CCTV of Stormwater Systems. Cairns Regional Council. Commentary Guidelines #4037587



Similar documents
Guidelines for closed circuit television (CCTV) inspection of newly constructed sewers

DIVISION 4300 STORM DRAINAGE

SEWER CLEANING, INSPECTION AND ASSESSMENT

CCTV INSPECTION OF SEWER LINES. A. Section Sanitary Gravity Sewer Lines. B. Section Sanitary Gravity Sewer Line Testing

SECTION CLEANING AND CLOSED CIRCUIT TELEVISION (CCTV) INSPECTION OF SEWER PIPE

San Antonio Water System Standard Specifications for Construction ITEM 866 SEWER MAIN TELEVISION INSPECTION

Wastewater Capital Projects Management Standard Construction Specification

REPAIRS TO DAMAGED SEWERS

Section 2100-Trenching and Tunneling

Section 402. STORM SEWERS

CORPORATION OF THE CITY OF BURLINGTON SPECIFICATION INDEX FOR CCTV VIDEO INSPECTION OF PROPOSED STORM SEWERS (SPEC. NO. SS7) 1. Scope of Work SS7-1

SECTION 25 CLOSED CIRCUIT TELEVISION INSPECTION OF SEWER LINES

SECTION 724 PIPE CULVERTS

March 2006 DIVISION 3 - CW 2140-R3 TABLE OF CONTENTS

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

Setting Priorities for Stormwater Infrastructure to Achieve Best Results Using a Risk Analysis

VIDEO INSPECTION AND LASER PROFILING IN FLORIDA. AASHTO SOC Conference Larry Ritchie, FDOT August 14, 2013

SECTION IV - TESTS AND INSPECTIONS PART 1 - GENERAL Testing - General

PRE INSTALLATION MANUAL

San Antonio Water System Standard Specifications for Construction ITEM NO POINT REPAIRS AND OBSTRUCTION REMOVALS

SECTION STORM DRAIN SYSTEM

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

APPENDIX K PIPE INSPECTION

SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO)

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

CCTV PIPE INSPECTION AND EVALUATION RUNWAY 17L-35R

CITY OF COLFAX REQUIREMENTS AND STANDARDS FOR CLOSED CIRCUIT TELEVISION SEWER LATERAL INSPECTIONS

Building over or close to a public sewer

REHABILITATION OF UNDERGROUND SEWER LATERAL PIPES WITH CURED-IN-PLACE-PIPE LINER SECTION 02542

SIDE SEWER CONDITION ASSESSMENT AND REPAIR RECOMMENDATIONS

CCTV INSPECTION OF SEWERS AND STORMWATER DRAINS, TRAINING OF OPERATORS AND MANAGERS, AND THE CONDUIT INSPECTION REPORTING CODE OF AUSTRALIA

ALL YOUR DRAINAGE NEEDS. Tel:

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

3. QUALITY ASSURANCE REQUIREMENTS

FAULTS FOUND IN SEWER PIPES, CAUSES AND REMEDIES

PURCHASE AND ACCEPTANCE OF PRECAST STEEL REINFORCED CONCRETE PIPE UTILISING THE AUSTRALIAN STANDARD, AS

SECTION 810 SEWER LINE CLEANING

Utilizing Remaining Useful Life for Asset Management of Critical Wastewater Assets

Storm Sewer Trenchless Upgrade Alternatives and Recommendations

X Planning X Quality X Maintenance & Operations

Sewer System Inspection: Techniques and Resources. Presented by: Doug Severson

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA (7300 Short Road, Serene Lakes)

Sewer Rehabilitation Design Requirements

Section SEWER PIPE INSTALLATION AND TESTING

Exhibit A. Rules and Regulations for House Connections and Sewer Extensions

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

Estimating Stormwater System Annual Maintenance and Repair Costs - A GIS Approach

PIPE INSPECTION AND REPAIR. Larry Ritchie

MODEL WEB CONTENT FOR CITY SANITARY SEWER DEPARTMENTS

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING

SPR PE Steel Reinforced Liner

We love the drains you hate! A partner you can depend on to deliver dedicated drainage maintenance services, 24 hours a day, 365 days a year

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

ARLINGTON HEIGHTS MUNICIPAL CODE CHAPTER 22 SEWERS

SECTION STORM DRAINAGE TABLE OF CONTENTS

Section 4. Sewer Testing

Premature Storm Drainage System Repairs and Replacement

UNDERGROUND INFRASTRUCTURE SPECIALISTS TABLE OF CONTENTS

SECTION PRECAST CONCRETE UTILITY STRUCTURES

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development

CLEANING, INSPECTION, AND TESTING OF SEWERS

Using Frequent Sewer Inspection to Prioritize Asset Management. May 1, John Schroeder, P.E., BCEE Drew Richards, EI Tim Fallara, P.E.

