Approval Standard for Water Motor Gong



Similar documents
ELECTRIC/DIESEL FIRE PUMP CHECK LIST

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

TD01211 PIN: NX nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

NFPA31FuelOilPiping 1 Revised

OREGON FIRE CODE Interpretations and Technical Advisories

Approval Standard for Plastic Suspended Ceiling Panels

Float and Thermostatic Traps Series H, C and X

Wet System. Technical Manual for Operation, Maintenance, and Troubleshooting

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

ROUGHNECK II Pumpless Drain

The following definitions apply with regard to requirements specified in this document:

TECHNICAL DATA. 30a. September 18, /4-8 (DN32 - DN200)

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

PBX Series Quick Fit Connector Bimetallic Steam Traps

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

Technical Data. Installation

LINEAR MOTION CONTROL

Design & Construction Standards, Revised January

SECTION FACILITY STORM DRAINAGE PIPING

BLADDER SURGE CONTROL SYSTEM

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

James M. Pleasants Company

Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts

OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual

Tube Type Oil Skimmer Comparison

HYDROSTATIC TEST PUMPS

! WARNING. Before using product, read and understand instructions.

Wet alarm valves. Wet alarm valves. FM trim

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

TYPE E Main Valve Sizes 3 /8 through 12

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz

Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

PLUMBING ROUGH IN INSPECTION

SPECIFICATIONS FOR APPROVED OFFSITE RECORDS STORAGE FACILITIES

Ultrasound Condition Monitoring

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

SANITARY GRAVITY SEWER LINE TESTING. B. Section CCTV Inspection of Gravity Sewer Lines

Optimizing Tank Cleaning Operations

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

The following definitions apply with regard to requirements specified in this document:

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

FAIRBANKS NIJHUIS FIRE PUMPS.

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER TECHNICAL ASSISTANCE FAX:

San Antonio Water System Standard Specifications for Construction ITEM 866 SEWER MAIN TELEVISION INSPECTION

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

Model 362A AURORA. 340A/360A Series SINGLE STAGE END SUCTION PUMPS.

OWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Morrison Bros. Co. General Product Specifications

BERMAD Fire Protection

Fall Protection System: A system put in place to protect workers from falling. (i.e. installation of guardrails, fall arrest, fall restraint, etc.

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

FOAM CHAMBER MODEL - FC

Transformer Deluge Systems

Engineering Specifications

MODEL INSTALLATION INSTRUCTIONS

BSM MOTOR DRIVEN CENTRIFUGAL PUMPS

SANITARY SEWER SPECIFICATIONS

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100

SAFETY SAFETY APPAREL 20,000 PSI

Operating, Installation, and Maintenance Instructions

In-Line Air Separators

Horizontal Split Case Fire Pumpset Diesel Engine Driven

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

VACUUM REFRIGERATION SYSTEMS

Mechanical Installation

DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING REPORT HOLDER: CURAFLO IP LLC 4035 E. OASIS STREET MESA, AZ 85215

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.

How To Use A Corona Mdi 110

BERMAD Fire Protection

[see Figure 3 below] Ferrite tile walls and ceiling RF Absorber parcel walls and ceiling Removable floor section to make fully anechoic

Approval Standard for Flammability of Absorbent Battery Acid Spill Containment Pillows

ASME Packaged Indirect Fired Water Heater

1300 MAXTRAK SPECIFICATION

MAC-120HE-01 Air-Cooled Chiller

Arapahoe County Residential Water Heater Installation and Inspection Guide

TECHNICAL DATA. Dry 122a. November 12, 2013

BOWIE PUMPS OPERATION - MAINTENANCE

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford

MONITOR SECTION INDEX

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

Model 1210C Battery Powered Pump Shown. Description

Inspection and Testing of Water-Based Systems

Installation S19-220PT S19-220BPT. Wall-Mounted Eyewash with Plastic Bowl. Wall-Mounted Eyewash with Stainless Steel Bowl.

OWNER S/OPERATOR S - PARTS MANUAL CEMENT MIXER MODEL MX-80

Industrial Electric Monitors. Industrial

EXTeRUS. EXTeRUS - With patented design, able to join technology. and quality of materials with a charming shape. Unique

CG PTFE Diaphragm Liquid Transfer Pump

Fire Pump Plan Review March 2010

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Installation Manual DIAPHRAGM WELL TANK

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

This will also provide you with the knowledge to insure long life for your Investment

Transcription:

Approval Standard for Water Motor Gong Class Number 1055 July 1970 2002 FM Approvals LLC. All rights reserved.

