presents Hydraulic Separation Beyond Primary / Secondary Piping



Similar documents
Condensing Boiler Efficiency

Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Commercial Boiler Systems and Controls

Mini-HYDRO TM Installation Manual

Gas Boilers - Commercial

FILLING AND PURGING THE SYSTEM

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

TD10. Selecting Circulators. Technical Documents. Taco Radiant Made Easy Application Guide STEP 1: ESTABLISH THE TARGET FLOW RATE FOR THE SYSTEM

Steam System Best Practices Condensate System Piping

Mixing Valves. ARGUS Application Note: Mixing Valves

Electric Flow Boiler

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

Principals of Condensing Boiler System Design

Maximizing Boiler Plant Efficiency. Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc.

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

BULLETIN NO. TEH-908. Bell & Gossett R T. Hydronic System Design with the Bell & Gossett System Syzer / ON GPM FLOW

CGC s Hybrid System Loop Control

Laddomat Charging unit

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

High efficiency, cast-iron gas boiler

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

Commissioning - Construction Documents (Page 1 of 6)

HUB RADIATOR HYBRID. Multi-energy hybrid system to produce heating and DHW. Multi-energy hybrid system to produce heating, cooling and DHW

Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide

Boiler Manual. Installation Startup Maintenance Parts WARNING

How To Make A Fuel Manager Filter/Separator

ENERGY RETROFIT PROGRAM

Commercial Semi-Instantaneous Water Heaters

Description of functions

G234X-55 Conventional Gas Boiler

HS-901(A) BASIC STEAM HEATING SYSTEMS

Cast-Iron Performance Meeting today s commercial demands with effi ciency, strength and intelligent controls.

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

Sanitary Type Electronic Flow Switches

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

I. STEAM GENERATION, BOILER TYPES

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

DESIGNER S GUIDE EFFICIENCY+ BOILER

Better Boilers.

Integrated Solar Radiant Systems

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Theta Dual service BFC, SGE, SGS for 20/30/40 kw heating capacity

STATE SUPER HIGH EFFICIENCY Up To 96% Thermal RESIDENTIAL PREMIER POWER-VENT MODELS

FYI > California Title 24

HOT WATER SYSTEMS CONTENTS

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB

GAS CONVERSION PROJECT ˆAn Alternative to Oil

Water hammering in fire fighting installation

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC DRAFT V0.

THERM Tankless Water Heaters. Applications Manual

Heating Water by Direct Steam Injection

In-Line Air Separators

Link-Up. Solid Fuel Association Guide to Central Heating.

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Design and Implementation of Geothermal Systems for Heating and Air Conditioning

MUELLER FALLING FILM CHILLERS

Hybrid Modeling and Control of a Power Plant using State Flow Technique with Application

Buderus. Superior Equipment by Design. Comfortable. Efficient. Intelligent Heating. G315 G515 G615 Cast Iron Commercial Boilers.

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers

HYDRONIC DESIGNER / INSTALLER MODULE DESCRIPTIONS

How To Use A Water Source Heat Pump

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Installation & Operation Manual Models: STU

C. starting positive displacement pumps with the discharge valve closed.

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23

PLBG/GAS SAFETY Information Bulletin

Boiler Applications Drawings

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

DRAFT HOOD OUTLET GS6-30-YORT NG Select - Tall - C3 Technology 28 FIRST HOUR RATING BTU INPUT PER HOUR

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to Nonvolatile TOC content < 1.0 ppm

300 Series PA Pump and Cooler Assemblies

Vitodens 200, B2HA / B2HB - Product Introduction

Logamax plus GB142. Applications Manual. Gas condensing boiler

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

Design guidelines for hybrid boiler systems.

Steam System Efficiency. Bill Lumsden Leidos Engineering

COUNTERBALANCE VALVES

Method to Determine PERFORMANCE OF INDIRECT-FIRED WATER HEATERS March 2003 Edition

UNDERSTANDING CENTRAL HEATING SYSTEMS

Buderus. Flexible Energy Efficient Solutions. Comfortable. Efficient. Intelligent Heating. GB312 Series Natural Gas Condensing Boiler.

