Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN



Similar documents
Automation System TROVIS 6400 TROVIS 6493 Compact Controller

ACS-30-EU-EMDR-10-MOD

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Digital display DA 48

Actuator for modulating control AME 435

Digital Pressure Measuring Instrument MDR480

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

UM-X Field display for continous level sensors

Speed Control Relays SX2

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

HERZ-Thermal Actuators

Instruction Manual Differential Pressure Transmitter

Non-invasive CLAMP-ON ultrasonic flowmeter for liquids

Contents. Document information

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

W150: Miniature photoelectric switch series with completely integrated electronics

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Technical Data. Dimensions

LUT Luminescence scanners: Seeing what no-one else can

WD-AMX Water Detection Controllers

Short information Parameters are programmed via front-side membrane keypad

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Advantium 2 Plus Alarm

Duct Humidity Transmitter

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

OLI. Oil level indicator

W 36: Mastering complex tasks reliably

Model SRMD Setra Remote Monitoring Display

Operating Instructions for Plastic Flow Meter. Model: KSK

Software and Display instruments

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S , GH Q R0111. ABB i-bus EIB

Digital input modules

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

GAE953 Electrical Alarm Unit 19" with Indicator

RY2 miniature industrial relays

Proportional pressure regulators VPPE

How To Read A Pipe From A Sensor

Inductive sensor NI10-M18-Y1X-H1141

J TB/TW Temperature limiter, temperature monitor

Floodlight Range Installation Guide

Electronic Pressure Switch EDS 300

Cross-beam scanning system to detect slim objects. 100 mm in

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

Air damper actuators

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Plastic tube flowmeters Series PT/PS

Three-phase monitoring relay CM-PFE

DALI RC BASIC SO. Control unit Operating instructions

Thermistor motor protection

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

Electric Rotary Actuator - On/Off or programmable control actuator

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

Digital Keypad Use s Manual

Smile. The All-In-One Heating Controller

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119

Quick Connect. quick - simple - efficient.

T7079A,B Solid State Remote Temperature Controllers

is then retained absolutely without interruption.

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

FIRERAY 2000 Installation Guide

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

Vario-Series Accessories

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Wind Sensor W-RS485 with RS485 Interface

Operating Instructions

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS

Problem / Solution. The problem:

GREISINGER electronic GmbH

BACnet Automation Interface Module (Network Version)

GSM HOME SECURITY SYSTEM

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval.

MINI MCR-SL-R-UI(-SP)

Combi B Alarm box. Mounting instructions

Type Sealing Poles Contacts Rated voltage Model Standard d Flux-tight 4 poles oes 3PST-NO, SPST-NC 24 VDC G7SA-3A1B 3PST-NO, 3PST-NC

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

CompactLogix Power Supplies Specifications

Self-operated Temperature Regulators Temperature Regulator Type 1u

Control- and feedback head for integrated mounting on Robolux valves Type 2036

DS DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

SINEAX U553 Transducer for AC Voltage

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

CONFIGURABLE SAFETY RELAYS

Transcription:

Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003

Application 1 Application The Type 5024-1 Power Supply and Indicator Unit is used to supply power to two-wire transmitters (4 to 20 ma) such as Media 6 devices (Type 5006), Type 6051 Electrical Transmitters for Pressure or CTMd pressure sensors from the AB company and other devices. In addition to displaying current data on the LC display, two floating contacts indicate when adjustable minimum and maximum values are reached. The direction of action of the alarm contacts over relays that open or close when the minimum or maximum value is reached together with the corresponding illumination of an LED is selectable over switches. Technical data Power Supply and Indicator Unit Type 5024-1001 5024-1002 5024-1003 Power supply 230 V, 45 to 60 Hz 115 V, 45 to 60 Hz 24 V, 45 to 60 Hz Power consumption Measuring circuit Transmitter power supply Output Contact rating Approx. 1.8 VA 4 to 20 ma 24 V at 20 ma 2 floating contact alarms, max. 250 V AC/3 A 10 $ with AC voltage and max. 300 Ω resistive load Perm. ambient temperature 0 to 50 C Degree of protection IP 54 The device may only be mounted, started up or serviced by fully trained and qualified personnel, observing the accepted industry codes and practices. In these mounting and operating instructions, the term experienced personnel refers to individuals who are able to evaluate the responsibilities assigned to them as well as recognize potential hazards due to their specialized training, knowledge, and experience as well as their special knowledge of the relevant standards. Proper shipping and appropriate storage are assumed. Note: The device with a CE marking fulfills the requirements of the European Pressure Equipment Directive 97/23/EC as well as the Directive 89/336/EEC. The declaration of conformity can be viewed and downloaded on the Internet at http://www.samson.de. 2 EB 9539

