SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING



Similar documents
SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

SECTION TESTING OF FIBER OPTIC CABLES

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

Reliable, Consistent, Quality

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

Discontinued. Volition. Fiber Optic Cable. 3Innovation

The color scheme for the fibers in the cable complies with the Telcordia (formerly Bellcore) specification.

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

UT Southwestern Medical Center Information Resources Cable Installation Standard

Multiple Solutions for Connecting Multiple Dwelling Units (MDUs)

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

Intelligent Cable Management Systems

ATTACHMENT F 050R CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

Fibre Optic Indoor/Outdoor Cable

SECTION ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

SECTION COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

Fiber Optic Cable

TCTC Cabling Specifications

SECTION FIBER OPTIC CABLE AND ACCESSORIES

Scope: Communications and Electronic Systems addressed in this section include:

SECTION TELECOMMUNICATIONS ACCEPTANCE TESTING

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

FOCONEC. Network Connectivity & Cabling Management. Overview: Features: Brighter Future

home site map help ECMS Project: Standard / Federal Oversight Advertised

800 Communications Circuits

Polymer Coated Fiber Cable (PCF)

DEPARTMENTAL REGULATION

SECTION O FIBER OPTICS

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

Intrabuilding Installation of Corning Cable Systems Fiber Optic Cable

Cable Preparation Best Practices for Fiber Optic Indoor/Outdoor Stranded Loose Tube Cable

FIBER OPTIC CABLE PLANT DOCUMENTATION

Fiber Optics in Harsh Environment Applications

Cable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Victor Elementary School District. Technology Infrastructure Standards Victor Elementary School District

1 Campus Cabling Systems Introduction

part number number Description B96551 M96551 Tactical, All Dielectric Cable, Tight Buffer, Oudoor, Multimode OM1, 62.5 µm, 4 fibers B96566 M96566

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

SECTION 680 FIBER OPTIC CABLE DESCRIPTION

Fiber Optic Cordage. Interconnect A Furukawa Company. Product Description. Why OFS Interconnect Cordage?

Pretium Connector Housings

fiberopt Whirlwind Fiber Optic Solutions product guide Ling Rd. Rochester, NY whirlwindusa. com

Patch Cords for Data Center Applications

March Commissioning of Communications. See Appendix E

FOA Technical Bulletin. Guide To Fiber Optic Installation

ANSI/TIA/EIA A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable

Fiber Optic Specifications

SECTION TELECOMMUNICATION ROOMS

Industry solutions: Broad cast

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

SECURE Fiber Optic Products

Fibre optic cables MDIC LSZH

InstaPATCH Cu Cabling Solutions for Data Centers

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec )

InstaPATCH ZERO Solution Guide

SPECIFICATION STANDARD OPTICAL FIBER BACKBONE CABLING

The Pennsylvania State University Physical Security Office. Intrusion Alarm. Performance Specification

Cable Installation Project

Guidelines for Installation of Fiber Optic Cables

RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables

AERIAL FIBER OPTIC CABLE PLACEMENT

Fibre Optic Cable. Catalogue.

21 st Century Campus Network Responsibility Matrix 5/26/10

ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va / Fax 434/

Building Telecommunications Infrastructure Requirements

Cable Assemblies. Corning Cable Systems

FCS-FCT-FCP Housings and Connector Panels. InfiniCor SX+ OM3, InfiniCor 600 OM2, InfiniCor 300 OM1, SMF 28e OS1/OS2

Cable Assembly Solutions at the Speed of Light

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

How To Design An Outside Plant (Osp) Network Design

SECTION OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Optical Fibers Fiber Optic Cables Indoor/Outdoor

OPTICAL FIBRE CABLES. for very-high bit transmission and FTTx networks

Specifying an IT Cabling System

Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman

CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL. Fiber Optic and Data Cabling Project Shelby Township Police Building

FiberGuide Fiber Management Systems. 4th Edition

SECTION TELECOMMUNICATIONS SYSTEM (Cat 6)

Specifications for Communication Cabling Distribution Systems

Errata NFPA 70. Proposed 2014 Edition

SECTION DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

DESIGN GUIDELINES. Local Area Network

Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc.

DOUBLE STAINLESS STEEL TUBE DTS FIBER OPTIC CABLE FTSF-FSUTS(DTS)

Data Center Cabling Design Trends

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

Transcription:

