Degrees of protection. IP codes. W.M.M. Menheere Holec Holland N.V. The Netherlands



Similar documents
Technical application guide IP codes in accordance with IEC 60529

White Paper IK code: Impact protection in line with the IEC standard. By Sven Schnautz

Disclosure to Promote the Right To Information

SAFETY ALERT SWITCHBOARD INTERNAL SEGREGATION AND IP RATING. May 2014 BACKGROUND

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

ANSI/IEC Degrees of Protection Provided by Enclosures (IP Code) (identical national adoption)

FAQs-Main switchboard design criteria

Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC. BU 3101 Low Voltage Systems June 27, 2013 Slide 1

Tables Technical data Standards Explanations Increased safety e

Solving the Problem of Motor Protection from Moisture, Water and Dust in Commercial Refrigerators.

Technical Application Papers No.11 Guidelines to the construction of a low-voltage assembly complying with the Standards IEC Part 1 and Part 2

Unified requirements for systems with voltages above 1 kv up to 15 kv

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Dorman Smith PowerForm Low Voltage Factory Built Assemblies

NEMA Enclosure Types

Understanding LED Drivers

Securing your electrical installations Prisma,

Explosion proof enclosures

IP Probes: Test Probe A

IP Rating Chart. 910 East Orangefair Lane Anaheim, CA USA , Fax

General information. Your Connection to Light

SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A

OVERVIEW EMERGENCY CALL & INFORMATION PILLARS

ATL Fuel Level Sender Probes

MIT510/2, MIT520/2 and MIT1020/2

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ANSI/NEMA-FL1 Standard. Heroes Trust Streamlight

Ex q Powder Filling. This is a technique primarily used for oil filled switch-gear. The spark is formed under oil and venting is controlled.

Installing PoE for Outdoor Deployments. White Paper

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Common Features of Electromechanical Switches

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Electrical Injuries, Dangers and Prevention

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

INSTALLATION. General. Important Note. Design. Transport

HAZARDOUS AREA TECHNICAL GUIDE

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Liquid Level Limit Switch liquiphant T FTL 20

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

ODU MEDI-SNAP. Miniature Circular Connectors with Push-Pull Locking Made of Plastic or Metal.

SELECTION GUIDE FOR OUR JOYSTICK CONTROLLERS

Life Insurance for Switches & Circuit Breakers

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

MINI BUBO design Fabio Rotella

IEC specifications for LV assembly switchboards

RAPPORTO DI PROVA TEST REPORT

David O Brien, CMP Products (David.OBrien@cmp-products.com)

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U Technical characteristics types D and E

Transformer Bushings for GIS

ENVIRONMENTAL TESTING

2CP. Twin-impeller pumps PERFORMANCE RANGE INSTALLATION AND USE APPLICATION LIMITS OPTIONALS AVAILABLE ON REQUEST CONSTRUCTION AND SAFETY STANDARDS

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

The easy way to build switchgear and controlgear assemblies in compliance with the regulations

Basics of Explosion Protection

Machine Safety Switches

WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

This section applies to the design and installation of transformers.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

know-how Giant in distributing electricity for industry Prisma GK

Operating instructions

Comparative study for cables and busbars

Interference Suppression Film Capacitors MKP Radial Potted Type

Access and Object Testing Probes

Rapide Inline Ceiling Extractor Fan, White Fascia Rapide Inline Ceiling Extractor Fan, Chrome Fascia

Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W

OPERATING PRINCIPLES FOR PHOTOELECTRIC SENSORS

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.


ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of

VdS en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS en : (01)

italtec PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Product catalogue, pipe and sewer cleaning systems

Test Report No. C829QPEN

CLASSIFICATION NOTES

HVAC air curtains. Type InduAir

MOUNTING AND OPERATING INSTRUCTIONS

D.C. Motors. Products and specifications subject to change without notice.

