PLUMBING FIXTURES GUIDELINES
|
|
|
- Gertrude Harris
- 10 years ago
- Views:
Transcription
1 COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING & SAFETY DIVISION 2902 BUILDING CODE MANUAL Article Page 1 of 6 PLUMBING FIXTURES GUIDELINES The following policy establishes guidelines which are intended to develop minimum number of plumbing fixtures for various occupancies. This guideline was developed in conjunction with the Los Angeles Regional Uniform Code Program (LARUCP) and covers new construction, as well as additions and alterations. The procedures outlined in this BCM are to be used by the building plan check engineers to determine the required number of plumbing fixtures. According to Section 2901 of the Los Angeles County Building Code(LACBC), all plumbing systems shall comply with the Los Angeles County Plumbing Code (LACPC). The LACPC Tables 4-1, 4-2, 4-3, and 4-4 shall be used in determining the required number of plumbing fixtures. Table 4-1 applies to all occupancies, while the remaining tables apply to the specific occupancies governed by the adopting State Agencies. (See Matrix Adoption Tables in the LACPC) For occupancies not listed in Table 4-1, the number of required plumbing fixtures shall be determined by the Administrative Authority, as stated in Section of the LACPC. In determining the required number of plumbing fixtures, the footnotes under item F below shall always be considered. A. New Buildings A. Calculate the occupant load using Table 10-A of the 2002 LACBC. B. Determine the required number of fixtures using the appropriate LACPC tables. B. Existing Buildings A. Change of Occupancy shall be treated as a new building. B. Additions and Alterations which increase the existing occupant load, may use one of the following options: Option I Calculate the occupant load of the addition or altered area (Table 10-A LACBC). Determine the required number of fixtures using the applicable table in LACPC. Provide the required number of fixtures within the addition or altered area. The required number of new fixtures may be located in a common area
2 2902 Article 3 Page 2 of 6 within the existing building as long as the common area is accessible to and from the addition or altered area. Option II Calculate the occupant load of the existing building (Table 10-A LACBC). Determine the required number of fixtures from the applicable table in LACPC. Calculate the total occupant load for both the existing building and the addition, or alteration (Table 10-A LACBC). Determine the required number of fixtures from the applicable table in LACPC. Subtract the number of required existing fixtures from the number of required existing plus the addition or alteration fixtures. The difference is the required number of additional fixtures. Option III Calculate the occupant load of the addition or alteration (Table 10-A LACBC). Determine the number of fixtures from the applicable table in LACPC. Determine the number of fixtures that was required for the existing building based on the Building Code under which the building was permitted. Subtract the number of required fixtures of the existing building from the actual number of fixtures of the existing building. Credit the difference to the number of fixtures required for the addition or alteration and provide additional required fixtures if needed. C. Alterations that do not increase the occupant load and are not a change in occupancy classification but may be a change in use, may maintain their existing nonconforming rights. D. Relocated Buildings shall be treated as new buildings. E. The following guideline for occupancies not included in Table 4-1 of LACPC shall be considered: 1. Retail spaces, markets, and wholesale stores Use 200 square feet per occupant to determine the occupant load for use in the following chart: Type of Building Water Closets* (fixtures per persons) Lavatories (fixtures per person)
3 2902 Article 3 Page 3 of 6 Male Female Male Female Retail, markets, or wholesale stores 1 : : : : : : One for each two water closets over 400, add one fixture for each additional 500 males and one for each 150 females. *Where urinals are provided, one water closet less than the number specified may be provided for each urinal installed, except the number of water closets in such cases shall not be reduced to less than two-thirds (2/3) of the minimum specified. 2. Hotels and Motels Minimum required bathroom facilities at lobby area shall be one toilet facility for each sex. For lounge, bar, and restaurant areas, determine occupant load based on Table 10-A of LACBC and calculate the required number of plumbing fixtures using Table 4-1 of LACPC. Hotel guest rooms are required to have one toilet facility. For conference rooms, ballrooms, meeting and gathering areas, determine the occupant load (OL) based on Table 10-A of LACBC. If OL is fifty (50) or more, use assembly places category of Table 4-1 of LACPC to determine the number of plumbing fixtures, otherwise, use office or public buildings category of Table Warehouses and Storage Buildings Table 10-A of LACBC usually yields high number of occupant load for these categories. If submitted plans show fixed rack structures, machinery, equipment, etc. on the floor plans, the plan check engineers may deduct the footprint of these elements from the gross floor area and calculate the occupant load based on Table 10-A of LACBC items No. 20, 26, and 29 respectively. Consequently, a determination of the number of plumbing fixtures is performed by using Table 4-1 of LACPC Industrial Warehouses category. 4. Self Service Laundromats The occupant load is determined by either using 30 square feet per occupant based on the gross floor area or based on the total number of washers and dryers by counting one occupant for every two machines (either a washer or a dryer). The number of plumbing fixtures is determined based on the chart below.
