Configuring the HydroRanger 200 to measure open channel flow. Specific parameter setting to configure the following primary measurement devices:



Similar documents
Open Channel Flow Measurement Weirs and Flumes

713 Open Channel Flowmeter and Transmitter. All-in-one package for open channel flow measurement.

Sharp-Crested Weirs for Open Channel Flow Measurement, Course #506. Presented by:

FLOW HUNTER II & XDS 03

Centre d expertise en analyse environnementale du Québec

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly

Flow Measurement Calibration and Measurement

Steven R. McManus Environmental Product Support Teledyne Isco

Flow Like An Egyptian: The Basics of Open channel flow

...Eq(11.6) The energy loss in the jump is dependent on the two depths y 1 and y 2 3 = E =...Eq(11.7)

Experiment (13): Flow channel

O C M III. Open Channel Flow Monitor

6. FLOW MEASUREMENT. A. Evaluation of Permittee's Flow Measurement

Gertrudys B. Adkins, Ph.D. Division of Water Rights 2006

2.0 BASIC CONCEPTS OF OPEN CHANNEL FLOW MEASUREMENT

MJK 713 Open Channel Flowmeter

Module 9: Basics of Pumps and Hydraulics Instructor Guide

FLOW RATE MEASUREMENTS BY FLUMES

PART E WATER AND WASTEWATER SAMPLING. Her Majesty the Queen in Right of the Province of British Columbia 2003 All Rights Reserved

FLOW CONDITIONER DESIGN FOR IMPROVING OPEN CHANNEL FLOW MEASUREMENT ACCURACY FROM A SONTEK ARGONAUT-SW

CE415L Applied Fluid Mechanics Laboratory. Experiment: No. 5 Open Channel Flow Measurements and Grade Lines

The Unique Accelabar Flow Meter

MagneW 3000 PLUS Flowmeter for Open Channel

Open channel flow Basic principle

Mobrey open channel flow measurement systems

HYDRAULICS. H91.8D/C - Computerized Open Surface Tilting Flow Channel - 10, 12.5, 15 and 20 m long

CEE 370 Fall Laboratory #3 Open Channel Flow

FLOW SYSTEM flow measurement system in open channels and non-pressurized pipes

What is the most obvious difference between pipe flow and open channel flow????????????? (in terms of flow conditions and energy situation)

Sanitary Sewer Overflows Leave Telltale Signs in Depth-Velocity Scattergraphs

Sect Solving Equations Using the Zero Product Rule

Open Channel Diffusers

Flow Over Weirs. By John Fuller. Fluid Mechanics Lab. Wednesday(1-345pm) Group member: Abdur Rahaman

Chapter 9. Steady Flow in Open channels

Flow Measurement Options for Pipeline and Open Channel Flow

EVALUATION OF UNSTEADY OPEN CHANNEL FLOW CHARACTERISTICS OVER A CRUMP WEIR

Hydraulic Jumps and Non-uniform Open Channel Flow, Course #507. Presented by: PDH Enterprises, LLC PO Box 942 Morrisville, NC

Understanding the Flo-Dar Flow Measuring System

Superb accuracy in water measurement, Jessica thought. Dune, F. Herbert (1965)

Open Channel Flow. M. Siavashi. School of Mechanical Engineering Iran University of Science and Technology

EXAMPLES (OPEN-CHANNEL FLOW) AUTUMN 2015

Lecture 24 Flumes & Channel Transitions. I. General Characteristics of Flumes. Flumes are often used:

Polynomial Degree and Finite Differences

Chapter2. Installation

Testing Protocol for Differential Pressure Measurement Devices API MPMS Chapter 22.2

Mobrey open channel flow measurement systems

Backwater Rise and Drag Characteristics of Bridge Piers under Subcritical

Open Channel & Partially Filled Pipe Ultrasonic Flow Meters

MATH 100 PRACTICE FINAL EXAM

Exercise (4): Open Channel Flow - Gradually Varied Flow

Solving Quadratic Equations

Practice Tests Answer Keys

Basic Math for the Small Public Water Systems Operator

10.1. Solving Quadratic Equations. Investigation: Rocket Science CONDENSED

Smart Electromagnetic Flowmeter Open channel Flowmeter Detector

Fluid Flow Instrumentation

Broad Crested Weirs. I. Introduction

Tracking the Flow: Meeting the Challenge of Open- Channel Flow Measurement in Municipal Applications

