NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS



Similar documents
San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

SECTION STORM DRAINAGE SYSTEM

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SECTION STORM DRAIN SYSTEM

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

Section 2100-Trenching and Tunneling

FY08 SEWER POINT REPAIRS BID TABULATION

Wastewater Capital Projects Management Standard Construction Specification

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

Specifications for Residential Property Owners Connection to New Public Sewer

SECTION PRECAST CONCRETE UTILITY STRUCTURES

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

Section SEWER PIPE INSTALLATION AND TESTING

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

SECTION STORM DRAINAGE TABLE OF CONTENTS

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

INDEX. Sec. No. Items Page Nos.

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO)

San Antonio Water System Standard Specifications for Construction ITEM NO POINT REPAIRS AND OBSTRUCTION REMOVALS

LS 2540 SEWER LATERALS AND INSPECTION TEES

Beacon Hill Sewer District Standard Specifications

Town House Center Highway North Huntingdon, PA 15642

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

TABLE OF CONTENTS. Manhole, Frame, and Cover Installation (includes Drop Manhole) Additional Manhole Depth

DIVISION 4300 STORM DRAINAGE

SECTION ABANDONMENT OF SEWER MAINS

CHAPTER 6 - SANITARY SEWER

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

SANITARY SEWER SPECIFICATIONS

SECTION BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

SECTION ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL

C. Section TESTING LABORATORY SERVICE.

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

SECTION 3 SANITARY SEWER DESIGN

EXHIBIT "A. Technical Specifications for Water and Sewer Service Lines

STANDARD SPECIFICATIONS SECTION INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

SECTION PRECAST CONCRETE STRUCTURES

ASTM C76, Class III, Wall B, except as modified herein. Clean natural sand, ASTM C33. Artificial or manufactured sand will not be permitted.

SECTION SANITARY SEWER PIPE

SECTION POLYVINYL CHLORIDE (PVC) PIPE

SECTION 7- STORM SEWER

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

CW GRAVITY SEWERS TABLE OF CONTENTS

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

City of Virginia Beach Public Utilities HRPDC Regional Construction Standards, 5 TH Edition Amendments May 19, 2014

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 21

Sewer Rehabilitation Design Requirements

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe

Exhibit A. Rules and Regulations for House Connections and Sewer Extensions

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

SECTION 724 PIPE CULVERTS

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

SECTION 21 REHABILITATION OF SANITARY SEWER MAINS BY THE PIPE BURSTING AND TRENCHLESS PIPE REPLACEMENT METHOD

FY15 Gravity Sewer and Manhole Rehabilitation

ENGINEERED SOLUTIONS. A2 Liner Pipe for Trenchless Technology

LOGAN TOWNSHIP MUNICIPAL UTILITIES AUTHORITY DESIGN, CONSTRUCTION, INSPECTION AND TESTING MANUAL

SECTION CAST-IN-PLACE CONCRETE

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH Purpose and Application.

Section 402. STORM SEWERS

Guide to working on Public Sewers

CONSTRUCTION PERMIT REQUIREMENTS

ARTICLE VI (ALTERNATE) STANDARD SPECIFICATIONS. for (PVC) SANITARY SEWER MAIN CONSTRUCTION

OAR52 A-1 (September, 1981)

SECTION 5: SANITARY SEWER SYSTEM DESIGN

550 PIPE CULVERTS, SEWERS AND DRAINS

Customer Procedures and General Information for Sewer Customers

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Stormwater/Wetland Pond Construction Inspection Checklist

EFFECTIVE FEBRUARY note: drainage permit required to call for a dampproof inspection

SECTION UNDERGROUND ELECTRIC SERVICE

September 2012 Brunswick County Engineering Department Revision 1.0. Technical Specification GRAVITY SANITARY SEWER SYSTEM

Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

CLEANING, INSPECTION, AND TESTING OF SEWERS

Nebraska Department of Roads Drainage and Erosion Control Manual December 2011 Appendix C: Pipe Material Policy Page C-1 PIPE MATERIAL POLICY

WATER & SEWER CORROSIVE RESISTANT PRODUCTS

City of West Linn Public Works Standard Construction Specifications. Table of Contents

The Manitoba Water Services Board SECTION Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11

Meeting the Challenge of Pipeline Emergency Repair

Transcription:

STANDARD COLLECTION DETAILS Detail No. Detail Title Pages ND-01 NOTICE TO CONTRACTORS 1 ND-02 MANHOLE CONSTRUCTION NOTES AND INDEX 2 ND-10 STANDARD MANHOLE CONNECTION 2 ND-11 STANDARD MANHOLE DETAIL 54" DIA OR LARGER DISTRICT PIPE 2 ND-12 STANDARD MANHOLE DETAIL CCFRPM DISTRICT PIPE 2 ND-13 STANDARD MANHOLE DETAIL FRP 2 ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETE 3 ND-15 STANDARD GREASE INTERCEPTOR 2 ND-16 STANDARD MANHOLE DETAIL CIPP REPAIR 1 ND-20 STANDARD SERVICE CONNECTION - CONCRETE PIPE 1 ND-21 STANDARD SERVICE CONNECTION - CIPP LINED PIPE 1 ND-22 STANDARD SERVICE CONNECTION - CCFRPM FIBERGLASS PIPE 1 ND-23 STANDARD SERVICE CONNECTION - ABANDONMENT 1 ND-30 CRACKED PIPE REPAIR 1 ND-31 STRUCTURAL SUPPORT AT CROSSING 2 Table of Contents

Effective immediately, the following will be accomplished by all contractors before starting any work or excavation around or on any sewer line owned by the North Davis Sewer District: 1. 2. 3. 4. 5. 6. Hours of Operation a) b) c) Sewer Lateral Connections: a) b) c) d) e) The District's working hours are 7:30 a.m. to 4:00 p.m., Monday through Friday. No sewer inspection will be done on weekends, holidays or after 3:00 p.m. All inspections lasting after 4:00 p.m. will result in overtime being billed to the contractor. Multiple inspection visits required for work that is incomplete, not to District standards, or not ready for inspection will result in additional time being billed to the contractor. No work shall begin until the proper fees of $240.00 for connection and inspection, plus impact fees as calculated by the City or District (whichever may apply) are certified to the District as having been paid. The District only accepts cash or check. No work shall begin until the proper building permits and licenses have been obtained from the City, County, or Sewer District. Minimum notice of 48 hours shall be given to the District prior to any work commencing on or digging being done on District-owned lines. No digging or work shall be done on District-owned lines without the presence of a District Inspector. All sewer taps must be Core Drilled, INSERTA TEE, GPK 4, or equivalent. Setting of Manholes on District owned-line a) Manholes are required to be set for connecting lines 6 inches or larger. b) No manholes shall be set on District-owned lines without prior approval by the District. Contractors shall submit design drawings and manhole details of proposed manholes on District line for approval 14 days prior to work commencing. Design drawings shall be submitted in PDF electronic format unless otherwise requested by the District. c) After approval of drawings, a minimum of 48 hours notice shall be given to the District inspectors before any manhole is set on a District-owned line. The manhole must be set in the presence of a District inspector. Flow Control and Bypass Pumping Operations a) Where required to complete the Work, the Contractor shall provide bypass pumping and flow control. Contractor shall submit a bypass pumping plan prior to commencement of the work for review and acceptance by the District. The plan shall at a minimum provide materials, equipment and flow calculations and be of sufficient detail to demonstrate the system's capacity to control flows. The Contractor shall coordinate with the District to determine the required capacity. Concrete Batching a) Ready mix concrete shall be provided in accordance with ASTM C94, Standard Specification for Ready-Mixed Concrete. b) The design water content of the mix (w/c ratio) shall not be exceeded. Addition of water, air entrainment or superplasticizer shall only be performed by the Supplier. c) Non-air entrained concrete shall be discharged ninety (90) minutes after batching. Air entrained concrete or concrete that includes silica fume shall be discharged within sixty (60) minutes of batching. d) Requests for longer batching times shall be submitted and accepted by the District prior to procurement of concrete by the Contractor. e) The District shall not be responsible for the cost of rejected batches exceeding time limitations, loss of air-entrainment or slump. Warranty: a) Contractor shall guarantee work for a period of one year from the date of installation. Failure of contractors to comply with these guidelines could result in the contractor being barred from working on District lines. If there are any questions on a line being a District line, please contact the District office @ 801-825-0712. ND-01 Notice to Contractors

