2012 Operating Room Design Manual



Similar documents
Essam E. Khalil

Ventilation Standard For Health Care Facilities

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Operating Room Manual

Radford University. Indoor Air Quality Management Plan

Infection Control In Hospitals

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

HEALTH CARE GUIDELINES AND STANDARDS

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health

Energy Efficiency in Industrial HVAC Systems

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG March 24, 2010

CHAPTER 4 VENTILATION

applications laminar flow Laminar Flow Diffusers CRITICAL ENVIRONMENT LAMINAR FLOW: GENERAL

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

Construction Drawings and Terminology for the Infection Prevention Professional. Objectives. Disclaimer

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Molds and mildew are fungi that grow

SPECIAL APPLICATIONS

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Glossary of Heating, Ventilation and Air Conditioning Terms

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality

Answers to Your Questions from the Webinar

Mechanical and Natural Ventilation

HVAC Systems: Overview

Direct Fresh Air Free Cooling of Data Centres

Element D Services Plumbing

Traffic Patterns in the OR: Has it Become a Super Highway?

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

HVAC Checklist - Long Form

NIOSH Interim Recommendations for the Cleaning and Remediation of Flood-Contaminated HVAC Systems: A Guide for Building Owners and Managers

Glossary of HVAC Terms

Indoor Air Quality Issues for Hotels

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

IEQ-15 Air Distribution System

MIOSHA s Tuberculosis Guidelines For Worker Protection from Mycobacterium (Occupational Health Program Directive No. 96-9)

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

Hazardous Drug. Cleanroom. Standards

Using Time-of-Day Scheduling To Save Energy

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

SAM HOUSTON STATE UNIVERSITY

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

ENHANCED LABORATORY HVAC SYSTEM

Veterinary Clinics and Hospitals

Fume Hood Questions and Answers

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS

Risk Assessment: Biosafety Cabinet

Procedures for the Effective Use of Biological Safety Cabinets

1.2 Refrigerant Equipment. General

Basics of HVAC Cleaning

Pool Dehumidification Basics

Environmental Monitoring

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)

Design Options for HVAC Distribution Systems

ASBESTOS SCIENCE TECHNOLOGIES, INC.

Residential HVAC System Sizing

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS

Lesson 36 Selection Of Air Conditioning Systems

ASTACEA4 Inspect complex/central air conditioning systems

MANAGING A STERILE PROCESSING DEPARTMENT IN CRISIS: HOW TO STAY COOL WHEN YOUR SPD GETS TOO HOT

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

ENVIRONMENTAL MONITORING

MECHANICAL SYSTEMS DESIGN. Team

Air distribution effectiveness with stratified air distribution systems

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA.

Laboratory Design & Construction Guidelines

Energy Efficiency HOSPITALITY.

Improving Data Center Energy Efficiency Through Environmental Optimization

Indoor air quality monitoring made easy

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

To provide good indoor air quality

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

The Different Types of Air Conditioning Equipment for IT Environments

Preliminary Final Proposal

GENERAL VENTILATION HSG202

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

Indoor Environmental Quality Management Plan

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

Risk Bulletin. Mold Prevention and Control for Mechanical and HVAC Contractors. XL Group Insurance

Ductless Heat Pumps for Passive Houses

air conditioners how to choose a cooling system

SECTION HVAC AIR-DISTRIBUTION SYSTEM CLEANING

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

Transcription:

