Documenting Results to Validate Energy Savings Projects: Case Study of Direct Drive Cooling Tower Installations: Before and After



Similar documents
Permanent Magnet Technology within Direct Drive Cooling Tower Motors Creates System Energy Savings

COOLING TECHNOLOGY INSTITUTE

solutions Baldor Is Redefining the Future of Cooling Tower Performance with Innovative 'Green' Motor and Drive Technology Plus

We will discuss common industrial applications with guides for the proper use of electric motors on these.

Unidrive M Energy Savings

ENGINEERING BULLETIN No. EB 039 Product: Cooling Towers, Closed Circuit Coolers & Evaporative Condensers Date: June 2003

Reliability. The Essentials of Eliminating Downtime of your Electric Motor. Asset Management? Or, Maintenance Management, Re-branded?

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford

DOUBLE A VFD DRIVEN TEST-STAND S THROUGHPUT AND CAPACITY Copyright Material IEEE Paper No. PCIC-(PCIC )

Product Brochure. Controlled start transmission

Basic Nameplate Information

SUSTAINABLE TECHNOLOGY

Controlled Start transmission

EVER EFFICIENT. EVER RELIABLE. EVER PROFITABLE.

HVAC Preventative Maintenance Basics. Presented by Mike Crawley

Power Factor The Basics

V kw The turbine that goes anywhere

300 Series PA Pump and Cooler Assemblies

AC Electric Motors best practice

Rules of Thumb Energy Efficiency in Buildings

Xcel Business Customers: Program and Rebate Summary

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Brochure. Generators for wind power Proven generators reliable power

ELECTROPUTERE ROTATING ELECTRICAL MACHINES DIVISION

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

1 Temperature Derating Guide

How To Save Energy On A Power Supply

Solving VFD-sourced Bearing Current Problems in AC Motors.

APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS

2011 DC Electropumps Bull. Rotation Ø 15 6,45 3,5 5,7

Centrifugal Fans and Pumps are sized to meet the maximum

Your professional Partner also for special Miniseries & special Series.

Shaft Alignment White Paper

ELECTRODE BOILERS VAPOR POWER INTERNATIONAL

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

Motor Specifications. Nameplate

Shaft grounding. Carbon brushes for shaft grounding are used in turbo-generators, in distinct AC- and DC motors and as a special application in Ships.

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Field Service and Replacement Parts for Air Cooled Heat Exchangers

Peak Shaving - A Method to Reduce Utility Costs

Comparing Energy Savings of Different VAV Systems

Drives and motors. A guide to using variable-speed drives and motors in data centres

vacon ac drives for mining & minerals

IEC Three Phase AC Motors (Aluminum Frame) Installation & Operating Manual

Variable Frequency Drives and Energy Savings

PMDD WIND TURBINE 1.5MW

V MW. Your best option for low cost energy production at low and medium wind sites. Federico Gonzalez Vives. Director Technology.

Unit 96: Marine Propulsion Power Plant

Wind Energy Math Calculations Calculating the Tip Speed Ratio of Your Wind Turbine

Energy Audits Waste Water Treatment Plants

Electric Motors and Drives

\ srl High Technology Gear Reducers and Cardan Shafts CERTIFIED QUALITY SYSTEM: UNI ISO EN 9001:2008 ICIM 2779/2; IQNET N. IT UNIVERSAL SHAFT

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

ENERGY-SAVINg DRIVE PACKAGE DE ES FR IT. Overview

Baldor Electric Position on DOE Small Motor Rule

Systematic Optimisation of Gearboxes for Hybrid and Electric Vehicles in Terms of Efficiency, NVH and Durability

The Reliance on Wind Energy Depends on Advancements in Blade Pitch Control

A Guide to Trouble-Free Cooling Towers

What Do All Those Things on an AC Motor Nameplate Mean?

Top Technology for Industry, Agriculture, Business and Communities

ABB drives for water Medium voltage drives for energy savings and life-cycle improvements

This slide is hidden. It will not show up during presentation.