STANDARD MANHOLE ON EXISTING SEWER LINE 1. Manhole shall be constructed so as to prevent load to the existing pipe. The base of the manhole shall provide a minimum of 9 inches of concrete beneath the existing pipe unless otherwise shown, placed on 12 inches of one inch gravel bedding compacted to 95% density. 2. Manhole floor elevation shall be a minimum of 2 inches above top of pipe, have a 12:1 slope to the pipe, and a smooth finish. 3. Connection to manhole shall be made using a flexible, watertight connection per ASTM C923, Kor-n-seal or equal. Flexible couplings shall be correctly sized, flexible water tight couplings per ASTM C1173, Fernco Inc, Mission Rubber Company or approved equal. All hardware shall be 316 series stainless steel, unless otherwise approved. 4. Manhole shall be constructed using a pre-cast eccentric type sections and cast iron traffic type frame and cover marked "NORTH DAVIS SEWER". Section joints shall be sealed with rubber gaskets and shall be watertight. 5. Wrap exterior joints. Wrap shall conform to ASTM C877 Type II or Type III. Press-seal Ez-Wrap, Cretex Wrap, Conseal 2/2 or approved equal. 6. Invert of branch line at manhole connection shall be adjusted to be at or near crown of existing main line. 7. Branch line channel to be formed with same slope, size, depth, and shape as pipe with smooth finish; it shall be curved in direction of flow with uniform radius and minimize dropping and splashing of flow. 8. Cutting into existing line shall be made by smooth saw cuts. 9. Installing contractor shall be responsible for proper slope and installation of connecting line. 10. Installing contractor shall be responsible for proper backfilling, compacting, and pavement restoration. 11. Contractor shall notify District 48 hours before installation begins and a District inspector must be present before installation takes place. 12. Contractor shall meet all restoration requirements of the agency, city or UDOT where the manhole is installed and shall coordinate any additional installation or inspection requirements with the agency. CONNECTION TO AN EXISTING MANHOLE 1. Item numbers 3, 5, 8, 9, 10 and 11 above shall apply. 2. In addition, the manhole junction channel shall be constructed to the same size, shape, and slope of the incoming line. Channel shall curve in the direction of flow with uniform radius and minimize dropping and splashing of flow. 3. No manhole connection shall be made until complete design drawings of the manhole and line installations are submitted to the District for approval - 14 days prior to work commencing. ND-02 Manhole Construction Notes and Index 1 of 2

Detail no. Detail Title Use ND-10 ND-11 STANDARD MANHOLE CONNECTION STANDARD MANHOLE DETAIL 54" DIA OR LARGER DISTRICT PIPE Concrete, RCP, and PVC District Pipe < 54" DIA. (See Note 1) RCP District Pipe 54" DIA ND-12 STANDARD MANHOLE DETAIL CCFRPM DISTRICT PIPE CCFRPM Pipe 18" DIA ND-13 ND-14 STANDARD MANHOLE DETAIL FRP STANDARD MANHOLE DETAIL POLYMER CONCRETE Lined Concrete and RCP, CCFRPM or as directed by District Lined Concrete and RCP, CCFRPM or as directed by District ND-15 STANDARD GREASE INTERCEPTOR As directed by District ND-16 STANDARD MANHOLE DETAIL CIPP REPAIR CIPP Lined District Pipe NOTE 1. District reserves the right to require precast FRP or polymer manholes on pipes that are planned to be rehabilitated by cured-in-place (CIPP) or other methods within two years of drawing submittal. ND-02 Manhole Construction Notes and Index 2 of 2

EXISTING DISTRICT PIPE NOTES: 1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTING PIPELINE. HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 10. 2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. CUTTING OF EXISTING LINE TO FORM CHANNEL SHALL BE ACCOMPLISHED WITH SMOOTH SAW CUTS A FLOW 2'-0" MAX. A 4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. 5. PRECAST MANHOLE BASES SHALL BE USED FOR CONSTRUCTION OF ALL NEW DISTRICT SEWER SYSTEMS. PRECAST MANHOLE BASES OR CAST-IN-PLACE MANHOLE BASES MAY BE USED AT THE CONTRACTOR'S OPTION FOR NEW MANHOLES INSTALLED ON EXISTING DISTRICT SANITARY SEWERS. CONTRACTOR SHALL PROVIDE A SUITABLE FOUNDATION IN ALL AREAS. CONNECTING PIPE JUNCTION CHANNEL SHALL BE FORMED WITH SAME SLOPE, SIZE, DEPTH, AND SHAPE AS CONNECTING PIPE WITH SMOOTH FINISH - CHANNEL SHALL CURVE IN DIRECTION OF FLOW WITH UNIFORM RADIUS AND MINIMIZE DROPPING AND SPLASHING OF FLOW 6" (TYP) 6. CAST-IN-PLACE BASE SHALL BE COMPLETED IN A SINGLE POUR. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150 WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 4000 PSI PER ASTM C39. NO ADDITIVES SHALL BE PERMITTED WITHOUT PRIOR APPROVAL BY THE DISTRICT. 7. PRECAST MANHOLE BASES SHALL CONFORM TO ASTM C478. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150 WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 4000 PSI PER ASTM C39. CONNECTIONS TO PRECAST BASES SHALL BE FACTORY INSTALLED AND MEET THE REQUIREMENTS OF ASTM C923, Z-LOK, PRES-SEAL PSX OR APPROVED EQUAL. 8. MANHOLES ON CCFRPM OR CIPP LINED DISTRICT SEWERS SHALL BE PRECAST FRP (HOBAS, LF MANUFACTURING INC OR EQUAL) OR POLYMER (ARMOROCK OR EQUAL) UNLESS OTHERWISE APPROVED BY THE DISTRICT. SEE DETAIL ND-12, ND-13 AND ND-14. 9. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION. GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINK TYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINST HYDROGEN SULFIDE ATTACK. PLAN 10. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CAST CONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIRE BRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN, DURABLE SURFACE. SECURE WATERSTOP TO PIPE USING MANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OF GREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEEN WATERSTOP AND PIPE. ND-10 Standard Manhole Connection 1 of 2