CHAPTER 9 ROOM VENTILATION SYSTEMS Lead Author: Kamal Maheshwari, MD, Staff Anesthesiologist, Cleveland Clinic Foundation Checklist 1. Does the ventilation system in your operating room (OR) meet the standards given by NIOSH (National Institute of Occupational Safety and Health), ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers), CDC (Centers for Disease Control and Prevention), and AIA (American Institute of Architects)? 2. Can the temperature be adequately regulated? 3. Can the humidity be adequately regulated? Many regulatory institutions, such as NIOSH, ASHRAE, CDC, and AIA, have developed standards and guidelines for OR ventilation systems. As in any other environment, ventilation in the OR is an important issue. The OR has some special needs, however. The goals of the ventilation system are: 1. Comfort of the patient in the OR 2. Comfort of surgeons and other personnel in the OR 3. Control of the concentration of pollutants: Chemical (anesthetic gases/volatile substances) Physical (particulates/aerosols) 4. Ability to quickly raise or lower the temperature 5. Control of infections (microbiological pollutants) There are various components of ventilation systems in the OR: 1. Ventilation 2. Heating and cooling 3. Humidity control 4. Waste anesthetic gas scavenging (see Chapter 7) Ventilation A ventilation system in the OR can be either a recirculating or non-recirculating system. A recirculating system is one that recirculates some or all of the inside air back to the OR suites or some other part of hospital, whereas in a non-recirculating system, all air brought to the room is conditioned, outside air. When a recirculating system is used, the air return duct should have a high efficiency particulate air (HEPA) filter built into the system. In an OR where inhalational anesthetics are used, there should be separate systems for ventilation, vacuum (patient and 1

surgical suction), and waste anesthetic gas disposal (WAGD). A recirculating ventilation system in the OR can be a problem if a passive WAGD system is in use. In a passive WAGD system, waste anesthetic gas from the anesthesia machine is directed to the room ventilation return duct that removes air from the OR. In a recirculating ventilation system, this waste anesthetic gas will mix with fresh air inflow and be returned to the same room or other areas of the facility. Thus, it is recommended not to use a passive WAGD system in new construction, and if it is used, ventilation should be the non-recirculating type. It is best to have a separate active WAGD system that is independent of both the ventilation and vacuum systems, and gases from the WAGD system need to be exhausted directly to the outside. Infection control is critical in ORs. Studies have demonstrated that most of the causes of wound contamination in the OR are the result of the patient s skin flora and bacteria shed on airborne particles from the OR personnel. 1,2 Room ventilation affects the distribution of these airborne particles in four ways: total ventilation (dilution), air distribution (directional airflow), room pressurization (infiltration barrier), and filtration (contaminant removal). As the air flows of the room increases, the greater the dilutional effect on airborne particles. Balancing this phenomenon is that while increased flow increases the effectiveness of air exchange, resultant turbulent flow increases microbial distribution throughout the room. Low-velocity unidirectional flow minimizes the spread of microbes in the room. Directional flow can be inward, from the outside into the OR (negative pressure), or outward, from the OR to the outside (positive pressure). Negative pressure ventilation is used for highly infective rooms in the hospital (e.g., isolation rooms for tuberculosis patients) and positive pressure ventilation is used for protective environments (e.g., ORs and rooms with immunocompromised patients). Positive-pressure ventilation is used with a minimum differential pressure of 2.5 Kpa between the OR and the corridors. Rarely, if there is highly infective patient in the OR, negative-pressure ventilation might be used (if available). Most hospital ORs are currently designed with HEPA filtration systems to maximize removal of contaminants in the air. Operating room ventilation systems should operate at all times, except during maintenance and conditions requiring shutdown by the building s fire alarm system. During unoccupied hours, air exchange can be reduced as long as positive pressure is maintained in each OR. Complete shutdown of the ventilation system may permit airflow from areas with less clean air into the relatively negative pressure area of the ORs. Air is delivered to each OR from the ceiling, with downward movement toward several exhaust or return ducts near the floor. This design helps provide steady movement of clean air through the breathing and working zones. The AIA has specific guidelines for the location of outside fresh air inlets to minimize contamination from exhaust systems and noxious fumes. Fresh-air intakes (for instance, on the roof) are to be located at least 25 feet (7.62 meters) from exhaust systems and areas where noxious fumes may collect. Plumbing vents may end as close as 10 feet (3.05 meters) to the air intake system. 2

