Testing, maintenance and operation of Electronic Flow Computers for the Gas Industry



Similar documents
Effects of Atmospheric Pressure on Gas Measurement

Improving SCADA Operations Using Wireless Instrumentation

SCADA Systems. Make the most of your energy. March 2012 / White paper. by Schneider Electric Telemetry & Remote SCADA Solutions

Micro Motion Net Oil Computer Software and NOC System

WEATHER STATION FOR SOLAR FARM MONITORING

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Alarm Systems. Peace of Mind. Agri-Alert alarms have been protecting swine operations across the world since automated production systems

Gas Custody Transfer Calibration

Charge Regulator SCR 12 Marine

SDI Multi Sensor Module with Charger Enclosure Station Support

Scanner 1141C. Single & Dual Stream Measurement Remote Telemetry Unit (RTU) NUFLO MEASUREMENT SYSTEMS

UPM Figure 1 MPFM installed on well pad

REMOTE TELEMETRY UNITS FOR CONTINUOUS WATER QUALITY MONITORING: AN EXAMPLE FROM SILVERSTREAM LANDFILL Mike Millar, Geotechnics Ltd ABSTRACT

Telemetry system for cathodic protection equipment of underground metal pipelines

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

Natural Gas Well Automation using Kingfisher RTU Products

NETWORK ENABLED EQUIPMENT MONITOR

Temperature & Humidity SMS Alert Controller

PRODUCT PROFILE FEATURES

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

Identifying Gas Ultrasonic Measurement. Problems Using Advanced Techniques. John Lansing CEESI

Energy and Flow Measurement for Hydronic Systems

FLOW COMPUTERS METERING, MONITORING, & DATA ACQUISITIONS. Sami Halilah Dynamic Flow Computers Houston, Texas

Telemetry & Remote SCADA Solutions. Make the most of your remote assets

Condition Based Monitoring A Fully Automated Station Solution

SNMP Web Management. User s Manual For SNMP Web Card/Box

EC 350 Simplifies Billing Data Integration in PowerSpring Software

SCADA Systems Automate Electrical Distribution

Rackmount Intelligent Pressure Scanners

REMOTE MONITORING AND CONTROL SYSTEM

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

IP Sensing Water & Wastewater AMR/SCADA System

for CS flow / dew point sensors

Features: RMU REMOTE MONITORING UNIT AND WEB-BASED SOFTWARE

Industrial Strength Leak Detection

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar

Sentinel I28 and Blackbelt Mass Flow Calibration and Verification

Ultrasonic Gas Meters for Industrial and Commercial Applications. Ohio Gas Association Technical Seminar March 27-28,2014

CAMS. Combustion Airflow Management System. Proven solutions for a tough industry

Medical Air Systems: Scroll

Digital inductive conductivity transmitter

LDG DTS-4/4R Desktop Coaxial Switch / Remote

Application Note 12: TrendView Recorders Continuous Emissions Monitoring

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

Fundamental Principles of Rotary Displacement Meters

Distributed Temperature Monitoring of Energy Transmission and Distribution Systems

PrintFleet Local Beacon

COMBIMASS. Technical Data COMBIMASS eco-bio +

Technical Information POWER PLANT CONTROLLER

BLAST MONITORING Solutions

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

Reducing operating costs of telecom base stations with remote management

Hydro MPC Integrated Pump Systems and HVAC Applications GRUNDFOS HYDRO MPC

For Multi-Parameter Meters see mvx

Take total control of your HVAC system with cost-saving flow and thermal energy meters

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where

Proactive Monitoring of Friction Management Systems Reduces Costs and Downtime

Remote monitoring & control solutions for cathodic protection rectifier

FUNCTIONAL SPECIFICATION FOR AN ADVANCED METERING INFRASTRUCTURE VERSION 2

Implementing New Technology at TransCanada Meter Stations -- Better, Faster, Cheaper

Introduction To SCADA and Telemetry

Device Management Jonas Berge Emerson Process Management

Observer Analysis Advantages

Intelligent Mould Flow Monitoring

ngenieros Ingenieros Asociados De Control S.L.