12" WIDE MIN, 8" DEEP CONCRETE COLLAR IN PAVED AREAS REINFORCEMENT REQUIRED (1) #4 BAR ALL AROUND 30" MANHOLE RING AND COVER MARKED "NORTH DAVIS SEWER" (D & L SUPPLY A-1180-18, OR APPROVED EQUAL) GRADE RINGS - A MINIMUM OF ONE 6-INCH RING, BUT NOT MORE THAN 18" TOTAL HEIGHT INCLUDING FRAME, RINGS, AND GROUT, SHALL BE USED PRECAST ECCENTRIC CONE (SHALL MEET ASTM C-478 STANDARDS) WHEN INSUFFICIENT DEPTH PREVENTS THE USE OF A CONE, A CONCRETE PRECAST H-20 FLAT LID SHALL BE USED. MANHOLE DIAMETER SHALL BE 4'-0" FOR PIPE SIZES LESS THAN 15" - MANHOLE DIAMETER SHALL BE 5'-0" FOR PIPE SIZES OF 15" TO 30", MANHOLE DIAMETER SHALL BE 6' FOR PIPE SIZES GREATER THAN 30" AND FOR ALL CONNECTING AND JUNCTION MANHOLES (FOR DISTRICT PIPES 54" DIA OR LARGER SEE DETAIL ND-11). 30" DIA. IF LOCATED IN UNIMPROVED GROUND SET COVER 6" ABOVE GRADE UNLESS DIRECTED OTHERWISE BY DISTRICT GROUT FOR SETTING GRADE RINGS AND FRAME SHALL PROVIDE A WATERTIGHT BARRIER TO PREVENT INFILTRATION AND BE PLACED ACROSS THE FULL WIDTH, 1/2-INCH MIN AND 1-INCH MAX THICK. SEAL ALL JOINTS WITH RAMNECK OR EQUAL (ALL JOINTS SHALL BE TESTED FOR WATERTIGHTNESS) TAPE WRAP EXTERIOR JOINTS. WRAP SHALL CONFORM TO ASTM C877 TYPE II OR TYPE III. (PRESS-SEAL EZ-WRAP, CRETEX WRAP, CONSEAL 2/2 OR APPROVED EQUAL) INVERT OF CONNECTING PIPE SHALL BE AT OR NEAR CROWN OF EXITING DISTRICT SEWER PIPE TOP OF FLOOR SHALL BE 2" MIN. ABOVE PIPE 1:12 FLOOR SLOPE WITH SMOOTH TROWELED FINISH 6" PRECAST CONCRETE MANHOLE SECTIONS PER ASTM C-478. PRECAST RISER TO BE SET IN CONCRETE (TYP) (CAST-IN-PLACE BASE) CONNECTING PIPE SHALL BE INSTALLED IN CORE DRILLED OPENING WITH A FLEXIBLE WATERTIGHT BOOT. (PSX, PRESS SEAL, KOR-N-SEAL OR EQUAL) IF A BOOTED CONNECTION IS NOT POSSIBLE, PLACE HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 10. 12" 9" MIN SECTION A PRECAST OR CAST-IN-PLACE MANHOLE BASE DISTRICT SEWER PIPE 1" MINUS GRAVEL BASE UNDISTURBED NATIVE SOIL ND-10 Standard Manhole Connection 2 of 2

PRECAST MANHOLE PER STANDARD MANHOLE CONNECTION DETAIL FRAME & COVER PER DETAIL ND-10 PRECAST MANHOLE PER STANDARD DETAIL PER TABLE "A" CONNECTING PIPE A HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 4. FLOW MIN WIDTH PER TABLE "A" "L" MIN EXISTING DISTRICT SEWER PIPE MIN LENGTH PER TABLE "A" CONNECTING PIPE A CLEAR HEIGHT PROVIDE STAINLESS STEEL BAND (NON-SHEAR) TYPE. (FERNCO OR APPROVED EQUAL) HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 4. 6' MIN TO TRANSITION (MIN 48" RISER TO GRADE) 1'-0" MIN 6" FROM WATERSTOP TO OUTSIDE EDGE OF MANHOLE 6" MAX MIN DIA PER TABLE "A" 3" MIN L VARIES 45 TYP VARIES SEE TABLE "A" MIN WIDTH PER TABLE "A" SECTION A 8" MIN SAW CUT & REMOVE EXISTING PIPE CROWN PRECAST RISER TO BE SET IN CONCRETE (TYP) (CAST-IN-PLACE BASE) 1'-0" MIN 1'-0" MIN #5 BAR 12" OC BOTH WAYS TOP & BOTTOM GRADE 60 3" MIN (TYP) 12" GRANULAR BEDDING COMPACTED TO 95% DRY DENSITY (OR CONTROL DENSITY FILL) UNDISTURBED NATIVE SOIL PLAN 6" MIN FROM EDGE OF CONCRETE ND-11 Standard Manhole Detail 54" DIA or Larger District Pipe 1 of 2

NOTES: 1. THIS STANDARD DRAWING SHALL BE USED FOR ACCESS TO EXISTING DISTRICT SEWER PIPES WITH DIAMETERS 54" DIA OR LARGER. THIS DETAIL SHALL NOT APPLY TO NEW DISTRICT SANITARY SEWER AND MANHOLE CONSTRUCTION. 2. WHERE DEPTH OF COVER OVER THE TOP OF PIPE EXCEEDS 10 FEET, REINFORCEMENT REQUIREMENTS SHALL BE REVIEWED AND VERIFIED BY A UTAH LICENSED CIVIL OR STRUCTURAL ENGINEER. 3. CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM 4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS UNLESS OTHERWISE DIRECTED BY THE DISTRICT. 4. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CAST CONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIRE BRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN, DURABLE SURFACE. SECURE WATERSTOP TO PIPE USING MANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OF GREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEEN WATERSTOP AND PIPE. 5. MINIMUM MANHOLE DIAMETER SHALL BE AS SHOWN IN TABLE A. MANHOLE COMPONENTS SHALL BE PROVIDED IN ACCORDANCE WITH DETAIL ND-10. DISTRICT PIPE DIA (IN) MIN MANHOLE DIA (IN) TABLE "A" ENCASEMENT MIN WIDTH (IN) 6. WHERE EXISTING DISTRICT PIPES HAVE BEEN REHABILITATED WITH CURED-IN-PLACE PIPE LINERS, CIPP LINERS SHALL BE CUT AND THE CIPP LINER ROUGHENED AND SEALED WITH AN APPROVED EPOXY PER DETAIL ND-16. 7. CONNECTING PIPE SHALL MATCH THE CROWN OF EXISTING DISTRICT PIPE. SAW CUT AND REMOVE EXISTING PIPE FROM CROWN TO SPRINGLINE. CONSTRUCT SLOPING INLET CHANNEL AND SHAPE CHANNEL TO FORM A SMOOTH FLOW SURFACE. ENCASEMENT MIN LENGTH (IN) 60" OR LESS 60" 96" 96" 78" OR LESS 72" 118" 118" 84" OR LESS 84" 124" 124" 8. PIPE CONNECTIONS SET IN THE CONCRETE BASE SHALL BE WATERTIGHT. PROVIDE HYDROPHILIC WATER STOPS, GROUT RINGS OR CAST-IN-PLACE RUBBER BOOTS MEETING APPLICABLE REQUIREMENTS OF ASTM C923. (PRESS SEAL, LINK-SEAL, OR APPROVED EQUAL) SUBMIT PRODUCT DETAILS AND PROPOSED CONNECTION FOR APPROVAL BY THE DISTRICT. ND-11 Standard Manhole Detail 54" DIA or Larger District Pipe 2 of 2

HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 6. EQ 2'-0" MIN. PRECAST MANHOLE PER CONNECTING PIPE DETAIL ND-13 OR ND-14 PROVIDE WATERTIGHT SEAL (INSERTA TEE OR APPROVED EQUAL WHERE CONNECTING TO CCFRPM) EQ FIELD CUT EXISTING PIPE, CLOSURE COUPLING PER CCFRPM MFR 2'-0" MIN. MIN DIA PER TABLE "A" PRECAST RISER TO BE SET IN CONCRETE (TYP) (CAST-IN-PLACE BASE) 2'-0" MIN. MIN WIDTH PER TABLE "A" A A CONCRETE ENCASEMENT 24" MIN CCFRPM TEE BASE OR FITTING HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 6. PRECAST MANHOLE PER DETAIL ND-13 OR ND-14. NOTES: MIN LENGTH PER TABLE "A" PLAN 1. THIS STANDARD DRAWING SHALL APPLY WHERE MANHOLES ARE CONSTRUCTED ON CCFRPM (FIBERGLASS) DISTRICT PIPES. AT THE CONTRACTORS OPTION, A PRECAST MANHOLE BASE MAY BE INSTALLED. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER MANHOLE CONNECTIONS AS ACCEPTED BY THE DISTRICT. 2. CUT EXISTING PIPE TO NEAT STRAIGHT LINES WITH CUTTING TOOLS SUITABLE FOR THE PIPE MATERIAL. DAMAGED PIPE SHALL BE REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE DISTRICT. EXISTING DISTRICT PIPELINES SHALL BE FULLY SUPPORTED AT ALL TIMES. CCFRPM TEE BASE OR FITTING EXISTING DISTRICT PIPE (CCFRPM, 18" DIA OR GREATER) UNDISTURBED NATIVE SOIL 3. CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM 4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS. 4. MINIMUM MANHOLE DIAMETER SHALL BE AS SHOWN IN TABLE "A". PRECAST MANHOLES COMPONENTS SHALL BE PROVIDED IN ACCORDANCE WITH DETAIL ND-13 OR ND-14. 5. ADDITIONAL DETAIL AND REINFORCING REQUIREMENTS SHOWN ON PAGE 2 OF 2. 6. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CAST CONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIRE BRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN, DURABLE SURFACE. SECURE WATERSTOP TO PIPE USING MANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OF GREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEEN WATERSTOP AND PIPE. DISTRICT PIPE DIA (IN) MIN MANHOLE DIA (IN) TABLE "A" 12" GRANULAR BEDDING COMPACTED TO 95% DRY DENSITY (OR CONTROLLED DENSITY FILL) MIN ENCASEMENT WIDTH (IN) MIN ENCASEMENT LENGTH (IN) 18" TO 45" 48" 74" 78" 60" OR LESS 84" OR LESS SECTION A 60" 88" 102" 90" 112" 132" ND-12 Standard Manhole Detail CCFRPM District Pipe 1 of 2

PRECAST MANHOLE PER DETAIL ND-13 OR ND-14 NON SHRINK GROUT #4 H2E - TYP. 4 SIDES #6 2'-0" MIN. #4 H2E @ 12" - TYP. 4 SIDES B #5 H2E @ 12" #5 @ 12" (18 @ 20 ) #4 X 1'-4" TYP. EACH END 2'-0" #5 @ 12" EF #5 H2E @ 12" EF VARIES CCFRPM TEE BASE OR FITTING 1'-0" #6 @ 12" - LAP 2'-4" (18 @ 20 ) #4 ADD (2) #6 EACH SIDE OF MANHOLE (4) #6 @ 12" B EXISTING DISTRICT PIPE (CCFRPM, 18" DIA OR GREATER) SECTION B REINFORCING #5 @ 12" EW SECTION A REINFORCING ND-12 Standard Manhole Detail CCFRPM District Pipe 2 of 2

12" WIDE MIN, 8" DEEP CONCRETE COLLAR IN PAVED AREAS EXISTING PAVEMENT REINFORCEMENT REQUIRED (1) #4 BAR ALL AROUND 30" MANHOLE RING AND COVER MARKED "NORTH DAVIS SEWER" (D & L SUPPLY A-1180-18, OR APPROVED EQUAL) FINISHED GRADE FRP NECK TO EXTEND INSIDE GRADE RINGS. GRADE RINGS TO EXTEND A MINIMUM OF 1" PAST FLAT SURFACE OF MANHOLE CONE PLACE AND COMPACT MANHOLE BACKFILL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS 30" EPOXY COATED PRECAST CONCRETE GRADE RINGS 12" MIN / 18" MAX. GROUT FOR SETTING GRADE RINGS AND FRAME SHALL PROVIDE A WATERTIGHT BARRIER TO PREVENT INFILTRATION AND BE PLACED ACROSS THE FULL WIDTH, 1/2-INCH MIN AND 1-INCH MAX THICK. FACTORY-BONDED JOINT FRP MANHOLE. WALL THICKNESS PER MANUFACTURER PRODUCT SUBMITTAL MIN 1/2" WALL THICKNESS FACTORY CAST FLOW CHANNEL WITH FRP CHANNEL SUPPORTS CONCRETE BASE AS REQUIRED TO COUNTERACT FLOTATION WATER TIGHT, FLEXIBLE PIPE CONNECTION, APPROVED BY THE DISTRICT CONNECTING PIPE MANHOLE DIAMETER SHALL BE 4'-0" FOR PIPE SIZES LESS THAN 15" - MANHOLE DIAMETER SHALL BE 5'-0" FOR PIPE SIZES OF 15" TO 30", MANHOLE DIAMETER SHALL BE 6' FOR PIPE SIZES GREATER THAN 30" AND FOR ALL CONNECTING AND JUNCTION MANHOLES (FOR DISTRICT PIPES 54" DIA OR LARGER SEE DETAIL ND-11.) FACTORY INSTALLED PVC STUBOUTS OR CONNECTIONS DISTRICT SEWER PIPE ANTI-FLOTATION RING 12" MIN #4 REBAR 12" OCEW PROVIDE MIN 12", 1" MINUS GRAVEL BASE UNDISTURBED NATIVE SOIL ND-13 Standard Manhole Detail FRP 1 of 2

