PROTECTION AGAINST ELECTRIC SHOCK by John Ware



Similar documents
ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24

Electrical installation condition reporting:

FORMS for the 17th Edition

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES

chapter8 Testing and commissioning Unit 2 outcome 2

BS 7671:2008+A3:2015 MODEL FORMS

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB

The Electricity Wiring Regulations

Healthcare interpretation of IEE Guidance Note 7 (Chapter 10) and IEC for

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

The Electricity Wiring Regulations 2007

Insulation resistance

FAQs-Main switchboard design criteria

Guide to the Selection & Use of Residual Current Devices

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

Criteria for Selecting a Residual-Current Device

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing

Unified requirements for systems with voltages above 1 kv up to 15 kv

Questions and Answers for Heating and A/C Contractors

A Guide to 17th Edition Testing

Safety in electrical testing at work

WIRING MATTERS. EARTHING: Your questions answered. Electrical installations outdoors Ongoing accuracy of test instruments PAT testing of equipment

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Experts in what we do. Portable Appliance Testing A Practical Guide.

ELECTRICAL INSPECTION BULLETIN (Effective )

SELECTION OF FINAL CIRCUIT PROTECTION

6.0 Electrical Installations

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Electrical safety dwellings APPROVED DOCUMENT. The Building Regulations 2000

Use of Residual Current Devices in Departmental Infrastructure

NZECP 14: 1995 ISSN COVER PAGE

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Circuit Electrical Testing

Electrical Resistance Resistance (R)

City of Riverside Building & Safety Division Phone: (951)

Electrical Grounding. Appendix C

Electrical safety requirements in DC distribution systems

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

FREQUENTLY ASKED QUESTIONS

Are you aware. Outline

Section B: Electricity

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Article 10 - ADMINISTRATIVE SECTION

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

EDS CUSTOMER LV INSTALLATION EARTHING DESIGN

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Earthing Guidance Notes

CHAPTER 2 EXAMPLES AND TABLES

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Electrical Contractors Association

CODE OF PRACTICE FOR THE ELECTRICITY (WIRING) REGULATIONS

Regulation IO-6.0: Electrical Safety Regulations

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3

Instructions for Safe Use

Electrical Practices for Construction Work

Building Services Engineering Technician

1 Introduction. 2 Hazards From Electricity

County of Riverside Building and Safety Department

Hyperlinks are Inactive

Grounding & Bonding Why it is done And How to Install Properly

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Screened cable and data cable segregation

Section 559 luminaires and lighting installations An overview by Geoff Cronshaw

Introduction to Data Centre Design

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Electrical safety and you

Residual Current Circuit Breaker

Errata NFPA 70. Proposed 2014 Edition

Best Methods for Safe Hipot Testing

Experiment NO.3 Series and parallel connection

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Technical guide Protection against earth faults with Residual Current Devices

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Guidance notes for the installation of electrical supply in mobile trailers for breast screening

How Much Voltage Drop Is Acceptable?

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

MASTER ELECTRICIAN CODE EXAMINATION EXAMINATION REFERENCE MATERIAL AND CONTENT OUTLINE. Answers to sample questions: CONTENT OUTLINE

employed to ensure the continuing reliability of critical systems.

Guide to the electrical parameter classifications of IEC and IEC safety standards

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits

Electrical test equipment for use on low voltage electrical systems

Level 3 Certificate in the Certification of Electrical Installations (Design, Erection and Verification of Electrical Installations) ( )

NEW ZEALAND ELECTRICAL CODE OF PRACTICE REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE

Code of Practice for In-service Inspection and Testing of Electrical Equipment. 4th Edition

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

GUIDANCE ON ELECTRICAL INSPECTIONS

Transcription:

