A Case Study on Coal to Natural Gas Fuel Switch

Size: px
Start display at page:

Download "A Case Study on Coal to Natural Gas Fuel Switch"

Transcription

1 A Case Study on Coal to Natural Gas Fuel Switch by Brian Reinhart, P.E. Presenter Alap Shah Mark Dittus Ken Nowling Bob Slettehaugh Black & Veatch December 12, 2012 INTRODUCTION In the United States, natural gas prices have fallen in recent years because of the stagnant economy, weakened demand for electricity and increased shale gas production supply. This has led to a reduction in coal-fired electricity generation, with some of the coal-fired generation being replaced by natural gasfired generation. Low natural gas prices and static coal prices have created a business opportunity for power producers to switch from coal-fired to underutilized natural gas-fired power plants. In addition, increasingly stringent environmental regulations will require many coal-fired units to be retired or to be retrofit with emissions control equipment for continued operation on coal. This paper explores several technically feasible options available in the current market. The selection of the most advantageous option is influenced by factors such as performance, capital cost, operating cost, fuel flexibility and emissions control requirements. Other factors to consider are ease of integration with the existing plant, the possibility of reusing existing balance-of-plant equipment, operating flexibility, operations and maintenance costs, and technical risk mitigation. Often, the characteristics of the coal-fired unit dictate the most advantageous generation option. The vintage, size, site characteristics and emissions control equipment currently in place can define which option is the most cost-effective and capable of aligning with the current business model. The case study presented is based on a subcritical pulverized coal-fired unit with a nominal gross output of 250 megawatts (MW). The unit was commissioned in the late 1970s. Emissions control is limited to a cold-side electrostatic precipitator (ESP), and heat rejection is by a wet mechanical-draft cooling tower. The unit was constructed on a two-unit site with limited space available between the boiler and the stack. The site layout included future expansion of a third unit, so space is available adjacent to the subject unit. Over the last few years, dispatch of the unit has declined because of low natural gas prices relative to coal prices in the region. The unit currently operates during intermediate and peak demand periods and has an annual capacity factor of about 45 percent. The nearest large natural gas pipeline is approximately 60 miles from the site. A new supply line to the site would traverse rural land. Transmission is not constrained in the area; sufficient margin exists for increased electrical export. Options considered for the case study include the following: Option 1a Full Conversion to Natural Gas Only. Natural gas would be used to fire the existing boilers. The major plant equipment such as the boiler, steam turbine and heaters would still be used; however, this conversion option may require modifications to the unit. Option 1b Conversion to Coal with Natural Gas Co-Firing. Coal would be retained as the primary fuel and co-fired with natural gas. As with Option 1, major equipment would be reused. In addition, emissions control equipment retrofits would likely be required to comply with air regulations for coal-fired generating units. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 1

2 Option 1c Emissions Control Equipment Retrofit. Emissions control equipment would be added to the existing coal-fired generation unit to reduce emissions. Option 2a Repowering Steam Turbine in a Combined Cycle. The existing steam turbine would be repowered as part of a combined cycle configuration. Repowering would consist of using new combustion turbine/heat recovery steam generator (HRSG) train(s) with the steam turbine. Option 2b Replace with New Combined Cycle. A new natural gas-fired combined cycle configuration block would replace the existing unit. Existing infrastructure, such as water/wastewater supply and treatment, transmission and buildings, may be reused. POTENTIAL OPTIONS Five potential options are presented. Option 1a, Option 1b and Option 1c all entail continued use of the case study unit s boiler. Each of these options retains approximately the same net output. Option 2a and Option 2b both entail retirement of the case study unit s boiler. Each of these options has a net output nearly three times the size of the existing unit. Replacing a small unit with a much larger unit might not be feasible for some owners. Option 1a Full Conversion to Natural Gas Only The unit being evaluated in this case study would be able to maintain gross output without modification or replacement of the forced draft fans and boiler heat transfer surfaces. Main steam and reheat steam conditions would be maintained. Therefore, steam turbine output and heat rate would remain unchanged. This will not always be the case. Refer to the following paragraphs for potential modifications required to minimize unit performance impacts. Coal handling and processing equipment and the primary air fans would be removed from service, which would reduce auxiliary load. However, boiler efficiency would be reduced because of an increase in latent heat losses. A summary of performance impacts associated with converting the case study unit from coal to natural gas is presented in Table 1. Option 1a, along with three other options presented, would require natural gas. The cost of bringing natural gas to the site is potentially significant. The cost to tie into an existing major gas pipeline, construction of a new pipeline to the site, installation of a revenue metering station and associated rights-of-way can be anywhere from several hundred thousand dollars to more than $1 million per linear mile of pipeline to the site. In addition, options involving the addition of combustion turbines would require elevated natural gas pressure, ranging from approximately 400 to nearly 1,000 pounds per square inch at the combustion turbine interface, depending on the model. Unless the site has ready access to a high-pressure (HP) natural gas pipeline, natural gas compressors would be required. TABLE 1 OPTION 1A CASE STUDY PERFORMANCE IMPACTS Parameter Approximate Change from Current (unless noted otherwise) Net Output, MW +5 Fuel Heat Input Coal, % of Total (HHV basis) 0* Natural Gas, % of Total (HHV basis) 100* Net Unit Heat Rate, Btu/kWh +200 *Percent of total heat input of the converted unit, on a higher heating value (HHV) basis. Btu/kWh = British thermal units per kilowatt-hour. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 2

