Wir schaffen Wissen heute für morgen

Similar documents
University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012

Crowne Plaza Copenhagen Towers The world s greenest hotel

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

EnergySTEP (Sustainability Tiered Efficiency Program) Our Approach to Energy Efficiency

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

ECOCIAT. Domestic hot water heat recovery unit

New technical solutions for energy efficient buildings

Office Buildings: Developer s Requirements Consultant s Solutions

Integrating renewable energy sources and thermal storage

Heat Recovery from Data Centers. Guided Tour in Kista, January 21, 2015

OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY

New absorption chillers for high efficient solar cooling systems

Small-Scale Solar Heating and Cooling Systems

The final numerical answer given is correct but the math shown does not give that answer.

Coupling the electricity and heat sectors - the key to the transformation of the energy system

Summary technical description of the SUNSTORE 4 plant in Marstal

District heating and district cooling with large centrifugal chiller - heat pumps

1A PLANNING AND DEVELOPMENT SHERIDAN COLLEGE GOES DANISH IMPLEMENTING THEIR DISTRICT ENERGY

CFD simulation of fibre material transport in a PWR core under loss of coolant conditions

Year project completed or estimated year of completion: October 2014

Heating and cooling with wastewater

Silicagel-water adsorption cooling prototype system for mobile air conditioning

District heating and cooling in Stockholm Site visit to the Ropsten plant

Field test of a novel combined solar thermal and heat pump system with an ice store

Hybrid system. Energy-efficient and environmentally friendly

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

Second Place: Industrial Facilities or Processes, New

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

Roche Basel/Kaiseraugst

Natural geothermal energy.

How To Get A Passive House

AIR CONDITIONING - ENERGY CONSUMPTION AND ENVIRONMENTAL QUALITY

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

FLUXUS Energy. Manage energy effectively using non-invasive measuring technology. Heat usage, chilled flows and compressed air flow rate

Cooling with Compact Absorption Chillers

Federation of European Heating, Ventilation and Air-conditioning Associations

Passive house rehabilitation of post war residential building in Zug, Switzerland

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Scope of Work. See for resources available

25. Fachtagung von GEOTHERMIE.CH

Typical Cooling Load Profile

NEW JERSEY CENTER OF EXCELLENCE

Best Practice Guide BPGCS007

Food industry Prosecc industry Heat & power (Production of district heating & cooling) Food industry Process industry Logistic centres Sport arenas

Passive Cooling Systems Air Conditioning Without the Need of Energy

Final Report by Air Conditioner Evaluation Standard Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural

LG Electronics AE Company, Commercial Air Conditioning

The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable buildings

ROTEX gas hybrid heat pump. A strong team.

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

The Second Law of Thermodynamics

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Experiences and future perspectives of biomethane in Germany from a regulatory perspective

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

Energy management in the city council of Frankfurt

University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008

Life Cycle Assessment (LCA) of solar cooling systems

EarthCents (DSM) Program Summary

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM

Fläkt Woods Building Future

AdSORPTION CHILLER NAK

The commissioning of the LHC: first the technical systems, then the commissioning with beam

Feasibility Study for Mobile Sorption Storage in Industrial Applications

State of the Art Energy Efficient Data Centre Air Conditioning

SolabCool. presentation.

Heating & Cooling Efficiency

This presentation is posted for public use. ACEEE does not endorse any product or service.

DEMONSTRATION ACCELERATOR DRIVEN COMPLEX FOR EFFECTIVE INCINERATION OF 99 Tc AND 129 I

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

LANDFILL GAS TO ENERGY- COMBINED ENGINE AND ORC-PROCESS

EnerSmart Programs. enercase. Performance Contracting. contracting. Tired of. chasing capital for infrastructure upgrades?

vacon ac drives for mining & minerals

FIVE PROJECTS OF HIGH RF POWER INPUT COUPLERS & WINDOWS FOR SRF ACCELERATORS*

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

HEATING, VENTILATION & AIR CONDITIONING

products 22 º C Ventilation Air Conditioning Refrigeration Energy & Cost Saving Products Inside PROVIDED BY HEINEN & HOPMAN

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary

Contract No.: IEE/08/776/SI

How Ground/Water Source Heat Pumps Work

Non Domestic BER Assessors Technical Bulletin

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Daikin Altherma hybrid heat pump. The natural combination

CHP Plant based on a Hybrid Biomass and Solar System of the Next Generation EU project No. ENER/FP7/249800/"SUNSTORE 4" Dipl.-Ing. Alfred Hammerschmid

Houses heated entirely by solar energy all year round

Thermal Coupling Of Cooling and Heating Systems

The Central Solar Heating Plant with Aquifer Thermal Energy Store in Rostock - Results after four years of operation