16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created by the passage of fault current through the impedance of the circuit protective conductors and the means of earthing. PROTECTION AGAINST ELECTRIC SHOCK by John Ware THE FUNDAMENTAL rule of protection against electric shock is: live parts, such as energized conductors, must not be accessible, and conductive parts which are accessible, such as metal of equipment or metal pipes, must not be hazardous-live These two conditions must be achieved both in normal conditions (no faults on the electrical system) and under single fault conditions (such as a fault from a live conductor to a metal casing). Protection under normal conditions Protection under normal conditions is achieved by basic protection, formerly known as protection against direct contact. Protection under single fault conditions is achieved by fault protection and was previously referred to as protection against indirect contact. Basic protection is defined as: Protection against electric shock under fault-free conditions Basic protection is provided to protect persons or livestock coming into direct contact with live parts. A live part is defined as: A conductor or conductive part intended to be energized in normal use, including a neutral conductor but, by convention, not a PEN conductor Figure 1 illustrates a person coming into contact with live parts. Protection under fault conditions or fault protection is defined as: Protection against electric shock under single fault conditions Fault protection provides protection against persons or livestock coming into contact with exposed-conductiveparts which have become live under single fault conditions. An exposedconductive-part is defined as: Conductive part of equipment which can be touched and which is not normally live but which can become live when basic insulation fails Figure 2 illustrates how a person could receive an electric shock under single fault conditions. The person in Figure 2 is in contact with the metal enclosure of an item of Class I electrical equipment which has Protective measures A protective measure must consist of provision of basic protection and provision of fault protection, which normally are independent. For example, in the case of automatic disconnection of supply, basic protection is provided by insulation and barriers and while fault protection is provided by protective earthing, protective bonding and automatic disconnection of supply. Basic and fault protection are independent. Enhanced protective measure A permitted exception is where the protective measure is an enhanced protective measure which provides both basic and fault protection. An example of an enhanced protective measure is reinforced insulation. Basic protection and fault protection are both provided by the reinforced insulation (Refer to Regulation 410.3.2). Recognized protective measures BS 7671: 2008 recognizes the protective measures listed in Table 1 ( see page 22). The protective measure of Automatic Disconnection of Supply The protective measure of automatic disconnection of supply consists of basic protection, fault protection and, for some circuits and locations, additional protection. Basic protection is provided by basic insulation of live parts and/or by barriers or. Fault protection is provided by (i) protective earthing, (ii) main protective equipotential bonding, and

(iii) automatic disconnection of supply in the case of a fault. 17 Protective earthing Protective earthing requires all exposedconductive-parts to be connected to a protective conductor which in turn is connected to the main earthing terminal and hence, via the earthing conductor to the means of earthing. Main protective equipotential bonding In each installation main protective bonding conductors complying with Chapter 54 are required to connect to the main earthing terminal extraneous-conductive-parts, such as water and gas installation pipes, other installation pipework and ducting, central heating and air conditioning systems and exposed metallic structural parts of the building. Figure 1: Contact with live parts Figure 2: Single fault conditions Automatic disconnection in case of a fault When a fault occurs, the fault current has to be of sufficient magnitude to operate the circuit protective device to automatically disconnect the supply to the faulty circuit within a prescribed time. A protective device such as a fuse, circuit-breaker or RCD is to be provided and the circuit designed such that the device operates and disconnects the supply. In the event of a fault of negligible impedance between a line conductor and an exposed-conductive-part or a protective conductor, the protective device must disconnect the supply within the appropriate time stated in Table 41.1 of BS 7671 (See Table 2, page 22). Requirements of the protective measure of Automatic Disconnection of Supply include protective earthing, main protective equipotential bonding and automatic disconnection. TN systems In a TN system each exposedconductive-part of the installation is Figure 3: Automatic Automatic Disconnection of Supply required to be connected by a protective conductor to the main earthing terminal of the installation which must be connected to the earthed point of the power supply system, i.e. the supply transformer. The characteristics of the protective device and the circuit impedances are required to fulfil the following requirement (Regulation 411.4.5): Zs x Ia Uo where: Zs is the impedance in ohms (Ω) the fault loop comprising: the source the line conductor up to the point of the fault, and the protective conductor between the point of the fault and the source. Ia is the current in amperes (A) causing the automatic operation of the disconnecting device within the time specified in Table 41.1 of BS 7671. Uo is the nominal a.c. rms or d.c. line voltage to Earth in volts (V) which is 230 V. TT system In a TT system, every exposedconductive-part is required to be connected, via the main earthing terminal to a common earth electrode (Regulation 411.5.1 refers). The preferred protective device for fault protection is an RCD (Regulation 411.5.2) but where an RCD is used, as it will be in most cases, overcurrent protection must nonetheless be provided by a fuse or a circuitbreaker, or, alternatively a combined RCD and overcurrent protective device

