Small wind PV-curves Schoondijke



Similar documents
Produce electricity in your own backyard.

ENERCON WIND TURBINES

Excerpts from: Performance, Duration and Acoustic test reports for the Skystream 3.7 wind generator

INTERNATIONAL STANDARD

ENERGY YIELD ASSESSMENT

The Reliance on Wind Energy Depends on Advancements in Blade Pitch Control

Relevance of Modern Optimization Methods in Turbo Machinery Applications

TECHNICAL SPECIFICATION

Lab 14: 3-phase alternator.

V kw The turbine that goes anywhere

CASE STUDY. History. National Renewable Energy Laboratory Testing Wind Turbine Power Generators using PULSE. United States of America

DIRECT MATCHING TO GRID WITHOUT INVERTER VARIABLE PITCH. 20/24/30 mt TOWER WITH HYDRAULIC SYSTEM YAWING SYSTEM SAFETY LEVELS PLC CONTROL

INDUCTION REGULATOR. Objective:

Letter Report No CRT-004 Project No. G

DATA VALIDATION, PROCESSING, AND REPORTING

THE EFFECT OF BLADE ANGLE AND SIZE ON WIND TURBINE PERFORMANCE

Directions for Frequency Tables, Histograms, and Frequency Bar Charts

V MW & V MW (OFFSHORE)

Sound Power measurements according to IEC

Template 1: Test Helicopter

Adjustment of Anemometer Readings for Energy Production Estimates WINDPOWER June 2008 Houston, Texas

Chapter 27 Using Predictor Variables. Chapter Table of Contents

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Micropower from Tidal Turbines

Aeroelastic Investigation of the Sandia 100m Blade Using Computational Fluid Dynamics

INTERNATIONAL STANDARD

Current Profiles at the Offshore Wind Farm Egmond aan Zee J.W. Wagenaar P.J. Eecen

Answer Key to Midterm

Gestation Period as a function of Lifespan

Microsoft Excel Tutorial

Equipment Performance Monitoring

MEASURES OF CENTER AND SPREAD MEASURES OF CENTER 11/20/2014. What is a measure of center? a value at the center or middle of a data set

in-service inspections

Óbuda University Power System Department. The wind. Dr. Péter Kádár Óbuda University, Power System Department, Hungary

Document number #12 DNS Authors #20 Telephone: Date #40 AUGUST 2013

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).

The recording angle based on localisation curves

Siemens Wind Turbine SWT The new productivity benchmark.

Development of 5-MW Offshore Wind Turbine and 2-MW Floating Offshore Wind Turbine Technology

Vertical Axis Wind Turbine at WVU Tech. Alex Perry, Tavon Johnson Undergraduate Mechanical Engineering Students

Permanent Magnetic Generator Construction Manual

Datum > Curve KIM,ME,NIU

WIND TURBINE TECHNOLOGY

Risø-R-1374(EN) Design of a 21 m Blade with Risø-A1 Airfoils for Active Stall Controlled Wind Turbines

8 Speed control of Induction Machines

The BASIS module in WindPRO is necessary for the use of any of the other calculation modules. It contains the four following elements:

The Delft Offshore Wind Turbine Concept (DOT)

Comparison between OpenFOAM CFD & BEM theory for variable speed variable pitch HAWT

Data Analysis Tools. Tools for Summarizing Data

SUSTAINABLE TECHNOLOGY

Wind Turbines - Biggest 5G Turbine Market Ever

Chapter 32 Histograms and Bar Charts. Chapter Table of Contents VARIABLES METHOD OUTPUT REFERENCES...474

Plotting: Customizing the Graph

Transient Wind Events and Their Effect on Drive-Train Loads INTERNATIONAL. siteurpublications

Wind Energy Math Calculations Calculating the Tip Speed Ratio of Your Wind Turbine

UCCS PES/ENSC 2500: Renewable Energy Spring 2014 Test 3 name:

Advanced nacelle anemometry and SCADA-data, analysis techniques and limitations. Frank Ormel Chief Specialist in Product Integration Vestas

Relative Power Curve Measurements Using Turbine Mounted, Continuous-Wave Lidar

InfiniteInsight 6.5 sp4

Exploratory data analysis (Chapter 2) Fall 2011

Wind Resource Assessment for BETHEL, ALASKA Date last modified: 2/21/2006 Compiled by: Mia Devine

v w is orthogonal to both v and w. the three vectors v, w and v w form a right-handed set of vectors.