NOTES: 1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTING PIPELINE. 2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. 5. MANHOLE BASE SHALL BE PRECAST FRP UNLESS OTHERWISE APPROVED BY THE DISTRICT. 6. THE CONTRACTOR SHALL BE A LICENSED OR CERTIFIED INSTALLER BY THE MANUFACTURER OF THE MANHOLE PROVIDED. 10. WHERE APPROVED BY THE DISTRICT, CONCRETE GRADE RINGS AND ALL OTHER EXPOSED CONCRETE SURFACES SHALL BE CORROSION PROTECTED WITH AN APPROVED EPOXY COATING. EPOXY SHALL BE A SOLVENT-FREE, 100% SOLID, MOISTURE TOLERANT HIGH BUILD EPOXY COATING, RAVEN 405, ENVIRONMENTAL COATINGS SEWER SHIELD 100, SAUEREISEN SEWERGARD 210 OR APPROVED EQUAL. SURFACE PREPARATION AND APPLICATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER. 11. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION. GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINK TYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINST HYDROGEN SULFIDE ATTACK. 12. CONNECTING PIPE SHALL MATCH CROWNS WITH DISTRICT PIPE UNLESS OTHERWISE DIRECTED BY THE DISTRICT, 7. MANHOLES AND THEIR BASES SHALL BE CIRCULAR FIBERGLASS REINFORCED POLYESTER MANHOLES DESIGNED, FABRICATED AND TESTED TO MEET OR EXCEED THE REQUIREMENTS OF ASTM D3753. HOBAS, L.F. MANUFACTURING OR APPROVED EQUAL. 8. PRECAST CONCRETE AND CAST-IN-PLACE COMPONENTS SHALL NOT BE ALLOWED UNLESS OTHERWISE APPROVED BY THE DISTRICT. 9. ALL MANHOLES SHALL BE PROVIDED WITH ANTI-FLOTATION RINGS FULLY ENCASED IN A CONCRETE PAD OF SUFFICIENT SIZE AND THICKNESS TO PREVENT FLOTATION. ND-13 Standard Manhole Detail FRP 2 of 2

30" MANHOLE RING AND COVER MARKED "NORTH DAVIS SEWER" (D & L SUPPLY A-1180-18, OR EQUAL) CONCRETE COLLAR, 12" WIDE, 8" DEEP (ALL LOCATIONS) W/ (1) #4 REINFORCEMENT BAR ALL AROUND EPOXY COATED CONCRETE, POLYMER OR EPP GRADE RINGS AS APPROVED BY THE DISTRICT. 18" MAX TOTAL HEIGHT INCLUDING FRAME, RINGS & GROUT PLACE AND COMPACT BACKFILL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS 30" FINISH GRADE (PAVED AND UNPAVED) GROUT FOR SETTING GRADE RINGS AND FRAME SHALL PROVIDE A WATERTIGHT BARRIER TO PREVENT INFILTRATION AND BE PLACED ACROSS THE FULL WIDTH, 1/2-INCH MIN AND 1-INCH MAX THICK. BUTYL MASTIC PRECAST POLYMER MANHOLE MIN WALL THICKNESS PER MANUFACTURER PRODUCT SUBMITTAL I.D. BARREL O.D. BUTYL MASTIC BELL O.D. MANHOLE DIAMETER SHALL BE 4'-0" FOR PIPE SIZES LESS THAN 15" - MANHOLE DIAMETER SHALL BE 5'-0" FOR PIPE SIZES OF 15" TO 30", MANHOLE DIAMETER SHALL BE 6' FOR PIPE SIZES GREATER THAN 30" AND FOR ALL CONNECTING AND JUNCTION MANHOLES (FOR DISTRICT PIPES 54" DIA OR LARGER SEE DETAIL ND-11.) PRECAST POLYMER BASE OR CAST-IN-PLACE BASE AS DIRECTED BY THE DISTRICT DISTRICT SEWER PIPE WATER TIGHT, FLEXIBLE PIPE CONNECTIONS APPROVED BY DISTRICT PROVIDE MIN 12", 1" MINUS GRAVEL BASE OVER UNDISTURBED NATIVE SOIL FACTORY CAST FLOW CHANNEL ND-14 Standard Manhole Detail Polymer 1 of 3

NOTES: 1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTING PIPELINE. 2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. 5. MANHOLE BASE SHALL BE PRECAST POLYMER UNLESS OTHERWISE APPROVED BY THE DISTRICT. 6. THE CONTRACTOR SHALL BE A LICENSED OR CERTIFIED INSTALLER BY THE MANUFACTURER OF THE MANHOLE PROVIDED. 7. MANHOLES AND THEIR BASE SHALL BE CIRCULAR PRECAST POLYMER DESIGNED, FABRICATED AND TESTED TO MEET OR EXCEED THE REQUIREMENTS OF D6783. POLYMER COMPONENTS SHALL BE A MIXTURE OF UNSATURATED ISOPHTHALIC POLYESTER RESIN, SAND AND AGGREGATE. NO CEMENTIOUS OR CALCIUM CARBONATE MATERIALS SHALL BE ALLOWED. ARMOROCK OR APPROVED EQUAL. 8. PRECAST CONCRETE AND CAST-IN-PLACE COMPONENTS SHALL NOT BE ALLOWED UNLESS OTHERWISE APPROVED BY THE DISTRICT. 9. ALL MANHOLES SHALL BE PROVIDED WITH ANTI-FLOTATION RINGS FULLY ENCASED IN A CONCRETE PAD OF SUFFICIENT SIZE AND THICKNESS TO PREVENT FLOTATION. 10. WHERE APPROVED BY THE DISTRICT, CONCRETE GRADE RINGS AND ALL OTHER EXPOSED CONCRETE SURFACES SHALL BE CORROSION PROTECTED WITH AN APPROVED EPOXY COATING. EPOXY SHALL BE A 100% SOLID, EPOXY COATING, ARMORROCK EPOXY OR APPROVED EQUAL. 11. GRADE RINGS AND DOG HOUSE MANHOLE CONNECTIONS SHALL BE GROUTED TO PREVENT INFILTRATION. GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINK TYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINST HYDROGEN SULFIDE ATTACK. 12. CONNECTING PIPE SHALL MATCH CROWNS WITH DISTRICT PIPE UNLESS OTHERWISE DIRECTED BY THE DISTRICT. ND-14 Standard Manhole Detail Polymer 2 of 3

MANHOLE I.D. FIELD APPLIED EPOXY COATING, ARMORROCK EPOXY OR APPROVED EQUAL PRECAST POLYMER RISER SET IN CONCRETE WITH WATER TIGHT SEAL FACTORY CAST FLOW CHANNEL PRECAST POLYMER BASE BASE HEIGHT PER MANUFACTURER RESIN AGGREGATE WALL & BENCH SAWCUT AND REMOVE TOP OF PIPE PRIOR TO COATING 12" MIN CAST-IN-PLACE BASE 6" MIN, 12" MAX FROM EXTERIOR OF MANHOLE OR BELL OD IF GREATER CAST-IN-PLACE CONCRETE BASE OR ENCASEMENT HYDROPHILLIC WATERSTOP ALL AROUND EXISTING DISTRICT PIPE AND CONNECTING PIPE(S) (TYPICAL), GREENSTREAK HYDROTITE (OR APPROVED EQUAL), SEE NOTE 5. BASE OPTION NOTES: 1. CONTRACTOR SHALL PROVIDE SUITABLE FOUNDATION AS DIRECTED BY THE DISTRICT IN AREAS OF UNSTABLE TRENCH BOTTOM, WET CONDITIONS, OR OVER EXCAVATION. 2. CAST-IN-PLACE CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM 4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS UNLESS OTHERWISE DIRECTED BY THE DISTRICT. BASE SHALL BE CURED A MINIMUM OF THREE DAYS PRIOR TO STACKING MANHOLE. 3. BENCH TO HAVE 1:12 FLOOR SLOPE WITH TROWELLED FINISH. 4. EPOXY COATING TO BE APPLIED MIN 4" ABOVE BENCH AND OVERLAP CUT OUT SEWER PIPE. 5. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CAST CONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIRE BRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN, DURABLE SURFACE. SECURE WATERSTOP TO PIPE USING MANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OF GREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEEN WATERSTOP AND PIPE. ND-14 Standard Manhole Detail Polymer 3 of 3

