load cooling requirements will be discussed in this paper. A classroom is a common example of a space with a higher latent load due to the students. It will be used as an example. Table 1: Typical Classroom Zone Cooling Load Sensible Latent Total Btu/h Btu/h-ft² % Btu/h Btu/h-ft² % Btu/h Btu/h-ft² % Wall 1 Load 2464 2.5 11% 2464 2.5 8% Glass 1 Conduction 564 0.6 2% 564 0.6 2% Glass 1 Solar 1422 1.4 6% 1422 1.4 5% Light Load 3412 3.4 15% 3412 3.4 11% Plug Load 6824 6.8 30% 6824 6.8 22% Occupant Load 7576 7.6 33% 7576 7.6 94% 15152 15.2 49% Infiltration Load 475 0.5 2% 516 0.5 6% 990 1.0 3% Subtotal 22736 22.7 100% 91 8.1 100% 30828 30.8 100% Safety Factor 2274 2 9 0.8 3083 3.1 Total 210 25 8901 8.9 33910 33.9 Table 1 shows the sensible cooling loads for a typical classroom with a south exposure in Toronto, Canada. Only the space latent load will be considered because various different HVAC systems manage the ventilation load in a wide range of manners. The ventilation latent load will be discussed separately. WBCS Ventilation and Latent Load Calculations The classroom ventilation and latent load primary airflow calculations for a Waterborne Climate System (WBCS) will be used as a base line. The ventilation calculation is the same for packaged rooftop units, Fan fan coils, Water Source Heatpumps (WSHP), Ground Source Heatpumps (GSHP) and Variable Refrigerant Flow (VRF) systems. Ventilation rates for VAV is little more complex due to the multi-zone calculation requirements. 1 Application Guideline

Using the classroom example in Table 1; Ventilation Rate The ventilation rate is based on ASHRAE Std 62.1 single zone systems. This is the most straightforward method in ASHRAE Std 62. V bz = R p P z + R a A z V oz = V bz /E z V ot = all zones V oz (For 100% outdoor air systems like WBCS) where V bz = outdoor airflow rate in the breathing zone (cfm) R p = people outdoor air rate (cfm/person) P z = number of people R a = area outdoor air rate (cfm/ft²) A z = area (ft²) V oz = zone airflow rate (cfm) E z = zone air distribution effectiveness (E z = 1.0 for ceiling chilled beams) Occupancy (NP) = 30 Area = 1000 ft² R p = 10 cfm/person R p = 0.12 cfm/ft² Ventilation rate = 30 10 cfm + 0.12 1000 ft² = 423 cfm Latent Rate The latent load in a classroom will dominate the primary airflow sizing for a WBCS system. The change in humidity ratio will likely be 20 gr/lb or more. Such a large change will require a higher humidity level in the space and a lower humidity level from the primary unit. = P latent /(0.68*( W r W primary air )) where w primary air = the humidity ratio of primary air in gr/lb w r = the humidity ratio of the design space condition in gr/lb P latent = the latent load in Btu/h = the primary air flow in cfm = P latent /(0.68 (W r W primary air )) Latent load Platent = 7165 Btu/h w r = 71.2 gr/lb (Note: this is based on 75 F and 55% RH) w primary air = 51.6 gr/lb (Note: this is based on F leaving coil temperature) Primary air flow for latent load = 7165 / (0.68 (71.2 51.6) = 538 cfm Swegon Application Guide 2

Table 2 shows the summary of the calculations for a WBCS system. In this case, the latent airflow requirement is dominant so the primary airflow rate should be 538 cfm or 0.54 cfm/ft². For other decentralized HVAC systems, the primary airflow will just be the ventilation airflow. Depending on the design of the ventilation unit, the primary air may handle some of the zone latent load. The rest of the zone latent load will be managed by the terminal unit (fan coil, WSHP, etc.) Table 2: Summary of Primary Airflows for Classroom using WBCS System Rate cfm cfm/ft 2 Design Sensible Rate 419 0.42 Design Ventilation Rate 423 0.42 Design Latent Rate 538 0.54 Comparing Latent Load Management Consider using a VAV system for the classroom example. The design airflow rate to meet the sensible load will be; = 210 / (1.085 (75-57)) = 12 cfm or 1.28 cfm/ft² The latent airflow rate will be; = 7165 / (0.68 (71.2 62.4)) = 1197 cfm or 1.2 cfm/ft². The supply air will pass through the cooling coil being cooled to 55 F DB and 62,4 gr/lb. The fan heat will reheat the air 2 F to 57 F as shown in Figure 1. Figure 2 and 3 (right) show the latent and sensible cooling curves for both VAV and WBCS systems as the sensible load goes from 0 to 100%. In a VAV system (Figure 2) the supply air is reduced as the sensible load drops. The system will spend the bulk of its operating hours around %. The primary airflow will drop to % meaning the latent capacity will also drop to %. In a WBCS system (Figure 3) the latent load is controlled independently of the sensible load. A WBCS system will deliver the same latent capacity regardless of sensible load. 1 In a VAV office design with a high sensible heat ratio, the drop in latent cooling capacity as the sensible load drops is generally not an issue (a conference room could be problematic). However, in a classroom application, the latent load generally remains constant (the students are in the classroom all day). Most classrooms have an exterior exposure which has a large impact on the sensible load. As the sensible load drops with a VAV system, humidity control can be lost. Figure 1: VAV System 10 30 30 15 WET BULB ºF 20 25 20 ENTHALPY BTU/lb 4 5 30 35 1 DRY BULB ºF 1. Space condition 75 F DB 55% RH, 71.2 gr/lb 2. Mixed air condition 3. Outdoor air condition 90 F DB, 75 F wb 4. Off coil condition 55 F DB 54.5 F wb 5. Fan heat 2 F Figure 2: Latent Performance for VAV System 30000 200 20000 100 10000 00 0 0 25 75 100 Sensible Capacity 2 45 90 3 100 Latent Capacity 1 120 100 20 110 HUMIDITY RATIO gr/lb Latent Load Management with Decentralized HVAC Systems Other popular decentralized HVAC systems for classrooms include; Fan coils WSHP GSHPs Variable Refrigerant Flow (VRF) systems The decentralized systems have dedicated outdoor air systems (DOAS) to manage the ventilation load. For the most part, the latent load of the ventilation air is handled by the DOAS unit. Only the space latent load is managed by the terminal unit to reduce unit capacity. Figure 3: Latent Performance for WBCS system 30000 200 20000 100 10000 00 0 0 25 75 100 Sensible Capacity Latent Capacity 1 At % sensible load, the WBCS still provides the design latent cooling capacity. 3 Application Guideline

