WO32 HVAC Evaluation Interim Findings of Commercial Quality Maintenance HVAC Programs



Similar documents
Lessons Learned from Field Observations of Commercial Sector HVAC Technician Behavior and Laboratory Testing

Preventive Maintenance Strategies and Technologies Can Pave the Path for Next Generation Rooftop HVAC systems

California Public Utilities Commission, Energy Division CPUC Contract # 12PS5095 (HVAC-3)

GUIDELINES ON AIRFLOW AND REFRIGERANT CHARGE VERIFICATION AND DIAGNOSTICS

Commissioning and Maintenance: Two Sides of the Same Coin? Kristin Heinemeier, PE, PhD Principal Engineer UC Davis WCEC

C-QM Advanced Sales Training

Todd M. Rossi, Ph.D. President

Customized Assessment Blueprint

Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034

Uncertainties in Achieving Energy Savings from HVAC Maintenance Measures in the Field

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

2016 HVAC Test and Repair Application Specifications

Lower Energy Costs with Rooftop Air-Conditioning Package Units

1/15/2013. HVAC Maintenance Repair or Replace & Planned Replace Initiative. Reduce Operating Costs. Improve Comfort / Process Conditions

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Measure Guideline: Air Conditioner Diagnostics, Maintenance, and Replacement

Meeting the Challenge of Persistence Energy Efficiency in Rooftop Units

Dehumidification Frequently Asked Questions

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Trade Professional Alliance EE Programs Training. Napa, CA January 20, 2015 Mark Salavitch Trade Professional Manager, Bay Region

Research shows that there are significant savings opportunities in installation and operation of packaged air conditioning units.

FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center

Get the FACTS about SEER and Deliver Better Customer Value

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord

Zoned Air Conditioners - A Real Value?

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

HVAC Energy Efficiency. Maintenance Study

HVAC Claims: Repair vs. Replacement

PG&E 2 SCE SDG&E Residential 42% 37% 39% Commercial and Industrial Small 12% 13% Medium 27%

HVAC Systems: Overview

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

How to Measure HVAC System Airflow

Ventilation Retrofit Opportunities for Packaged HVAC

Test Code: 8297 / Version 1

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Air Conditioning Contractors of America

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES


Catalyst RTU Controller Study Report

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Characteristics of Evaporators

The HVAC Service Assistant

February 1, Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

HIGH EFFICIENCY RTU. HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

, User s Manual

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

Hot Dry Climate Air Conditioner (HDAC) Combined Field Test Report

air conditioners how to choose a cooling system

What Can 13,000 Air Conditioners Tell Us?

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

AC System Equipment Specification, Installation and Operational Options for Improved Indoor Humidity Control

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Your Guide to Buying an Energy-Efficient Central Air Conditioner

123 street Salt Lake City, Utah 84092

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

HVAC Basic Science - System Capacity

BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda

Energy Efficiency. Energy Efficient Home Cooling:

Massachusetts COOL SMART. RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application

Failure code manual. content

Residential Air Conditioning. Program Standards

STANDARD COMMISSIONING PROCEDURE FOR PACKAGED HEAT PUMP (AIR-TO-AIR) & AIR CONDITIONING UNITS

California HVAC Contractor & Technician Behavior Study

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Air-Conditioning Buying Guide

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Introduction. Motor Types

Field Service Tools. SA Mobile Application Service Assistant Tool. Todd M. Rossi, Ph.D. 609/ (mobile)

SECTION HEAT PUMPS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

HVAC Permitting: A Study to Inform IOU HVAC Programs. Pacific Gas and Electric Company Prepared by DNV GL 10/10/2014 CALMAC ID: PGE0349.

HVAC. Combat rising energy costs

Green Building Practice Summary 12/13/2010

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Air Conditioning 101. STN Presentation AC101

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

HVAC Efficiency Definitions

Wet Bulb Temperature and Its Impact on Building Performance

Top 10 Energy Efficiency Opportunities

Residential Duct Systems for New and Retrofit Homes

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

2015 HVAC Excellence Educator Conference Variable Refrigerant Flow & Variable Refrigerant Temperature

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Investigation Of The AC2 Air Conditioner

Hidden Power Drains: Residential Heating and Cooling Fan Power Demand

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

Transcription:

WO32 HVAC Evaluation Interim Findings of Commercial Quality Maintenance HVAC Programs DNV KEMA Energy and Sustainability Robert Mowris & Associates, Inc. 1

