Inverter / Charger Installation General Operations and AC and DC Connections



Similar documents
HM-W536 Install Guide

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction

4KVA/5KVA Parallel Installation Guide

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Automatic management of two different energy sources

Qualitative Analysis of Power Distribution Configurations for Data Centers

Contractors Guide Central Inverter System Installation

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

BB800 Off-Grid Solar System

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Current Transformer (CT) Selection Guide

Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.

Ontario Electrical Safety Code 25 th Edition/ 2012

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

ESP PANELS TM & SYSTEM COMPONENTS. Instruction and connection manual

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

INSTALLATION & SERVICE MANUAL. Display Panel

User Manual 1K/2K/3K Online UPS

Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

YSmart Technology Co.,Ltd

Automatic start of a generator

City of Riverside Building & Safety Division Phone: (951)

12 Volt 30 Amp Digital Solar Charge Controller

Reverse-feed applications for circuit breakers

INSTALLATION MANUAL. SAILOR 5080 AC Power Supply

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Transfer Switch 30 Amps STS-30. Manual. Please read this manual before operating your transfer switch

User s Manual Before using the inverter, you need to read and save the safety instructions.

USER MANUAL Online UPS 6K/10K RACK

Anti-blackout system for grid connected solar installations (Solsafe concept)

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz

Understanding Emergency Power Off (EPO)

FIT TIER 2 Application

PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw

MCR1900 Media Converter 19-Slot Chassis

Achieving the impossible

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

USER MANUAL Online UPS 1K/2K/3K Rack

OWNER'S MANUAL. Model CUL AC Power Inverter/Charger System OM/A96283 REV. A

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

10000HXL31/15000HXL31/20000HXL31

Three-Phase Electric Power Distribution for Computer Data Centers

Charge Regulator SCR 12 Marine

Specification Requirements DBL 700MX and 1000MX Series UPS

User Manual of Grid Tie Inverter with Limiter

Photovoltaic Solar Energy Unit EESFB

70-Series CAN Power Management System

Paralleling Switchgear

Manual. Solar Fountain Mobile Phone Charger

SWITCHGEAR. EGP Switchgear

TROUBLESHOOTING PRELIMINARY

USER MANUAL Online UPS 1K/2K/3K

TruPower-Portable-500W. Solar Starter kit

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

UPS Applications and VRLA Battery Sizing

FW-X240 AUTO TRANSFORMER Installation Manual

Home Solar Kit Owner s Manual. Model: HS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

MIDNITE SOLAR AND SOLAR WASHINGTON

CURRENT TRANSFORMERS INSTALLATION GUIDE

Unified requirements for systems with voltages above 1 kv up to 15 kv

EC450 Power Control System

Battery Power Inverters

MidNite Solar E-Panels Explained

Parallel Redundant Uninterruptible Power Supply

Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A.

Power Distribution Considerations for Data Center Racks

Quick Start Guide for High Voltage Solar Inverter DC-AC Board EVM. Version 1.3

MAJORSINE Power Inverter

Fronius IG Plus. The next generation grid-connected PV inverter

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

Installation Instructions for Alarm Module Kit A043F059

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Quick Connect. quick - simple - efficient.

County of Riverside Building and Safety Department

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

Transcription:

Inverter / Charger Installation General Operations and AC and DC Connections

The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better if we pay attention to the other practices that make a good, reliable installation.

Elements of the Inverter / Charger

Elements of the Inverter / Charger DC to AC Inverter; AC to DC Battery Charger; Transfer Switch between using AC Incoming Power or Battery Power; Transfer Switch to choose between two different AC Sources; Relays to perform a variety of user selected functions; and Computer with LCD screen and user input for customizing most of the variables.

Applicability This presentation is based on the Xantrex Model SW inverter, observed most frequently during field visits, and is applicable to models SW 4048 and SW 5548, which were most prevalent. With minor variations, this information can be applied to Outback Power equipment and other manufacturers equipment.