These are all constant airflow variable supply air temperature systems. As the cooling load drops, the supply airflow rate remains constant and the supply air temperature is raised. Figure 4 shows the part load cooling performance of a typical constant volume, variable supply air temperature unit. This is how most energy modelling programs model this style of equipment. At % capacity, the supply air temperature has been raised to 65 F, significantly lowering the latent cooling capacity of the terminal unit. A fan coil with a modulating control valve can actually modulate the supply air temperature, although in many applications an off-on style valve is used. For a typical classroom-sized unit (3 to 5 tons), most of the other terminal units are either on-off or may have two-stage cooling. When an on-off style unit operates at % sensible cooling capacity, the unit cycles on and off so over the course of an hour the unit runs 30 minutes. While it might appear that the unit will fully dehumidify the supply air for at least 30 minutes in an hour, this has been proven to be false. Figure 5 shows that unless a unit operates at least % of the time, there is almost no dehumidification. While the unit is operating (dehumidifying), condensate forms on the coil and collects in the drain pan. When the unit cycles off, the condensate is re-evaporated into the airstream. In recent years several innovations have been added to improve part load performance. Both WSHPs and GSHPs can be supplied with Hot Gas Reheat (HGRH) and dehumidification controls. When the controls sense high humidity, the unit cools the air to remove the latent load and then reheats the air using waste heat from the refrigeration circuit. This maintains the space dry bulb temperature while removing moisture. Two-stage and now inverter (modulating compressors) have also become available. This matches the cooling capacity to the actual space sensible load and allows the compressor to stay on, dehumidifying all the time. The use of ECM motors on the fans has also allowed for improved dehumidification by reducing the airflow at part load conditions, thus lowering the supply air temperature so there is condensate removal. Figure 4: Part Load Performance for Constant Volume HVAC Unit 30000 20000 10000 0 0 25 75 100 Sensible Capacity Disch Air Temp Latent Capacity Figure 5: Dehumidification Performance for On-Off Style Units 1 Latent Load Management with Package Rooftop HVAC Systems Package rooftop units can be used in school applications where typically there is one unit per classroom. Packaged rooftop units differ from decentralized systems because they include the ventilation air. While this is a low cost solution, it can have severe latent management issues. Packaged rooftops unit are designed for office space conditions. Their capacity is based on about 10 to 15% outdoor air whereas a classroom application is closer to 35% outdoor air. They are not intended to be used for such high latent load applications. Basic rooftop units in this size range are either on-off or two-stage cooling. They are constant supply air units that cycle the cooling on- 1 Henderson, H. 1998 The impact of part-load air conditioner operation on dehumidification performance. Validating a latent capacity degradation model Proceedings of the 1998 Indoor Air Quality Conference. Swegon Application Guide 4

off to maintain overall space sensible temperature. During the off cycle, humid outdoor air is being introduced into the space as well as re-evaporating the condensate that has formed on the coil and collected in the drain pan. Hot gas reheat can be added to the unit to keep the compressor operating and not re-evaporate condensate. By doing so, however, the supply air temperature will rise at part load, quickly negating the latent cooling capacity of the unit. Using Hot gas bypass also means the unit will operate at full power regardless of the actual cooling load. This will be a very expensive system to operate. Except for a few select areas that favor this system, packaged rooftops are a poor choice for school classroom applications. They can be improved by adding an energy recovery module but latent performance is still compromised during part load operation. In recent years, several specialty manufacturers have introduced packaged rooftop units specifically designed for high latent load applications. They include modulating DX cooling, hot gas reheat and energy recovery. Conclusions High latent load applications such as classrooms require special attention to dehumidification not just at design conditions but even more so at part load conditions. In the case of a classroom, the latent load and the sensible load do not follow the same unload profile, making dehumidification even more complicated. Decentralized systems improve the situation considerably by separating the ventilation air load from the zone load. A dedicated outdoor air system (DOAS) can then manage the dehumidification in the ventilation air independently from the zone loads. WBCS systems take it one step further by completely managing the latent load both from the ventilation air and the zone separately from the zone sensible load, thus providing dehumidification control over the full cooling load range. 5 Application Guideline