SONNENKLIMA package solution description

Glossary of Heating, Ventilation and Air Conditioning Terms

Geothermal Ice Arenas

Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland

Temperature control solutions to help you improve business performance

Transcription:

Wir schaffen Wissen heute für morgen Paul Scherrer Institut Reinhard David Heat Recycling at PSI, a Project to Cover up to 75% of the Campus`s Heat Consumption PSI, 24. Oktober 2013

Introduction Target of the presentation Presentation of the boundary conditions and interfaces relevant to the realisation of the project Facts an figures Project scope and impressions Agenda General PSI maps, sections and accelerators Main power consumers Potentials for efficiency improvements Heat Recycling Heating and building infrastructure Cooling infrastructure, available heat sinks Potential heat sources for heat recycling A long term 2-step strategic plan for the heating system of PSI (Measures, Economy, Impressions) Potential adsorption cooling PSI, 24.10.2013 Seite 2

PSI Overview Number of Employees 1500 Annual external user 5000 Annual budget Annual cost of electricity Annual cost of heat 365Mio CH Fr 3.5-4 % appr. 2 appr. PSI s scientific activities are strongly linked with the design, construction and operation of large and complex research facilities

PSI Large Scale Research Facilities Proton Accelerator (Myons, Neutrones) Proscan (Proton Therapy) Synchrotron Light Source: SLS PSI, 24. Oktober 2013 Seite 4

Power Consumers PSI Energiedaten PSI ETH Qheiz [gwh] 12 72 Wel [gwh] 125 110 Verhältnis [-] 10.4 1.5 Main electrical consumers (85%) 0.25MW 0.3MW 0.7MW 0.3MW 0.4MW Pel, PSI-Ost 3MW 2MW 10MW 1MW 3.5MW SwissFel 6MW Pel, PSI-West, ca. 18MW

Load Profile Power and Heat Energiedaten PSI ETH Qheiz [gwh] 12 72 Wel [gwh] 125 110 Verhältnis [-] 10.4 1.5

Saving Potential for Accelerators? Example PSI-HIPA: 10MW total power 1,3MW proton beam power RF: 4,1MW Magnets: 2,6MW aux.systems: 3,3MW finally: 10MW heat 32% efficiency = already quite good, improvements difficult, potential low high cost improvements possible, but high investments (new magnets) not balanced by savings improvements possible and undertaken; often high investments Heat recovery is investigated and used; Efficient use for smaller portion of high temperature RF cooling loop only. thus important to utilize energy efficient technologies right from the design phase of an accelerator; later improvements are typically expensive and will not amortize Heat Recycling is an important measure to decrease the use of primary energy

Saving Potential of New Machines (Swiss FEL)? Swiss FEL is optimised for low energy consumption! compared with SACLA (Japan) reduced by -40% compared with LCLS (Stanford USA) reduced by -55% (statements from SwissFEL project management, background not subject of presentation)

Saving Potential of New Machines (Swiss FEL)? Infrastructure Cooling Design (ground water, minimized through cascading temperature levels) HVAC concept and design (ventilation efficiency, very limited compression chillers) Class A components (Motors, Pumps, Ventilators, Filters, etc.) Heat Recycling (focus of this presentation)

Heat Recycling Project Relevant boundary conditions and criteria's Building and heating infrastructure Cooling infrastructure, available heat sinks Potential heat sources for heat recycling A long term 2-step strategic plan for the heating system of PSI (Measures, Economy, Impressions) Potential adsorption cooling

Building Infrastructure of PSI Campus Building Infrastructure and condition, casing and insulation Age from 0 to 50 years Office, laboratories and functional buildings with high internal heat loads Some huts as permanent interim arrangements Closed but still legal «research atomic reactor buildings» Buildings to be removed but ever and ever used Reduction of heat consumption by passive insulation less effective than waste heat recycling but very costly!

Heating Infrastructure of PSI Campus District heating system Refuna Heat source nuclear power plant Beznau I+II Future heat source unknown, today`s low CO2-emission source not further guaranteed! System designed for high temperature of 115 C

Todays and Future Heat Consumption and Costs Actual consumption = expected long term consumption=12gwh Yearly cost: Future cost: 750kFr??? (actual heat price is based on process heat from nuclear power plant Beznau), price increase very likely! PSI, 24.10.2013 Seite 13

Heat Sinks PSI River Aare 15MW (cavities, magnets, ) Ground water 5MW (+6MW from 2017 for SwissFEL) (various, 3 cascading circuits ) Air 2.5MW +5MW (direct+indirect mainly for HVAC`s only) Total 27.5 MW (33.5 MW incl. SwissFEL) Rich Groundwater @12 C 14 C River Aare @ 1 24 C Most efficient cooling systems with very little compressing cooling machines in terms of energy! (capacity is 5MW for peak and/or summer loads or redundancy)