Outdoor-air intakes are to be as high as practical, with their bottoms at least 6 feet (1.83 meters) above ground level or, if on a roof, 3 feet (0.9144 meters) above roof level. Air that could otherwise be recirculated ( relief air ) but is discharged to the outside to maintain building pressure is exempt from this separation requirement. Using computational fluid dynamics analysis, a mathematical technique to comprehensively look at room airflow, Chen et al. showed that a higher air inflow rate and a larger air-inlet area are desirable for contaminant control, but these approaches are detrimental to the thermal comfort of the staff and patient. 3 Similar studies by Memarzadeh and Manning 4 as well as Memarzadeh and Zheng Jiang 5 led the AIA to recommend an air-change rate in an OR of 20 to 25 air changes per hour (ACH) for ceiling heights between 9 feet (2.74 meters) and 12 feet (3.66 meters); a ventilation system providing a single-directional flow regime, with both high- and low-exhaust locations; a face velocity of around 25 to 35 fpm (0.13 to 0.18 m/s) from a nonaspirating diffuser array (i.e., ceiling air inlets), provided that the array size itself is set correctly such that it covers at least the area footprint of the OR table plus a reasonable margin around it; and that if additional diffusers are required, they may be located outside this central-diffuser array. According to the AIA, up to 30% of the central-diffuser array may be allocated to nondiffuser items (e.g., medical gas columns, lights, and equipment booms.) Some controversy exists between engineers and clinicians over the need for laminar airflow ventilation in the OR to further minimize airborne infection. Careful mathematical analyses of airflow suggest laminar airflow is not necessary when the previously noted recommendations are met. Clinical studies are confirmatory. 6,7 Similarly, the use of ultraviolet light to cleanse the room air is no longer recommended. 8 Heating and Air Conditioning Many studies have shown that keeping patients warm during the perioperative period is highly beneficial. Additionally, the comfort of the surgical team should be kept in mind. Recommended temperatures for ORs are between 68 F and 73 F during surgery and between 62 F and 80 F otherwise, and recommendations for the post-anesthesia care unit (PACU) are between 70 F and 75 F. 9 Heating and air conditioning systems must allow the individual room temperature to be raised or lowered rapidly as needed for patient and surgeon comfort. This temperature change must be accomplished without a large overshoot in the desired temperature and can be accomplished with individual reheat coils in each OR. Care in how the room temperature is measured is important because in a very large room, a thermostat controlling the air temperature by measuring the air around a distant wall will not reflect the temperature around the surgical table. Some thought should be given to placing the thermostat in the middle of the room. A move to LED surgical lights, which produce significantly less heat, may make the temperature of the immediate surgical environment easier to control since it will more likely reflect the environment further away from the patient. 3

The use of devices to directly warm the patient also makes the room temperature less important, except when patient cooling is desired. Humidity Control Humidity control is important because decreased humidity may lead to damage in the respiratory tract and loss of body heat through evaporation of sweat. Excessive humidity is also undesirable for patient and staff comfort. Relative humidity should be approximately 30%-60% in most ORs and in the PACU. Today, because of long procedures, multiple-layered gowning, and x-ray protection, many surgeons are requesting lower temperatures in the OR. These lower temperatures affect the moisture content of the air, as cooler air can hold less water vapor. Obtaining specified temperature and humidity conditions can be a difficult, but not impossible, task. If all the factors that affect environmental conditions are taken into consideration, the goal is certainly achievable. Some key points to remember are: 1. Purchase a conditioning system with a tight single-point control thermostat and humidistat. 2. Buy a thermostat and humidistat suitable for OR application; be sure that they are properly positioned and routinely calibrated. 3. Ensure that the system has the capacity to handle the internal heat load and that it has sufficient air-handling capability to promote uniform air temperature and humidity. 4. Be mindful of the influences of heat loads (i.e., heat-generating OR equipment, including anesthetic and surgical equipment as well as patient- and fluid-warming devices) and try to minimize them. 5. Ensure that the system has adequate design capacity for extreme outside temperatures. As an example, many commercial buildings are designed to provide an interior temperature of 78 F with a maximum outside design temperature of 94 F. In other words, the system will provide a maximum of 16 F of cooling. If the outside temperature rises to 108 F, as may happen in some parts of the United States, the inside temperature will be no lower than 92 F. 6. Ensure that the conditioned space and ductwork are well-insulated with an uninterrupted vapor barrier. Scavenging of Waste Gases (see Chapter 7) 4