3 Natural gas supply lines to the burner levels are a potential explosion hazard and would require careful consideration of pipeline routing and electrical equipment design. Areas around potential leak points would be classified as hazardous areas. Equipment and systems within these areas would need to be designed to function safely. Conversion to natural gas could be as simple as installing a gas nozzle on an existing coal burner and tying into the existing natural gas supply system, or the conversion could be more complex, requiring the installation of completely new burners, boiler modifications, boiler auxiliary equipment modifications or replacements, and entirely new off-site and on-site natural gas supply systems. In order to maintain unit capacity, modifications might be required when converting from coal to natural gas including modification or replacement of existing forced draft fans, air heater modifications, and superheat and reheat surface modifications. The degree of the required modifications would depend on the unit being considered. Control system modifications would be required to incorporate natural gas into the plant s operating system. The modifications include updating or replacing the existing burner management system with a system that incorporates the new natural gas valve trains and instrumentation. Since natural gas has only trace amounts of ash, slagging and fouling would not occur. This lack of slagging and fouling may have a hidden risk of leading to more heat transfer problems in the boiler; coal-fired boilers are designed with a default assumption of a certain amount of slag and reflective ash coating their surfaces. In addition, some boilers have been modified over time to better accommodate coal-based slagging levels (such as adding heat transfer surface in the upper furnace), which might lead to heat transfer imbalances in the unit. Where they exist, these imbalances could normally be corrected with heat transfer surface changes, use of refractory overlays to shield tubes or by careful attention to the gas burner placement and heat distribution within the boiler. Gross output of the unit may be affected if the forced draft fans are unable to maintain adequate combustion air to the boiler or if heat transfer from the combustion flame to the boiler surfaces is altered enough to affect flow through the boiler. Turbine output and heat rate are generally not affected unless boiler heat transfer is so strongly impacted that the target main steam or reheat steam conditions cannot be met. Some small Rankine steam cycle benefits might be realized if the unit could reduce superheat steam attemperation and reduce or cease operation of steam soot blowers, air preheat coils and flue gas desulfurization (FGD) reheat coils. Auxiliary electric load requirements would be reduced as a result of removing the coal handling system and pulverizers from service and shutting down or bypassing emissions control equipment. Natural gas hydrogen content is drastically higher than that of coal. Therefore, latent heat losses tend to be higher. The boiler efficiency would generally be decreased, depending on the type of coal currently being fired in the unit. Converting a unit from coal to natural gas generally increases unit availability. This is because a switch to natural gas tends to alleviate the following four fuel-related problem areas most likely to cause forced unit derates: Pulverizer capacity limitations/failures. Fan flow capacity limitations. While forced draft fan duty could increase, induced draft (ID) fan duty would decrease. Excessive stack emissions rates. Boiler slagging and fouling. Any option involving the complete conversion from coal to natural gas would likely reduce staff requirements at the plant, since coal yard personnel and some emissions control and maintenance staff would no longer be needed. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 3