MECHANICAL SYSTEMS DESIGN. Team

NORMAN FILTER COMPANY PRODUCT OVERVIEW

RVR Hybrid System Installer Instructions RVR Hybrid System Controller Installation Instructions

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Heating, air-conditioning, cooling

Stanadyne Fuel Manager Diesel Fuel Filter/Water Separator System. User s Guide

Engineered Heating Cable Systems

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED

Conlift1, Conlift2, Conlift2 ph+

Transcription:

presents Hydraulic Separation Beyond Primary / Secondary Piping This Webinar is exclusively sponsored and the property of Caleffi Hydronic Solutions. All rights reserved. October 2007

Modern compact boilers have much higher flow resistance than cast iron boilers. If they are simply substituted for cast iron boiler problems are likely to develop, most notably interference between simultaneously operating circulators. condensing/ modulating boiler zoned distribution system

The solution to this problem is hydraulic separation. In short, preventing flow in one circuit from interfering with flow in another circuit. In systems with hydraulic separation the designer can now think of each circuit as a stand-alone entity: Simplifying system analysis Preventing flow interference Hydraulic separation is a new term to hydronic system designers in North America. flow-check valve secondary circuit Primary / secondary piping, using closely spaced tees, is the best known form of hydraulic separation now used in North America primary circulator primary loop secondary circulator closely spaced tees flow D maximum 4xD

The secondary circuit is hydraulically separated from the primary circuit by the closely spaced tees. This concept can be extended to multiple secondary circuits served by a common primary loop: high temperature secondary circuit medium temperature secondary circuit primary loop closely spaced tees low temperature secondary circuit

This configuration is more called a series primary/secondary system: Although hydraulic separation exists between all circuits, so does an undesirable effect a drop in water temperature from one secondary circuit to the next when operating simultaneously high temperature secondary circuit primary loop medium temperature secondary circuit closely spaced tees low temperature secondary circuit

A parallel primary/secondary piping configuration provides the same water temperature to each secondary circuit: This benefit is achieved at the expense of more complicated and costly piping.

In addition, both series and parallel primary/secondary systems require a primary circulator. modulating / condensing boiler having high flow resistance secondary circuits #1 #2 #3 #4 modulating / condensing boiler having high flow resistance boiler circulator primary circulator secondary circuits closely spaced tees series primary loop boiler circulator closely spaced tees parallel primary loop crossover bridge primary circulator closely spaced tees balancing valves This adds to the installed cost of the system AND add hundreds, even thousands of dollars in operating cost over a typical system life.

An example of primary loop circulator operating cost: Consider a system that supplies 500,000 Btu/hr at design load. Flow in the primary loop is 50 gpm with a corresponding head loss of 15 feet (6.35 psi pressure drop). Assume a wet rotor circulator with wire-to-water efficiency of 25 is used as the primary circulator. The input wattage to the circulator can be estimated as follows: W = 0.4344 f P 0.25 = 0.4344 50 6.35 0.25 = 552watts Assuming this primary circulator runs for 3000 hours per year its first year operating cost would be: 1st year cost = 3000hr yr 552w 1kwhr 1 1000whr $0.10 = $165.60 kwhr

Assuming electrical cost escalates at 4% per year the total operating cost over a 20-year design life is: c T = c 1 ( 1+ i ) N 1 i 1+ 0.04 = $165.60 0.04 ( ) 20 1 = $4,931 This, combined with eliminating the multi-hundred dollar installation cost of the primary circulator obviously results in significant savings.

Beyond Primary / Secondary Piping How is it possible to achieve the benefits of hydraulic separation and equal supply temperatures without the complexities and costs of a parallel system and primary circulator?

