1. Installing and configuring APC UPS Management



Similar documents
Configuration Manual English version

Customer Tips. Configuration and Use of the MeterAssistant Option. for the user. Purpose. Xerox Device Configuration. Xerox Multifunction Devices

AXIS Camera Companion Internet access

Setup Guide for Exchange Server

Intelligent Power Protector User manual extension for Microsoft Virtual architectures: Hyper-V 6.0 Manager Hyper-V Server (R1&R2)

ViewPower. User s Manual. Management Software for Uninterruptible Power Supply Systems

1. Open the preferences screen by opening the Mail menu and selecting Preferences...

GE Measurement & Control. Remote Comms System. Installation and User Reference Guide

Hillstone StoneOS User Manual Hillstone Unified Intelligence Firewall Installation Manual

Server Installation Guide ZENworks Patch Management 6.4 SP2

Scan to Quick Setup Guide

Reason 8 Multi Licenses

Installation and Configuration User's Guide

VRC 7900/8900 Avalanche Enabler User s Manual

Firmware upgrade instructions for the Web/SNMP and Network

Dell UPS Local Node Manager USER'S GUIDE EXTENSION FOR MICROSOFT VIRTUAL ARCHITECTURES Dellups.com

Before You Start 1 Overview 2 Supported Devices 4 Public (User LAN) and Private (APC LAN) Networks 5. Initial Configuration Requirements 6

The FlexiSchools Online Order Management System Installation Guide

Installing GFI MailSecurity

Connecting the DG-102S VoIP Gateway to your network

Setting Up a Unisphere Management Station for the VNX Series P/N Revision A01 January 5, 2010

This chapter explains a preparation for the use of RemoteControlService.

c. Securely insert the Ethernet cable from your cable or DSL modem into the Internet port (B) on the WGT634U. Broadband modem

SevOne NMS Download Installation and Implementation Guide

Configuring Your Client: Eudora 5.x

1 You will need the following items to get started:

Fax User Guide 07/31/2014 USER GUIDE

Software Installation Guide

Defender Token Deployment System Quick Start Guide

User guide. Business

MFPConnect Monitoring. Monitoring with IPCheck Server Monitor. Integration Manual Version Edition 1

F-Secure Messaging Security Gateway. Deployment Guide

Exchange Outlook Profile/POP/IMAP/SMTP Setup Guide

Deploying Windows Streaming Media Servers NLB Cluster and metasan

Acellus Lab Cart. User s Manual. Version 4B. Acellus Corporation Copyright 2010 Acellus Corporation. All Rights Reserved.

User s Manual Network Management Card

Installation Guide for Pulse on Windows Server 2012

Netwatch Installation For Windows

CLEARONE DOCUMENT (REVISION 1.0) October, with Converge Pro Units

Quick Installation and Setup for WinPower Software

HP Intelligent Management Center v7.1 Virtualization Monitor Administrator Guide

Rev 7 06-OCT Site Manager Installation Guide

Title Page Web/SNMP Management SmartSlot Card

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems

Addonics T E C H N O L O G I E S. NAS Adapter. Model: NASU Key Features

Configuring NXT Hardware with Mercury Inside into Doors.NET TM Application Note

Transferring Scans from your Dolphin into Destiny

Studio 5.0 User s Guide

Online Help StruxureWare Data Center Expert

Microsoft Windows Built-In Serial and USB UPS Support

How To Create An Easybelle History Database On A Microsoft Powerbook (Windows)

Chapter 1 Configuring Basic Connectivity

Pharos Control User Guide

Quick Installation Guide DAP Wireless N 300 Access Point & Router

Team Foundation Server 2010, Visual Studio Ultimate 2010, Team Build 2010, & Lab Management Beta 2 Installation Guide

Core Protection for Virtual Machines 1

Sage 200 Web Time & Expenses Guide

Configuring Your Client: Eudora 5.x. Quick Reference

Client Configuration Guide

The FlexiSchools Online Order Management System Installation Guide

Outlook Profile Setup Guide Exchange 2010 Quick Start and Detailed Instructions

CONFIGURATION AND SETUP USER GUIDE AND REFERENCE MANUAL

Trend Micro Incorporated reserves the right to make changes to this document and to the products described herein without notice.