4 Option 1b Conversion to Coal with Natural Gas Co-Firing In addition to replacing oil-fired warm-up guns with natural gas-fired guns, the unit being evaluated in this case study would need to be retrofitted with emissions control equipment to comply with Mercury and Air Toxics Standards (MATS) for mercury, hydrogen chloride (HCl) and particulate matter (PM). Issues associated with other air emissions regulations, such as the currently vacated Cross-State Air Pollution Rule (CSAPR), Regional Haze Rule/Best Available Retrofit Technology (BART), National Ambient Air Quality Standards (NAAQS) and greenhouse gases (GHGs), are not considered in this example. Emissions control retrofits for the case study unit would consist of powdered activated carbon (PAC) injection (alternatively referred to as activated carbon injection [ACI]) for mercury control and semidry flue gas desulfurization (SDFGD) and fabric filter combination for HCl and PM control. The existing cold-side ESP would be demolished and removed from service. The additional pressure loss associated with addition of an SDFGD and replacement of an ESP with fabric filter would necessitate the addition of ID booster fans. A summary of performance impacts associated with converting the case study unit from coal to coal with natural gas co-firing is presented in Table 2. TABLE 2 OPTION 1B CASE STUDY PERFORMANCE IMPACTS Parameter Approximate Change from Current (unless noted otherwise) Net Output, MW -9 Fuel Heat Input Coal, % of Total (HHV basis) 50* Natural Gas, % of Total (HHV basis) 50* Net Unit Heat Rate, Btu/kWh +600 *Percent of total heat input of the converted unit, on an HHV basis. Retrofitting a coal-fired boiler to co-fire natural gas could be as simple as replacing the existing oil-fired ignitors with new natural gas-fired Class 1 ignitors. This modification typically allows for a maximum gas firing capability of 10 to 20 percent. If the unit is equipped with oil-fired warm-up guns, these can be replaced with natural gas-fired guns to increase the potential natural gas capability to approximately 30 to 50 percent. If a higher level of natural gas co-firing is required, natural gas firing capability would need to be incorporated into the main burner system. Potential modifications include installation of gas rings around the existing coal burners, installation of gas spuds in the annulus or center of the burner, or other means to allow for inserting natural gas into the existing burner. Typically, the most cost-intensive option for coal and natural gas co-firing is either the addition of fullsized natural gas burners or the replacement of coal burners with natural gas or dual-fuel burners. Often, the largest risk associated with co-firing is poor natural gas burner placement, which could result in excessive temperatures or incomplete combustion in certain areas. Modifications to the boiler and boiler auxiliary equipment are often minimal or not required. Control system modifications would be required to incorporate additional burners and natural gas into the plant s operating system. As long as the burner management system is of a newer vintage, the existing system can be modified and reused. Updates to the combustion control system would also be required. A disadvantage of coal and natural gas co-firing is that the converted unit would still be considered a coal-fired unit from a regulatory perspective. In addition, displacing only a portion of coal with natural gas generally would not, by itself, be sufficient to meet air regulations. For example, in most cases, a BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 4

5 combination of natural gas co-firing and emissions control equipment retrofits would be required to ensure compliance with the MATS for existing coal-fired electric generating units. Option 1c Emissions Control Equipment Retrofit The selection of emissions control equipment is project-dependent, and the compliance solutions vary widely. For the purpose of this case study, the unit being evaluated would need to be retrofitted with emissions control equipment to comply with MATS for mercury, HCl and PM. Emissions control retrofits for the case study would consist of PAC injection, SDFGD, fabric filter and ID booster fans. The existing cold-side ESP would be demolished and removed from service. A summary of performance impacts associated with retrofitting the case study unit with emissions control equipment is presented in Table 3. TABLE 3 OPTION 1C CASE STUDY PERFORMANCE IMPACTS Parameter Approximate Change from Current (unless noted otherwise) Net Output, MW -12 Fuel Heat Input Coal, % of Total (HHV basis) 100* Natural Gas, % of Total (HHV basis) 0* Net Unit Heat Rate, Btu/kWh +600 *Percent of total heat input of the converted unit, on an HHV basis. Some potential issues to consider when retrofitting an existing coal-fired unit with emissions control equipment include the following: Switch from ash sales revenue to ash disposal cost (particularly with PAC injection). Increased fly ash production. Replacement or addition of flue gas fans. Flue gas duct and boiler stiffening. Increased truck traffic. Increased operating and maintenance expenses and staffing. Additional effluent concerns (particularly with wet flue gas desulfurization [WFGD]). Increased auxiliary electric loads. Option 2a Repowering Steam Turbine in a Combined Cycle For the case study, the 2-on-1 combined cycle block configuration consisting of the existing steam turbine receiving steam from two combustion turbine/hrsg trains is assumed to produce a gross output of approximately 600 MW on an average day without the use of supplemental HRSG duct firing. The existing condenser and wet mechanical-draft cooling tower would continue to reject heat from the steam cycle. A summary of performance impacts associated with repowering the case study unit s steam turbine in a combined cycle configuration is presented in Table 4. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 5