MANHOLE RING AND NON-VENTED COVER MARKED "SEWER" - (TYPICAL) (D & L A-1181, OR EQUAL) INLET SEWER SEWER OUTLET PLAN DOUBLE SWEEP CLEANOUT 1'-6" WIDE, 6" DEEP CONCRETE COLLARS IN PAVED AREAS. REINFORCEMENT REQUIRED. (1) #4 BAR ALL AROUND 20" MIN. DIA. FINISH GRADE (PAVEMENT OR LANDSCAPING) MANHOLE COVERS LOCATED TO ALLOW VIEWING OF AND SAMPLING FROM INLET AND OUTLET TEES (TYPICAL) INLET SANITARY TEES PRECAST CONCRETE TANK 6" GREASE STORAGE LIQUID LEVEL OUTLET TEE - 6" MIN. RISER SECTION / GRADE RINGS (NOT TO EXCEED 12" TOTAL HEIGHT). GROUT FOR SETTING GRADE RINGS AND FRAME SHALL PROVIDE A WATERTIGHT BARRIER TO PREVENT INFILTRATION AND BE PLACED ACROSS THE FULL WIDTH, 1/2-INCH MIN AND 1-INCH MAX THICK. 1" MINUS GRAVEL BASE SST PIPE SUPPORTS REQUIRED (TYP) 12" SECTION UNDISTURBED NATIVE SOIL ND-15 Standard Grease Interceptor 1 of 2

NOTES: 2 SS EXP ANCHORS EACH CLAMP "Z" SHAPED STEEL STRAP FITTING, TYP 1. GREASE INTERCEPTOR SHALL BE LOCATED TO BE CONTINUOUSLY AND EASILY ACCESSIBLE FOR INSPECTION AND CLEANING AND AS CLOSE AS PRACTICAL TO THE SOURCE OF WASTEWATER. IT SHALL NOT BE LOCATED IN DRIVE-UP LANES, PARKING STALLS, OR SIMILAR AREAS THAT COULD BE PERIODICALLY BLOCKED. 2. WHEN LOCATED IN PAVED AREA, THE TRAP, MANHOLE COVERS, ETC, SHALL BE TRAFFIC RATED. 3. INLET AND OUTLET TEES SHALL BE LOCATED DIRECTLY BELOW MANHOLE ACCESSES. WALL NOTE: ALL HARDWARE 316 STAINLESS STEEL 4. GREASE INTERCEPTORS SHALL HAVE A MINIMUM OF TWO COMPARTMENTS. 5. MINIMUM HYDRAULIC VOLUME OF THE TRAP SHALL BE 1000 GALLONS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALL UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 7. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 8. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. SST PIPE SUPPORT 9. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION. GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINK TYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINST HYDROGEN SULFIDE ATTACK. ND-15 Standard Grease Interceptor 2 of 2

EXISTING DISTRICT PIPE MANHOLE WALL (PRECAST FRP OR POLYMER MANHOLES ONLY ON CIPP LINED PIPES) GROUT ANNULAR SPACE AS REQ. COAT 4" MIN OF CIPP LINER AT CUT EDGE (SEE NOTE 3) REMOVE EXISTING HOST PIPE CROWN W/ CIPP LINER CUT AND BEVEL CIPP LINER 45 (ALL AROUND) PRIOR TO COATING 4" MIN TYP GROUT ANNULAR SPACE AS REQ. EXISTING CIPP LINER 45 COAT 4" MIN OF CIPP LINER AT CUT EDGE (SEE NOTE 3) MANHOLE INVERT EXISTING CIPP LINER 4" MIN EXISTING DISTRICT PIPE DETAIL B MANHOLE BASE (VIEW SHOWN FOR MANHOLE WITH HOST PIPE & LINER REMOVED) DETAIL A MANHOLE BASE CAST AROUND EXISTING PIPE NOTES: 1. THIS STANDARD DRAWING SHALL APPLY WHERE MANHOLES ARE CONSTRUCTED ON DISTRICT PIPES REHABILITATED WITH CURED-IN-PLACE PIPE LINERS(CIPP). 2. CUT CIPP LINER TO NEAT STRAIGHT LINES WITH CUTTING TOOLS SUITABLE FOR THE LINER MATERIAL. DAMAGED LINERS SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE DISTRICT. 3. REMOVE POLYETHYLENE LAYER IF PRESENT AND ROUGHEN CIPP SURFACE AT ALL CUT EDGES. WHERE FRP LINERS ARE CUT, REMOVE PRE LINER SHEET AND FOIL (IF INSTALLED). SMOOTH LINER EDGE PRIOR TO COATING. 4. CONTRACTOR SHALL COAT CIPP LINER AND EXPOSED CONCRETE AT CHANNEL AND BENCH WITH AN APPROVED EPOXY COATING SYSTEM; NEOPOXY, SEWER SHIELD 100, SAUEREISEN SEWERGARD 210, RAVEN 405 OR APPROVED EQUAL. COATINGS SHALL BE PROVIDED BY A CERTIFIED CONTRACTOR/APPLICATOR IN STRICT ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS. 5. WHERE EXISTING HOST PIPE AND LINER ARE REMOVED PROVIDE A SMOOTH TRANSITION BETWEEN MANHOLE INVERT AND CUT EDGE OF CIPP LINER PER DETAIL B. ND-16 Standard Manhole Detail CIPP Repair

CONNECTING SERVICE LATERAL (MATERIAL AND CONSTRUCTION SHALL CONFORM TO REQUIREMENTS OF APPLICABLE JURISDICTIONAL AGENCY) 45 BEND FLEXIBLE AND WATERTIGHT CONNECTION FITTING - FITTING SHALL HAVE POSITIVE STOP TO PREVENT PROTRUSION INTO SEWER LINE (INSERTA TEE, GPK 4, OR EQUAL) CORE DRILLED OPENING (INSTALLATION OF ANCHOR BOLTS IN THE PIPE WALL OR HAMMER DRILLING SHALL NOT BE ALLOWED AS PART OF THE CORE DRILLING OPERATION) LATERAL SHALL BE FLUSH WITH INSIDE OF PIPE PEA GRAVEL FILL SHALL BE PLACED AND COMPACTED BENEATH CONNECTING SERVICE TO UNDISTURBED SUBGRADE AND TO A MINIMUM DEPTH OF 6" ABOVE PIPE 45 NOTES: 1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TO THE SERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT. 2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTING SERVICE LATERAL. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. 6. CONCRETE CORES SHALL BE RETAINED AND NOT ALLOWED TO FALL INTO THE SEWER LINE. EXISTING DISTRICT PIPE. CONTRACTOR TO VERIFY PIPE MATERIAL PRIOR TO CONSTRUCTION ND-20 Standard Service Connection - Concrete Pipe