IMPACT OF TRAUMA HELICOPTERS ON AIR QUALITY INSIDE HOSPITALS. J.F.W. Koopmans Peutz bv, Mook, The Netherlands,

Qualitative Analysis of Power Distribution Configurations for Data Centers

INFLUENCES OF VERTICAL WIND PROFILES ON POWER PERFORMANCE MEASUREMENTS

VDI FIT and VDI UX: Composite Metrics Track Good, Fair, Poor Desktop Performance

School of Engineering Department of Electrical and Computer Engineering

FTS Real Time System Project: Using Options to Manage Price Risk

MBA 611 STATISTICS AND QUANTITATIVE METHODS

CT Application Guide for the 489 Generator Management Relay

PMDD WIND TURBINE 1.5MW

V kw. Pitch regulated wind turbine with OptiTip and OptiSlip

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

Exercise 1.12 (Pg )

Haliade 150-6MW Experiencia funcional con la nueva generación offshore

Wind Turbine Power Calculations

Performance Comparison of a Vertical Axis Wind Turbine using Commercial and Open Source Computational Fluid Dynamics based Codes

AERODYNAMIC ANALYSIS OF BLADE 1.5 KW OF DUAL ROTOR HORIZONTAL AXIS WIND TURBINE

Principles and Working of DC and AC machines

BAAN IVc/iBaan ERP 5.0c, 5.2a. Integration Guide for Crystal Reports 8.5

APPENDIX A Using Microsoft Excel for Error Analysis

Using Renewable Energy To Recharge Industrial Forklifts At Borroughs Corporation

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

Experimental Wind Turbine Aerodynamics

AIMMS Tutorial for Professionals - Absentee and Planning Overviews

Univariate Regression

PMG vs. DFIG the big generator technology debate

Where and Why Does the Wind Blow?

TRITON CPM. Cylinder Pressure Control & Monitoring. Replaces mechanical indicators on diesel engines. Helps to improve combustion

Reflection and Refraction

Inverters & Variable Frequency Drives

Upwind 20MW Wind Turbine Pre- Design

Basics of Electricity

IV. Three-Phase Induction Machines. Induction Machines

Appendix 2.1 Tabular and Graphical Methods Using Excel

EFFECTS OF COMPLEX WIND REGIMES ON TURBINE PERFORMANCE

Transcription:

PV-curves of 7 small wind turbines based on test results of Schoondijke, The Netherlands Repport 1009000.R01 September 24, 2010

. c Ingreenious BV. No part of this publication may be reproduced, stored in a tetrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of the author. Opdrachtgever: Project Group Schoondijke Rapport nummer: 1009000.R01 Datum: September 24, 2010 Auteur: dr. Sander Mertens E-mail: sandermertens@ingreenious.com Website: www.ingreenious.com

Summary The PV-curves of 7 small wind turbines are calculated from the measurements gathered at open air test facility Schoondijke in the Netherlands. The PV-curves are calculated from binned samples of the wind speed and energy yield. These samples had a sample frequency of once every 5 minutes. As a consequence of this procedure, the PV-curves are comparable to the PV-curves measured according to the IEC-61400 procedure up to a wind speed of approximately 10 m/s. Down times of the wind turbines are calculated from the % of time where the power output equals zero at a wind speed of 6 m/s or higher. The PV-curves show sometimes high cut in wind speeds for urban applications and actual performances are not always what manufacturers claim. Down times of the wind turbines vary an order of magnitude. I

Contents Summary 1 1 On the analysis 2 1.1 PV-curves calculation............................... 2 1.2 Interpretation of the results............................ 3 2 The results 5 2.1 Down time..................................... 5 2.2 PV-curves...................................... 5 1

