Part 9 SUBDRAIN DESIGN AND LAYOUT



Similar documents
SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

Beacon Hill Sewer District Standard Specifications

Part 7 GEOTEXTILE FILTER FABRICS

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems

A perforated conduit such as pipe, tubing or tile installed beneath the ground to intercept and convey ground water. or structures.

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION STORM DRAIN SYSTEM

Section 402. STORM SEWERS

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

Table of Contents Multi-Flow Golf Course Drainage Guide

Permeable Pavement Construction Guide

EXHIBIT "A. Technical Specifications for Water and Sewer Service Lines

Section 2100-Trenching and Tunneling

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

= gallons of water produced by a 1-inch rainfall. Basic Principles of Artificial Drainage. length (feet) X width (feet) X.

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

Stormwater/Wetland Pond Construction Inspection Checklist

EFFECTIVE FEBRUARY note: drainage permit required to call for a dampproof inspection

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA (7300 Short Road, Serene Lakes)

CHAPTER 6 - SANITARY SEWER

SIENA STONE GRAVITY RETAINING WALL INSTALLATION SPECIFICATIONS. Prepared by Risi Stone Systems Used by permission.

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION 9. All sewer laterals shall tie into the sewer main lines unless approved by the City Engineer.

Drainage A Crucial Component for Athletic Field Performance. Part Three: Sub-Surface Installed Drainage Systems

GEOSYNTHETICS ENGINEERING: IN THEORY AND PRACTICE

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

Specifications for Residential Property Owners Connection to New Public Sewer

SANITARY SEWER SPECIFICATIONS

Chapter 7 Plumbing Connections

FY08 SEWER POINT REPAIRS BID TABULATION

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS

SECTION STORM DRAINAGE SYSTEM

Indiana State Department of Health Construction Guidelines for Gravity and Flood-Dose Trench Onsite Systems

Checklist for plans to Construct, Alter or Repair An Individual Subsurface Sewage Disposal System

SECTION STORM DRAINAGE TABLE OF CONTENTS

SECTION 5: SANITARY SEWER SYSTEM DESIGN

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

817 - PIPE CULVERTS, EROSION PIPE, STORM SEWERS, SANITARY SEWERS & END SECTIONS SECTION 817

Ultra-Rib PVC Storm Sewer Pipe 8" - 30"

Installation of Large Diameter Buried Pipes

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

Exhibit A. Rules and Regulations for House Connections and Sewer Extensions

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

Sewer Rehabilitation Design Requirements

BMP-7. A sediment filter or an excavated impounding area around a storm drain drop inlet or curb inlet.

RETAINING WALL CONSTRUCTION DETAILS 2006 ESTIMATING AND INSTALLATION MANUAL. Featuring Highland Stone. anchorwall.com

TABLE OF CONTENTS. Manhole, Frame, and Cover Installation (includes Drop Manhole) Additional Manhole Depth

CHAPTER 8 CIVIL DESIGN

Nebraska Department of Roads Drainage and Erosion Control Manual December 2011 Appendix C: Pipe Material Policy Page C-1 PIPE MATERIAL POLICY

BMP 6.4.6: Dry Well / Seepage Pit

SECTION GRAVITY SANITARY SEWERS

Section 2 Specification 2.18 Concrete and/or Corrugated Steel Storm Sewer TABLE OF CONTENTS

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

The Manitoba Water Services Board SECTION Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11

City of Virginia Beach Public Utilities HRPDC Regional Construction Standards, 5 TH Edition Amendments May 19, 2014

8.01 STORM SEWERS, CATCH BASIN LEADS, AND EXTENSIONS

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST

MDWASD 8/1999 SECTION TRENCHING AND BACKFILLING FOR PIPING SYSTEMS

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

Chapter 3 CULVERTS. Description. Importance to Maintenance & Water Quality. Culvert Profile

Meets astm d3034 and astm f679. Building essentials for a better tomorrow

STANDARD SPECIFICATIONS SECTION INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

SECTION G SEWERS (STORM, SANITARY AND FDC)

SEPARATION OF WATER MAINS, SEWERS, STORM DRAINS, AND UNDER DRAINS

Foundation Drainage. Gable Roof Runoff. Hip roof Runoff. By: Brent Anderson, P.E. Moisture Control Engineering Leader STRUCTURAL TECHNOLOGIES

SECTION 5. Sediment Control Measures

CULVERT AND STORM SEWER PIPE MATERIAL POLICY ON FEDERALLY FUNDED LOCAL AGENCY PROJECTS UPDATED March 2013

Special Specification 7021 Water Main and Sewer Line Replacements

GAS INSTALLERS MANUAL CINERGY AND SUBSIDIARY COMPANIES CUSTOMER PROCEDURE FOR INSTALLING 3", 4", 6", AND 8" IPS PLASTIC GAS SERVICE PIPING