2100, 2200, 2300, 4100, 6200, MPB Series Side Mount Drive Package for Standard Load 90 Industrial Gearmotors

Using Renewable Energy to Pump Water

Tim Facius Baltimore Aircoil

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

Mobile field balancing reduces vibrations in energy and power plants. Published in VGB PowerTech 07/2012

Harmonic Drive acutator P r e c i s i o n G e a r i n g & M o t i o n C o n t r o l

ROTATING MACHINES. Alignment & Positioning of. Fast, easy and accurate alignment of rotating machines, pumps, drives, foundations, etc.

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

EM Series Electrically Released Brakes

Chapter 3.5: Fans and Blowers

Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion

CNC Vertical Machining Center Alpha-Center HD Heavy cast iron design, precise guideways, high-performance gear designed for heavy machining

Fundamentals of Inverter Fed Motors

THE COMPOSITE DISC - A NEW JOINT FOR HIGH POWER DRIVESHAFTS

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Lecture 4 Energy Conversion in Wind Turbine

Product Data Bulletin

Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, HP

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

APPENDIX F VIBRATION TESTING PROCEDURE

Model 362A AURORA. 340A/360A Series SINGLE STAGE END SUCTION PUMPS.

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw

Reducing Data Center Energy Consumption

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future

Atlas Copco Stationary air compressors

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

Transcription:

Documenting Results to Validate Energy Savings Projects: Case Study of Direct Drive Cooling Tower Installations: Before and After Roman Wajda, Baldor Electric Company ABSTRACT Documenting the actual energy saving for green projects is often needed to validate expenditures and can be used to justify future energy savings projects. Often an energy savings project is started as a trial before it is scaled up across a plant or to other facilities in an organization. A Direct Drive Cooling Tower Motor and Drive package is a relatively new technology that can provide significant energy, environmental and reliability improvements. This presentation will be a case study that compares existing mechanical cooling tower drive system with a new Direct Drive Cooling Tower Solution. At a time were energy efficiency / savings is of utmost importance, recent developments in motor technology have changed the playing field within cooling tower HVAC systems. This new permanent magnet / laminated frame motor technology allows for the removal of all the mechanical components such as gearboxes, drive shafts, disc couplings and existing motors and replaces them with one direct drive Cooling Tower Permanent Magnet (CTPM) motor. With the removal of these mechanical components, the mechanical energy losses are also removed decreasing your overall system energy demands. Plus the system also sees higher motor efficiency gains with PM technology over standard induction motor efficiencies. To more fully understand the benefits of this technology, an understanding of the cooling tower application is important to clarify. There are typically two types of cooling towers found in the industry, cross flow towers and counter flow towers. These are defined by the direction of air passed over the waste water. A cooling tower is defined as a structure which extracts waste heat from a process and distributes it to the atmosphere. The most common method is to let heated water fall through a moving air stream created by a fan located at the top of the tower. This is an evaporative process which takes a large amount of heat from the process. The heated water is distributed over a "fill" material which increases surface area the water travels on and increases the cycle time within the tower. The water is cooled as it descends through the fill. The cooled water is then collected in a cold water basin below the fill from which it is pumped back through the process to absorb more heat. A typical tower arrangement is shown in Figure 1. 4-1

Figure 1. Typical Field Erect Cooling Tower Commonly, the size of a tower is identified by the diameter of the fan. Fan sizes range from 6 to 40 feet, with the most common applications in the 10 to 26 foot range. The speed of the fan is typically limited by industry standards for stressing which are typically rated as a max fan tip speed of 12,000 fpm. This max tip speed generates a fan speed in the range of 147-382 rpm. As the fan diameters become smaller or larger than the 10-26 ft. sizes the fan speeds can differ. The most common solution for driving the fan in current cooling tower designs utilizes an induction motor, driveshaft, disc couplings, and gearbox arrangement, as shown in Figure 2. Figure 2. Typical Fan Drive Arrangement The motor used is normally a standard NEMA induction motor. Cooling tower applications follow fan affinity laws which state that HP varies by the cube of the fan speed. To put this in perspective if we had an application requiring a 40hp load at full speed if we were able to reduce the speed to 50% due to lower heat load requirements the application needs would only be 5hp or only 12.5% of rated full load requirements which reflects a great reduction of energy consumption. Sometimes a 2-speed variable torque motor is used and these motors are not regulated by the U.S. DOE for efficiency level. The use of variable frequency drives (VFDs) has become much more commonplace in recent years within the industry on new construction due to the energy savings associated with 4-2