SANITARY GRAVITY SEWER LINE TESTING. B. Section CCTV Inspection of Gravity Sewer Lines

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

PROVIDING THE SAFE CHOICE FOR UNDERGROUND PIPE RENEWAL, INTEGRITY MANAGEMENT AND ASSET RELIABILITY

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE

SECTION REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

Policy Guidance Notes and Requirements

CITY OF BEVERLY RULES AND REGULATIONS - SEWER SYSTEM TESTING. General

RIPRAP From Massachusetts Erosion and Sediment Control Guidelines for Urban and Suburban Areas

Scheduling Maintenance for Infiltration Basins and Trenches

Session 7: Retrofitted Edge Drains 7.1

STANDARD SPECIFICATIONS SECTION SEWER MAIN AND LATERAL CONNECTION SEALING BY CHEMICAL GROUT

Durability of reinforced concrete pipe the hard facts!

Home Drainage & Causes of Basement Flooding. Water

Final Report. Sacramento County Sanitation District No. 1. Engineering Sustainability of Piping Materials

Transport and Main Roads Specifications MRTS25 Steel Reinforced Precast Concrete Pipes

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

STANDARD OPERATING INSTRUCTION SOI-GVW-198 CCTV Inspection of Sewerage Reticulation Works 1 PURPOSE 2 REFERENCES 3 DEFINITIONS

Waste Collection Systems

SANITARY SEWER SPECIFICATIONS

How To Install An Overhead Sewer

SECTION 1 GENERAL REQUIREMENTS

provided for improvements for each structure during these timeframes. Rehabilitation and Investment Strategies:

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

City of Regina Standard Construction Specification SECTION 1320 SEWERMAIN TESTING

SANITARY SEWER BACKUP. Causes & Prevention

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

Industrial Pipeline Integrity Management & Remote Polyurea Pipe Lining Systems.

BACKUPS! Solving the Problem in a Seattle Neighborhood

Force Main Condition Assessment: New Technologies & Case Studies

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

Sanitary Sewer Smoke Testing

Photographs: Acceptable, Unacceptable, and Unacceptably Repaired Precast Concrete Products

CHAPTER 6 - SANITARY SEWER

Interactive Decision Tree Automates Sewer Rehabilitation Planning

Transcription:

CCTV of Stormwater Systems Cairns Regional Council Commentary Guidelines

Introduction Councils inherit assets through the donated asset process. In doing so, Councils immediately receive assets that are fit for purpose and consequently assume the long term maintenance responsibilities and any potential liability of future failures or deficiencies that occur during the life of the pipe. The high cost, of retroactive repairs or replacement, creates a need for Councils to check the integrity of the pipe and workmanship of the assets being donated. Council seeks to do this by undertaking CCTV Inspections of underground pipe drainage works received by Council as part of the donated assets process. The purpose of this commentary is to provide guidance on the interpretation of CCTV footage and on what Council s expectations are with regard to acceptable defects and unacceptable defects. This document is to be read in conjunction with FNQROC Development Manual Specification S4.26 CCTV Inspection of Stormwater Drainage Systems. Current FNQROC Submission Requirements As part of the project documentation to be provided at the early plan sealing (EPS) 1 or works acceptance stage, the CCTV footage and associated certification or CCTV inspection report 2 are to be submitted to Council. The CCTV inspection report must be prepared in accordance with the requirements of section S4.26 of the FNQROC development manual. Council s acceptance of such must be obtained prior to the issue of acceptance of the Early Plan Seal (EPS) or Works Acceptance (WA) inspections. In order to expedite the acceptance process it is recommended that the Certifying Consultant arrange a joint viewing of the CCTV footage with a Council officer. Both parties can then agree on which items may present issues to be addressed. The Consultant should ensure that their own assessment, including recommendations, has been done prior to any joint viewing with Council. CCTV Requirements The Current FNQROC Development Manual Stipulates that all underground stormwater pipe drainage (between 375mm and 2000mm) must be inspected using CCTV camera on completion of all backfilling and compaction operations. This must be undertaken not more than two (2) weeks prior to the EPS or WA inspections whichever is earlier.) 1 If the CCTV inspection is undertaken as part of the EPS process, Council may request that portions of the stormwater network be reinspected as part of the WA inspection. An example of when the re-inspection of stormwater pipes would be required to be re-inspected by CCTV may include:- - Stormwater pipes which run under trafficable areas (street, access-ways etc.), which may have been exposed to additional compaction works between the EPS inspection and the WA inspection. It is the RPEQ s responsibility to identify any stormwater pipes which may be exposed to further compaction works between EPS/ WA, and Council s responsibility to identify which lengths (if any) need to be reinvestigated. A full CCTV re-inspection of the stormwater network is not expected. The cost of reinspection shall be borne by the applicant. 2 If no defects are identified in the CCTV footage, then the RPEQ may simply certify the works as being in accordance with the requirements of FNQROC and the relevant Australian Standards. However, if defects are identified, a CCTV inspection report is to be provided in accordance with sections S4.26, Acceptance Criteria and Submissions in the Council s FNQROC manual. The recommended method and extent of any remediation works required are to be identified in the report.