6 TABLE 4 OPTION 2A CASE STUDY PERFORMANCE IMPACTS Parameter Approximate Change from Current (unless noted otherwise) Net Output, MW +350 Fuel Heat Input Coal, % of Total (HHV basis) 0* Natural Gas, % of Total (HHV basis) 100* Net Unit Heat Rate, Btu/kWh -3,300 *Percent of total heat input of the converted unit, on an HHV basis. Reusing a portion of an existing coal-fired unit by replacing the boiler with natural gas-fired combustion turbine/hrsg train(s) as the steam source for an existing steam turbine generator in a combined cycle block configuration has the potential for modest life cycle cost savings compared to using a new combined cycle block because some of the major equipment and common systems from the existing coal-fired unit may be reused in the combined cycle configuration. In addition, efficiency would be much higher than converting a coal-fired boiler to natural gas. However, the modest life cycle cost savings are often not enough to offset the unit outage requirements and associated project risk when compared to a new combined cycle. A reused steam turbine would likely experience a derate from nameplate capacity. A coal unit s Rankine cycle converts fuel into heat through steam in a boiler. Typically, all of the steam sent from the boiler to the steam turbine is first sent at high pressure and temperature to the HP turbine admission. As the steam travels from the first stage of the HP turbine to the last stage of the low-pressure (LP) turbine, the mass flow decreases, so that the LP turbine receives only a portion of the flow the HP turbine passes. In a combined cycle block configuration where the HRSG produces steam by using the waste heat from the combustion turbine exhaust, steam is sent to the steam turbine, often at two or more pressures, and the condensate is heated in the HRSG itself. Going from the HP turbine to the LP turbine, steam mass flow increases, which is the opposite of a traditional coal unit s Rankine cycle. As a result, the repowered steam turbine is much more back-end loaded than it was originally designed and is usually unable to meet its original nameplate capacity. Typically, the derate is approximately 10 to 20 percent of original nameplate capacity. However, the addition of combustion turbine generators would more than make up for the steam turbine generator derate, resulting in a major overall increase in plant output. The attractiveness of this option will depend on the extent to which existing facilities and systems can be reused. Candidate facilities for reuse include the control room, administration building, maintenance building, water sample laboratory, turbine hall and site security. Candidate systems for reuse include water supply and treatment, wastewater, chemical feed, compressed air, condenser, condensate system, fire water supply, auxiliary power and plant communications. In addition to inside-the-fence plant savings, ready access to transportation, transmission and water could result in substantial cost savings. The three most critical considerations for this option are as follows: Existing means of heat rejection. Facilities with closed loop heat rejection systems that are based on either a cooling tower or air-cooled condenser are ideal candidates for consideration. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 6