DIVISION 4300 STORM DRAINAGE

STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION SOURCES OF MOISTURE IN NEW CONSTRUCTION. Natural ground slope

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

UNIFIED FACILITIES GUIDE SPECIFICATIONS

CHAPTER 11 STORM DRAINAGE

X Planning X Quality X Maintenance & Operations

NRCS Overview. National Dam Safety Program Technical Workshop #19 February 22-23, 2012

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

CHAPTER 11 STORM DRAINAGE

Caltrans non-standard Special Provisions Pervious Concrete. David Akers Feb 28, 2012

1. ASTM C Sampling and Testing Concrete Masonry Units 2. ASTM C 1372 Standard Specification for Dry-Cast Segmental Retaining Wall Units

SECTION CONCRETE SEGMENTAL RETAINING WALL SYSTEM

Gravelless Distribution Products

Technical Manual: Plastic Pipe Used in Embankment Dams

SUMMARY OF PUBLIC WORK STANDARD SPECIFICATION REVISIONS 2016

SECTION 701 CULVERT PIPE, ENTRANCE PIPE, STORM SEWER PIPE, AND EQUIVALENTS

Installation Guidelines for Segmental Block Wall. Contents 1. INTRODUCTION MATERIALS... 2

SUDAS Revision Submittal Form

Transcription:

Part 9 SUBDRAIN DESIGN AND LAYOUT

Early subdrainage often consisted of placing free-draining material, mostly gravel and rock, in the axis of filled swales, as sketched above. These began to be employed in the late 1930s.

In the mid to late 1950s soil mechanics pioneers like Harry A. Cedargren developed permeable gravel mixtures which were intended to be self-filtering

SELF-FILTERING PERMEABLE GRAVEL DRAIN MIXES Sieve Size Percent Passing* 1 100 ¾ 90-100 3/8 40-100 No. 4 25-40 No. 8 18-33 No. 30 5-15 No. 50 0-7 No. 200 0-3 *CA Div Hwys Class 2 Permeable Mixture recommended by H. A. Cedargren and adopted as Caltrans Std Spec 68-1.025 in 1958

LIMITATION ON PERCENT FINES A key component of the Class 2 permeable mix is limiting the percent passing the No. 200 sieve to less than 3 percent by weight, meaning that the material has to be essentially free of silt or clay. This was because lab tests performed by revealed that small percentages of silt and clay sized material exert great impact on permeability. A material with 6 percent passing the No. 200 sieve can be expected to have 1/3 to 1/5 the permeability of a mixture limited to 3% fines.

HYDRAULIC EFFICIENCY Harry Cedargren recognized that hydraulic efficiency of subdrains depends upon the effective hydraulic conductivity of the adjacent native materials. For example, Class 2 Permeable mixtures generally exhibit hydraulic conductivity that averages about 5.0 x 10-2 cm/sec. Clean crushed rock (3/4" x 1.5" gravel) supports an average hydraulic conductivity of about 2 cm/sec. This range suggests that an equivalent volume of clean gravel could transmit about 40 times as much water as the Class 2 permeable mix to transmit the same volume of water that a single cubic foot of the clean gravel.

In the mid 1960s contractors began using asphalt coated perforated corrugated metal pipes (cmp) for subdrain collectors, to retard long-term corrosion of such pipes. Not of much value in long term

Polyvinyl Chloride (PVC) plastic pipes were gradually introduced for use as subdrain collectors beginning in the late 1960s. In the 1970s Acrylonitrile-Butadiene-Styrene (ABS) pipes became increasing utilized in sanitary sewer applications, which has carried over into subdrainage work

In 1964 the Uniform Building Code began requiring 9 cubic feet of Class 2 filter material per lineal foot of subdrain, with at least 6 inches of bedding beneath the perforated collector pipe

Subdrains can be laid out on keyway benches using any variety of techniques; such as lime or chalk to mark the desired trench line

After excavation, the subdrain trench should be inspected to see if intercepts the desired horizons and checked for longitudinal gradient using a hand level

A 6 inch bed of free draining material is placed in the floor of the subdrain trench prior to laying the perforated collector pipe

This shows placement of a perforated ABS collector pipe in the subdrain trench, prior to placement of any free-draining filter material. Collected water moves through the filter material, not necessarily through the perforated pipe. The pipe simply allows inspection of the system s operability.

After placing the bedding and the perforated collector pipe with cleanout risers, the entire subdrain trench is backfilled with free draining material and compacted

Since the introduction of geotextile filter cloths in the early 1980s, it has become increasingly common to employ cloth wraps around freedraining material, such as crushed ¾ x 1-1/2 drainrock. Increasingly stiff ABS collector pipes are also becoming more common.

Subdrain excavations can be provided with filter cloths and collector pipes without entering the trenches. Trenches deeper than 5-1/2 feet should be shored before allowing workmen to enter them

Geotextile filter wrapped subdrains have come to be known as burrito drains Drains should always be placed in low areas, where gravity flow is expected