CONNECTING SERVICE LATERAL, (MATERIAL AND CONSTRUCTION SHALL CONFORM TO REQUIREMENTS OF APPLICABLE JURISDICTIONAL AGENCY) PVC LATERAL SERVICE ENCASE IN CONCRETE, MINIMUM 12" BELOW & 6" ABOVE 45 SHOP FABRICATED BEND PEA GRAVEL FILL SHALL BE PLACED AND COMPACTED BENEATH CONNECTING SERVICE TO UNDISTURBED SUBGRADE AND TO A MINIMUM DEPTH OF 6" ABOVE PIPE FLEXIBLE AND WATERTIGHT CONNECTION FITTING - FITTING SHALL HAVE POSITIVE STOP TO PREVENT PROTRUSION INTO SEWER LINE AND ENGAGE AT CIPP LINER - (INSERTA TEE OR EQUAL - SEE NOTE 12) NON SHRINK, NON METALLIC GROUT PROVIDE ENCASED FULL STAINLESS STEEL BAND (NON-SHEAR) TYPE. (FERNCO OR APPROVED EQUAL) WHERE CONNECTING TO EXISTING SERVICE LATERAL NOTES: 1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TO THE SERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT. 2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTING SERVICE LATERAL. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. 45 CORE DRILLED OPENING IN HOST PIPE CORE DRILLED OPENING IN CIPP LINER EXISTING CIPP LINER THICKNESS AS PROVIDED BY THE DISTRICT - SEE NOTE 12. EXISTING REHABILITATED DISTRICT PIPE (NTS) 6. SERVICE CONNECTION BANDS, SCREWS, HOUSING AND HARDWARE SHALL BE 316 SST. RUBBER MATERIALS SHALL BE NITRILE OR NEOPRENE UNLESS OTHERWISE DIRECTED BY THE DISTRICT. 7. CONTRACTOR SHALL MANUALLY BACKFILL AND COMPACT AROUND INSERTA TEE OR SADDLE UNTIL A MIN OF 12 OF COVER IS PLACED OVER THE CONNECTION. 8. CORE DRILLING OF CONCRETE PIPE SHALL USE THE WET DIAMOND BIT PROCESS. DO NOT ATTACH GUIDES TO THE EXISTING PIPE TO PERFORM CORE DRILLING. CORE DRILL DIAMETER SHALL BE PER THE CONNECTION MANUFACTURER'S REQUIREMENTS FOR INSTALLATION OF THE PROVIDED PRODUCT. CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED PIPE AND LINER. 9. CORE DRILLING OF THE CIPP LINER SHALL BE ACCOMPLISHED EITHER ROBOTICALLY FROM INSIDE THE PIPE OR EXTERNALLY. DIAMETER OF THE HOLE SHALL BE SIZED FOR THE FLEXIBLE AND WATERTIGHT CONNECTION FITTING. 10. FILL VOIDS, OVER CUT OR REMOVED CONCRETE PIPE WITH NON SHRINK NON METALLIC CEMENT GROUT. 11. CONCRETE AND CIPP LINER CORES SHALL BE RETAINED AND NOT ALLOWED TO FALL INTO THE SEWER LINE. 12. INSERTA TEE PROVIDED SHALL BE PER TABLE 1 UNLESS OTHERWISE RECOMMENDED BY THE MANUFACTURER BASED ON THE EXISTING REHABILTATED DISTRICT PIPE DIAMETER, SERVICE CONNECTION DIAMETER, AND EXISTING CIPP LINER THICKNESS. CONTRACTOR SHALL VERIFY THE LINER THICKNESS PRIOR TO INSTALLING THE CONNECTION INTO THE CORED LINER. ND-21 Standard Service Connection - CIPP Lined Pipe 1 of 2

TABLE 1 Rehabilitated District Concrete Pipe CIPP Liner Thickness INSERTA - TEE ORDERING INFORMATION Lateral Nominal Diameter (inch) Standard CIPP INSERTA-TEE LINER: RUBBER SLEEVE THICKNESS* Nominal Pipe Diameter (in) Minimum Liner Thickness (mm) Maximum Liner Thickness (mm) 4 6 8 Minimum Liner Thickness (mm) 12 3.5 5.0 4P26FB12CIP 6P26FB12CIP 8P3512CIP 8.0 15 4.5 6.0 4P26FB15CIP 6P26FB15CIP 8P3515CIP 10.5 18 5.0 8.0 4P26FB18CIP 6P26FB18CIP 8P3518CIP 10.5 21 5.5 7.0 4P26FB21CIP 6P26FB21CIP 8P3521CIP 10.5 24 7.0 9.0 4P26FB24CIP 6P26FB24CIP 8P3524CIP 14.0 27 8.0 10.0 4P26FB27CIP 6P26FB27CIP 8P3527CIP 14.0 30 8.0 12.0 4P26FB30CIP 6P26FB30CIP 8P3530CIP 16.0 36 8.0 12.0 4P26FB36CIP 6P26FB36CIP 8P3536CIP 19.0 WHEN ORDERRING INSERTA TEE, CONTRACTOR SHALL PROVIDE THE NOMINAL DISTRICT PIPE DIAMETER, LATERAL DIAMETER AND MATERIAL TO BE INSTALLED, AND EXISTING CIPP LINER THICKNESS TO VERIFY PROPER SIZING OF THE RUBBER SLEEVE. INSERTA TEE WITH RUBBER SLEEVE THICKNESS SIZED FOR STANDARD CIPP LINER THICKNESS WITHOUT VERIFICATION SHALL NOT BE ACCEPTED BY THE DISTRICT. ND-21 Standard Service Connection - CIPP Lined Pipe 2 of 2