Modes of Operation: AC IN Operational The SW can be connected into an electrical scheme in many different ways. However, some common elements remain unchanged from installation to installation. The over-riding purpose of the SW is to provide continuous power to the loads (AC OUT). If there is power (with the proper characteristics) at the AC IN terminals, then the equipment will utilize this power to: Power the Loads (AC OUT); and Charge the Batteries through the built-in Battery Charger. The following diagram shows the operation and power flow when there is proper power supply at the AC IN terminals:

Modes of Operation: AC IN Operational

Operation: When AC IN Power is lost When power is lost to AC IN, the on-board computer switches the transfer switch so that the AC OUT loads are fed from the battery through the DC to AC Inverter, and the inverter is turned on. This happens nearly instantaneously. When this situation occurs, the entire load is powered by the battery bank. Of course, this can not go on forever, and when the battery bank reaches a programmed low state of charge (depicted by low voltage) the system turns off. (Alarms can be installed to warn operators of impending cut-out, see section 10.2)

Modes of Operation: AC IN Operational

AC IN 1 and AC IN 2 The SW model inverter/charger includes provisions for two AC Inputs. Field visits did not reveal any field application where both inputs were used. In many cases, both inputs will not be needed, but there are many applications where they would be useful. The basic system diagram changes only at the AC IN provisions:

AC IN 1 and AC IN 2

Connections to the Real World The SW equipment is strictly the core equipment necessary to monitor and switch power sources to feed the given load. In order to become part of the entire wiring system, it is essential to use proper wire sizes, and the proper fusing and disconnecting means to (a) protect the wiring, (b) protect the equipment, and (c) protect people. In many cases, when improper auxiliary equipment is used (or not used at all) not only is the result unsafe, but it also results in improper operation, battery failure and un-powered loads. These problems can be avoided by following some guidelines on connecting the SW equipment to the rest of the electrical system. In the next section, the manual will discuss AC OUT connections, AC IN connections, and finally DC and battery connections.

Connections to the Real World

AC OUT Connections All of the AC terminal blocks inside the SW AC box (on the left hand side of the unit) will accept up to #6 AWG conductors (16mm2). It is advised that this #6, 10mm2, or 16mm2 wire be used. The AC OUT terminals should be supplying only a predetermined set of loads. These loads should have been the basis of the selection of the size of the battery bank and the size of the inverter. These loads should be fed from a separate, dedicated circuit breaker panelboard connected to the AC OUT terminals. The conductors carrying the load current from the SW to this panelboard should land first in either a fused disconnect switch, or a main circuit breaker on the panelboard.

AC OUT Connections

AC IN Connections There are several options for AC IN connections: AC IN from a grid supply only AC IN from a generator supply only AC IN from both a grid supply and a generator supply AC IN from a combined grid / generator supply. The following section discusses each option.

AC IN 1 Grid Supply

AC IN 1 Grid Supply Even though the output of the inverter is limited to either 33 or 46 amps, it is important that the 60 amp circuit breaker is used and conductors feed the AC IN terminals. This is because when the grid power is on, it is performing two functions: First it is feeding the loads, and secondly it is powering the battery charger. The battery charger could draw up to as much as 30 amps depending on how the settings are programmed. If it is not possible to provide a 60 amp supply to the ACIN 1 terminals of the SW, then certain settings MUST be changed in the programming, and the design needs to be studied to be sure that the batteries will receive enough charging power. See the discussion under Programming for more information on this subject.

AC IN 1 Grid Supply

AC IN 2 - Generator

AC IN 2 - Generator The amount of power that can be drawn from the generator needs to be calculated (based on the size of the generator and other loads the generator may have to supply). If, for example, a 6KW generator is dedicated to this inverter, then the maximum power that can be obtained from the 6KW generator (if it is single phase) is 6000w / 120V or 50Amps. In this case, a 40 amp breaker to feed the SW and a therefore, 40A wire will be sufficient. If the generator is designed to support other loads as well, then how much of its power can be dedicated to the SW equipment needs to be determined and the breaker and conductors needs to be sized accordingly. The proper programming needs to be completed to match this value. The equipment needs to be programmed so that it does not try to pull any more power than the circuit breaker feeding it (or any more power than the generator feeding it.). This would trip the breaker and/or overload the generator. See the section on Programming for more information.