Acknowledgements Work Order 32 EM&V Team, Jarred Metoyer, Brandon Gill PE, David Cranford, Jennifer McWilliams, John Stoops PhD from DNV KEMA, Robert Mowris PE, Bob Eshom AS & NATE, Ean Jones BS from RMA CPUC EM&V WO32 Study Manager Nils Strindberg and EM&V Supervisor Carmen Best CPUC Consultant Pete Jacobs PE, Building Metrics and John Hill, PhD from J.J. Hirsch & Associates Gilbert Taracena, Jaime Gutierrez, and Chris Haws of Intertek Testing Services, NA IOU program implementers and HVAC technicians 2

Presentation Overview CPUC Strategic Plan Goals WO32 Research Study Goals & Sample CQM Program Overview ASHRAE Standard 180 Manufacturer Instructions provide performance baseline for ACCA 180 Field Observations Laboratory and Field Measurements Conclusions 3

CPUC Strategic Plan for HVAC CLEESP Goal 3: Heating, Ventilation and Air Conditioning (HVAC) will be transformed to ensure that its energy performance is optimal for California s climate. Vision: The residential and small commercial heating, ventilation, and air conditioning (HVAC) industry will be transformed to ensure that technology, equipment, installation, and maintenance are of the highest quality to promote energy efficiency and peak load reduction in California s climate. 4

HVAC Maintenance Rules of Thumb Testing or adjusting refrigerant charge based on an approved specification improves efficiency Increasing airflow by increasing fan speed improves efficiency Opening outdoor air dampers improves efficiency Adding new sensors and digital FDD controllers to economizers improves efficiency Without proper instructions, installation, maintenance, evaluation, and laboratory testing these procedures can actually reduce efficiency 5

WO32 Research Study Goals Develop load impact savings estimates for residential and commercial HVAC QM and QI measures implemented by statewide and 3 rd party programs Provide feedback for program improvement Field observations and laboratory measurements of QM and QI measures will be used to develop reliable energy and peak demand savings estimates for program design, implementation, and strategic planning 6

WO32 Sample Frame (127/199) Data logger sample of 44 units and 75 circuits SCE 53 units and 92 circuits 73% of total PG&E statewide ex post observations of 5 units and 10 circuits with more scheduled SDG&E statewide data logger observations of 20 units and 35 circuits 100% of total PG&E ACP ex post observations of 37 units and 50 circuits 59% of total SDG&E 3 rd party ex post inspections of 12 units and 12 circuits 36% of total 7

Commercial HVAC Programs EM&V study of 5 HVAC maintenance programs 3 statewide programs require ACCA 180 and 3- year maintenance agreements and pay customer incentives up to $3836/unit, contractor inventory incentives of $75/unit plus $2230/unit for repairs 2 local programs do not require ACCA 180 or 3-yr agreements and pay contractor incentives up to $775/unit (8x less than statewide) Measures: coil cleaning, refrigerant charge, airflow, economizers, thermostats, and notched v-belts 8

Statewide CQM Programs Statewide contractors are required to have C-20 license, financials, insurance, 5-yrs experience, no BBB claims, 3 qualified technicians, references, etc One large property management customer without C-20 license is participating in program Statewide programs offer training on marketing and entering data into program database ACCA 180 includes 30 inspection/maintenance tasks for Rooftop Units (per table 5-20) CSA includes 40+ tasks (30% > ACCA 180) 9

ACCA 180 Implementation 1. Responsible party (owner or designate) 2. Maintenance program for each unit to achieve manufacturer performance baseline ( discretion of technician is inconsistent with ACCA 180) 3. Inventory to establish unacceptable conditions, indicators, inspection frequencies, and tasks 4. Maintenance plan development (objectives, indicators, inspection & maintenance tasks, frequency, documentation) 5. Maintenance plan authorization and implementation 6. Revision of maintenance program 10

ACCA 180 Check List Note: ACCA 180 includes 30 tasks, but only seven (7) tasks impact energy efficiency for most units. 11

ACCA 180 Check List Note: Blue and yellow highlighted tasks impact energy efficiency for most units. Blue are already performed by technicians and yellow are not. 12

ACCA 180 Check List Programs assume technicians know how to properly perform all ACCA 180 tasks to bring a unit up to discretionary performance baseline According to one program bringing a unit to baseline means the contractor has completed all tasks, required repairs, and maintenance to make the unit operate efficiently ACCA 180 doesn t provide procedures for technicians to follow to properly diagnose and perform repairs for the unit to operate efficiently 13