7 Space availability for combustion turbine/hrsg trains and associated equipment. The need for significant demolition of existing facilities would add cost and could result in increased outage time/generation losses during construction. Current site electrical export capacity. Replacing a small unit with a unit nearly three times the size might not be possible without transmission interconnection upgrades. The capacity increase could make this option difficult to adopt for many owners with smaller fleets or assets within transmission-constrained regions, which are strategically distributed to meet local demand. Option 2b Replace with New Combined Cycle The option considered for this case study consists of two F-class natural gas combustion turbine/hrsg trains supplying steam to a reheat steam turbine generator in a 2-on-1 combined cycle block configuration constructed at the site of the case study coal-fired unit. Heat rejection would be accomplished by a new wet mechanical-draft cooling tower. A summary of performance differences between the existing coal-fired unit and the new combined cycle unit is presented in Table 5. TABLE 5 OPTION 2B CASE STUDY PERFORMANCE IMPACTS Parameter Approximate Change from Current (unless noted otherwise) Net Output, MW +370 Fuel Heat Input Coal, % of Total (HHV basis) 0* Natural Gas, % of Total (HHV basis) 100* Net Unit Heat Rate, Btu/kWh -3,500 *Percent of total heat input of the converted unit, on an HHV basis. Replacing an existing coal unit with a combined cycle is often the most capital intensive, but also the most efficient, means of switching from coal to natural gas. In addition to being the most efficient of the options presented, a combined cycle could be designed to offer a greater degree of generation flexibility. The largest and most economical combined cycle block configurations comprise F-class, G-class, H-class and J-class combustion turbines; triple pressure HRSGs; and reheat steam turbines. These combined cycle blocks range from a nominal rating of 300 MW-net to more than 1,200 MW-net. The replacement of an existing coal unit with a combined cycle would require the owner to consider what to do with the retired unit. Leaving a unit in place would require periodic maintenance and security measures. Demolishing the unit would require careful planning and may involve additional cost, depending on the complexity of decommissioning and the value of the salvaged materials. CASE STUDY FINDINGS The characteristics of the particular coal-fired unit being considered dictate the most advantageous generation option. The size, vintage, site characteristics and emissions control equipment currently in place can define which option is the most cost-effective and capable of aligning with the current business model. High-level levelized bus bar cost estimates, presented on a U.S. cents per kilowatt-hour ( /kwh) basis, were developed for the options considered for the case study. The options were compared with annual capacity factors (CFs) ranging from 30 to 90 percent. Figure 1 presents a comparison of the five options for a planned service life of 30 years. Some utilities have considered BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 7

8 Levelized Bus Bar Cost /kwh Levelized Bus Bar Cost, /kwh POWER-GEN INTERNATIONAL short-term solutions for bridging the gap in the near term to postpone large expenditures. The five options were also compared for a planned service life of 10 years (Figure 2). For both comparisons, two natural gas price scenarios were evaluated. Delivered fuel prices considered for the case study are presented in Table Low Natural Gas Price Capacity Factor (%) Figure 1 Bus Bar Cost Comparison of Options 30 Year Service Life Service Life - 30 Years a - Full Conversion 10 to Gas 1b - Coal/Gas Co- firing 9 Firing 8 1c - Emissions Control Retrofit 7 2a - Repower as 6 Combined Cycle 2b - New Combined 5 Cycle 4 High Natural Gas Price Capacity Factor (%) Low Natural Gas Price Capacity Factor (%) Service Life - 10 Years Figure 2 Bus Bar Cost Comparison of Options 10 Year Service Life 18 High Natural Gas Price 17 1a - Full Conversion 16 to Gas 15 1b - Coal/Gas firing Firing 13 Co- 14 1c - Emissions Control Retrofit 10 2a - Repower as 9 Combined Cycle 8 2b - New Combined 7 Cycle Capacity Factor (%) TABLE 6 ASSUMED COMPARISON OF DELIVERED FUEL PRICES Coal Low Natural Gas High Natural Gas Initial Year Fuel Price, $/MBtu/HHV Annual Escalation Rate, % per year $/MBtu-HHV = 2012 U.S. dollars per million British thermal units, HHV basis. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 8