the fan affinity laws. Additionally, most towers being upgraded or refurbished are also being equipped with VFDs. These drives have the advantage of a soft mechanical start, no large starting current draw, and the ability to run the fan at any desired speed from zero to the maximum design speed for the application. The energy savings realized by using a VFD are well recognized and documented and in case study evaluations can be shown to save 37-47% of energy use as compared to applications without VFD s Historically, the mechanical components of the fan drive system, specifically the right angle gearbox, have been the largest maintenance issue for cooling tower installations. Gearbox failures, oil leaks, oil contamination, failed drive shafts, misaligned drive shafts and excessive vibration are all significant problems related to this type of fan drive system. And has been instrumental in the acceptance of this new technology into the industry. The features and benefits of the Direct Drive Cooling Tower Permanent Magnet technology have been embraced by the industry and have shown to deliver performance reliability and energy savings over traditional solutions. - Reduces Energy Use - Soft start capability reduces overall tower stress - Removes alignment issues - Removes mechanical rotating equipment - Increase reliability - Decreases noise levels - Decreases yearly maintenance - Decreases vibration levels - Decrease ingress of contamination due to trickle current during idle periods - Incorporates anti-wind mill option during idle periods - Increases safety by enclosing all rotating equipment inside the tower Many of the problems associated with cooling tower maintenance and reliability are solved with the CTPM motor design. The relatively high speed gear input shaft which typically runs at 1750rpm has been eliminated. The CTPM Direct Drive motor runs at the fan operating speed which are typically slow in the range of 147 382rpm. Vibration and noise concerns have been minimized. The driveshaft and associated disc couplings have been removed, thus eliminating problems associated with misalignment, natural frequencies, or delaminating of the driveshaft itself. The right angle spiral-beveled gearbox has been removed. Difficult maintenance associated with changing the oil, proper oil fill levels, contamination of the oil, oil leaks, and gearbox failures is no longer a concern. New motor technology now provides an alternative solution, the direct drive of cooling tower fans. PM motor technology combined with the finned, laminated frame design now allows the construction of low speed, compact motor for use in place of the existing gearbox. Data obtained to date indicates this solution will eliminate the problems associated with the right angle 4-3

gearbox and drive shaft design. By eliminating the gearbox, which is a significant source of loss in the system, improved system efficiencies can be realized. Case Study Dates Performed: The study was performed on August 5 th and 6 th, 2014. Location: This study occurred in Fort Worth, Texas Temperature: The high temperatures for August 5 th and 6 th, 2014 were approximately 96 to 98 Fahrenheit. Background Information The study was performed on a bank of cooling towers at a major manufacturer in the Dallas/Fort Worth area. The cells studied were physically located side by side from each other. The cells were original installed in the early 1980s (exact date unknown) and are assumed to be approximately 20 to 25 years old. The fiberglass towers were manufactured by the Ceramic Cooling Tower Company. The fans were each 16 feet in diameter with 24 X 24 bases (measured at bundles). Each fan had 10 blades. It was observed at the beginning of the study that the pitch and blade type of each fan were different (the new Cooling Tower Direct Drive (CTDD) solution having been upgraded fully at the time of the drive conversion). This study focused exclusively on energy usage differences between the Mechanical and Direct Drive (CTDD) Solutions. Sound levels were not considered for the purpose of this study. Specifics of Applications Studied 1) New Direct Drive Solution T-1A Motor - Cooling Tower Direct Drive (CTDD) Motor Duty - Continuous HP - 100 RPM - 219 Amps - 128 Volts - 460 Hertz - 14.6 Framesize FL4421Y Fan Blades - Bai. Moment 3397 Inch Lbs. Weight 64.99 Lbs Blade Pitches All blades on this fan were pitched at 15.6 as measured by the M-D Building Products Digital Level. 2) Mechanical (Geared) Solution T-1B Motor Premium Efficiency 4-4