- CONSTRUCTIONS 300 SECTIONAL VIEW 300 MECHANICAL SEAL DIMENSIONS AND WEIGHT 400 PUMP 400 PACKING 401

Installation and safety instructions for AC/DC built-in devices

Cross-beam scanning system to detect slim objects. 100 mm in

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

Mounting Instructions. Torque Transducer. A en

COMPACT. Drilling COMPACT

Technical data UNIBLOCK UBSF

MINISTRY OF THE ENVIRONMENT, CLIMATE PROTECTION AND THE ENERGY SECTOR

Emergency safety showers Part 3: Body showers for production and logistic sites

DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155

Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****

INTERNATIONAL STANDARD

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles. Prepared for: Ben Hales

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

Transcription:

Degrees of protection IP codes W.M.M. Menheere Holec Holland N.V. The Netherlands 1

INDEX Introduction...3 1. The IEC protection code (International Protection IP)...3 2. Interpreting the IP code...3 3. Optional letters...4 4. Elements of the IP Code and their meanings:...5 5. Examples of IP codes...6 6. Access probes for testing of persons against access to hazardous parts:...8 7. Test means for the tests for protection against solid foreign objects:...10 8. Test means and main test conditions for the test for protection against water...10 9. Examples of situations:...11 10. Conclusion:...13 11. References:...13 2

Degrees of Protection Introduction Equipment has to fulfil its functional requirement. But only that is not enough. The equipment has also to be protected against possible external influences and the equipment may not be harmful to the user or operator or to the environment. Several means or combination of means can be used to comply with the requirements: Placing out of reach, for instance by means of an obstacle; Total insulation, which is not easily applicable for moving parts; Use of an enclosure To support the easy use of understanding between user and manufacturer this requirement IEC60529 is made. This requirement can be used for electronic equipment as for telecommunication equipment as well as for high-voltage as for low-voltage equipment or rotating machines. The enclosure can be build as a part of the equipment or as a loose component, sold empty. 1. The IEC protection code (International Protection IP) The IP codes are used to define protection against the ingress of solid foreign objects and water with harmful effects. Since the IP code is used for all equipment annex B of the IEC standard gives instructions to technical committees for applying IP codes. The protection against the ingress of solid foreign objects is also used as a means of specifying protection against accidental contact with live parts and therefore serves two different but related purposes. 2. Interpreting the IP code The IP code defined in the second edition of "IEC60529 Degrees of protection provided by enclosures (IP code)" consists of 2 numerals and 2 optional extra letters. The first numeral 0, 1,...6, or X defines the protection against ingress of solid foreign objets and against access to hazardous parts. The second numeral 0, 1,...8, or X defines the protection against the ingress of water. Arrangement of the IP Code: IP 2 3 C H Code letters (International Protection) First characteristic numeral (numerals 0 to 6, or letter X) Second characteristic numeral (numerals 0 to 8, or letter X) Additional letter (optional) (letters A, B, C, D) Supplementary letter (optional) (Letters H, M, S, W) The higher the number the more stringent the protection requirement. The standard defines the protection corresponding to each number and the method of testing for compliance. The first number serves 2 purposes and therefore it has 2 definitions and 2 test methods. protection of persons against access to harmful parts and protection of equipment against ingress of foreign bodies. To check compliance with the first numeral, two probes must therefore be used (an access-probe and an object-probe) with the application forces specified in the standard, or the same probe is used with two acceptance criteria. Where there is no requirement for protection against either solid objects or water, the letter X is used instead of a numeral. 3