Installation 2Installation Mount the device directly in the control room or to a wall using the supplied mounting clips, nuts and bolts. Refer to the dimensional diagram on page 5 for the distances between holes. 2.1 Electrical connections For electrical installation, you are required to observe the relevant electrotechnical regulations and the accident prevention regulations that apply in the country of use. In Germany, these are the VDE regulations and the accident prevention regulations of the employers liability insurance. 2.1.1 Determining the direction of action for the contact alarms When connecting the relay contacts c, nc and no for A1 and A2 (see Fig. 2 for switching function), the direction of action must be set at the selector switches A1 and A2 (located at the top right-hand corner of the lower board) as follows: Point on switch is visible: When minimum alarm is reached, the relay is energized and the LED is illuminated. Point on switch is not visible: When the maximum alarm is reached, the relay is energized and the LED is illuminated. Connect wires to terminals over the cable glands as illustrated in Fig. 2. + _ Transmitter supply L N PE c nc no c nc no A1 A2 Network Relay contacts Switching function: no c nc c common connection nc normally closed Contact opens when the relay is energized no normally open Contact closes when the relay is energized Fig. 2 Terminal assignment and switching function EB 9539 3

Operation 3Operation 3.1 Positioning the decimal point and selecting label with engineering units A jumper located on the top right-hand corner of the display board can be installed at four different positions, depending on where the decimal point should be positioned. Refer to Fig. 3 for the setting. Select the required multiplication factor and the appropriate engineering units from the supplied adhesive label and stick them on the front cover below the display. 3.2 Setting the display The display can be set in combination with a rheostat of R = 10 kω and an ammeter or, alternatively, a pressure transmitter or differential pressure transmitter that has already been adjusted. An ammeter can be connected to the TEST terminals for the transmitters. 3.2.1 Adjusting zero Required for this adjustment: 2-wire signal from, for example, the transmitter must be 4 ma Turn potentiometer N on the display board until the required initial value appears on the LC display. Decimal point I. X. X. X Without decimal point 4...20mA Direction of action Relay A2 Test ( Δ)p A1 A1 A2 LED ma _ + A1 A2 N SP ma R = 10 kω Switches and potentiometer for switching point of Zero max./min. alarm Initial Fine Span Fig. 3 Display board 4 EB 9539

Operation 3.2.2 Adjusting span: Required for this adjustment: 2-wire signal from, for example, the transmitter must be 20 ma First adjust the rotary switch SP (initial adjuster), then the potentiometer SP (fine adjuster) until the required final value appears on the LC display. 3.3 Setting the contact alarms Set the contact alarms A1 and A2 over the selector switch and potentiometer located at the bottom of the display board (Fig. 3). To set the required switching point, adjust the corresponding selector switch for A1 or A2 to point not visible. The currently adjusted limit value then appears on the LC display. Set the associated potentiometer until the required limit value appears on the display. Reset the selector switch to point visible to display value supplied by the transmitter. Dimensions in mm 122.5 110 90 128 120.5 70 M20x1.5 22 56 EB 9539 5

SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 60314 Frankfurt am Main Germany Phone: +49 69 4009-0 Fax: +49 69 4009-1507 Internet: http://www.samson.de EB 9539 EN S/Z 2007-08