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated or to be incorporated in such construction and all services, facilities, tools and equipment necessary or used to perform and complete such construction. The work of this section shall include, but is not limited to, the following: 1.02 QUALITY ASSURANCE 1. OSP optical fiber backbone cabling system A. Refer to Section 27 00 00 for general details. B. As noted in Section 27 00 00, all contractors and installers working on structured cabling system elements must hold a current manufacturer s certification for each individual component they install. 1.03 CODES, STANDARDS, AND GUIDELINES A. Except as modified by governing codes and by the Contract Documents, comply with the applicable provisions and recommendations in Section 27 00 00. B. Customer Owned Outside Plant Design Manual (BICSI) 1.04 SUBMITTALS A. Refer to Section 27 00 00 for general details. B. Shop Drawings: 1. Shop drawings shall show the locations where cables are to be routed and where terminating hardware is to be installed. C. Submit Manufacturer s Cut Sheets for the following: 1.05 IDENTIFICATION 1. Any products not specifically listed in the PRODUCTS section shall require a submittal of the manufacturer s cut sheets. A. Outdoor cables must be labeled with 1¼ stamped brass tags within 18 of all conduit endpoints and both cable endpoints. Within all underground structures larger than 3 in any dimension, label each cable as it enters the structure, and when it exits the structure 1 of 9

B. Refer to Section 27 05 53 for additional details. 1.06 DEFINITIONS A. CMP: Communications Plenum Cable B. CMR: Communications Riser Cable C. MPP: Multipurpose Plenum Cable D. OFNP: Optical Fiber Nonconductive Plenum Cable E. OFCP: Optical Fiber Conductive Plenum Cable F. LSZR: Low Smoke Zero Halogen Rated Cable G. OM1: Defined by ISO 11801 & TIA-492-AAAA, 62.5/125 µm multimode fiber. H. OM2: Defined by ISO 11801 & TIA-492-AAAB, 50/125 µm multi-mode fiber. I. OM3: Defined by ISO 11801 & TIA-492-AAAC, laser-optimized 50/125 µm multi-mode fiber J. OM4: Defined by TIA-492-AAAD, laser-optimized 50/125 µm multi-mode fiber 1.07 WARRANTY A. Refer to Section 27 00 00 for general details. 2 of 9

PART 2 PRODUCTS 2.01 PRODUCT CONSISTENCY A. Product Consistency: Any given item of equipment or material shall be the product of one manufacturer throughout the facility. Multiple manufacturers of any one item will not be permitted. 2.02 FIBER OPTIC CABLES GENERAL A. Cable jacket marking: Must be legible and shall contain the following information: 1. Manufacturer s name and/or trade mark 2. Strand count 3. Cable Type 4. Pair Count 5. UL listing 6. Sequential distance markings, in one foot increments B. All multimode shall be OM4, 50 μm multimode fiber. C. All singlemode shall be zero water peak singlemode fiber 2.03 MULTIMODE OPTICAL FIBER OSP CABLE (144 STRAND) A. Non-Armored Jacket shall be MDPE, with strength elements and zipcord immediately underneath. B. Internal structure shall include water swellable tape layer and 2 mm gel filled buffer tubes. C. Fibers shall be contained in loose tube construction surrounding a central dielectric strength member D. Shall be 12 strands per subunit, 144 multimode fibers in one overall jacket. E. Jacket color shall be black. F. Manufacturer/Product: Commscope Part #: O-144-LN-5K-F12NS/20T 2.04 SINGLEMODE OPTICAL FIBER OSP CABLE (144 STRAND) A. Non-Armored Jacket shall be MDPE, with strength elements and zipcord immediately underneath. B. Internal structure shall include water swellable tape layer and 2 mm gel filled buffer tubes. C. Fibers shall be contained in loose tube construction surrounding a central dielectric strength member D. Shall be 12 strands per subunit, 144 singlemode fibers in one overall jacket. 3 of 9

E. Jacket color shall be black. F. Manufacturer/Product: Commscope Part #: O-144-LN-8W-F12NS/20T 2.05 COMPOSITE OPTICAL FIBER OSP CABLE (36/36) A. Non-Armored Jacket shall be MDPE, with strength elements and zipcord immediately underneath. B. Internal structure shall include water swellable tape layer and 3 mm gel filled buffer tubes. C. Fibers shall be contained in loose tube construction surrounding a central dielectric strength member D. Shall be composite cable, 12 strands per subunit, 36 singlemode and 36 multimode fibers in one jacket. E. Jacket color shall be black. F. Manufacturer/Product: Commscope Part #: O-072-LN-CM-F12NS/8W036/5K036 2.06 COMPOSITE OPTICAL FIBER INDOOR/OUTDOOR CABLE (12/12) A. Non-Armored Jacket shall be plenum and OSP rated B. Cable shall have strength elements and zipcord immediately underneath jacket. C. Internal structure shall include water swellable tape layer and 2.5 mm gel filled buffer tubes. D. Fibers shall be contained in loose tube construction surrounding a central dielectric strength member E. Shall be composite cable, 12 strands per subunit, 12 singlemode and 12 multimode fibers in one jacket. F. Jacket color shall be black. G. Manufacturer/Product: Commscope Part #: P-024-LN-CM-F12BK/25D/8W012/5K012 2.07 MULTIMODE OPTICAL FIBER INDOOR/OUTDOOR CABLE (6 STRAND) A. Non-Armored Jacket shall be plenum and OSP rated B. Cable shall have aramid yarn and zipcord immediately underneath jacket. C. Internal structure shall include water barrier layer and a central dielectric strength member D. Jacket color shall be black. E. Manufacturer/Product: Commscope Part #: P-006-OD-5K-FSUBK 2.08 SINGLEMODE OPTICAL FIBER INDOOR/OUTDOOR CABLE (6 STRAND) A. Non-Armored Jacket shall be plenum and OSP rated B. Cable shall have aramid yarn and zipcord immediately underneath jacket. 4 of 9