An example of this is sub-clause 5.13.2 of "IEC60694 Common specifications for high-voltage switchgear and controlgear" which defines the second numeral as being X since no protection against ingress of water is specified. This is understandable for high-voltage indoor equipment which is normally installed in electrical rooms having controlled access. Specifying protection against the ingress of water should be done only if there is a real danger of much water falling on the equipment. The test requirement for numeral 1 calls for at least 10mm of water dripping on the enclosure during a 10 minute period. This is much more than just a bit of condensation. In general, for the first characteristic numeral, adequate clearance is sufficient. That means for lowvoltage equipment that the access probe shall not touch the hazardous parts. For high-voltage equipment it means that when the access probe is placed in the most unfavourable position it must be possible to withstand the dielectric test applicable to the equipment. For equipment with hazardous mechanical parts the access probe shall not touch hazardous mechanical parts. To pass the test for the first characteristic numerals 1, 2, 3, and 4 against solid foreign objects it is satisfactory if the full diameter of probe does not pass through any opening. To pass the test for the first characteristic number 5 it is satisfactory if talcum powder has not accumulated in a quantity or location such that it could interfere with correct operation of equipment or impair safety. To pass the test for the first characteristic number 6 it is satisfactory if no deposit of dust is observable inside the enclosure at the end of the test. To pass the test for the second characteristic numerals it is sufficient that in general, if any water has entered there are no harmful effects on operation, safety or insulating parts. To pass the test for the additional letter for protection against access of hazardous parts it is sufficient that adequate clearance is kept between the access probe and hazardous parts. 3. Optional letters Sub-clause 7 of IEC60529 allows the use of an additional letter A, B, C, or D to indicate protection of persons against access to hazardous parts. For example, such higher protection may be provided by barriers, suitable shape of openings or distances inside the enclosure. Additional letters are only used: if the actual protection against access to hazardous parts is higher than indicated by the first characteristic numeral; or if only the protection against access to hazardous parts is indicated, first numeral being then replaced by an X. An example of this is sub-clause 7.7 "IEC60439 Low-voltage switchgear and controlgear assemblies" which specifies the protection against contact with hazardous parts belonging to adjacent functional units as being at least IPXXB. Sub-clause 8 of IEC60529 allows the use of supplementary letters H, M, S, or W to indicate additional requirements generally associated with the ingress of water. As an example; sub-clause 5.13.2 of IEC60694 states that outdoor equipment should use the supplementary letter W rather than a second numeral (for example IP5XW) and gives the specific test procedure to be used. General rule with regard to IP Code: An enclosure shall only be designated with a stated degree of protection indicated by the IP Coding if the enclosure also complies with all lower degrees of protection. 4

4. Elements of the IP Code and their meanings: Element Numerals or letters Meaning for the protection of equipment Code letters IP - - Meaning for the protection of persons First characteristic numeral X 0 1 2 3 4 5 6 Against ingress of solid foreign objects: not required (non-protected) 50 mm diameter 12,5 mm diameter 2,5 mm diameter 1,0 mm diameter dust-protected dust-tight Against access to hazardous parts with: not required (non-protected) back of hand finger tool wire wire wire Second characteristic numeral X 0 1 2 3 4 5 6 7 8 Against ingress of water with harmful effects: not required (non-protected) vertically dripping dripping (15 tilted) spraying splashing jetting powerful jetting temporary immersion continuous immersion - Additional letter: optional Against access to hazardous parts with: A B C D - back of hand finger tool wire Supplementary Letter: optional H M S W Supplementary information specific to: High voltage apparatus Motion during water test Stationary during water test Weather conditions - 5