Recommended Tools and Supplies: Small Flat Blade Screwdriver, 35mm x 7.5mm DIN Rail. Qwik Install

XFC 6201EX flow computer XSeries products

Fiscal Measurement Natural Gas

Battery Powered Thermal Mass Flow Meters for Gases

Rosemount 3095FC MultiVariable Mass Flow Transmitter

How To Use A Corona Mdi 110

Custody Transfer Measurement. with the V-Cone Flowmeter

SDX Submersible Depth Transmitter User Manual

Thermal Dispersion Mass Flow

Flow Measurement Options for Pipeline and Open Channel Flow

Lightweight, compact, ergonomic, safe POLARIS FID. Portable TOC Analyser for Stack Emissions

INTERFACING SECURITY SYSTEMS TO HOMEVISION

Network Instruments white paper

GX-2009 Data Logger Management Program Operator s Manual

Batteries and inverters

Flow System Calibration in Medical and Bio-medical Production Processes.

Integrating Digiquartz MET3 and MET3A Broadband Meteorological Systems with Leica GX1200 Series GPS Receivers

At the bottom of the screen you will also see some of our sister brands, all of which can also plug in to the Storm data logger.

LLB-OCMFM 2000 PORTABLE DOPPLER AREA-VELOCITY FLOWMETER

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Micro Motion 3098 Gas Specific Gravity Meter

HOW-TO GUIDE FOR STORMWATER MONITORING

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

Service catalog Flow products

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

CONTROL MICROSYSTEMS DNP3. User and Reference Manual

Dew-Point Measurement Solutions

StruxureWare Power Monitoring 7.0.1

MULTICAL 21 DATA SHEET. Electronic ultrasonic cold and hot water meter

Remote Management White Paper 27th June, 2012

Cooling Channel Optimization

Unidirectional Transmitter/ Receiver Units Introduction

PROCESS AUTOMATION. ALARM SYSTEMS FOR SEPARATORs PRODUCT OVERVIEW

Battery Powered Thermal Mass Flow Meters for Gases

Transcription:

Testing, maintenance and operation of Electronic Flow Computers for the Gas Industry Class # 3170.1 March 2012 / White paper by Denis Rutherford Regional Sales Manager Central US Schneider Electric Telemetry & Remote SCADA Solutions 6650 W Sam Houston PKY N Suite 420 Houston, TX 77041 USA Make the most of your energy

Summary Executive Summary... p 2 Introduction... p 3 Configuration... p 4 Installation... p 5 Solar Power System Selection... p 6 Flooded or Sealed Batteries... p 6 Solar System Sizing Example... p 7 Operation... p 8 Maintenance... p 8 Testing... p 8 Conclusion... p 9

Executive summary This white paper discusses an overview of current flow computer technology and criteria for selection. White paper on Electonic Flow Computers for the Gas Industry 02

Introduction Say goodbye to obsolete chart recorder technology and bulky multi-component flow computers and make way for Electronic Flow Measurement (EFM). The EFM is a solar-powered single to multi-run flow computer - an evolution in gas measurement technology. Designed for use in remote locations where solar is the only power and technician access is less than ideal, the EFM incorporates a dedicated single-run flow computer, solar/battery power supply and communication system in an all-in-one, compact, easy-to-install package. The EFM requires a Man-Machine Interface (MMI) to configure. The MMI or Configuration Software allows editing of the flow computer configuration parameters with configuration dialogs for process inputs, contract specifications, compressibility calculations, and flow calculations for each meter run. The operator may write configuration data to the flow computer or read it back. Parameter checking is provided on user entries. The EFM is an electronic natural gas flow computer providing the following industry standard calculations: AGA-3 (1992) for gas volume calculation with orifice meters AGA-7 for gas volume calculation with turbine meters AGA-11 for gas volume calculations with Coriolis meters; V-Cone for gas volume calculation with V-Cone gas flow meters; AGA-8 detailed calculation for gas compressibility NX-19 for gas compressibility calculation in legacy applications. AGA-10 speed of sound calculation for verifying the accuracy of an ultrasonic meter The MMI configuration software (normally software residing on a laptop) displays the flow computer current readings, historical logs, alarm logs, and event logs for each meter run. The MMI supports multiple configuration and display windows open simultaneously to display data from multiple views. The MMI can be used to configure and calibrate the EFM to the individual sensors or Multivariable Transmitters (MVT). The gas flow computer automatically polls the MVT transmitter for sensor information used in the gas flow calculations. The EFM provides wizard-style dialogs to guide you through the configuration, maintenance and calibration procedures. The MMI configuration software can display current readings, historical data logs, and event logs to spreadsheet files. The configuration software generates customised reports consisting of configuration data, historical data logs, gas quality logs, event logs, alarm logs, and calibration in format suitable for Volumetric Validation Software such as Flow-Cal. The flow computer integrates with SCADA systems using Modbus-compatible communications. You can access data, configuration, and calculation factors over a SCADA network as well as locally at the flow computer. White paper on Electonic Flow Computers for the Gas Industry 03