Appendix 4-C. Open Channel Theory

COMPETENCY TEST SAMPLE TEST. A scientific, non-graphing calculator is required for this test. C = pd or. A = pr 2. A = 1 2 bh

Chapter 13 OPEN-CHANNEL FLOW

Area of Parallelograms, Triangles, and Trapezoids (pages )

CHAPTER 3 STORM DRAINAGE SYSTEMS

PIPELINE INSPECTION UTILIZING ULTRASOUND TECHNOLOGY: ON THE ISSUE OF RESOLUTION By, M. Beller, NDT Systems & Services AG, Stutensee, Germany

Index-Velocity Rating Development for Rapidly Changing Flows in an Irrigation Canal Using Broadband StreamPro ADCP and ChannelMaster H-ADCP

Equipment for Engineering Education

Peeling the Onion of Meter Accuracy Two Steps to Evaluating Flow Meter Data

Lecture 25 Design Example for a Channel Transition. I. Introduction

Open channel & partially filled pipe Ultrasonic flow meters

2.3 Maximum and Minimum Applications

Trimble CFX-750 Display with the Yield Monitoring System

PNEUMATIC CONTROLS Dual Duct Sequence Descriptions

SEMICONDUCTOR TECHNICAL DATA

Quick Reference ebook

Characteristics of the Four Main Geometrical Figures

Laminar and Turbulent flow. Flow Sensors. Reynolds Number. Thermal flow Sensor. Flow and Flow rate. R = Mass Flow controllers

Hydraulics Prof. A. K. Sarma Department of Civil Engineering Indian Institute of Technology, Guwahati. Module No. # 02 Uniform Flow Lecture No.

7.2 Quadratic Equations

Emergency Spillways (Sediment basins)

FREE FALL. Introduction. Reference Young and Freedman, University Physics, 12 th Edition: Chapter 2, section 2.5

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

Theory overview of flow measurement using differential pressure devices based on ISO-5167 standard.

CHAPTER 8, GEOMETRY. 4. A circular cylinder has a circumference of 33 in. Use 22 as the approximate value of π and find the radius of this cylinder.

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

Advanced Differential Pressure Flowmeter Technology V-CONE FLOW METER TECHNICAL BRIEF

Storm Drainage Systems

Expression. Variable Equation Polynomial Monomial Add. Area. Volume Surface Space Length Width. Probability. Chance Random Likely Possibility Odds

PORTABLE FLOW METER KITS TDS-100H

OPEN-CHANNEL FLOW. Free surface. P atm

6.3 FACTORING ax 2 bx c WITH a 1

10 7, x + 30x + 36 SOLUTION: 8-9 Perfect Squares. The first term is not a perfect square. So, 6x + 30x + 36 is not a perfect square trinomial.

Acceleration levels of dropped objects

F1 Fuel Tank Surging; Model Validation

2O-1 Channel Types and Structures

PREMIUM CLEAN ROOM MONITOR MODELS 8630-CRM-S 8630-CRM-P

VOLUME of Rectangular Prisms Volume is the measure of occupied by a solid region.

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

1. Kyle stacks 30 sheets of paper as shown to the right. Each sheet weighs about 5 g. How can you find the weight of the whole stack?