4 2902 Article 3 Page 4 of 6 Regardless of the occupant load, facilities with a total floor area of 1500 square feet or less need only provide a unisex toilet facility designed for use by both sexes. Type of Building Water Closets* (fixtures per persons) Lavatories (fixtures per person) Male Female Male Female Laundromats 1 : : : : : : One for each two water closets over 400, add one fixture for each additional 500 males and one for each 150 females. *Where urinals are provided, one water closet less than the number specified may be provided for each urinal installed, except the number of water closets in such cases shall not be reduced to less than two-thirds (2/3) of the minimum specified. 5. Sport Facilities Sport facilities may be used for other events (i.e. concerts, shows, ceremonies, etc.). To determine the proper occupant load, the use of the facility shall be defined at the time of plan submittal. The following guidelines shall be used to determine required number of plumbing fixtures. a. Facility is used only for sport activities Facility with fixed seating: Calculate the occupant load based on Section of LACBC and determine the number of plumbing fixtures according to Table 4-1 of LACPC under assembly places for public use. Number of toilet fixtures for designated employee and player arenas shall be determined based on type of occupancies using Table 10-A of LACBC and utilizing Table 4-1 of LACPC. Facility without fixed seating: Calculate the occupant load for the event area based on Table 10-A of LACBC and determine the number of plumbing fixtures according to Table 4-1 of LACPC under assembly places for public use. The number of toilet fixtures for designated employees and player arenas shall be determined based on occupancy groups using both Table 10-A of LACBC (use an occupant load factor of 50) and Table 4-1 of LACPC. b. Facility used for sport activities and other events If the center court or other areas in the facility is used for special events and/or labeled as multi-purpose room, an additional occupant load for these areas shall be determined based on a mutual agreement between the
5 2902 Article 3 Page 5 of 6 applicant, Building Plan Check Section, and Fire Department. This additional load shall be added to the numbers calculated in Section E.5.a. 6. Shell Buildings The following guidelines shall be used to determine the number of plumbing fixtures and the size of sewer and water lines required: II. III. IV. Calculate the occupant load based on the gross floor area and the projected use and occupancy of the building using Table 10-A of the 2001 LACBC. Determine the required number of fixtures using the appropriate LACPC tables. Although restrooms need not to be shown on floor plans, a determination of the size of sewer and water lines based on the total number of plumbing fixtures per item II is required and must be shown on the approved Plumbing and Building Plans. Building permits shall not be finalized unless properly sized building sewer is installed. Keep in mind, Certificate of Occupancy is not issued for shell buildings. F. Footnotes In multi-story buildings, Section of LACPC requires that accessibility (meaning availability) of the required plumbing fixtures not exceed one vertical story. For facilities in mercantile and business occupancies serving customers, Section of the LACPC allows a single set of restrooms to be accessible (meaning available) to both customers and employees. The required number of fixtures shall be the greater of the required number for employees or the required number for customers. Access to public facilities (for the customer) shall not be through areas designated for employee use only. Accessibility Requirements for Persons with Disabilities: New Facilities: When new facilities are provided, they must comply with disabled access regulations. Existing Facilities: When the existing facility is to be used in determining the overall required plumbing fixtures count (for both proposed addition and existing area), the existing facilities must comply with disabled access regulations (unreasonable hardship may be granted as applicable in Chapters 11A and 11B). Conflicts between Codes: Whenever there is a conflict between Codes or different provisions of the same Code, the most restrictive provision shall be applied.