CONNECTING SERVICE LATERAL, (MATERIAL AND CONSTRUCTION SHALL CONFORM TO REQUIREMENTS OF APPLICABLE JURISDICTIONAL AGENCY) ENCASE IN CONCRETE, MINIMUM 12" BELOW & 6" ABOVE 45 SHOP FABRICATED BEND PEA GRAVEL FILL SHALL BE PLACED AND COMPACTED BENEATH CONNECTING SERVICE TO UNDISTURBED SUBGRADE AND TO A MINIMUM DEPTH OF 6" ABOVE PIPE FLEXIBLE AND WATERTIGHT CONNECTION FITTING - FITTING SHALL HAVE POSITIVE STOP TO PREVENT PROTRUSION INTO SEWER LINE (INSERTA TEE OR EQUAL) NON SHRINK, NON METALLIC GROUT CORE DRILLED OPENING PROVIDE ENCASED FULL STAINLESS STEEL BAND (NON-SHEAR) TYPE. (FERNCO OR APPROVED EQUAL) WHERE CONNECTING TO EXISTING SERVICE LATERAL 45 EXISTING CCFRPM (FIBERGLASS) DISTRICT PIPE (18" DIA OR GREATER) NTS. NOTES: 1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TO THE SERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT. 2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTING SERVICE LATERAL. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. 6. SERVICE CONNECTION BANDS, SCREWS, HOUSING AND HARDWARE SHALL BE 316 SST. RUBBER MATERIALS SHALL BE NITRILE OR NEOPRENE UNLESS OTHERWISE DIRECTED BY THE DISTRICT. 7. CONTRACTOR SHALL MANUALLY BACKFILL AND COMPACT AROUND INSERTA TEE UNTIL A MIN OF 12 OF COVER IS PLACED OVER THE CONNECTION. 8. CORE DRILLING OF PIPE SHALL BE PERFORMED USING CUTTING EQUIPMENT RECOMMENDED BY MANUFACTURERS OF FIBERGLASS PIPE. DO NOT ATTACH GUIDES TO THE EXISTING PIPE TO PERFORM CORE DRILLING. CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED PIPE. 9. FLEXIBLE AND WATERTIGHT FITTING SHALL BE SIZED FOR THE CCFRPM PIPE. 10. FIBERGLASS CORES SHALL BE RETAINED AND NOT ALLOWED TO FALL INTO THE SEWER LINE ND-22 Standard Service Connection - CCFRPM Fiberglass Pipe

EXISTING SERVICE LATERAL, ABANDON IN PLACE ENCASE CAP IN CONCRETE THRUST BLOCK EXISTING DISTRICT PIPE REMOVE INTERFERING PORTIONS OF EXISTING SERVICE LATERAL, CUT AND CAP PIPE (TYP) ROW INSTALL WATER TIGHT EXPANSION PLUG AT EXISTING SERVICE LATERAL CONNECTION TO MAIN EXISTING SERVICE LATERAL, VARIES NOTES: 1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION. 2. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS. 3. CONCRETE THRUST BLOCKS SHALL BE A MINIMUM ONE CUBIC FOOT IN SIZE PLACED AT CAP TO PREVENT DISPLACEMENT OF CAP DURING SEWER CLEANING AND OTHER MAINTENANCE ACTIVITIES. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI PER ASTM C39. 4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR. ND-23 Standard Service Connection Abandonment

CRACKED PIPE SECTION REINFORCED CONCRETE ENCASEMENT 2 x EXISTING PIPE OD BUT NOT LESS THAN 12" A DISTRICT PIPE GRAVEL BEDDING REINFORCEMENT STEEL, 4 - CONT #4 #4 @ 24" OC MIN (2) EACH SIDE OF REPAIR COUPLING, MIN 3" CLR STAINLESS STEEL REPAIR COUPLING OVER CRACKS NOTES: 1. REPAIR COUPLINGS SHALL PROVIDE A WATER TIGHT SEAL AND BE MANUFACTURED FOR USE WITH THE GRAVITY SEWER PIPE MATERIAL TO BE REPAIRED. CONTRACTOR SHALL SUBMIT PRODUCT DATA FOR REVIEW AND ACCEPTANCE BY THE DISTRICT. 2. ALL HARDWARE (SHELLS, NUTS, BOLTS, WASHERS, TAKE UP CLAMPS OR RINGS) SHALL BE TYPE 304 STAINLESS STEEL PER ASTM A240 UNLESS OTHERWISE APPROVED BY THE DISTRICT. 3. GASKETS SHALL BE FULL LENGTH CIRCUMFERENTIAL SBR OR NITRILE (BUNA-N) UNLESS OTHERWISE APPROVED BY THE DISTRICT. 4. REPAIRS SHALL BE INSPECTED AND APPROVED BY THE DISTRICT PRIOR TO ENCASEMENT AND BACKFILLING. 5. CONRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI PER ASTM C39. NO ADDITIVES SHALL BE PERMITTED WITHOUT PRIOR APPROVAL BY THE DISTRICT. 6. MINIMUM ENCASEMENT SHALL BE AS FOLLOWS: NOMINAL DIAMETER (IN) A (IN) ENCASEMENT 24" OR LESS 6 OD + 12 33" OR LESS 8 OD + 16 39" OR LESS 10 OD + 20 42" OR LARGER 12 OD + 24 ND-30 Cracked Pipe Repair

12" MIN TRENCH WIDTH 12" MIN 6" MIN OD 6" MIN EXIST PIPE 6" MIN 24" MAX (SEE NOTE 3 AND 4) 1/2" FELT EXPANSION JOINT FILLER CLASS B CONCRETE NEW SEWER PIPE 1/2 OD 1/2"EXPANSION JOINT FILLER MATERIAL ALL AROUND, SEE NOTE 2 6" SCH 80 PVC DRAIN HOLE FILL W/ PEA GRAVEL (TYP) PROVIDE BEDDING PER DISTRICT REQUIREMENTS EXISTING PIPE OVER NEW SEWER MAIN ND-31 Structural Support at Crossings 1 of 2

NEW SEWER PIPE 12" MIN TRENCH WIDTH 12" MIN 1/2"EXPANSION JOINT FILLER MATERIAL ALL AROUND, SEE NOTE 2 6"MIN OD 6"MIN SPRINGLINE 6"MIN 24" MAX (SEE NOTE 3 AND 4) 1/2" FELT EXPANSION JOINT FILLER IF CONCRETE EXTEND UP TO BOTTOM OF NEW PIPE EXIST PIPE CLASS B CONCRETE DO NOT DISTURB EXISTING PIPE BEDDING BELOW SPRINGLINE OF PIPE SECTION D UNDISTURBED SOIL (TYP) D - EXISTING PIPE UNDER NEW SEWER MAIN NOTES: 1. INSTALL #15 FELT OR NEOPRENE WATERSTOP AROUND NEW WATER PIPE PRIOR TO THE POUR OF CONCRETE ENCASEMENT TO PREVENT BONDING. 2. BACKFILL TO BE BROUGHT UP UNIFORMLY ON BOTH SIDES OF CONC. SUPPORT. 3. THIS DETAIL SHALL APPLY WHERE VERTICAL CLEARANCE OUTSIDE TO OUTSIDE OF SEWER PIPE OR LATERAL IS LESS THAN 24-INCH. 4. WASTEWATER LINES SHALL BE INSTALLED BELOW POTABLE WATER LINES. A MINIMUM SEPARATION OF 18 INCHES BETWEEN THE BOTTOM OF THE POTABLE WATER LINE AND THE TOP OF THE WASTEWATER LINE SHALL BE MAINTAINED. WHERE A POTABLE WATERLINE CROSSES UNDER A WASTEWATER OR STORM LINE, A FULL LENGTH OF PIPE SHALL BE CENTERED ABOVE THE WATER LINE SO THAT BOTH JOINTS WILL BE AS FAR FROM THE POTABLE WATER LINE AS POSSIBLE. ADDITIONAL MITIGATION MEASURES MAY BE REQUIRED PER UTAH DEQ AND R309-105-6(2)(b). ND-31 Structural Support at Crossings 2 of 2