Configuration The configuration parameters are fairly typical with each of the EFM manufacturers. Initialise Command The Initialise command erases programs in the flow computer and sets the flow computer to default settings. Real Time Clock Sets the Real time Clock in the Flow Computer Sensor and Display Configures the sensor parameters of external transmitters. Sets operating limits, alarms and configures the display. Flow Run Configures the parameters for a selected meter run such as AGA-3 parameters, AGA-8 parameters, pressure and temperature base references. Power Management Configuration Setting the power management features to minimise the power consumption of the EFM. Pulse Input Configuration Configuration of the AGA-7 parameters. Gas Sampler Output Configuration Configuration of the pulse output for stroking the external gas sampler. Read Configuration The ability to retrieve the EFM s configuration and save it to a file. Write Configuration Writing the changes to the parameters of the configuration back down into the EFM Communications - Configures the protocol and data format for the individual communication ports on the EFM White paper on Electonic Flow Computers for the Gas Industry 04

Installation The installation of the EFM is the key to performing practically zero corrective maintenance. Because the device is microprocessor-controlled with micro surface-mount integrated circuitry, the unit needs to be electrically isolated completely from cathodic protection devices. These devices produce a negative voltage that cause degrading effects to the electronics and causes intermittent readings and communication errors. Eventually the unit catastrophically fails. Many EFMs incorporate built-in enhanced lightning protection by utilising MOVs, diode resistor protection and optical isolating devices. This circuitry works by dissipating the energy through a common ground that is connected to a grounding rod. A copper ground rod that is driven 2.4m (~8ft) into the ground is needed to ensure a good solid ground. Even with the EFM grounded properly a nearby lightning strike could travel up the pipe and damage the EFM. Isolating the EFM from the pipe can be done at a fairly low cost. Even with isolating gaskets to keep the cathodic protection and nearby lightning strikes electrically isolated from the EFM, you have to look at the entire measurement skid for other ways that unwanted stray current can travel to the EFM. Tubing lines are frequently run along the side of the pipe and routed over the isolating gaskets thereby having a null effect on any isolation attempt. To be completely sure the EFM is isolated a dielectric isolation kit can be inserted between the EFM and five-way manifold valve attached to the transmitter. A PVC coupling could be used to isolate the temperature probe from the pipe. White paper on Electonic Flow Computers for the Gas Industry 05

Solar Power System Selection The EFM is almost always located in remote areas where power is not available. Due to the low current consumption components of the EFM system, a small battery and solar panel can be deployed at a much lower cost than bringing in power from another source. The battery needs to be sized so that the system can last 14 days without usable sunlight. The solar panel needs to be of sufficient size to recharge the battery within 10 days of the return of usable sunlight. There are two types of batteries that are used with an EFM. Let s discuss the differences and which one is the best choice. Flooded or Sealed Batteries Sealed batteries make sense in some applications - but not all. Sealed Absorbed Glass Mat (AGM) batteries are generally about 2 times as expensive as flooded, and the cycle lifetime is usually similar or a little longer. Nearly all sealed batteries are AGM or gelled. Sealed AGM types are usually the best choice in these situations: > In areas with poor or no ventilation > In areas or applications where maintenance is a problem, or is poorly done > Any place that a flooded battery might spill or break and cause damage Flooded batteries are probably your best choice if none of the above applies. Flooded batteries are fine for most applications. They are nearly always less expensive, and there is better availability of types and sizes. They are the best choice where: > Adequate ventilation for the batteries is present > Tipping, spillage or breakage is not a concern > The batteries are in an area where maintenance can be performed without too many problems > A very large battery bank is required > Where the escape of hydrogen and oxygen gases normally lost in flooded lead-acid batteries must be prevented > The batteries are in a spot where it is difficult or time-consuming to check water levels > In situations where the batteries must be sidemounted in order to fit in the installation enclosure White paper on Electonic Flow Computers for the Gas Industry 06