What is Performance Baseline? Manufacturers provide unit-specific Installation, Start-Up and Service Instructions for airflow (fan speed/belt tension/alignment), coil cleaning, economizer setup/maintenance, refrigerant charge Non-TXV specifications: suction temperature as a function of condenser entering temperature and suction pressure TXV specifications: liquid pressure and temperature or discharge pressure and suction pressure as a function of condenser entering and indoor drybulb/wetbulb temperature 14

Mfgr Coil Cleaning Instructions 15

Mfgr Economizer Instructions 16

Mfgr Fan-Pulley/Belt Instructions 17

Manufacturer Charging Charts Non-TXV Suction Line Temperature LIQUID LINE TEMPERATURE (F). 160 140 120 100 80 60 TXV Liquid Line Temperature ADD CHARGE IF ABOVE CURVE REMOVE CHARGE IF BELOW CURVE 18 40 100 150 200 250 300 LIQUID LINE PRESSURE (PSIG) TO USE COOLING CHARGING CHARTS Non-TXV - Measure outdoor temperature, suction pressure and temperature. TXV - Measure liquid pressure and temperature. Refer to charts for targets. Add refrigerant if high and recover charge if low. Tolerance is +/-5F.

Manufacturer Charging Charts TXV Cooling Cycle Pressure Curves (Based on Indoor Airflow of 400 CFM/ton) Check Operating Pressures: 1. Start unit and allow pressures to stabilize. 2. Measure indoor DB/WB temperature entering indoor coil. 3. Measure outdoor air dry bulb temperature. 4. Take discharge and suction pressure readings. 5. Plot outdoor dry bulb and indoor DB/WB temperature onto chart. 6. At point of intersection, read down for suction pressure and left for discharge pressure. 19

Manufacturer Charging Charts Non-TXV Target Suction Temp Check Charge: 1. Start unit, energize all circuits, and allow pressures to stabilize for at least 15 minutes. 2. Measure outdoor air dry bulb temperature ad suction pressure. 3. Lookup outdoor temperature and suction pressure on chart. 4. At point of intersection, read down for suction temperature (tolerance is +/-5F). 20

Mfgr Restriction Instructions Check restrictions in multiple non-txv devices by disconnecting supply fan, start compressor, and verifying uniform frost pattern on evaporator Check for liquid line filter drier restriction by verifying temperature drop is less than 2 F If restrictions are present, recover refrigerant, make repairs, leak test with Nitrogen for 10 minutes (repair leaks and repeat), evacuate to 500 microns held at or below 1000 microns for 20 minutes before weighing in factory charge 21

Mfgr Heating Instructions Issue: Inefficient or inadequate space heating or continuous operation of furnace Probable cause: Dirty air filters, restricted airflow, or too much outdoor air Remedy: Clean or replace air filters, remove airflow restrictions, or adjust economizer minimum outdoor air damper position Analysis of laboratory data: Efficient OA damper position can improve heating efficiency and satisfy ASHRAE 62.1 for most buildings 22

Manufacturer OA Damper Charts Manufacturer Data of Outdoor Air Damper Position for 7.5-ton RTU (OA CFM versus Inlet Pressure) NEGATIVE PRESSURE (in. wg). 1.0 0.8 0.6 0.4 0.2 Laboratory Tests of Outdoor Air Damper Position for 7.5-ton RTU (OA CFM versus Inlet Pressure) CLOSED 0.75" OPEN 1.3" OPEN 2" OPEN 5" ECONO 0.0 0 2 4 6 8 10 12 OUTDOOR AIRFLOW (cfm x 100) @ 2500 scfm Dampers open ¾ to 2 reduce efficiency by 5 to 62% compared to closed dampers which provide 15%+ OA 23

Manufacturer Airflow Charts Manufacturer Airflow (cfm) vs. ESP (in H2O) and RPM At 935 RPM (3 turns) lab-measured airflow is 2682 cfm (358 cfm/ton) with 1.0 ESP and 6.85 EER At 756 RPM (6 turns) lab-measured airflow is 2523 cfm (336 cfm/ton) with 0.5 ESP and 7.66 EER (11.8% higher) with 6% total kw savings and 33% fan kw savings 24

Field Observations Field observation protocols follow the statewide or local program data collection protocols The study includes 4 types of field observations: 1) Pre-observations of 44 participating units (75 circuits) with data loggers installed 2) Ride-along observations of maintenance performed by participants on 44 units and 72 circuits 3) Post-maintenance observations after program services were performed of 83 units and 127 circuits 4) Observations of 22 non-participant units 25