6 2902 Article 3 Page 6 of 6 RECOMMENDED BY: ED ALEXANIANS Senior Civil Engineer APPROVED JOHN KELLY Superintendent of Building BY: HASSAN ALAMEDDINE Principal Engineer
BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION
BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC #135 2902 Article 1 01-26-15 Page 1 of 6 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
Revised: Previously Issued As: P/BC 2011-095 PLUMBING FIXTURES
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LABC Sec. 2901 Effective: 01-01-2014 DOCUMENT NO. P/BC 2014-095 Revised: Previously Issued As: P/BC 2011-095 PLUMBING FIXTURES Section 2901
CHAPTER 29 PLUMBING SYSTEMS. [P] TABLE 2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES a (See Sections 2902.2 and 2902.3) 1 per 40 for the
CHAPTER 29 PLUMBING SYSTEMS > SECTION 2901 GENERAL [P] 2901.1 Scope. The provisions of this chapter and the Phoenix Plumbing Code shall govern the erection, installation, alteration, repairs, relocation,
CHAPTER 29 PLUMBING SYSTEMS
CHAPTER 29 SYSTEMS Note: The amendments to Chapter 29 are different than the 2009 Seattle Building Code and are not marked with margin bars or arrows. SECTION 2901 GENERAL [P] 2901.1 Scope. The provisions
How To Calculate Fixture Counts For A Building
Calculating Plumbing Fixture Counts By Ronald L. Geren, AIA, CSI, CCS, CCCA, SCIP In 2005, New York City s legislature unanimously passed the Women s Restroom Equity Bill, which essentially requires that
BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC
BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC #145 106.4 Article 3 04-01-14 Page 1 of 7 PLUMBING FIXTURE REPLACEMENT ISSUE:
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
Chapter 16.130 PLUMBING CODE
DISSCUSSION ITEM 3 ATTACHMENT E Chapter 16.130 PLUMBING CODE 16.130.100 Plumbing Code - Incorporation. There is incorporated by reference, for purpose of adopting regulations, provisions, conditions, terms,
9770 CULVER BOULEVARD CULVER CITY, CA 90232-0507 www.culvercity.org. Incidental improvements: improvements that do not qualify as minor or
9770 CULVER BOULEVARD CULVER CITY, CA 90232-0507 www.culvercity.org Construction Permitting Guidelines for Businesses Moving into Existing Buildings in Culver City If your business is moving into an existing
Utility Service Application
Utility Service Application for Multi-family/Non-residential Developments Thank you for contacting the City of Tampa for your water and wastewater utility service needs. We have assembled this package
(1) (a) through (1) (e) (iv) Remain the same.
24.301.301 CORPORO BY REFERECE OF UFORM PLUMBG CODE (1) he Department of Labor and ndustry adopts and incorporates by reference the Uniform Plumbing Code, 2006 2009 Edition, referred to as the Uniform
Commercial Fee estimate The Building department will provide the actual fees at the time the permit is issued.
1. Determine the occupancy, type of construction, and floor area (square footage) Commercial Fee estimate The Building department will provide the actual fees at the time the permit is issued. 2. Determine
New York City Department of Buildings
The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright
Water Use Reduction Additional Guidance
December 1, 2009 (Updated July 6, 2012) Version 7 Water Use Reduction Additional Guidance This guidance applies to Water Efficiency (WE) Prerequisite 1 and WE Credit 3 in LEED 2009 for New Construction,
ADA Scoping: New Construction
U. S. A CCESS B O A R D T E C H N I C A L G U I D E ADA Scoping: This guide provides an introduction to the scoping requirements that form the basis for the Department of Justice s 2010 ADA Standards and
THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: Section 1. Article V of Chapter XII of the Los Angeles Municipal Code is added to read:
ORDINANCE NO. 1,;...8_U_8_2_2_ An ordinance adding Article V to Chapter XII, and amending Section 94.103.1.2.9, of the Los Angeles Municipal Code establishing water efficiency requirements for new development
Schedule B to By-law 33-2009
Amended by By-law 8-2016 Note: This consolidation is prepared for convenience only. For accurate reference the original by-laws should be reviewed. Floor Area Calculation Floor area shall: Schedule B to
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:
CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY
Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary
BUSINESS USE PERMIT APPLICATION
BUSINESS USE PERMIT APPLICATION Instructions and Information for Business Use Permits and Temporary Certificates of Occupancy are included at the end of this application. Planning and Development Services
INSTALLATION OF WATER-CONSERVING PLUMBING FIXTURES SB 407 California Civil Code Section 1101.1 2013 Green Building Standards Code
INSTALLATION OF WATER-CONSERVING PLUMBING FIXTURES SB 407 California Civil Code Section 1101.1 2013 Green Building Standards Code In 2009, the California State Legislature passed Senate Bill SB 407 which
BOARD OF EDUCATION Attachment: Discussion 10. PALO ALTO UNIFIED SCHOOL DISTRICT Date: 01.26.16
BOARD OF EDUCATION Attachment: Discussion 10 PALO ALTO UNIFIED SCHOOL DISTRICT Date: 01.26.16 TO: FROM: SUBJECT: Glenn Max McGee, Superintendent Bob Golton, Bond Program Manager Submittal of Plans to Division
CHAPTER 2: The Plumbing System
CHAPTER 2: The Plumbing System SECTION I: SIZING REQUIREMENTS Establish building dimensions Building height can be determined either by architectural drawings or # of floors times height/floor. (ex: 1
Plumbing Fixture Replacement (SB 407) for Existing Single-Family Residential, Multifamily Residential and Commercial Buildings
Community Development Department Building Division 39550 Liberty Street, PO Box 5006, CA 94537-5006 510-494-4460 ph www.fremont.gov Plumbing Fixture Replacement (SB 407) for Existing Single-Family Residential,
Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY
Table 200.5.10.1 PARKING SPACE RATES AND PARKING SPACE OCCUPANCY. AM = 6 a.m. to Noon. Adult Education School Adult Entertainment (A) in Policy Area 1 (PA1), Policy Area 2 (PA2) Policy Area 3 (PA3) at
ACCESSIBILITY CHAPTER 11
CHAPTER 11 ACCESSIBILITY SECTION 1101 GENERAL 1101.1 Scope. The provisions of this chapter shall control the design and construction of facilities for accessibility to physically disabled persons. 1101.2
SIZING OF WATER PIPING SYSTEM
SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures
Schedule B to By-law 33-2009 Part A Fees Payable for Permits
Floor Area Calculation Floor area shall: Part A Fees Payable for Permits (Effective January 1, 2015) a) be calculated by measuring to the outer face of exterior walls and to the centre of party walls or
Highway Requirements Part 4
Highway Requirements Part 4 INTRODUCTION CLASS A1 SHOPS 1. Almost half of all pedestrian accidents and a quarter of all vehicular accidents involve the presence of a parked vehicle. Stationary vehicles
SCHEDULE A BY-LAW B-6 CLASSES OF PERMITS AND FEES
1. CALCULATION OF PERMIT FEES SCHEDULE A BY-LAW B-6 CLASSES OF PERMITS AND FEES Permit fees shall be calculated based on the formula given below, unless otherwise specified in this schedule: Permit Fee
One of the fundamental design elements that every
Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things
Guideline for Implementation of California Civil Code Sections 1101.1 1101.8 Water-Conserving Plumbing Fixtures
Guideline for Implementation of California Civil Code Sections 1101.1 1101.8 Water-Conserving Plumbing Fixtures Information Bulletin No. IB-021 Effective: January 1, 2014 By: Chief Building Official For
Facilities Operations Customer Service Standards WORK ORDER PRIORITIES
Facilities Operations Customer Service Standards WORK ORDER PRIORITIES In order to provide fair and consistent maintenance service to all University faculty, staff and students, a work priority system
CONSTRUCTION PERMIT APPLICATION AND INSTRUCTIONS (Permit Application follows instructions)
CONSTRUCTION PERMIT APPLICATION AND INSTRUCTIONS (Permit Application follows instructions) When is a permit required? Section 403.42 and Section 403.62 of the Uniform Construction Code states: Any owner
Plumbing Code Sections For Commercial Food Facilities
Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health
Contact: Michelle Benson [email protected] 708-907-5301
Contact: Michelle Benson [email protected] 708-907-5301 NEW CONVENTION CENTER DINING CONCEPT - TECHNOLOGY AND FRESH MENU INTRODUCED AT SAVOR CHICAGO S MCCORMICK PLACE RESTAURANT OPENING 23 RD
2010 ADA Standards for Accessible Design. Department of Justice
2010 ADA Standards for Accessible Design Department of Justice September 15, 2010 Reproduction of this document is encouraged. This publication may be viewed or downloaded from the ADA website (www.ada.gov).
CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714
CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714 BUILDING DIVISION (714) 961-7120 Single Family Residential New Construction, Additions & Alterations Submittal Requirements Required agency approvals
2016 BUILDING PERMIT FEES*
2016 PERMIT FEES* Fees are based on the cost of construction and shall be based on a value not less than the value determined using the Building Valuation Data Report published by ICC. Application Fee
Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents
Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The
Guidelines for Remodeling and Additions with Respect to On-site Wastewater Treatment Systems
PURPOSE Guidelines for Remodeling and Additions with Respect to On-site Wastewater Treatment Systems The Sonoma County Permit and Resource Management Department (PRMD) Well and Septic Division strives
Electrical Contractors. and the. New Jersey. Rehabilitation Code
Electrical Contractors and the New Jersey Rehabilitation Code Alan Chech Electrical Seminars 609-890-7072 www.alanchech.com Information is based on the presently adopted electrical subcode NEC 2005. Current
Measurement Standards for Structures
DALLAS/FT. WORTH INTERNATIONAL AIRPORT Measurement Standards for Structures November 2002 Updated: September 2003 Planning & Real Estate Department Table of Contents Standards for Measurements of Constructed
Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection
Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Jobs are Alaska s Future MECHANICAL INSPECTION CUSTOMER COUNTER LOCATIONS Main Office MI Anchorage
WATER & SEWER SERVICES
WATER/SEWER ENGINEERING SECTION PHONE (703) 228-3677 WATER & SEWER SERVICES INFORMATION & APPLICATION PACKAGE REVISED MAY 2014 1 MAY 2014 Dear Customer: Thank you for taking the time to read this information
SECTION THREE CONSTRUCTION CODES
SECTION THREE CONSTRUCTION CODES CHAPTER 36: Construction Codes in Michigan Purpose and Applicability of Regulations Manufacturing facilities and other businesses must be designed according to code in
Event & Sports Marketing Partnership Programs - Haymarket SportsPlex
Event & Sports Marketing Partnership Programs - Haymarket SportsPlex Partnership Opportunities: Main Sports Arenas Meeting Rooms Banners Lobby Wall Business Card Rack Business Flyer Rack Program Sponsorships
HOW TO START A COFFEE SHOP IN PHILADELPHIA
HOW TO START A COFFEE SHOP IN PHILADELPHIA Many newcomers to Philadelphia begin their careers as entrepreneurs by opening small business throughout Philadelphia s neighborhoods. Experts note that although
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
APPLICATION FOR NEW CONSTRUCTION
CITY OF ELKINS 401 DAVIS AVE ELKINS WV 26241 Date Pd: Receipt #: Session #: PHIL ISNER BLDG INSPECTOR / CODE ENFORCEMENT OFFICER 304-636-1414 Ext 1431 APP. DATE APPLICATION FOR NEW CONSTRUCTION APPLICANT
Commercial Energy Use Worksheet
Commercial Energy Use Worksheet Did you know? The City of Austin requires all commercial buildings that are 10,000 square feet or greater in size located within its city limits and served electricity by
REQUIREMENTS FOR SINGLE FAMILY DWELLINGS
REQUIREMENTS FOR SINGLE FAMILY DWELLINGS New Single Family Dwelling Additions or Renovations to Single Family Dwelling An application for a building permit, when adding plumbing fixtures to a new single
Typical storey plan with two toilet clusters SANITARY PROVISION SANITARY PROVISION. Individual washroom. Standalone, unisex individual washroom
ACCESSIBLE TOILET REQUIREMENTS Code 2007 o Where toilets are provided at every level of a building Accessible individual washroom or WC compartment can be provided Disadvantage If WC compartment is provided,
TARRANT COUNTY PUBLIC HEALTH DEPARTMENT 817-321-4960 fax 817-321-4961 FOOD ESTABLISHMENT REVIEW APPLICATION
TARRANT COUNTY PUBLIC HEALTH DEPARTMENT 817-321-4960 fax 817-321-4961 FOOD ESTABLISHMENT REVIEW APPLICATION Date: NEW REMODEL Name of Establishment: Category: Restaurant Institution Daycare Retail Market
RESIDENTIAL WINDOW REPLACEMENT
3S258 MANNING AVENUE WARRENVILLE, IL 60555 PH: 630.393.9050 FAX 630.393.1531 RESIDENTIAL WINDOW REPLACEMENT A building permit is required for the installation or replacement of windows in a residence.