Solar System Sizing Example Example 1 An EFM system with a spread-spectrum radio that is receiving and transmitting 12 times a day draws about 1.5A-Hr/day. Let us consider a system located in Conway AR. Referencing the solar isolation map in Figure 1, Arkansas falls within Zone C. Referencing Table 1 and cross referencing, Zone C with a total daily current consumption of 1.5A-Hr, you will find that a 10W solar panel and 36A-Hr battery is needed. Example 2 Changing the radio to an Ethernet spreadspectrum radio will increase the total hourly current consumption to 7.9A/Hr and the battery size to 100A-Hr, with a 60W solar panel. Figure 1: Solar Isolation Zone Map Note the increase in the size of the solar panel and battery, the further north you go where there are more cloudy days and cooler weather. Solar Wattage 10 20 40 Battery Size 18 36 18 36 18 36 99 Zone A Zone B Zone C Zone D Zone E 2.43 1.99 1.55 1.11 0.66 4.91 4.02 3.12 2.23 1.34 9.49 7.76 6.04 4.31 2.59 50 99 11.96 9.79 7.61 5.44 3.26 65 99 15.22 12.45 9.69 6.92 4.15 85 99 198 19.80 16.20 12.60 9.00 5.40 130 99 198 30.94 25.31 19.69 14.06 8.44 170 265 39.60 32.40 25.20 18.00 10.80 260 420 61.88 50.63 39.38 28.13 16.88 390 530 92.81 75.94 59.06 42.19 25.31 Figure 2: 12V Complete Solar-sizing Matrices White paper on Electonic Flow Computers for the Gas Industry 07

Operation The operation of a flow computer is broken up into three parts: Configuration of station and measurement parameters Maintenance (calibration of the sensors) Viewing of data and creation of reports Maintenance Maintenance of the flow computer is the verification and calibration of the transmitters to the EFM. This process starts with verifying that the EFM is accurately reading the sensors or transmitters that are measuring the Static Pressure, Differential Pressure and Temperature. When the EFM is brand new out-ofthe-box, the unit requires calibration. A reference that is twice as accurate to the stated accuracy of the transmitter is required. Testing Transmitter testing is divided into three routines: As Found Calibration As Left The As Found routine is the witness verification of the EFM where a user tests the EFM at five different pressure points for both the Differential and Static Pressure sensor. Depending on the manufacturer, the temperature transducer is tested at one or two points. The As Found routine is a test to determine if the EFM is within custody-transfer calibration. The volume that the meter is measuring determines the period of the AS Found routine. Each gas production company has different measurement policies and standards as to how often this check is performed. During the As Found check, if the EFM is found to be outside of calibration then a Calibration routine is performed. The Calibration routine is where the user will calibrate by setting a trim in the sensor to bring it in line with the reference standard. This trim is different for each EFM manufacturer. Some manufacturers require a zero mid-range and span. Others require a zero and span only. The As Left routine is performed after a calibration is done. This is just like the As Found routine where a five-point check is performed to insure that the sensors are operating within spec. The As Left check is a way to prove that the meter is accurately measuring across its entire range. White paper on Electonic Flow Computers for the Gas Industry 08

Conclusion EFMs are the de facto standard for measuring natural gas. These units can consistently perform with a much higher accuracy than chart recorders. The key to longevity and maintaining a trouble-free unit is the installation. Adhering to precautionary measures along with the proper selection of solar-power system components, will give you the best performance in the most adverse conditions. White paper on Electonic Flow Computers for the Gas Industry 09

Schneider Electric Telemetry & Remote SCADA Solutions 48 Steacie Drive, Kanata, Ontario K2K 2A9 Canada Direct Worldwide: 1 (613) 591-1943 Fax: 1 (613) 591-1022 Toll Free within North America: 1 (888) 267-2232 www.schneider-electric.com Document Number TBUL00001-33 This document has been printed on recycled paper March 2012 tk 2011 Schneider Electric. All rights reserved.