Design Charts for Open-Channel Flow HDS 3 August 1961

Transcription:

Flow Application Configuration AG040308 Configuring the HydroRanger 200 to measure open channel flow Objective: Specific parameter setting to configure the following primary measurement devices: exponential devices Universal Curved Flow Calculation Palmer-Bowlus Flume H-Flume BS 3680/ISO 4359 Rectangular Flume BS 3680/ISO 1438/1 Thin Plate V-Notch Weir Equipment: Universal Linear Flow Calculation HydroRanger 200, transducer, IR Hand Held Programmer or Dolphin Plus software, and primary measurement device. While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied. Overview: This application guide is an addition to the instruction manual. Please review manual to ensure you are familiar with configuring the HydroRanger 200 using the IR Hand Held Programmer or the Dolphin Plus software tool. Setting up the Common Parameters These parameters are configured for all the open channel flow measuring applications supported by the HydroRanger 200. Parameter Parameter Index* Value Parameter and Value Definition ** P001 G 6 Selects Open Channel Flow measurement. P002 G 1 Sets measured material to liquid. P003 G 2 Sets maximum processing speed, or speed of response, to medium. P004 G 102 (example) Selects transducer (e.g. 102 = XPS 10) connected to HydroRanger 200. P005 G 1 (example) Sets units for head measurement (e.g. 1 = meters). P006 G Empty Distance Sets the distance from zero point of measurement (many times bottom of the weir or channel) to the sensor surface. Head is measured with reference to this zero point P007 G Span of Head measurement Sets the range of head measurement. Often equal to the maximum head. P801 G Range Extension Permits the liquid level to go below the zero point to the amount set here without indicating an LOE condition (pre-set is 20% of span). * G means global. If f you have dual channel unit then the index is either 1 or 2. For both, select 00. ** Here we have chosen one value. Other choices can be selected from the manual as needed. Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225, Peterborough, ON Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 www.siemens-milltronics.com Email: techpubs@siemens-milltronics.com

Selecting the Primary Measuring Device (P600) The HydroRanger 200 supports the following primary measuring devices to calculate the flow rate based on either the Absolute method or Ratiometric method. The design standards of these devices are programmed in the HydroRanger 200, and it applies the correct standard formula to calculate the flow. If you do not have a primary device, or your primary devices are not included in this list, selecting Universal Linear Flow Calculation or Universal Curved Flow Calculation enables the HydroRanger 200 to calculate the flow rate based on Ratiometric method. Parameter Parameter Index Value P600 G (dual channel 1 or 2, if both enter 00) Choose from 0 through to 7 Select one value from the following list of primary measuring devices and methods per channel application. Value Description of Selected Value Flow Calculation Method 0 Flow calculation is off and no flow rate or total flow will be calculated None 1 Exponential devices Ratiometric 2 Palmer-Bowlus Flume Ratiometric 3 H-Flume Ratiometric 4 Universal Linear Flow Calculation Ratiometric 5 Universal Curved Flow Calculation Ratiometric 6 BS-3680/ISO 4359 Rectangular Flume Absolute 7 BS-3680/ISO 1438/1 Thin Plate V-notch Weir Absolute Configuring for the Selected Measurement Devices The following sections present the calculations required to set the parameter values necessary to configure the applications according to the measuring device. Section 1.0 Exponential Device (P600 = 1) Single exponent devices supported by HydroRanger 200: Standard Weirs Flumes Other Parshall Leopold Lagco Cut Throat V-notch or triangular Rectangular or Suppressed Trapezoidal or Cipolleti any other single exponent primary measuring device, whose exponent value is known. HydroRanger 200 and Flow Configuration AG040308 2 of 10

Section 1.1 Exponential Device Flow Calculation Equation HydroRanger 200 calculates flow rate () based on Ratiometric calculation method using the following exponential equation: = max (H/H max ) X max H max x H know the measurement units (liters/sec. or gallons/min. etc.). Maximum flow (at maximum head H max ) as configured in P604. Its value is user provided, and is shown as a standalone number with no units indicated. User must know measurement units used. For example, if maximum flow is 1000 LPS then P604 = 1000 and P606 = seconds Maximum Head H max as configured in P603. Its value is provided by the user. Generally the same value as span configured in P007. The units are defined in P005. Exponent as configured in P601. Its value is provided by the user. If the value is taken from the HydroRanger 200 manual, it should be verified by the user or with the manufacturer documentation. Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. Section 1.2 Exponential Device Flow Configuration Table Set parameters P601, P603, P604, and P606 to calculated values. Parameter # Description Configuration Status P600 Set to 1 (exponential device) Must be configured. P601 Enter the value of exponent x Must be configured. P603 Enter the value of H max. Must be configured. P604 Enter the value of max. Must be configured. P606 Time units Must be configured. P605 Zero Head Off-set Optional, configure only when the actual zero is above channel bottom. P607 Flow rate decimal Optional, configured to display the flow rate (). Factory set to 2. P620 Low flow cut-off Optional, set to avoid totalizing at flows below this set level. P621 Auto zero head calibration Optional, configure only if head displayed has constant off-set. HydroRanger 200 and Flow Configuration AG040308 3 of 10