22 Protective measure Use Basic protection provided by Fault protection provided by Fault protection provided by Automatic disconnection of supply General Insulation or barriers and Protective earthing Protective bonding Automatic disconnection Used in 95% of all installations. Section 411 in BS 7671: 2008. Includes FELV (411.7) and RLV (411.8) Double or reinforced insulation General Basic insulation Supplementary insulation Section 412 Reinforced insulation Electrical separation for the supply to one item of current-using equipment General Insulation or barriers and Simple separation of the circuit from other circuits and Earth Section 413 Extra-low voltage (SELV and PELV). General Voltage must not exceed 50 V a.c. Supply from a suitable source Separation Obstacles Controlled or supervised by skilled persons With SELV the circuit is separated, with PELV it is earthed Section 414. Obstacles With or without Fault protection Refer to Regulations 417.1 and 417.2 Placing out of reach Placing out of reach Refer to Regulation 417.3 Non-conducting location Earth-free local equipotential bonding Electrical separation for the supply to more than one item of current-using equipment Installation is controlled or under the supervision of skilled or instructed persons so that unauthorized changes cannot be met Insulation or barriers and The conditions of supervision under which the fault protective provisions of Section 418 may be applied as part of the protective measure are given in Regulation 410.3.6. Refer to Regulation 418.1 Refer to Regulation 418.2 Refer to Regulation 418.3 Table 1: Recognized protective measures (an RCBO) may be employed. Where an RCD is used for fault protection, the following conditions are to be fulfilled: the disconnection time must be that required by Table 41.1, and R A x IΔn 50 V Where: R A is the sum of the resistances of the earth electrode and the protective conductor connecting it to the exposed-conductive-parts (in ohms). IΔn is the rated residual operating current of the RCD. Additional protection BS 7671 recognizes this measure as reducing the risk of electric shock in the event of failure of one or other of the two basic protective measures mentioned above (insulation and barriers or ) and/or failure of the provision for fault protection or carelessness by users. The measure must not be used as the sole means of protection and does not obviate the need to apply one of the protective measures specified in Sections 411 Automatic disconnection Final circuit not Final circuit Distribution exceeding 32 A exceeding 32 A circuit TN system 0.4 s 5 s 5 s TT system 0.2 s 1 s 1 s TT system (1) 0.4 s 5 s 5 s (1) Where, in a TT system, disconnection is achieved by an overcurrent protective device and main bonding is connected to all the extraneous-conductive-parts within the installation in accordance with Regulation 411.3.1.2, the maximum disconnection times applicable to a TN system may be used. A maximum disconnection time of 5 s applies to all circuits in a reduced low voltage system Regulation 411.8.3 refers). A maximum disconnection time of 5 s applies to all circuits supplying fixed equipment used in highway power supplies (Regulation 559.10.3.3 refers). Table 2: Extract from Table 41.1 (and others) of BS 7671: 2008 Maximum disconnection times for a nominal a.c. rms. line voltage to Earth of 230 V of supply, 412 Double or reinforced insulation 413 Electrical separation and 414 Extra-low voltage provided by SELV or PELV; Regulation 415.1.2 refers. Additional protection by means of a 30 ma RCD is specified as part of a protective measure for situations such as: socket-outlets for use by ordinary persons for general use (411.3.3) mobile equipment outdoors (411.3.3) concealed cables in walls and partitions where the installation is not intended to be under the supervision of a skilled or instructed person, (522.6.7) circuits in circuits in certain special Locations (410.3.2) The protective measure of Double or Reinforced Insulation Double or reinforced insulation is a protective measure in which: basic protection is provided by basic insulation, and fault protection is provided by supplementary insulation, or both basic and fault protection are provided by reinforced insulation between live parts and accessible parts (Regulation 412.1.1). Double or reinforced insulation is intended to prevent the appearance of