This inspection is required to ensure that the drainage system is without defects or deficiencies of any kind (construction, structural or serviceability). It is further utilised by Council to verify the information provided by the applicant as part of the 'As Constructed' drawings. CCTV inspections must be carried out by suitably qualified and experienced CCTV operators, utilizing equipment appropriate to record sufficient information for the assessment of compliance against the relevant Australian Standards and Manufacturer s recommendations. All CCTV work is to be performed under the direction of the Engineer (RPEQ) responsible for the site. Calibration of Equipment In order to accurately quantify defects within a nominated section of pipe, the CCTV equipment utilized must be calibrated against a standardised procedure. A simple procedure which provides a reliable reference point can be used. The sample procedure listed below is an acceptable calibration procedure for the CCTV camera. Other methods may be used with justification and validation. Sample Calibration Procedure Prior to the commencement of survey for each different pipe diameter, the CCTV camera is to be inserted into a reference pipe (or, alternatively, stock footage may be utilized) of the same diameter, and is then positioned in the invert of the pipe and the camera set to zero zoom. The camera is then to be pointed directly at the invert of the pipe and focused on a graduated 1:1 scale bar (including concentric scale). This initial setup (camera looking at the invert, zero zoom) is to be taken as the 0 O reference point (or datum ). The camera is to be rotated through 90, 180 and 270 from the datum, and reference footage taken of the scale bar at each location. All scales are to be clearly legible to the viewer. The camera resolution settings shall be adjusted, where necessary, to achieve this. Calibration of scale of the CCTV footage at a minimum of 3 different levels of zoom for each direction shall also be taken. 3 This calibration of the scaling mechanism will allow the determination of the size and extent of defects, and their assessment against allowable limits. Alternatively consultation can be made with the CCTV operators to determine if it is possible to attach a ruler or scale to the front of the camera (without obstructing the view) which would give an indication of crack of gap size as it traverse the pipe. Defect Types and Examples Reference Documentation The Water Services Association of Australia, Conduit inspection Reporting Code of Australia (WSA05-2008) is to be used as the basis of the determination and reporting of defect types and classifications. 3 Nominally zoom settings should include minimum zoom (zero), maximum zoom and one intermediate point.

1. Cracks and Fractures Cracks differ from fractures in that a crack has no discernible separation along the failure surface, whereas a fracture does. Table 1 summarises the major crack/ fracture defect types. Two major cracking types exist:- 1) Surface cracking, which is characterised by short virtually indistinguishable, zero separation type cracks which usually form as part of the casting process (ie. Plastic shrinkage cracking and the like), and 2) Wall cracking, which indicate poor pipe handling and installation techniques 4. Table 1: Examples of Crack and Fracturing defects Defect Type Failure Criteria Examples Minor (Surface Major (Wall Cracking) Cracking) Longitudinal 0-30mm to be documented and scored as per WSA05 guidelines and submitted to asset owner for review Not Acceptable 4 Reference is made to S4.26 Pre-Inspection Criteria, points 1 and 2, which state that it is the contractors responsibility to make the assessment that the pipes are fit-for-purpose and meet the requirements of AS4058. It is on the basis of the contractors checks being satisfactorily completed, and pipes accepted by the contractor, that if any defects are subsequently identified during the CCTV inspections (e.g. Cracking, fracturing, deflections, chipping, intrusions, etc.) they will be deemed to have occurred during installation.