Section 2.0 Palmer-Bowlus Flume (P600 = 2) Section 2.1 Palmer-Bowlus Flume Flow Calculation Equation HydroRanger 200 calculates flow rate () based on Ratiometric calculation method using the following equation: = max x f(h/ H max )/f(h max / D) max H max H D Flow rate calculated and displayed by HydroRanger 200. The units will not be displayed and user must know the measurement units used (liters/sec. or gallons/min. etc.). Maximum flow (at maximum head H max ) as configured in P604. Its value is user provided, and is shown as a standalone number with no units indicated. User must know measurement units used. For example, if maximum flow is 1000 LPS then P604 = 1000 and P606 = seconds Maximum Head H max as configured in P603. Its value is provided by the user. Generally the same value as span configured in P007. The units are defined in P005. Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. Flume width as configured in P602 in the units defined in P005. This Information will be available from the user or by referring to the flume manufacturer s published discharge tables (e.g. for 30 Palmer Bowlus Flume from Plasti-Fab set P602 to 30 and P005 to inches). Section 2.2 Palmer-Bowlus Flume Configuration Table P600 Set to 2 (Palmer-Bowlus Flume). Must be configured. P602 Enter the value D, the listed flume width. Must be configured. P603 Enter the value of H max. Must be configured. P604 Enter the value of max. Must be configured. P605 Zero Head Off-set. The flume is installed inside the Must be configured. pipe and its zero reference is above the zero reference of the pipe, where transducer monitors the head. P606 Time units Must be configured. P607 Flow rate decimal Optional, configured to display the flow rate (). Factory set to 2. P620 Low flow cut-off Optional, to avoid totalizing at flows below this set level. P621 Auto zero head calibration Optional, configured if displayed head has constant off-set. HydroRanger 200 and Flow Configuration AG040308 4 of 10

Section 3.0: H-Flume (P600) Section 3.1 H-Flume Flow Rate Calculation Equation HydroRanger 200 calculates flow rate () based on Ratiometric calculation method using the following equation: = max x f(h/ H max )/f(h max / D) max H max H D know the measurement units used (liters/sec. or gallons/min. etc.). Maximum flow (at maximum head H max ) as configured in P604. Its value is user provided, and is shown as a standalone number with no units indicated. User must know measurement units used. For example, if maximum flow is 1000 LPS then P604 = 1000 and P606 = seconds Maximum Head H max as configured in P603. Its value is provided by the user. Generally the same value as span configured in P007. The units are defined in P005. Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. Flume height as configured in P602 in the units defined in P005. This Information will be available from the user or by referring to the flume manufacturer s published discharge tables (e.g. for 1.5 ft. H-Flume set P602 to 1.5 and P005 to feet). Section 3.2 H-Flume Configuration Table P600 Set to 3 (H-Flume device) Must be configured. P602 Enter the value D, the maximum height for the flume. Must be configured. P603 Enter the value of H max. Must be configured. P604 Enter the value of max. Must be configured. P605 Zero Head Off-set Configured only when the actual zero is above channel zero. P606 Time units. Must be configured. P607 Flow rate decimal Optional, configured to display the flow rate (). Factory set to 2. P620 Low flow cut-off Optional, to avoid totalizing at flows below this set level. P621 Auto zero head calibration Optional, configured if displayed head has constant off-set. HydroRanger 200 and Flow Configuration AG040308 5 of 10