References 1. Whyte W, Hodgson R, Tinkler J. The importance of airborne bacterial contamination of wounds. J Hospital Infection. 1982; 3:123-135. 2. Edmiston CE, Seabrook GR, Cambria RA, et al. Molecular epidemiology of microbial contamination in the operating room environment: is there a risk for infection. Surgery. 138(4):573-582. 3. Jiang CZ, Moser A. Control of airborne particle concentration and draught risk in an operating room. Indoor Air. 1992; 2:154-167. 4. Memarzadeh F, Manning AP. Comparison of operating room ventilation systems in the protection of the surgical site. ASHRAE Transactions. 2002; 108, pt. 2. 5. Memarzadeh F, Jiang Z. Effect of operation room geometry and ventilation system parameter variations on the protection of the surgical site. IAQ. 2004. 6. Brandt C, Hott U, Sohr D, et al. Operating room ventilation with laminar airflow shows no protective effect on the surgical site infection rate in orthopedics and abdominal surgery. Ann Surg. 2008; 248:695-700. 7. Lipsett PA. Do we really need laminar flow ventilation in the operating room to prevent surgical site infections? Ann Surg. 2008; 248:701-703. 8. Guidelines for Environmental Infection Control in Health-Care Facilities. MMWR. 2003; 52( no.rr-10):13. 9. American Society of Heating, Refrigeration and Air-Conditioning Engineers. 2007 ASHRAE Handbook- HVAC Application. Atlanta, GA: ASHRAE; 2007. 10. Ehrenwerth J. ASA operating room design manual. 1998. 11. American Institute of Architects (AIA). 2006 Guidelines for Design & Construction for Health Care Facilities. Washington, DC: AIA Press; 2006. 12. Dickerman KN, ed. Florida Project Development Manual: A Guide to Planning, Design & Construction of Healthcare Facilities in the State of Florida. Jacksonville, FL: Health Facility Publishers INC; 1993. 13. American Society of Heating, Refrigeration and Air-Conditioning Engineers. HVAC applications. In: 2003 ASHRAE Handbook. Atlanta, GA: ASHRAE; 2003. 14. 15. Centers for Disease Control (CDC). Guidelines for Environmental Infection Control in Health- Care Facilities. Atlanta, GA: CDC; June 6, 2003.Available at: http://www.cdc.gov/mmwr/preview/mmwrhtml/rr5210a1.htm. 16. Ehrenwerth J. Operating room design. ASA Newsletter. 1994(Nov); 58:13-16. 17. Eichhorn JH, Ehrenwerth J. Medical gases: storage and supply. In: Ehrenwerth J, Eisenkraft JB, eds. Anesthesia Equipment: Principles and Applications. St. Louis, MO: Mosby; 1993: 3-26. 18. Azar I, Eisenkraft JB, eds. Anesthesia Equipment: Principles and Applications. St. Louis, MO: Mosby; 1993:114-139. 19. Formal Interpretations Guidelines for Design and Construction of Health Care Facilities, 2010 Edition. Available online at: http://www.fgiguidelines.org/2010guidelines.html. 20. Ventilation systems and thermal conditions in operating rooms. Available at: http://www.aiha.org/aihce06/handouts/c2mazzacane3.pdf 21. Chow TT, Yang XY. Ventilation performance in the operating theatre against airborne infection: numerical study on an ultra-clean system. Journal of Hospital Infection. 2005(Feb); 59(2):138-147. 5

Resources 1. American Institute of Architects. AIA Guidelines for Design and Construction of Health Care Facilities: 2006 Edition. Washington, DC: AIA; 2006. Available at: www.aia.org. 2. American Society of Heating, Refrigeration and Air-Conditioning Engineers. A07 Health Care Facilities (I-P). In: ASHRAE 2007 Handbook HVAC Application. Atlanta, GA: ASHRAE; 2007. Available at: www.ashrae.orgwww.ashrae-elearning.org. 3. American Society of Heating, Refrigeration and Air-Conditioning Engineers. HVAC Design Manual for Hospital and Clinics. Atlanta, GA: ASHRAE; 2003. Available at: www.ashrae.orgwww.ashraeelearning.org. 6