AC IN from both Generator and Grid

AC IN from both Generator and Grid When both grid power supply and generator power supply are available, the above is the preferred method for connecting to the system, particularly when the generator size requires a smaller circuit breaker and feeder that would be allowed by the grid input power. However, in most cases with grid and generator available, the two sources are combined in a transfer switch, with one set of conductors going into the SW, as shown below.

AC IN from both Generator and Grid

AC IN from both Generator and Grid Discuss pros and cons of the combined Generator / Grid AC IN wiring versus the separate Generator and Grid AC wiring.

AC IN and OUT Connections Summary of AC IN and AC OUT Connections There are several different configurations possible for the AC IN and AC OUT connections. Key factors to consider in planning the installation are: Sizing of the conductors for the greatest possible current that they may experience; Using dedicated, separate, AC OUT circuit breaker panelboards for the loads decided to be powered by the SW; Bringing separate AC IN 1 Grid conductors and AC IN 2 Gen conductors to the SW equipment panel; and Providing disconnecting means for the ACIN 1, AC IN 2, and AC OUT conductors to be able to isolate the SW equipment from any power wires. Additionally, the SW Cabinet should be installed in a readily accessible location (not in a storeroom), where ventilation from left to right is unobstructed, to provide adequate cooling.

AC IN and OUT Connections All of things cost money and take added effort, but compare the cost of the electrical work to the cost of the medical equipment we are trying to protect.

DC Connections

DC Connections Discussion topics here will include: Proper DC Cable connections to the SW Cabinet; Overcurrent / Disconnecting means in the DC Input cables; Connecting Strings of Batteries; and Paralleling the Strings of Batteries.

Connecting the DC Cables to the Inverter

Polarity IT IS EXTREMELY IMPORTANT THAT POLARITY IS NOT REVERSED AT THESE TERMINALS. THIS IS ONE OF THE FEW CONDITIONS THAT IS NOT PROTECTED WITH INTERNAL PROTECTION ON THE SW EQUIPMENT. IF BATTERY POWER IS APPLIED AT THESE TERMINALS WITH REVERSE POLARITY, BESIDES PHYSICAL DAMAGE, MOST OF THE INTERNAL POWER TRANSISTORS WILL BE DESTROYED RESULTING IN NON-WARRANTY DAMAGE AND THE UNIT WILL HAVE TO RETURNED FOR EXPENSIVE REPAIRS.

DC Cable from Battery to Inverter

Battery Cable Sizing (use 4/0)

DC Cable from Battery to Inverter Current Limiting Fuses in Positive Cables (4/0) Positive and Negative Cables kept together. DC Circuit Breakers in positive feed to individual inverters. System shown is Outback

Series Connections Sometimes the series connections are made with copper bus bars. These are 2V batteries, in sets of 24 in series

Series Connections More often, series connections are made with cables. These are 12V Batteries in sets of 4 in series

Connecting Batteries

Connecting Batteries

Paralleling Batteries ILSCO common bus terminal blocks for 4/0 cables 4 Strings of 48VDC batteries connected in parallel, and 2 home run cables back to cabinet.

Keep the Battery Cables Together We need to always keep the positive and negative battery cables together, as long as possible. As battery cables are separated by a distance, they have much more inductance than if they are close together. This induction creates an induced current which opposes the applied current. This leads directly to loss of inverter performance and greatly reduced efficiency. With cables separated by 48, the inductance can be 3 times greater than the inductance recognized if the cables are together. The result can be as dramatic as the inverter failing to allow certain loads to start, because it can not get the required current to flow in the batteries. This has been seen in cases where installers have done a very neat job in the installation but have grouped all positive cables on one side of a wall, and the negative cables on the other side.

Sum-UP We have Covered Elements of the Inverter / Battery System Connections to the Real World AC OUT Connections AC IN Connections DC Connections Still to come: Programming Operations and Maintenance Troubleshooting