a dangerous voltage on the accessible parts of electrical equipment through a fault in the basic insulation. There is no provision for the connection of exposed metalwork of the equipment to a protective conductor, and no reliance upon the earthing arrangements in the fixed wiring of the installation. Wiring systems Wiring systems must have a rated voltage of the cable(s) is not less than the nominal voltage of the system and at least 300/500 V and adequate mechanical protection of the basic insulation must be provided by one or more of the following the non-metallic sheath of the cable, or non-metallic trunking or ducting or non-metallic conduit. The protective measure of Electrical Separation Electrical separation is a protective TRAINING measure in which basic protection is provided by basic insulation of live parts or by barriers or and fault protection is provided by simple separation of the separated circuit from other circuits and from Earth (Regulation 413.1.1). The two main principles underlying protection by electrical separation is that neither the source of the supply nor any live parts of the separated circuit is connected to any other circuit or to Earth. Thus, in the event of a single fault to an exposedconductive-part of equipment in the separated circuit, fault protection is afforded because there is no path for fault current to return to the source. For an installation in a dwelling, the only likely application of the use of electrical separation is a shaver supply unit complying with BS EN 61558-2-5 Except under particular circumstances (Refer to Regulation Brought to you by the Institution of Engineering and Technology 418.3 of BS 7671) this protective measure is limited to the supply of one item of current-using equipment supplied from one unearthed source with simple separation. The source of supply is an isolating transformer conforming to BS EN 61558 (which supersedes BS 3535), or one of the other sources specified in Regulation 414.3 having an equivalent degree of separation from any other system. Protection by electrical separation requires the following conditions to be met: The separated circuit must be supplied through a source with at least simple separation The voltage of the separated circuit must not exceed 500 V Live parts of the separated circuit must not be connected at any point to another circuit or to Earth or to a protective conductor Power your way towards the 17th Edition 23 TRAIN TO THE 17TH EDITION These new regulations come into force July 2008: Understand the changes Upgrade courses fromthe 16th Edition to the 17th Edition 17th Edition qualifications New City & Guilds awards Meet industry standards To find out more about our short courses and workshops visit www.theiet.org/wmcourses For advice on the best course to meet your needs, call +44 (0) 01438 767289 or email coursesreg@theiet.org

24 Figure 4: The principle of electrical separation Figure 5: Simple PELV system No exposed-conductive-part of the separated circuit must be connected either to the protective conductor or exposed-conductive-parts of other circuits, or to Earth. If the exposedconductive-parts of the separated circuit are liable to come into contact, either intentionally or fortuitously with the exposed-conductive-parts of other circuits, protection against electric shock no longer depends solely on protection by electrical separation but on the protective provisions to which the latter exposedconductive-parts are subject. Separated circuits The use of separate wiring systems is recommended. If separated circuits and other circuits are in the same wiring system, multi-conductor cables without metallic covering, or insulated conductors in insulating conduit, nonmetallic ducting or non-metallic trunking shall be used, provided that the rated voltage is not less than the highest nominal voltage, and each circuit is protected against overcurrent. The protective measure of Extra-Low Voltage provided by SELV or PELV Protection by extra-low voltage is a protective measure which consists of either of two different extra-low voltage systems, SELV (Separated Extra-Low Voltage), or PELV (Protective Extra-Low Voltage), Regulation 414.1.1 refers. SELV is defined as: An extra-low voltage system which is electrically separated from Earth and from other systems in such a way that a single fault cannot give rise to the risk of electric shock PELV is defined as: An extra-low voltage system which is not electrically separated from Earth, but which otherwise satisfies all the requirements for SELV Protection by extra-low voltage provided by SELV or PELV requires all of the following: Limitation of voltage in the SELV or PELV system to the upper limit of voltage Band I which is 50 V a.c. or 120 V d.c. and Protective separation of the SELV or PELV system from all circuits other than SELV and PELV circuits, and Basic insulation between the SELV or PELV system and other SELV or PELV systems, and For SELV systems only, basic insulation between the SELV system and Earth. The extra-low voltage is generally considered insufficient to present a hazard of electric shock (as defined) in dry situations where the person protected has a body resistance within normal limits. In certain locations the requirements of Part 7 limit the value of the extra-low voltage to a value lower than 50 V a.c. or 120 V d.c. If the nominal voltage exceeds 25 V a.c. or 60 V d.c., or if the equipment is immersed, basic protection shall be provided for SELV and PELV circuits by insulation in accordance with Regulation 416.1. Basic protection and fault protection is provided under the following conditions: The nominal voltage cannot exceed the upper limit of voltage Band I, and The supply is from a permitted source, and The requirements applicable to SELV or PELV circuits listed below are met. (Regulation 414.2 refers). If the system is supplied from a higher voltage by equipment which provides at least simple separation between that system and the extra-low voltage system but which does not meet the requirements for a SELV and PELV source, the requirements for FELV may be applicable. For further information refer to Guidance Note 5: Protection against electric shock.