Belkin. Automatic Power Management Software. User s Manual

Software Installation Guide

WEBSERVER OPERATION MANUAL

The PostBase Connectivity Wizard

How To Set Up A Thermal Cycler With Veritilink Remote Management Software

Configuring Your Client: Outlook Express

ViewPower User Manual

RoomWizard Synchronization Software Manual Installation Instructions

User Manual. Onsight Management Suite Version 5.1. Another Innovation by Librestream

Quick Installation and Setup for WinPower Software

CentreWare Internet Services Setup and User Guide. Version 2.0

1.6 HOW-TO GUIDELINES

The FlexiSchools Online Order Management System Installation Guide

Installation Guide. Research Computing Team V1.9 RESTRICTED

Overview of ServerView Windows Agent This chapter explains overview of ServerView Windows Agent, and system requirements.

Software Installation Requirements

Steltronic Focus. Main Desk Internet connection

SIP Proxy Server. Administrator Installation and Configuration Guide. V2.31b. 09SIPXM.SY2.31b.EN3

TANDBERG MANAGEMENT SUITE 10.0

CMP-102U. Quick Installation Guide


Operating Instructions

Quick Scan Features Setup Guide. Scan to Setup. See also: System Administration Guide: Contains details about setup.

User s Manual. Management Software for ATS

Remote Monitoring Service - Setup Guide for InfraStruXure Central and StruxureWare 1 5

MultiSite Manager. User Guide

Trend Micro Encryption Gateway 5

User s Manual. Management Software for Uninterruptible Power Supply Systems

How To Use 1Bay 1Bay From Awn.Net On A Pc Or Mac Or Ipad (For Pc Or Ipa) With A Network Box (For Mac) With An Ipad Or Ipod (For Ipad) With The

How To Set Up Power Supply On Windows (Windows) With Powerup (Windows 8) On Windows 7.1) On A Pc Or Windows 8 (Windows 7) On An Ipad Or Ipad (Windows Xp

BUSINESS CLASS POP3 END USER GUIDE TIME WARNER CABLE BUSINESS SERVICES VERSION 1.0, RELEASE 1.2

Using ESXi with PowerChute Business Edition

Installation Guide for WebSphere Application Server (WAS) and its Fix Packs on AIX V5.3L

F-SECURE MESSAGING SECURITY GATEWAY

Professional Mailbox Software Setup Guide

Transcription:

1. Installing and configuring APC UPS Management 1.1. Objectives and Overview In this lab, you will learn how to install and configure the APC UPS power management suite and the Web/SNMP Management Card. The hardware used in this exercise is a typical UPS configuration in many small to small/medium sized business environments. It reflects the customer s need for high availability at a reasonable cost and low complexity. The lab encompasses: Small environment / serial connection o Installation of PowerChute Business Edition (PCBE) for managing a PRIMERGY server via serial port. o Program PowerChute for a maximum runtime shutdown strategy. Medium sized environment / LAN connection o Configuring and accessing the Web/SNMP Management Card (WSMC) which is included in all rack models. o Installation and configuration of PowerChute Network Shutdown (PCNS) and integration with the WSMC. o Setting notification options for broadcasts and SMTP e-mail. o Explore the WSMC

1.2. Requirements and Pre-requisites An APC UPS One WSMC installed in the SmartSlot and configured with an IP address and a user with administrative privileges. Username: apc, password: apc. A Windows PC with a NIC and a serial port. The NIC must have a link signal to enable the network interface and TCP/IP. Recommended: Current service pack installed. The WSMC and the PC must connect via LAN. The UPS must be connected via smart signaling serial cable to the PC. A current version of PowerChute Business Edition and PowerChute Network Shutdown. The labs are designed with PowerChute Network Shutdown v2.2.1 for Windows XP/2000/NT and PowerChute Business Edition Basic v 7.0.2 An email client installed on the students computers and configured for mail access to the account serverxx@fsctraining.com on the mail server 192.168.xxx.200. The SMTP mail server 192.168.xxx.200 needs an entry in the DNS server: trainer.fsctraining.com.

1.3. Conventions = This symbol points out hazards that can lead non-functional configurations, data loss, equipment damage or even personal injury; Text = This symbol followed by smaller text highlights important background information and tips; 2.3.4 = These numbers refer to steps that you must carry out in order to continue with the procedure; Italics = Commands, menu items, names of buttons, options, variables, file names and path names; <abc> = Angle brackets are used to enclose variables which are to be replaced by actual values. fixed font = Screen output [Key] = Square brackets represent keys on the keyboard. If capital letters are to be entered explicitly, then the Shift key is shown, e.g. [Shift] - [A] for A. If two keys need to be pressed at the same time, then this is shown by placing a hyphen between the two key symbols.