Isometric Plumbing Drawings
Building Inspections Isometric Plumbing Drawings All commercial building permit applications, in which the plumbing system has not been designed by a mechanical engineer, must include two sets of isometric
MARICOPA COUNTY ENVIRONMENTAL HEALTH CODE
MARICOPA COUNTY ENVIRONMENTAL HEALTH CODE CHAPTER II SEWAGE AND WASTES SECTION 6 CHEMICAL TOILETS, PORTABLE RESTROOM UNITS, PORTABLE WASTE HOLDING TANKS REGULATION 1. Definitions a. "Chemical toilet" means
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 [email protected]
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 [email protected] b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:
2-7.5 2-7.8 CITY OF BAY CITY ORDINANCE NO. 628
CITY OF BAY CITY ORDINANCE NO. 628 AN ORDINANCE FOR THE CONTROL OF BACKFLOW AND CROSS- CONNECTIONS, REPEALING ORDINANCE NO. 560 AND DECLARING AN EMERGENCY. THE CITY COUNCIL OF THE CITY OF BAY CITY, OREGON
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS
2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS IBC CODE DESIGN CHECKLIST (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Transfer the resulting data on the building plans Life Safety & Building
CITY OF CHICAGO DEPARTMENT OF BUILDINGS RULES AND REGULATIONS for CERTIFICATES OF OCCUPANCY
Rule 1. Definitions. CITY OF CHICAGO DEPARTMENT OF BUILDINGS RULES AND REGULATIONS for CERTIFICATES OF OCCUPANCY For the purpose of these Rules, the following definitions shall apply: Applicant means any
The Raleigh Convention Center Raleigh, North Carolina Green Building Education A Self Guided Walking Tour
The Raleigh Convention Center Raleigh, North Carolina Green Building Education A Self Guided Walking Tour Building Dedication Ceremony September 05, 2008 An evening view of the west facing Shimmer Wall
ADA Design Guide Washrooms & Showers
ADA Design Guide Washrooms & Showers Accessories Faucets Showers Toilets Lavatories interactive version available at bradleycorp.com/adaguide.pdf Accessible Stall Design There are many dimensions to consider
Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text
Code Amendment 12/20/12 2011 Oregon Plumbing Specialty Code, Grease Interceptors & Fats, Oils and Greases Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text 204.0
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST
KBC Chapter 34 : Applying the Kentucky Building Code to Existing and Historic Buildings
KBC Chapter 34 : Applying the Kentucky Building Code to Existing and Historic Buildings Presented by: Kentucky Department of Housing, Buildings, and Construction Kentucky Heritage Council Louisville Metro
The New Realities of Water Recycling in San Francisco
The New Realities of Water Recycling in San Francisco World-Leading Technology and Expertise in Commercial Water Recycling Gibran Farrah Manufacturers Representative Mega Western Sales Christian Park Environmental
City of Riverside. Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING PERMIT & PLAN CHECK FEES The attached sheets will assist you in calculating an estimate of the fees for your building project.
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
MEMPHIS FACT SHEET TOURISM STATISTICS
For further information, contact the Public Relations Staff of the Memphis CVB: Regena Bearden, [email protected] Jackie Reed, [email protected] Alissa Clark, [email protected] MEMPHIS FACT SHEET TOURISM STATISTICS
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
Saint Cloud Business Center
Saint Cloud Business Center 14 7th Avenue North Saint Cloud, MN 56303 For Sale Located on 7th Avenue in the heart of downtown across from the Court House Square. A large professional reception area with
PLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
CHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving
COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No.
COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No. 2013-0049) Effective July 1, 2014, Electrical Permit Fees in the unincorporated
TENT AND STAGE CUSTOMER ASSISTANCE GUIDE
TENT AND STAGE CUSTOMER ASSISTANCE GUIDE Charles County Government Department of Planning & Growth Management P.O. Box 2150 La Plata, MD 20646 (301) 645 0692 / (301) 870 3935 Fax: (301) 645 0575 Web Site:
Accessibility Guide for Small Businesses
. Accessibility Guide for Small Businesses June 2015 Second Edition Preface This document is intended to provide explanation and technical guidance to assist owners of small businesses of the accessibility
Building Permit, Fire Inspection and Operating Permit Fee Schedule
Chenango County Code Enforcement Building Permit, Fire Inspection and Operating Permit Fee Schedule Building Permit Exceptions: Buildings being used solely for the purpose of agriculture. As per Agricultural,
Applies to: All Employees within the Facilities Management Department (FMD)
Building Area Measurement Guidelines Applies to: All Employees within the Facilities Management Department (FMD) GUIDELINES: Issued: December 17, 2013 Author: FMD Physical Planning Team PURPOSE: To establish