Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29



Similar documents
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

How To Design A Refrigeration System

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Why and How we Use Capacity Control

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

Refrigeration Installation 101

Elements Elements describe the essential outcomes.

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigeration Basics 101. By: Eric Nelson

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

DESIGN STANDARDS SECTION

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

High School Graduation years 2013, 2014, Unit/Standard Number

Nirvana. Cycling Refrigerated Dryers

TRAINING, EXAMINATION AND CERTIFICATION

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

AIR CONDITIONING TECHNOLOGY

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Automobile Air Conditioning Primer

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

Test Code: 8297 / Version 1

Model 2128 AIR COMPRESSOR PUMP Operating Instructions

marine/bespoke split applications

Chapter 3.4: HVAC & Refrigeration System

Recharge Procedure for Telemark TVP-2000 and TVP-3500

Fully automatic air conditioning service! Bosch ACS 600, 601 and 650 for the workshop

RS-44 (R424A) : Q & A

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

ON-VEHICLE INSPECTION

DIABLO VALLEY COLLEGE CATALOG

COMPRESSOR REPLACEMENT PROCEDURE

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

VACUUM REFRIGERATION SYSTEMS

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration & Air-conditioning Technician

HVAC Systems: Overview

ECOCIAT. Domestic hot water heat recovery unit

3/29/2012 INTRODUCTION HVAC BASICS

How To Clean Water From An Ammonia Refrigeration System

Subject: 2005 Air Conditioning Service Guidelines

How Ground/Water Source Heat Pumps Work

Mechanical Engineering Technician- Plant Technician

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Thermal Coupling Of Cooling and Heating Systems

Open Cycle Refrigeration System

RS-24 (R426A): Q & A

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

UNIT 2 REFRIGERATION CYCLE

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Why Daikin? 2015 Houston, Texas USA

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Direct Fresh Air Free Cooling of Data Centres

Guide to good leak testing

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

Centrifugal Water Chillers. Scott Meyerkord

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

Oil-Free Screw Compressors. Water-injected Technology. Rely on GD to provide the perfect fit

Precision for Professionals: Air Conditioner Service with Bosch ACS 751, 651 and 551

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

10 tips for getting more reliability from your air-conditioning system [reliability]

Energy Efficiency Best Practice Guide Industrial Refrigeration

Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Low GWP Replacements for R404A in Commercial Refrigeration Applications

MAC-120HE-01 Air-Cooled Chiller

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23

SECTION AIR COOLED WATER CHILLERS

High Pressure Ammonia Systems New Opportunities

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Screw Compressors ESM Fixed Speed & VS Variable Speed

UNDERSTANDING CENTRAL HEATING SYSTEMS

Large Energy Savings Per Installation VFDs for Large Chillers

COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A

Cool Design for Homes and Offices

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. Page

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

Transcription:

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont s M029), has been carried out by Business Edge. ACR Today reports on a unique project A unique plant conversion took place last month at the corporate headquarters of a major financial services organisation in central London. The chiller in question was originally designed and built by Mike Creamer and colleagues in 1998, just prior to the launch of Business Edge Ltd. The Water Chiller, which has operated successfully 24/7 for 20 years, comprises two Bock F16 six-cylinder compressors, each driven by 37.5kW Schorch motors, and equipped with 37.5 kw Yaskawa Power Inverters. The approximate cooling capacity of the plant is 400 kw. This water-cooled machine is served by large cooling towers on the roof of the building. It is believed to be the

first VRF Water Chiller of its kind to have been constructed in the UK. The design is unusual, being based on variable speed reciprocating compressors rather than screw, scroll or centrifugal compressors. The plant s control system features full floating suction and floating head pressure control, delivering chilled water at a constant and precisely regulated 8 C. This was a key requirement of the project, in order to prevent excess latent cooling within the Data Rooms served. The Data Room is critical for the organisation and the Water Chiller thus provides a vital service that underpins and supports their business. There are several other water chillers in the building. However, as a consequence of its reliability and robustness, this is the only original machine still in operation. As a result, in view of the impending R22 phase out, the client asked Business Edge to evaluate the refrigerant retrofit options. Mike Creamer, Managing Director of Business Edge, takes up the story: This was an exciting challenge for us. From the beginning I had envisaged that our VRF

technology would ultimately allow the machines we were building in the late Eighties to be adaptable to alternative refrigerants in the future - and here was a perfect opportunity to at last put that into practice. He added: It enables the Water Chillers and DX Systems we were building at that time to maintain either precision temperature or precision suction pressure control for a group of evaporators, irrespective of changes of load at the evaporators, changes in ambient condition and indeed even a change in refrigerant characteristics. Following initial research, Mike decided to concentrate on the Du Pont range of alternative refrigerants. Following technical discussions and a joint site visit, it was agreed that the most appropriate refrigerant would be MO29, ASHRAE Reference Number R422D. Mike says: Given the critical nature of the application, it was important to prepare all tools and equipment, consumables and recovery cylinders in such a way as to allow us to retrofit the machine with MO29 - and then run a performance evaluation test using the ClimaCheck Performance Analyser.