2. Preparing Steps 2.1. Activating Windows Messenger Service in Windows Server 2003 2.1.1. Log in as administrator. 2.1.2. By default, the messenger service in Windows 2003 is disabled. To be able to send and receive instant network pop up messages, it must be activated. To do this, open the service control manager. 2.1.3. Locate the Messenger service, right click and select properties.

2.1.4. Set the Startup Type to Automatic and press OK. 2.1.5. Right-click Messenger and select start.

2.1.6. This shows that Messenger has started. The automatic setting ensures that it will start automatically at every system reboot. To confirm that the messenger service is running correctly and can reach every point in the network, you can open a command line and type net send <your username> test. If Messenger is running and the network is functioning properly, you will see a pop up saying test.

3. Installation and Configuration of PowerChute Business Edition 3.1. Initiating a PowerChute Business Edition Installation Note: This lab was designed for V7.0.2 Start PowerChute Business Edition setup by either o Inserting the PowerChute CD, or o Executing pcbesetup.exe which has been previously downloaded off the APC website. Recent versions of PowerChute can be downloaded off the APC website at http://www.apcc.com. Chose your country and pick Software and Firmware s from within the Quick Links menu at the bottom left of the page. Then select PowerChute Business Edition Basic v 7.0.2 for Linux, Novell, Solaris or Windows. Click on PowerChute Business Edition v7.0.2 for Windows 2003/XP/NT/2000 and download it after a free registration. PCBE only manages UPS connected via serial port. After starting, you will be welcomed by the installer. Click Install Product to begin.

3.2. Installing PCBE Agents 3.2.1. Select Agent Install PCBE consists of three components. These are: Agent : Manages the serial connection, displays messages and initiates shutdowns. Server : Middle-layer software which configures and manages agents distributed throughout the network. The Server can only be accessed through the Console or a web interface. Console : PowerChute s UI (user interface). 3.2.2. Click Next:

3.2.3. Acknowledge the license agreement with Yes.

3.2.4. Confirm the default installation path with Next. 3.2.5. Any existing windows UPS services are stopped and disabled. 3.2.6. Click No to select your communications port manually. 3.2.7. Select your UPS type and COM port or click Run Auto Detect to define your UPS.

3.2.8. Enter apc both as username and password to protect access to PowerChute. The username and password entered here must be re-entered during all further activities, otherwise there will be no access to the PCBE Server.

3.2.9. The UPS Agent Service is automatically created and configured. 3.2.10. Confirm the completed installation with Finish.

3.2.11. PCBE agent setup is complete.

3.3. Installing PCBE Server 3.3.1. Click the corresponding Install button. 3.3.2. Click Next to continue. 3.3.3. Acknowledge the license agreement with Yes.

3.3.4. Enter the previously defined username and password: apc. The username and password entered here must be re-entered during all further activities, otherwise there will be no access to the PCBE Server. 3.3.5. If a permanent internet connection exists, you may leave the checkbox Automatically check for Updates activated. Click Next.

3.3.6. The settings are updated and the PCBE server service is installed and started. 3.3.7. Acknowledge the completed wizard with Finish.

3.3.8. The PCBE server configuration starts automatically. Click Next when the login has completed. Make sure at least one NIC has a link signal. Otherwise, no connection to the PowerChute service is possible, causing the installation to fail. 3.3.9. Select E-Mail Notification and Broadcast as notification methods, then click Next.

3.3.10. Configure e-mail parameters as shown below. Substitute your server/group number for <XX> and enter the appropriate IP subnet for your classroom. Mail servers may require the sender-address (SMTP User Name) to exist as a mail account on the mail server. If it does not, e- mail notification will fail. 3.3.11. Configure broadcasting options as shown below. Unfortunately, Windows messaging service is not very reliable. To test: open a command line box and type: net send * this is a test. If you do not see a pop-up on your screen within a minute or two, you have a Windows messaging problem which must be solved first.

3.3.12. Click Keep computer on as long as possible to shut down the server when the battery has been drained. You may select a Preserver Battery Power strategy which will actually shut the server down when you pull the plug. This is certainly more fun in class, but will not be the most likely strategy in real life! 3.3.13. Click Next.

3.3.14. Verify the Configuration Summary. 3.3.15. Click Finish.

3.3.16. Pick you OWN manageable server from the list and add it to the Current Device List. In this lab, your server will be called ServerXX, where XX is your group number. 3.3.17. Click Apply. 3.3.18. Wait while agent information is retrieved. 3.3.19. Click Close.