Table 1: Examples of Crack and Fracturing defects (continued) Defect Type Failure Criteria Examples Minor (Surface Major (Wall Cracking) Cracking) Circumferential Not Acceptable Longitudinal Fracturing

Table 1: Examples of Crack and Fracturing defects (cont.) Defect Type Failure Criteria Examples Minor (Surface Cracking) Major (Wall Cracking) Helical/Spiral 0-30mm to be documented and scored as per WSA02 guidelines and submitted to asset owner for review Multiple Defects

2. Deformed, Collapsed and Broken Pipes Deformation of the stormwater pipe can be defined as a departure from the initial cross section of a pipe. This is often caused by dents or deflections within the pipe or in more extreme cases, the pipe deforming into an elliptical profile. The deformations of stormwater pipes into elliptical profiles are not common in RCP pipes, but become more common\ prevalent in flexible pipes. The more serious extension of this defect is the failure and collapse of the pipe structure. This sequence of the failure is shown in Table 2, along with other discrete causes of failures (breaks and punctures). Table 2: Major failure types (deformation) Defect Type Failure Criteria Example Punctures Break

Table 2: Major failure types (continued) Defect Type Failure Criteria Example Deflection/compression >5% original measurement after 60 days, Elliptical profile >5% original measurement after 60 days, Dents Collapse

3. Displaced and Open Joints Joints which are displaced and / or misaligned allow water and debris to pass between bedding material and the internal stormwater pipe. Table 3, shows examples open or displaced joints. Table 3 Causes of failure, resulting from open or displaced joints. Defect Type Extension of Gap in Joint (minor) Failure Criteria General Guide 5 : >5mm for <250mmø Pipes >10mm for 250mmø to 500mmø >15-20mm for >500mmø Example Extension of Gap In Joint (major Bedding material Exposed) Not Acceptable 5 Tolerances levels set outside of those nominated by the general guide shall be accepted by Council on the basis of conformation of compliance with the tolerance limits set by the pipe manufacturer. In such cases a copy of the manufacturer s most recent documentation detailing the tolerable limits shall be provided to support the claim.

Defect Type Lateral Displacement (Offset Pipes) Failure Criteria Not Acceptable Example Dropped Invert (Misalignment) Not Acceptable

4. Surface Damage The two most common forms of surface damage are: 1) Exposed steel reinforcement, and 2) Visible or protruding aggregate in the finish of the concrete pipes. The consequential corrosion of the exposed reinforcement is also considered a defect. If the CCTV footage identifies evidence of corrosion of exposed reinforcement, Council will consider this a defect. Table 4 shows examples of these forms of defects Table 4 Surface defects of concrete stormwater pipes. Defect Type Failure Criteria Example Exposed Reinforcement

Table 4 Surface defects of concrete stormwater pipes (continued) Defect Type Failure Criteria Example Exposed Aggregate

5. Connections Nominally, all changes of direction or connection to existing pipes should be done with the construction of a manhole. Mid line connections such as the one shown in Table 5 are not acceptable. Table 5 :Stormwater connection defects Defect Type Failure Criteria Example Break-In Type Connections

6. Debris, Silt and Obstructions Debris, silt and other foreign obstructions reduce the hydraulic capacity of the stormwater drainage network. The reduction of the capacity may lead to the back-up or blockage of stormwater and cause additional risk &/or damage to people and property. (Refer Table 6) Table 6 Obstruction defects in Stormwater pipes Defect Type Failure Criteria Example Silt Build up on new installations Debris or Alternative Service Blockages on new installations Joint seal material on new intallations

7. Infiltration Where opportunity exists for groundwater to infiltrate the stormwater network (from selected defects listed here), it may lead to the secondary defects. These may include the: - erosion of bedding material, - failure of the bedding trench, and - consequential failure(s) of adjacent material(s) affected by the areas of scour and/ or erosion.. Figures showing the defects are shown below (Table 7). Table 7: Secondary defects caused by Infiltration Defect Type Failure Criteria Example Deposits Cause to be determined, report/remediation plan prepared and submitted to Asset owner for Acceptance determination Water infiltration within pipe structure 6 (Ag drains within the bedding trench shall be utilized for the drainage of the bedding trench) Bedding material erosion 6 This does not include sites where specific design consideration has been given to ground water infiltration, which is to be approved by the LGA on a case by case basis.

8. Root Infiltration Root infiltration occurs when stormwater infrastructure is installed in close proximity to trees or other vegetation (Figure 8), whose roots may infiltrate the structure of the stormwater pipe and cause various levels of blockages as shown in Table 8. Figure 8: Schematic of root infiltration. Table 8.1: Root infiltration defects Defect Type Failure Criteria Example Root infiltration (minor) <20% Blockage Refer to Joint Failure Criteria for acceptable limits on joint separation Root infiltration (Major) 20% - 70% Blockage Root infiltration (Total Blockage) >70% Blockage 7 7 It is noted that this extent of root infiltration and blockage is not expected to occur prior to the Works acceptance or final works acceptance inspections. It provided as an example only.