If that revealed a problem, in terms of refrigerant efficiency, performance or oil return at low refrigerant velocity, it would allow us to recover the M029 and recharge the R22 immediately, in order to keep the machine running and ensure business continuity for the client. The VRF technology at the site uses a special lubricating oil and expansion valve to enable the compressors to run at only a few hundred rpm for extended periods. Oil separators are fitted to each compressor. The refrigeration design of this machine is such that liquid refrigerant can actually be allowed to flash in the liquid line at low load condition without any impairment to performance. Return of oil to the crankcases of each compressor is vital. Given that the large shell and tube evaporator is sited below the compressors, the lift of this oil via adequate suction pipe velocity and miscibility was a key aspect to consider. Having made the necessary preparations and assembled tools such as recovery machines, cylinders, vacuum pumps and so on onsite, work on the conversion commenced.

The first task was to recover the R22 refrigerant from the chiller and system. We had also decided to replace a number of 20 year old peripheral items, such as shut-off valves, oil line pipework, oil filters, HP and LP safety switches at this time. Some replacement refrigerant lines were run in copper with suitable anti-vibration loops. The remainder were run in Gomax flexible plastic tubing, terminated at each end with special brass compression nuts and olives. The flexible lines are quick and easy to install, since the process of careful pre-shaping and routing of copper pipework, especially if one wishes to achieve a neat job, is far more readily achieved with this method. Once all the replacement ancillary components and interconnecting pipework had been fitted, a Leak Pressure Drop Test was carried out on the entire system. Compressors were isolated via their Service Valves for the following reasons: These were known to be sound in terms of leaktightness as a result of recent and regular service visits

It had been previously noted that the compressor shaft seals occasionally leak when subject to nitrogen pressure testing, yet do not leak when under refrigerant/oil pressure. In light of this, we decided that the compressors would be checked with an Electronic Leak Detector, once the system had been charged, re-commissioned and put into service. The Condenser Water Flow Switch had been observed sticking on occasion, so this was replaced. Special steel nipples were manufactured to facilitate this. To protect the Compressor Shaft Seals, a Leak Test Pressure of only 8bar was applied over an extended time period, and all new joints checked with a Leak Test Solution. As a result of careful workmanship, only one leak was found among all the new joints made. This minor leak was detected at a compression joint between a Tee and the Gomax flexible tubing. This was quickly repaired and the system again pressurised for the final Leak Pressure Test. Once all the joints had been leak tested and passed, the test solution residue was carefully cleaned up. During the extended Leak Pressure Test was under way, the electronic controller and main control panel were also

checked in readiness for ultimate start-up and recommissioning. Three high performance vacuum pumps were used to evacuate and dehydrate the system to less then 4mbar / 6 Torr. Having achieved a satisfactory vacuum and Vacuum Rise Test, the team then began charging the system with the new refrigerant, Du-Pont s M029, otherwise known as R422D. Mike says: It was fortunate that we had reached this stage without difficulty as we then received news that the temporary cooling brought in to maintain conditions in the Data Rooms was struggling, with the temperature steadily rising and already at 28 C! IDS / Du Pont supplied the refrigerant in high quality cylinders with a Tare Weight of 8.45kg. The net content was approximately 20kg per cylinder. The cylinders featured a single valve / single port type arrangement, with a dip tube to enable liquid to be drawn from the cylinder without the need to invert. A nice touch, reports Mike, was the inclusion of a bottle adaptor of high grade quality plastic fitted to every cylinder.

The team then used a ClimaCheck Performance Analyser to monitor the refrigerant charging process and the general running condition of the Water Chiller. After injecting the first liquid charge directly at the large liquid line drier Schrader Valve connection, we progressively ran the machine under controlled speed conditions. This was done after ensuring that the Chilled Water Pumps and Condenser Water Pumps were operational and that the Cooling Towers were functioning. As the Water Chiller had been out of operation for a few days, the chilled water loop and pipe work had risen substantially in temperature. The heat energy from the running Chilled Water Pumps had also contributed to this temperature rise. Consequently, when the Water Chiller was re-started, a substantial thermal load had to be dealt with, in addition to the thermal load from the Data Rooms. Consequently, the initial pull-down of water temperatures to the design level of 8 C took a little while. As the operating conditions settled toward normal levels, it was immediately apparent that the discharge temperature

was much lower than before when running with R22. While it was too early to finalise commissioning and associated readings at this point, our first impressions were very favourable. It was also pleasing to see the machine actually working and cooling the data rooms effectively! Mike adds: As we gradually trimmed the refrigerant charge, superheat came under steady control and was steady at around 7K. Surprisingly, the sub-cooling was reading a negative value of approximately -0.3K. We established that this was due to the fact that we were initially having to read the high side pressure at the liquid line connection, which led to a lower saturation pressure and temperature reading at that point (in relation to the temperature reading that was correctly being taken just before the TEV). The final total refrigerant charge added was recorded at 61kg. However, this was with only one of the two compressors running, and then at only 780rpm, as opposed the full speed capability of 1800rpm.

Under normal circumstances, if a higher building load were likely to be experienced, it would be necessary to conduct a Hot Day Test, fully commissioning the Water Chiller with the ClimaCheck Performance Analyser and adjusting the refrigerant charge to meet higher load conditions. However, this was a relatively warm day and the Data Room loads are fairly consistent. The team decided to make adjustments to the refrigerant charge during the next visit, which will be timed to coincide with the highest possible ambient. After careful study and preparatory work, the conversion to the new refrigerant proved a great success. Initial readings taken with the ClimaCheck suggest the Water Chiller will operate more efficiently than on R22, no mean achievement, as we know it was already an incredibly efficient plant and way ahead of it s time, says Mike. ENDS