3.3.20. Click Register Later. 3.3.21. PCBE server has been successfully installed.

3.4. Installing PCBE Console 3.4.1. Click the appropriate button next to Console. 3.4.2. Click Next. 3.4.3. Acknowledge the license agreement.

3.4.4. Make sure the check box Launch PowerChute Business Edition Console is set and click Finish to launch the console. 3.4.5. Decline the question to send information to APC by clicking No.

3.4.6. Log in to the console with username: apc and password: apc. The server should be your own (127.0.0.1) 3.4.7. The UPS has been successfully installed. Close the console. The console displays active UPS agents. Status shows the configuration and current operating status. Analysis displays histories of events or voltages. 3.4.8. Pull the mains plug of the UPS and see what happens. Do not forget to replace the mains plug after completing this section.

NOTE: Remove all components again in reverse order before proceeding to the next steps. PowerChute Network Shutdown does not co-exist on the same machine as PCBE.

4. Installation and Configuration of PowerChute Network Shutdown (PCNS) 4.1. Installing PCNS 4.1.1. Start the installation program pcns221win.exe and click Next.

4.1.2. Acknowledge the license agreement with I Agree. 4.1.3. Confirm the default installation path and Select Typical Install.

4.1.4. Enter the IP address of your WSMC. 4.1.5. Confirm the user name and password. Do not change these settings.

4.1.6. Wait until communication has been established and then click Next. 4.1.7. Click No.

4.1.8. Click Finished to complete the installation. PCNS is only accessible via browser. The URL is: http://hostname:3052. If no connection can be established while using Internet Explorer, try de-activating the proxy.

4.2. Configuring PCNS Event Handling The following steps will configure the UPS to Send a notification when it goes on battery (power failure). This allows users ample time to save their work Send another notification when the UPS shuts down the server. This is the last call. Actually shut down the server when the battery is empty. 4.2.1. After opening your web interface at http://localhost:3052, click serverxx Configure Events to open the event configuration matrix. Then click the light-green dot in the line UPS: On Battery and the column Notify Users. You may need to loosen the security settings in Internet Explorer to be able to access these pages.

4.2.2. Set the notification parameters as shown below and click Apply. This notifies all users on the network 5 seconds after a power failure. Configure notification on one PCNS service only. Programming multiple PCNS services will result in a flood of notifications, since each PCNS service notifies independently of each other. 4.2.3. Back in the matrix of step 4.2.1., click the light-green dot at line Runtime: Exceeded and column Notify Users. Set the notification options as shown below. up. This notifies all users on the network that the battery runtime has been used

4.2.4. Back in the matrix of 4.2.1., click the light-green dot at line Runtime: Exceeded and column Shut Down System. 4.2.5. Set the shut down options as shown below. This programs PCNS to initiate a graceful shutdown when the battery runtime has been used up. 4.2.6. This is the resulting event matrix. 4.2.7. Pull the mains plug and see what happens. Do not forget to replace the mains plug after completing this section.

5. Configuring the Web/SNMP Management Card for e-mail notification in a LAN environment PCNS only supports notification via network broadcast. For e-mails to be sent in a LAN environment it is necessary to configure the Web/SNMP Management Card (WSMC). 5.1.1. Open a browser window and connect to your WSMC by entering its IP-Address. Log in using apc as <User Name> and apc as <Password>.

5.1.2. Click through Events Recipients and enter your group s email address in the To Address window as shown. Set all other parameters to match the screenshot and confirm by pressing Apply. Substitute your group number for x in Server0x@fsctraining.com. 5.1.3. Click through Network TCP/IP & DNS to enter the DNS server: 192.168.xxx.200. Confirm the settings with Apply. Then test the DNS lookup by entering the mail server trainer.fsctraining.com in <Query Question> and clicking apply. WSMC requires a DNS lookup to be able to send e-mails.

Entering an IP-address directly will cause the notification to fail. 5.1.4. Now enter the mail server itself by clicking through Network Email and enter the SMTP server s details. Then enter your group s mail address in <From Address>. Note that the number should be adjusted to match your group number. 5.1.5. Click through Events Actions and make sure all checkboxes for Severe, Warning and Informational are set. Confirm by pressing Apply. Informational would not normally be set in a real life environment, since this could cause unnecessary event flooding.

5.1.6. Close the browser window. Pull the mains plug of the UPS and see what happens. Do not forget to replace the mains plug after completing this section.