9.Encrustation and Scale and Physical Damage Physical defects associated with concrete works such as scaling, spalling, chipping, erosion (chemical or otherwise) and encrustation with various foreign material are also defects which can reduce the performance and or design life of stormwater infrastructure. Typical defects have been identified in Table 9. Table 9 Physical Defects (Stormwater Infrastructure) Defect Type Failure Criteria Example Erosion of Pipe Lining Cause to be determined, remediation plan prepared and submitted to Asset owner for Acceptance determination Lip/Lining Chipping Puncturing Breakage/Collapse

Table 9 Physical Defects (Stormwater Infrastructure) continued. Defect Type Failure Criteria Example Concrete Slurry/Aggregate deposition from construction To be submitted to asset owner for Acceptance determination

Bibliography Brisbane City Council, (2008), Brisbane City Council, Subdivision and Development Guidelines, Part B Infrastructure Elements, Chapter 2 Stormwater Drainage, http://www.brisbane.qld.gov.au/documents/building_development/subdivision_development/2008 _%20ed_part_b_chapter%2002_stormwater_drainage_(contents_to_section_4).pdf Department of Transportation, State of Delaware (2009). Storm Sewer CCTV Manual for Storm Sewer Assessment and Acceptance. Delaware: State of Delaware, Department of Transport - Quality Division. http://www.deldot.gov/information/pubs_forms/manuals/pipe_video/video_pipe_manual_optimiz ed.pdf Department of Transportation, State of Florida (2010). PIPE INSPECTION AND REPAIR. Ohio Construction Conference, February 23, 2010, http://www.ftba.com/external/wcpages/wcmedia/documents/2010_construction_conference_pipe _inspection_and_repair3.pdf FNQROC (2012), Inspections of Stormwater Drainage Systems, S4.26 CCTV Inspections of Stormwater Drainage Systems. FNQROC Development Manual_ver5, http://www.fnqroc.qld.gov.au/images/stories/documents/rdms/2012/version_5_updated_october_2012/spe cifications_version_5/s4_stormwater_drainage_specifications -_FNQROC_Development_Manual_01-11_Finalised.pdf ROCLA, (2010), Product Guide http://www.toogoomerosion.com/wpcontent/uploads/2013/02/rocla-product-guide_qld_2010.pdf Urban Drainage and Flood Control Division (2012), Division 33 Utilities, Report 33 41 00-1: Reinforced Concrete Pipe,2480 West 26th Avenue Suite 156-B Denver, CO 80211, http://www.udfcd.org/downloads/pdf/dist_specifications/division%2033%20- %20Utilities/33_41_00_Reinforced_Concrete_Pipe.pdf Warringah Council (2011) Guideline for Closed Circuit Television (CCTV) Investigation of Council Stormwater Assets, Natural Environment Unit, http://www.warringah.nsw.gov.au/plan_dev/documents/2009084728guidelineforcctvinvestigatio nofcouncilstormwaterassets2.pdf Water Services Association of Australia (WSA), (2008), Conduit Inspection Reporting Code of Australia WSA 05 2008, Second Edition Version 2.2, https://www.wsaa.asn.au/codes/shop/extracts/wsa%2005%20version%202_2_code%20contents %20Extract.pdf Weatherstone, S. (2009), CCTV Inspection of Sewers and Stormwater Drains, Training of Operators and Managers, and the Conduit inspection reporting code of Australia, 3rd Annual WIOA NSW Water Industry Engineers & Operators Conference, Tamworth Regional Entertainment & Conference Centre31 March to 2 April, 2009, http://www.wioa.org.au/conference_papers/09_nsw/documents/steveweatherstone.pdf

Humes (2009), Concrete Pipe Reference Manual http://www.humes.com.au/fileadmin/templates/humes/doc/brochures/humes_concretepipeman ual.pdf Concrete Pipe Association of Australia (unknown), The Facts About Cracking in Steel Reinforced Concrete Pipes, Engineering Guideline, http://www.cpaa.asn.au/images/publications/engineering_guidelines/cracking%20reinforced%20pi pe.pdf Concrete Pipe Association of Australia (unknown), Longitudinal Cracking, http://www.cpaa.asn.au/images/publications/engineering_guidelines/longitudinal%20cracking.pdf