Chapter 1 On the analysis 1.1 PV-curves calculation The PV-curves are destilled from the measurements of the average energy yield per 5 minutes as a function of the wind speed, sampled once every 5 minutes. As a consequence, the power of the small wind turbines P is calculated from P = E 12 (1.1) The power P is binned to bins of 0.5 [m/s]. The wind speed is taken as the bin centre. The PV-curves are based on the measurements of the past two measurement years (Default), except for the Donqi and Raum: Default (date/month/year): 8/4/2008-8/9/2010 Donqi (date/month/year): 27/5/2010-8/9/2010 Raum (date/month/year): 1/4/2009-1/4/2010 All measurements are used except those where P=0 [Watt] at V>6 [m/s]. It should be stressed that wind directions in line with the row of turbines and wind directions where the wind turbines are located downwind of the neighbouring buildings, are part of these measurements. The result of the analysis is shown in graphs with the power P as a function of the wind speed V, these graphs thus show the so-called PV-curves of the small wind turbines. The error in the measurements is shown as error bars in the graphs. The error is calculated from the statistics of the measured variable (standard deviation, number of measurements). It should be stressed that any possible off-set in the measurements is not taken into account. Situations where P=0 [Watt] for V>6 [m/s] are counted and shown in a separate table as these situations are a measure for out of order. 2

Ingreenious BV 1.2. Interpretation of the results 1.2 Interpretation of the results One might expect discrepancies of the PV-curves from this measurement procedure compared to the PV-curves from the IEC-61400 certification measurement procedure. In order to qualitatively show the differences of the used procedure compared to the IEC procedure, the PV-curve of the Skystream based on the IEC-61400 procedure is shown as a solid line together with the PV-curve from the procedure followed in this report, shown as dots. The Figure 1.1: PV-curve Skystream. differences are relatively small except for wind speeds above 10 [m/s]. The differences above 10 [m/s] are probably caused by the measurement method. The wind speed is sampled every 5 minutes. As a consequence, the samples of high wind speeds are likely to be taken during gusts and not during lulls as the latter requires unlikely high windspeeds. In these gusts, the rotor RPM does not fit the wind speed because it takes a while before the flywheel of the rotor speeds up. We thus know that the measurements at high 3

Ingreenious BV 1.2. Interpretation of the results winds speeds, say above 10 m/s, do not represent information that can be used to calculate an IEC-61400 like PV-curve. Instead the measurements above 10 m/s inform us on the effect of stalled rotor blades. A too low RPM results in a higher angle of attack of the incoming flow on the rotor blade, so that a too low RPM forces the blades towards stall. 4

Chapter 2 The results 2.1 Down time The situations where P=0 [Watt] at V>6 [m/s] are counted. Suppose these situations are denoted as p6. Based on the measured wind speeds at Schoondijke (see [1]), a wind speed of 6 m/s or higher does occur approximately 10 % of the time so that the down time of the wind turbines in % of the total measurement time may be found with 10 p6. The down time of the turbines is shown in table 2.1. Turbine Down time [%] Airdolphin 0.7 Ampair 11 Donqi 12 EnergyBall 11 Passaat 0.6 Raum 41 Skystream 0.9 WRE007 14 Table 2.1: Down time of the turbines calculated from 10 p6, where p6 is the % of time where P=0 [Watt] at V>6 [m/s]. It is likely that the wind turbines needed maintenance during the down time. The downtime can thus be interpreted as the % of time where maintenance is needed. It has to be mentioned however that Schoondijke is a test location so that the actual down time on real production sites may be less, certainly for the Raum and Donqi that are new on the test site. 2.2 PV-curves The power curves calculated from the measurements are shown on the following pages in alphabetical order of the turbine names. 5

Ingreenious BV 2.2. PV-curves Figure 2.1: PV-curve Airdolphin. 6

Ingreenious BV 2.2. PV-curves Figure 2.2: PV-curve Ampair. 7

Ingreenious BV 2.2. PV-curves Figure 2.3: PV-curve Donqi. 8

Ingreenious BV 2.2. PV-curves Figure 2.4: PV-curve EnergyBall. 9

Ingreenious BV 2.2. PV-curves Figure 2.5: PV-curve Passaat. 10

Ingreenious BV 2.2. PV-curves Figure 2.6: PV-curve Raum. 11

Ingreenious BV 2.2. PV-curves Figure 2.7: PV-curve Skystream. Dots: calculated from Schoondijke measurements. Solid line: calculated from IEC 61400 measurements. 12

Ingreenious BV 2.2. PV-curves Figure 2.8: PV-curve WRE007. 13

Bibliography [1] Mertens, S., 1 ste Evaluatie meetresultaten testveld kleine windturbines Zeeland, Ingreenious Rapport 0904000.R01, mei 2009 14