Potential Heat Sources and Demand Category 1: 4MW @ appr. 60 C Category 2: 18MW @ appr. 30 C

2 Step Strategy - Step 1 Direct use of waste heat category 1 (>60 C) Increase use of waste heat from 20% to 75% appr. Projekt in Execution now! Required Measures Separation of heating water cycle (Refuna / PSI) Integration of heat sources category 1 Temperature decrase: Modification of building heating stations Replacement of Radiators Replacement of ventilation heaters

Integration of Heat Sources Integration of 4 existing sources and separation of PSI heating cycle: 700kFr PSI, 24.10.2013 Seite 17

Replacement of Radiators New Design: 45/30 C Original Design: 70/50 C 1500 Radiators have to be replaced Costs: 1500kFr PSI, 24.10.2013 Seite 18

Heat Exchangers of Building Heating Stations Existing heat exchanger with dtm=22k (type pipe bundle) 37 heat transfer stations to be adapted: 700kFr Existing heat exchanger with dtm=5k (plate type fusion bonded, stainless steel) very compact PSI, 24.10.2013 Seite 19

Ventillation Heaters Original Design Temperature 50 80 C New Design Temperature 35/20 C 150 heat exchangers to be replaced: 700kFr PSI, 24.10.2013 Seite 20

New District Heat Pipe for Waste Heat Swiss FEL 1000m of ground pipe Costs: 600kFr (ditch was needed for other puprose as well) PSI, 24.10.2013 Seite 21

Temperature Decrease to Comply with Heat Sources

kw Project Heat Recovery Step 2 (Future Option) Direct use of heat sources category 1 Indirect use of heat sources category 2 via heat pumps (Increase 20K) oil for peakload /backup) Wärmeleistungsverlauf PSI Ausbaustufe 2 6'000 5'000 4'000 3'000 2'000 1'000 0-1'000 Wärmepumpen z.b.ab SwissFel und SLS (Backup mit bestehenden Ölheizkesseln) 0 1000 2000 3000 4000 5000 6000 7000 8000 kumulierte Jahresstunden Future Option! Wärmepumpen WRG PSI Required Measures: All measures step 1 Installation of heat pumps of 3MW approximately

Project Heat Recovery Step 2 (Future Option) PSI, 24.10.2013 Seite 24

Economy Heatrecovery Step 2 Measures, Costs, timescale, economy, pictures comparable economy We have an alternative to todays efficient district heating system

Leistung in KW Potential for Adsorption Cooling Angebot und Nachfrage von Kälte und Wärme 6000 5000 Durchschnittlicher Kältebedarf PSI Heizwärmebedarf PSI 4000 3000 Heat excess Bandlast Abwärme SwissFEL 1'800kW Wärmebedarf für Kälte Wärmebedarf total 2000 1000 Cold water produced with heat: 2200 MWh 0 0 1000 2000 3000 4000 5000 6000 7000 8000 Jahresstunden

Potential for Adsorption Cooling - Demand matches availability of cooling circuit for 5 laboratories 6m 90m - Feasibility is given but temperature level is at limit and to find space for installation (recooling!) is a challenge 10m 22m 45m 18m 8m 34m 13m 31m 33m - Estimated costs with 1.8Mio above maximal economical investment of 1.3Mio. 121m 32m 37m Anschlusspunkte an bestehendes Kaltwassersystem Gebäude Anschlussleitung jeweils 10-20m PSI, 24.10.2013 Seite 27

Conclusions For the PSI it is effective and economic to recycle waste heat A considerable investment of 4Mio approximately was permitted Heat recycling is more effective and much more cost efficient than reducing the heat consumption by passive insulation only. Optimised campus wide energy concepts with a long-term stategy are highly recommended since according our experience more effective than fulfilling typical energy standards for buildings only! The Project supports Reduction of Primary Energy Reduction of Cost for Energy

Thank you for jour attention! PSI, 24. Oktober 2013 Seite 29

Jahresarbeitszahl Refuna COP= Coefficient of Performance (Leistungsziffer), COP =Qheiz/Pel, Coefficient of Performance bedeutet, dass beim Bezug von 6.5MW thermisch 1 MW El. Leistung eingesetzt werden muss. Physikalisch: 1/eta,carnot, wobei eta,carnot an 2-ten Hauptsatz der Thermodynamik gebunden ist: eta,carnot =(Tzu-Tab)/Tzu. COP der Refuna: 6.5 Netto *) Strom -1MW Wärme +6.5MW Verrifikation auf theor. Basis *)