Foreword The FM Approvals certification mark is intended to verify that the products and services described will meet FM Approvals stated conditions of performance, safety and quality useful to the ends of property conservation. The purpose of Approval Standards is to present the criteria for FM Approval of various types of products and services, as guidance for FM Approvals personnel, manufacturers, users and authorities having jurisdiction. Products submitted for certification by FM Approvals shall demonstrate that they meet the intent of the Approval Standard, and that quality control in manufacturing shall ensure a consistently uniform and reliable product. Approval Standards strive to be performance-oriented. They are intended to facilitate technological development. For examining equipment, materials and services, Approval Standards: a) must be useful to the ends of property conservation by preventing, limiting or not causing damage under the conditions stated by the Approval listing; and b) must be readily identifiable. Continuance of Approval and listing depends on compliance with the Approval Agreement, satisfactory performance in the field, on successful re-examinations of equipment, materials, and services as appropriate, and on periodic follow-up audits of the manufacturing facility. FM Approvals LLC reserves the right in its sole judgment to change or revise its standards, criteria, methods, or procedures.

TABLE OF CONTENTS INTRODUCTION... 1 REQUIREMENTS... 1 Durability... 1 Audibility... 1 Sensitivity... 1 Port Sizes... 2 Inlet and Outlet... 2 Moving Parts... 2 Water Motor Housing... 2 Accessibility for Service... 2 Protective Cover... 2 Materials... 3 Markings... 3

July 1970 1055 INTRODUCTION A water motor gong is used to give a locally audible alarm signal when a fire protection sprinkler system operates. Such a device should be highly reliable and durable. FM Approval is based on examination and test of production samples, inspection of the manufacturing and/or quality control facilities, and use experience. Particularly considered are functional suitability, adequacy of design and workmanship, uniformity and dependability of production, effectiveness of quality control, and assurance of service and of replacement parts. Minimum physical requirements given below are guides. Mere conformity does not assure Approval since other considerations may control. Nor is strict conformity necessary; devices having different characteristics may be considered and Approved, if shown to be essentially equivalent or superior in performance. REQUIREMENTS Durability The water motor gong shall be designed to operate reliably without excessive maintenance. It will be subjected to a 60-hour continuous endurance run with an average operating pressure of 50 psi at the inlet to the device. No lubrication or adjustment will be made during this test. There shall be no evidence of any excessive wear at the completion of the test. Audibility The water motor gong shall produce an audible signal sufficient to alert a nearby plant employee during working hours or a guard or other person during idle hours. The sound should be loud enough and of such a pitch as to be clearly heard, above the average factory noise levels, at a distance of several hundred feet. It shall generate sound waves having a minimum sound-pressure level of 90 decibels (referred to a 0.0002 microbar base) using the C weighting, when tested in a room having a background noise level within the approximate range of 50 to 55 decibels and using 30 lb operating pressure at the inlet to the gong. Sound pressure level measurements will be made at a point 10 ft in front of the gong with the protective cover in place. Sensitivity Operation shall commence at a maximum pressure of 5.0 psig measured at the inlet to the device, upstream of the strainer, when the pressure is increased from zero. FM APPROVALS 1

1055 July 1970 Port Sizes Operating ports such as nozzles shall have a diameter of not less than 1 8 in. and be protected by a suitable strainer of corrosion-resistant material. The total area of all openings in the strainer screen shall be at least ten times the port area. The strainer, which shall be furnished by the gong manufacturer, may be located at the waterflow detecting device. Inlet and Outlet The inlet opening shall be suitable for connection to 3 4 in. IPS supply piping. The outlet opening shall be of ample size to facilitate the removal of waste water. A connecting pipe in the order of1to1 1 2 in. IPS will be acceptable. Moving Parts Shafts and other moving parts shall be designed to prevent binding and protected against mechanical injury. Bearings shall be self lubricating or have means for lubrication. The lubricant must be suitable for use over the range of temperatures between -60 F and 110 F. Water Motor Housing The water motor housing shall be able to withstand a hydrostatic pressure of 200 psig for 5 minutes. Accessibility for Service Design must permit disassembly for inspection, lubrication, adjustment or repair without removal from the supporting wall or structure. Suitable means shall be provided so that nozzle and strainer can be readily cleaned. Protective Cover An outer shield or protective cover shall be provided to protect the gong from deteriorating effects of rain and snow and to prevent nesting of birds, vermin, etc. A combination gong-cover shall be able to withstand six (6) blows from a 10 1 2 lb. steel ball, swinging as a 10 1 2 ft. long pendulum, hung directly over the gong from a height of five (5) feet. Point of contact between ball and gong-cover will be halfway between center of gong-cover and its periphery on a horizontal plane. Following this test, the operating water motor gong shall still sound an audible alarm. 2 FM APPROVALS

July 1970 1055 Materials All materials used shall be suitable for the intended application. Markings The shield shall carry the words SPRINKLER ALARM having a minimum letter height of 1 in. The lettering may be cast on the shield or may be on a separate plate which shall be substantially fastened to the shield. Cast letters shall be raised approximately 3 32 in. The body of the device (motor housing) shall be marked with the manufacturer s name or trade mark, and a distinctive model or figure number. FM APPROVALS 3