C. Internal structure shall include water barrier layer and a central dielectric strength member D. Jacket color shall be black. E. Manufacturer/Product: Commscope Part #: P-006-OD-8W-FSUBK 5 of 9

PART 3 EXECUTION 3.01 GENERAL A. OSP fiber optic cables are for use between telecommunications facilities in different buildings, or any connections that are subject to moisture. B. Location, fiber count and placement detail for all fiber optic cables shall be as shown on the Drawings. C. OSP cable will be run in continuous rigid metallic conduit or underground until it is exposed in a telecommunications space where it is to be terminated. D. Provide 50 slack loops at the TR end of all OSP fiber optic cables over 12 strands. OSP fiber optic cables under 12 strands shall have 20 slack loops. E. Provide 36 of stripped fiber strands wrapped neatly at each fiber cabinet. F. Insure all fiber optic cables as installed are not subject to strain, and that correct bend radiuses are maintained at all times. G. Do not combine terminations of fiber optic cables leading to different endpoints into a single cabinet. Each distribution, riser, OSP or Fire Alarm serving cable shall require their own, dedicated fiber termination cabinet. The only exception is for station fibers, termination of station fibers can be combined into a single cabinet. H. Each fiber optic OSP cable shall be placed within one cell of innerduct per Section 27-05-33 I. Fiber optic cables and copper cables shall not share conduit or innerduct. J. Do not terminate fiber until after the rack locations and elevations of fiber cabinets have been accepted by the campus telecommunications representative. K. Do not install patch cables until after the fiber optic test reports have been accepted by the campus telecommunications representative. 3.02 QUANTITIES A. Quantities of system elements shown on the drawings are illustrative only and are meant to indicate the general configuration of the work. The Contractor is responsible for providing the correct quantities of materials to construct a system that meets the intent of these Specifications and the relevant codes. 3.03 INSTALLATION A. Optical Fiber OSP Cables: 1. Provide support for vertical runs of fiber optic riser cables. 2. Route fiber optic cables over telecom ladder racking avoiding the area directly in front of the wallfield. 6 of 9

3. Route fiber optic cables together as a single bundle, not to be combined with copper or coax cabling. 4. Installation of all fiber optic cables shall require the use of a breakaway swivel rated to the cable manufacturer s written specifications for pull strength. 5. Follow all manufacturers specifications for installation. B. Connector Installation 1. Terminate both ends of each fiber with an appropriate anaerobic type connector. Fibers will be terminated in strict compliance with the manufacturer s printed instructions. 2. Breakout kits will be required per manufacturer s specifications. 3. Maximum length deferential between terminated strands per bundle shall be 6. If the length does not meet this requirement the entire bundle must be re-terminated. C. Slack Loop 1. Slack loop shall be mounted on the wall, above ladder rack height. 2. Slack loop location shall be designated by the campus telecommunications representative. D. Underground 3.04 GROUNDING & BONDING 3.05 TESTING 1. OSP fiber optic cables need to be lashed to and supported by cable management arms within any underground facilities. 2. Outdoor cables must be labeled with 1¼ stamped brass tags at each location within 12 of where it enters or exits in each underground facility. 3. At each vault immediately prior to building entry, each fiber optic OSP cable shall make one complete horizontal wrap of the vault. A. None Required A. Refer to Specification Section 27 08 23. 3.06 ACCEPTANCE A. 100% of the fiber tested must meet requirements for the whole of the fiber installation to be accepted. B. Upon receipt of the Contractor s documentation of cable testing, the campus representative will review/observe the installation and randomly request tests of the cables installed. Once the installation and testing has been completed and the campus telecommunications representative is satisfied that all work is in accordance with the Contract Documents, the representative will notify the Contractor and/or campus project manager in writing or via email. 7 of 9

3.07 RECORD (ASBUILT) DRAWINGS A. The Project Record Drawings shall show the types and locations of all fiber optic cabling and fiber optic termination points. Drawings should include identifying information from the cable identification tags. B. Provided documentation shall include butterfly drawings for each vault, detailing specific conduit utilization for each cable. END OF SECTION 8 of 9

DOCUMENT VERSION CONTROL REVISION DATE AUTHOR REASON 1 08/07/2012 C. WHITEHOUSE INITIAL DOCUMENT CREATION 2 02/04/2013 CJW & CLC PRIMARY REVIEW COMPLETE 9 of 9