5. Examples of IP codes IP00 This code means that there is no protection at all. A typical example is a dry-type transformer without any enclosure. The transformer would be installed indoors in a bay having a door in order to prevent accidental contact with live parts. IPXXB This means protection against ingress of solid foreign objects and water is not required and access to hazardous parts is protected for incidental contact with fingers. IP2X This is the IP code necessary to prevent access to hazardous parts with fingers and protects the equipment inside the enclosure against ingress of solid foreign objects having a diameter of 12.5 mm and greater. IP3XD This is a typical IP code for high-voltage and low-voltage switchgear and controlgear located in electrical rooms and access to hazardous parts for protection of persons handling wires. IP53 This is the minimum IP code that should be used for equipment installed outdoors. IP54 would be a better choice since the second numeral 4 means protection against water coming from all directions whereas the numeral 3 means protection against water coming from an angle of 60. Table with examples: DEGREE OF PROTECTION Protected Against Definition IP0X Non-protected - IP1X Access to hazardous parts with the back of a hand. An access probe, sphere of 50 mm Ø, shall have adequate clearance from hazardous parts. Solid foreign objects of 50 mm Ø. An object probe, sphere of 50 mm Ø, shall not fully penetrate. IPXXB Access to hazardous parts with finger. A jointed test finger of 12 mm Ø, 80 mm length, shall have adequate clearance from hazardous parts Solid foreign objects not required. - IP2X Access to hazardous parts with finger. A jointed test finger of 12 mm Ø, 80 mm length, shall have adequate clearance from hazardous parts Solid foreign objects of 12.5 mm Ø. An object probe, sphere of 12.5 mm Ø, shall not fully penetrate. IP3X Access to hazardous parts with a tool. An access probe of 2.5 mm Ø shall have adequate clearance. Solid foreign objects of 2.5 mm Ø. An object probe of 2.5 mm Ø shall not penetrate at all. IP3XD Access to hazardous parts with a wire. An access probe of 1 mm Ø shall have adequate clearance. Solid foreign objects of 2.5 mm Ø. An object probe of 2.5 mm Ø shall not penetrate at all. IP4X Access to hazardous parts with a wire. An access probe of 1.0 mm Ø shall have adequate clearance. Solid foreign objects of 1.0 mm Ø. An object probe of 1.0 mm Ø shall not penetrate at all. IP5X Access to hazardous parts with a wire. An access probe of 1.0 mm Ø shall have adequate clearance. Dust (protected). Ingress of dust is not totally prevented, but dust shall not penetrate in a sufficient quantity to interfere with satisfactory operation of the apparatus or to impair safety. IP6X Access to hazardous parts with a wire. An access probe of 1.0 mm Ø shall have adequate clearance. Dust (tight). No ingress of dust. 6

Protected Against IPX0 Non-protected. - DEGREE OF PROTECTION Definition IPX1 Vertically falling water drops. Vertically falling drops shall have no harmful effects. IPX2 Vertically falling water drops when enclosure tilted up to 15º. Vertically falling drops shall have no harmful effects when the enclosure is tilted at any angle up to 15º on either side of the vertical. IPX3 Spraying water. Water sprayed at an angle up to 60º on either side of the vertical shall have no harmful effects. IPX4 Splashing water. Water splashed against the enclosure from any direction shall have no harmful effects. IPX5 Water projected in jets against the enclosure from any Water jets. direction shall have no harmful effects. IPX6 Powerful water jets. Water projected in powerful jets against the enclosure from any direction shall have no harmful effects. IPX7 IPX8 The effects of temporary immersion in water. The effects of continuous immersion in water. Ingress of water in quantities causing harmful effects shall be prevented when the enclosure is immersed in 1m of water for 30 minutes. Ingress of water in quantities causing harmful effects shall be prevented when the enclosure is continuously immersed in water under conditions which shall be agreed between manufacturer and user (>IPX7). Examples of designations with the IP Code: IP Code not using optional letters: I P 3 4 An enclosure with this designation (IP Code): (3) - protects persons, handling tools having a diameter of 2,5 mm and greater, against access to hazardous parts; - protects the equipment inside the enclosure against ingress of solid foreign objects having a diameter of 2,5 mm and greater; (4) - protects the equipment inside the enclosure against harmful effects due to water splashed against the enclosure from any direction. Examples of designations with the IP Code: IP Code using optional letters: I P 2 3 C S (2) - protects persons against access to hazardous parts with fingers; - protects the equipment inside the enclosure against ingress of solid foreign objects having a diameter of 12,5 mm and greater; (3) - protects the equipment inside the enclosure against harmful effects due to water sprayed against the enclosure; (C) (S) - protects persons handling tools having a diameter of 2,5 mm and greater and a length not exceeding 100 mm against access to hazardous parts (the tool may penetrate the enclosure up to its full length); - is tested for protection against harmful effects due to ingress of water when all the parts of the equipment are stationary. 7