Duty - Continuous HP - 125 RPM - 1785 Amps - 145 Volts - 460 Hertz - 60 Framesize 444T Gear Box Right Angle Gear Box Ratio 8:1 Blade Pitches Blades pitches were measured by the M-D Building Products Digital Level. Blade Number Pitch ( ) 1 6.9 2 7.4 3 7.0 4 7.4 5 7.0 6 7.5 7 7.5 8 7.0 9 7.0 10 7.4 Equivalency Ratio between Fans Since both the blade types and blade pitches between the 2 fans were different it was difficult to perform an apples to apples study without a conversion factor between the 2 units. Using available site parameters and Fan Design software, it was determined that an equivalency ratio of 1.983 would effectively scale the measured power of the mechanical drive Applying the equivalency ratio to this example allows us to consider this an apples to apples study and we find that the: Old Mechanical Drive Solution consumes an average of 87.25 KW New CTDD Solution consumes an average of 80 KW Findings Two samples were collected from each unit. A 36 minute sample was taken with a 4-5

sampling period of 0.5 seconds. A 15 day sample was also taken with a sampling period of 5 minutes. Data was collected during the sampling period for the following parameters. Voltage Current Frequency Active Power Reactive Power Apparent Power Power Factor Distortion Power Cos PHI Total Harmonic Distortion Volts Total Harmonic Distortion Amps Active Energy Reactive Energy 15 Day Study Average KW consumption over a 15 Day period (KW vs. Time) Figure 3: Average KW Consumption over a 15 Day Sample Period T-1A 36 minute Study Peak KW consumption over a 36 minute period (KW vs. Time) Note that KW is cycling up and down over a three minute period from ~ 0 KW to ~ 80 KW. This corresponds with a change in speed from ~24 RPMs to 217 RPMs. The average value of 44 KW seen in the fifteen day study is the average of these high and low values. For the purposes of this study, the full load full speed value of 80 KW as seen below in the 36 minute study was used for the comparison since the geared solution is operating at full load full speed. Figure 4: Peak KW Consumption over a 36 Minute Sample Period T-1A 4-6

15 Day Study KW usage over a 15 Day period (KW vs. Time) Scaled per the methodology discussed in section V, we can assume an average KW value of approximately 87.25 KW. Figure 5: kw Consumption over a 15 Day Sample Period T-1B 36 minute Study kw usage over a 36 Minute period (kw vs. Time) Scaled per the methodology discussed in section V, we can assume an average kw value of approximately 87.25 kw. 4-7

II. Summary Fan Pitch Present Motor Measured Power Equivalency Full Load Estimated Energy Arrangement Fan Design Fan Speed (Average) HP Full Load Full Speed Ratio Power Usage Savings Direct Drive 16KW10 217 15.6 100 80 kw 1X 80kW 8.31% Geared 16H10 223 7.2 125 87.25 kw 1.983X 87.25 kw Conclusion As well as the features and benefits of the Direct Drive Cooling Tower Permanent Magnet technology which delivered performance reliability and energy savings over traditional solutions. - Reduces Energy Use - Soft start capability reduces overall tower stress - Removes alignment issues - Removes mechanical rotating equipment - Increase reliability - Decreases noise levels - Decreases yearly maintenance - Decreases vibration levels 4-8

- Decrease ingress of contamination due to trickle current during idle periods - Incorporates anti-wind milled option during idle periods - Increases safety by enclosing all rotating equipment inside the tower 4-9