Section 4.0 Universal Linear Flow Calculation (P600 = 4) The HydroRanger 200 uses polynomial function routines to generate a linear curve fitting between the discrete data points (also called break points) entered by the user. A maximum of 32 data points each for head and corresponding flow discharge in the secondary indices of P610 (Head breakpoints) and P611 (Flow breakpoints) can be defined. With maximum head value defined in P603 and corresponding maximum flow value defined in P604, a total of 33 discrete points are available to the HydroRanger 200 for flow rate calculation. Use as many data points as possible where flow variations are maximum for increased accuracy. Section 4.1 Universal Linear Flow Calculation Equation The HydroRanger 200 calculates flow rate () based on Ratiometric calculation method using the following equation: = max x f(h)/f(h max ) max H max H f(h) know the measurement units used (liters/sec. or gallons/min. etc.). Maximum flow (at maximum head H max ) as configured in P604. Its value is user provided, and is shown as a standalone number with no units indicated. User must know measurement units used. For example, if maximum flow is 1000 LPS then P604 = 1000 and P606 = seconds. Maximum Head H max as configured in P603. Its value is provided by the user. Generally the same value as span configured in P007. The units are defined in P005. Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. Calculated by HydroRanger 200 using polynomial function. Section 4.2 Universal Linear Flow Calculation Configuration Table P600 Set to 4 (universal linear flow calculation) Must be configured. P603 Enter the value of H max. Must be configured. P604 Enter the value of max. Must be configured. P606 Time units Must be configured. P610 (Secondary Indices 1 32 max) P611 (Secondary Indices 1 32 max) Sequentially enter from lowest head value in break point 1 (generally 0) and gradually increase up to maximum 32 head break points. The units are as set in P005. Sequentially enter corresponding flow values for above head break points. Start from lowest flow value in break point 1 (generally 0) and gradually increase up to maximum 32 flow break points. The time units are as set in P606. Must be configured. Must be configured. P605 Zero head off-set Optional, configure only when the actual zero is above channel zero. P607 Flow rate decimal Optional, configured to display the flow rate (). Factory set to 2 HydroRanger 200 and Flow Configuration AG040308 6 of 10

P620 Low flow cut-off Optional, to avoid totalizing at flows below this set level P621 Auto zero head calibration Optional, configured if displayed head has constant off-set Section 5.0 Universal Curved Flow Calculation (P600 = 5) The HydroRanger calculates the flow rate using the same method as the linear flow calculations. It differs by applying a curved fitting between the discrete points. Section 5.1 Universal Curved Flow Calculation Equation The HydroRanger 200 calculates flow rate () based on Ratiometric calculation method using the following equation: = max x f(h)/f(h max ) max H max H f(h) know the measurement units used (liters/sec. or gallons/min. etc.). Maximum flow (at maximum head H max ) as configured in P604. Its value is user provided, and is shown as a standalone number with no units indicated. User must know measurement units used. For example, if maximum flow is 1000 LPS then P604 = 1000 and P606 = seconds. Maximum Head H max as configured in P603. Its value is provided by the user. Generally the same value as span configured in P007. The units are defined in P005. Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. Calculated by HydroRanger 200 using polynomial function Section 5.2 Universal Curved Flow Calculation Configuration Table P600 Set to 5 (universal curved flow calculation) Must be configured. P603 Enter the value of H max. Must be configured. P604 Enter the value of max. Must be configured. P606 Time units Must be configured. P610 (Secondary Indices 1 32 max) P611 (Secondary Indices 1 32 max) Enter sequentially from lowest head value in break point 1 (generally 0) and gradually increasing up to maximum 32 head break points. The units are as set in P005. Sequentially enter corresponding flow values for above head break points starting form lowest flow value in break point 1 (generally 0) and gradually increasing up to maximum 32 flow break points. The time units are as set in P606. Must be configured. Must be configured. P605 Zero Head Off-set Configured only when the actual zero is above channel zero P607 Flow rate decimal Optional, configured to display the HydroRanger 200 and Flow Configuration AG040308 7 of 10