Some systems begin and end individual load circuits in the mechanical room: short, wide diameter header supply temperature sensor for boiler reset controller closely spaced tees (for hydraulic separation) air vent A circulators with internal check valves shown equal supply temperature to all loads B distribution circuits purging vavles drain valve Header should be sized for max. flow velocity of 2 feet per second Each circuit must include a check valve. boiler #1 boiler #2 The generous diameter of the header and close spacing between supply and return connections results in a low pressure drop between points A and B. Each load circuit is effectively hydraulically separated from the others.

Another option is a specialized component called a hydraulic separator between the boiler and the load circuit: boiler hydraulic separator heating load The low vertical velocity inside the separator produces minimal pressure drop top to bottom and side to side. This results in hydraulic separation between the boiler circuits and load circuits.

Some hydraulic separators also provide air separation and sediment separation. To achieve these functions in a system using closely spaced tees additional components are required:

As the flow rates of the boiler circuit and distribution system change there are three possible scenarios: Flow in the distribution system is equal to the flow in the boiler circuit. Flow in the distribution system is greater than flow in the boiler circuit. Flow in the distribution system is less than flow in the boiler circuit. Each case is governed by basic thermodynamic...

Case #1: Distribution flow equals boiler flow: port #1 port #2 = = port #3 port #4 = = Very little mixing occurs because the flows are balanced.

Case #2: Distribution flow is greater than boiler flow: The mixed temperature (T 2 ) supplied to the distribution system can be calculated with: = = T 2 = ( f 4 f 1 )T 4 + ( f 1 )T 1 f 4 Where: f4 = flow rate returning from distribution system (gpm) f1 = flow rate entering from boiler(s) (gpm) T4 = temperature of fluid returning from distribution system ( F) T1 = temperature of fluid entering from boiler ( F) Mixing occurs within the hydraulic separator.

Case #3: Distribution flow is less than boiler flow: Heat output is temporarily higher than current system load. Heat is being injected faster than the load is removing heat. = = The temperature returning to the boiler (T 3 ) can be calculated with: T 2 = ( f 4 f 1 )T 4 + ( f 1 )T 1 f 4 Where: T3 = temperature of fluid returned to boiler(s) ( F) f1 = flow rate entering from boiler(s) (gpm) f2, f4 = flow rate of distribution system (gpm) T1 = temperature of fluid entering from boiler ( F) T4 = temperature of fluid returning from distribution system ( F) Mixing occurs within the hydraulic separator.

Use of a hydraulic separator alone does not prevent flue gas condensation under all circumstances. To ensure such protection automatic mixing devices can be installed: The variable speed injection pump in piped in parallel with the fixed speed circulator The injection pump and fixed speed circulator both require a check valve

Sizing & Application: Hydraulic separators must be properly sized to provide proper hydraulic, air, and dirt separation. Excessively high flow rates will impede these functions. Pipe size of hydr aulic separato r Max fl ow rate (GPM) 1 1.25 1.5 2 2.5 3 4 6 11 18 26 40 80 124 247 485 The header piping connecting to the distribution side of the Hydro Separator should be sized for a flow of 4 feet per second or less under maximum flow rate conditions.

Hydraulic separators are an ideal way to interface multiple loads to a Multiple boiler system.

Example of Hydro Separator Installation in New System: Magna Steel Corporation - Connecticut Photos courtesy of Peter Gasperini - Northeast Radiant

Example of Hydro Separator Installation in Old System: Because hydraulic separators remove sediment from systems they re ideal for applications where new boilers are retrofit to old distribution systems.

Example of Hydro Separator Installation in Old System: Here is how the previous system was retrofitted.

Hydraulic Separation in Micro-load systems: The small insulated tank provides: Thermal buffering Hydraulic separation Air separation and collection Sediment separation and collection

Summary: Hydraulic separation, when properly executed, allows multiple, independently controlled circulators to coexist in a system without interference. These devices eliminate the need for a primary loop circulator, which reduces system installation and operating cost.

Thank you for your participation. For additional questions, please contact: Caleffi Hydronic Solutions 3883 W Milwaukee Rd Milwaukee, WI 53208 414.238.2360 sales@caleffi.com This Webinar is exclusively sponsored and the property of Caleffi Hydronic Solutions. All rights reserved. October 2007