6. Access probes for testing of persons against access to hazardous parts: Access probe: Sphere 50 mm diameter; test force 50N +/- 10% 4 10 45 Sphere 50 +0,005 0 Handle Guard (Insulating material) Rigid test sphere (Metal) Access probe: Jointed test finger; test force 10N +/- 10% Stop face ( 50 20 ) 12 Jointed test vinger (Metal) Insulating material 80 Access probe: Test rod 2,5mm diameter, 100mm long; test force 3N +/- 10% Approx. 100 Sphere 35 ± 0,2 100 ± 0,2 10 Handle (Insulating material) Stop face (Insulating material) Rigid test rod, 2,5 (Metal) + 0,05 0 Edges free from burrs 8

Access probe: Test wire 1,0mm diameter, 100mm long; test force 1 N +/- 10% Approx. 100 Sphere 35 ± 0,2 100 ± 0,2 10 Handle (Insulating material) Stop face (Insulating material) Rigid test rod, 1 (Metal) + 0,05 0 Edges free from burrs Object probes and test means for the test for protection against solid foreign objects Example of test for second characteristic numeral 1: Drip box Xiria installation under test 9

7. Test means for the tests for protection against solid foreign objects: First numeral Test means (object probes and dust chamber) Test force 0 No test required - 1 Rigid sphere without handle or guard 50N ± 10% (50mm diameter) 2 Rigid sphere without handle or guard 30N ± 10% (12,5mm diameter) 3 Rigid steel rod 2,5mm diameter with 3N ± 10% edges free from burrs 4 Rigid steel wire 1mm diameter with 1N ± 10% edges free from burrs 5 Dust chamber, with or without - underpressure 6 Dust chamber, with underpressure - 8. Test means and main test conditions for the test for protection against water Second numeral Test means Water flow rate Duration of test 0 No test required - - 1 Drip box 1 mm/min. 10 min. 2 Drip Box (Enclosure 15 tilted) 3 mm/min. 10 min. 3 Oscillating tube: distance max. 200mm / Spray nozzle; Spray ±60 from vert. 10 l/min. 1 min/m 2 ( 5 min) 4 As for 3; Spray ±180 from vert. 5 Water jet hoze nozzle 6,3mm; distance 2,5 to 3m 12,5 l/min. 1 min/m 2 ( 3 min) 6 Water jet hoze nozzle 12,5mm; distance 2,5 to 3m 7 Immersion tank; water-level on enclosure 0,15m above top, 1m above bottom 8 Immersion tank; water-level by agreement 100 l/min. - 30 min. - by agreement 10

9. Examples of situations: Situation 1: IP Code: IP 0X Sphere 50 Situation 2: Sphere 50 IP Code: IP 1X (1X + A = 1X) Situation 3: IP Code: IP 1X (1X + A = 1X) 12 Sphere 12,5 Situation 4: 12 IP Code: IP 1XB (1X + B = 1XB) 30 11

Situation 5: 2,5 1,0 IP Code: IP 2XC (2X + C = 1XC) Situation 6: IP Code: IP 2XD (2X + D = 2XD) 2,5 1,0 Situation 7: 1,0 IP Code: IP 4X (4X + D = 4XD) Situation 8: Sphere 35 IP Code: IP 1XD (1X + D = 1XD) 1 100 > 12,5 < 20 12

Situation 9: IP Code: IP 1XB (1X + B = 1XB) Sphere 12,5 15 Situation 10: IP Code: IP 2X (2X + B = 2X) Sphere 12,5 12,3 Situation 11: IP Code: IP 3XD (3X + D = 3XD) 1,0 2 10. Conclusion: In general: for protection against direct contact with hazardous parts IP 2X or IP XXB is required In Holec products MMS, Unitole en Xiria installations the protection of persons against access to hazardous parts is IP 3XD and for SVS IP2XD. 11. References: IEC60529 Second edition 1989-11 + Am. 1 1999-11, EN60529, Degrees of protection provided by enclosures by CEI. Degrees of protection provided by enclosures (IP codes) M-124, Course (Syria - Damascus) 21 May 2002, Mr M. Leusenkamp, Holec, The Netherlands. Enclosures and degrees of protection, Çahier Technique N. 166 first issued January 1993, Mr. Jean Pasteau, Schneider Electric. 13