flow rate (). Factory set to 2 P620 Low flow cut-off Optional, to avoid totalizing at flows below this set level P621 Auto zero head calibration Optional, configured if displayed head has constant off-set Section 6.0 BS-3680/ISO 4359 Rectangular Flume (P600 = 6) For flowrate calculation, this method requires only the physical dimensions of the flume: B b p L Approach channel width Throat width Hump height Throat length Section 6.1 BS-3680/ISO 4359 Rectangular Flume Flow Calculation Equation The HydroRanger 200 calculates flow rate () based on the Absolute calculation method confirming to BS 3680 Part 4C standard for Rectangular flumes and uses the following equation: = (2/3) 1.5 x (g) 0.5 x Cv x Cs x Cd x B x (h) 1.5 know the measurement units used (liters/sec. or gallons/min. etc.). g Acceleration due to gravity B Throat width h Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. C v Velocity coefficient calculated by HydroRanger 200 C s Shape coefficient (= 1 here) C d Discharge coefficient calculated by HydroRanger 200 HydroRanger 200 and Flow Configuration AG040308 8 of 10

Section 6.1 BS-3680/ISO 4359 Rectangular Flume Flow Calculation Table Parameter # Description Priority Configuration Priority P600 Set to 6 (BS 3680/ISO 4359 Rectangular Flume) Must be configured. P602 = (1 6) Enter the values of B, b, p & L in indices 1 to 4 respectively. In Must be configured. indices 5 and 6 you can view calculated values of C v and C d respectively P605 Zero Head Off-set Must be configured due to hump height of the flume. P608 Flow rate units Must be configured. P607 Flow rate decimal is configured. Optional, configured to display the flow rate (). Factory set to 2. P620 Low flow cut-off (Its optional), to avoid totalizing at flows below this set level. Optional, to avoid totalizing at flows below this set level. P621 Auto zero head calibration (its optional), configured if head displayed has constant off-set. Optional, configured if displayed head has constant off-set. Section 7.0 BS-3680/ISO 1438 Thin plate V notch (P600 = 7) To calculate the flow rate this method requires only the angle of the weir notch () in degrees. Section 7.1 BS-3680/ISO 1438 Thin plate V Notch Flow Calculation The HydroRanger 200 calculates flow rate () based on Absolute calculation method confirming to BS 3680 Part 4A standard for thin plate weirs using the following equation: = C e x (8/15) x tan(/2) x (2g) 0.5 x (h) 2.5 know the measurement units used (liters/sec. or gallons/min. etc.). Weir notch angle in degrees g Acceleration due to gravity C e Discharge coefficient and is a function of weir notch angle. h Head measured by the ultrasonic head, or any other level measuring device, mounted upstream from the open channel measuring device. IMPORTANT: set in the same units selected in P005. HydroRanger 200 and Flow Configuration AG040308 9 of 10

Section 7.1 BS3680/ISO 1438/1 V Notch Weir Configuration Table Parameter number Description to explain the value Configuration Priority P600 Set to 7 (BS 3680/ISO 1438/1 V Notch Weir) Must be configured. P602 = (1 & 2) Enter the values of in degrees in index 1. In Must be configured. index 2, view the value of discharge coefficient C e P603 Enter the value of maximum head in unit as set in Must be configured. P005. P605 Zero Head Off-set Must be configured because the zero of the weir is above the channel zero. P608 Flow rate units Must be configured. P607 Flow rate decimal Optional, configured to display the flow rate (). Factory set to 2. P620 Low flow cut-off Optional, to avoid totalizing at flows below this set level. P621 Auto zero head calibration Optional, configured if displayed head has constant off-set. Note: Both Primary devices BS 3680 / ISO 4359 Rectangular Flume and the BS 3680 / ISO 1438/1 Thin Plate V notch weir can also be configured for Ratiometric calculation in case the flow rate units are not supported in P608. HydroRanger 200 and Flow Configuration AG040308 10 of 10