9 SUMMARY Natural gas prices have fallen in recent years because of the stagnant economy, weakened demand for electricity and increased shale gas production supply. Low natural gas prices and static coal prices have created a business opportunity for power producers to switch from coal-fired to underutilized natural gas-fired power plants. In addition, increasingly stringent environmental regulations will require many coal-fired units to be retired or to be retrofit with emissions control equipment for continued operation on coal. This case study explored five technically feasible options available in the current market for a late 1970s vintage subcritical pulverized coal-fired unit with a nominal gross output of 250 MW. The five options considered were compared with CFs ranging from 30 to 90 percent. Two natural gas price scenarios (low and high natural gas) and two planned service lives (30 and 10 year) were considered. A summary of options that are expected to be the most cost-effective for the case study 250 MW coal-fired unit is presented in Table 7. TABLE 7 OPTIONS EXPECTED TO BE MOST COST-EFFECTIVE 30 Year Service Life 10 Year Service Life Low Natural Gas Low CF 2a Repower as Combined Cycle 2b New Combined Cycle 1a Convert to Natural Gas High CF 2a Repower as Combined Cycle 2b New Combined Cycle Low CF 1a Convert to Natural Gas High CF 1a Convert to Natural Gas 2a Repower as Combined Cycle 2b New Combined Cycle High Natural Gas Low CF 1c Emissions Control Retrofit 2a Repower as Combined Cycle 2b New Combined Cycle High CF 1c Emissions Control Retrofit Low CF 1a Convert to Natural Gas High CF 1c Emissions Control Retrofit Full conversion to natural gas is only cost-effective with limited planned service hours because high natural gas consumption rates make this option not cost-effective when compared to the more efficient natural gas-fired and coal-fired options presented. Full conversion to natural gas might be advantageous for short-term applications or in instances where installed capacity is needed to meet reserves. For the case study, conversion to coal and natural gas co-firing is not the most cost-effective option. Displacing coal with natural gas results in incremental nonfuel operations and maintenance cost savings because of reduced emissions control reagent consumption. However, the capital cost required for supply of the natural gas, combined with the capital cost for emissions control equipment additions and the higher cost of natural gas compared to coal, negates these savings. Retrofitting the unit with emissions control equipment is one of the lowest cost options with high natural gas prices and is a moderate cost option for low natural gas prices. Future coal prices are expected to be relatively stable, so the perceived fuel risk associated with this option tends to be less than for natural gas-fired options. However, the uncertainty risk associated with this option is regulatory-driven. Air-related and coal combustion residuals-related environmental regulations could potentially threaten the future of coal-fired units, making continued operation cost prohibitive. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 9

10 Combined cycle-based options are cost competitive with lower natural gas prices. High efficiency means that natural gas-fired combined cycle units are less sensitive to natural gas price fluctuations when compared to full conversion of a coal-fired unit to natural gas. However, the capacity increase could make this option difficult to adopt for many owners with smaller fleets or assets within transmissionconstrained regions, which are strategically distributed to meet local demand. The examples presented are indicative only and are not representative of all situations. Owners and operators must consider other factors that cannot be easily represented in this paper. Factors such as the need to maintain fuel flexibility and stability, unit demand, siting costs, impacts to other fleet units and capital expenditure limitations will play a large role in the decision-making process for evaluating the future of coal units. Black & Veatch Holding Company All Rights Reserved. The Black & Veatch name and logo are registered trademarks of Black & Veatch Holding Company. BLACK & VEATCH A Case Study on Coal to Natural Gas Fuel Switch 10

Natural Gas Conversions of Existing Coal-Fired Boilers

Natural Gas Conversions of Existing Coal-Fired Boilers White Paper MS-14 Natural Gas Conversions of Existing Coal-Fired s Authors: F.J. Binkiewicz Jr., P.E. R.J. Kleisley B.E. McMahon J.E. Monacelli D.A. Roth D.K. Wong Babcock & Wilcox Power Generation Group,

More information

Assessing the Changes Required by the Industrial Boiler MACT Regulations

Assessing the Changes Required by the Industrial Boiler MACT Regulations Technical Paper MS-17 Assessing the Changes Required by the Industrial Boiler MACT Regulations Authors: A.L. LeClair L.M. McDermitt Babcock & Wilcox Power Generation Group, Inc. Barberton, Ohio, U.S.A

More information

SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA. Matthias Fränkle Siemens Power Generation (PG), Germany

SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA. Matthias Fränkle Siemens Power Generation (PG), Germany SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA Matthias Fränkle Siemens Power Generation (PG), Germany Page 1 of 11 1 Introduction Deregulation and competition are further

More information

The Technology and Business of Power Andrew Valencia, P.E. Lower Colorado River Authority

The Technology and Business of Power Andrew Valencia, P.E. Lower Colorado River Authority The Technology and Business of Power Andrew Valencia, P.E. Lower Colorado River Authority 1 2 What is Efficiency? Efficiency: What you get divided by what you pay for Heatrate is a measure of plant efficiency

More information

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain

More information

Well Positioned for the Future

Well Positioned for the Future Dominion Generation Virginia City Hybrid Energy Center Well Positioned for the Future The Coal Institute July 13, 2015 Rick Boyd Manager of Fuel Origination & Operations 1 Dominion Profile Operating Segments

More information

Efficiency Metrics for CHP Systems: Total System and Effective Electric Efficiencies

Efficiency Metrics for CHP Systems: Total System and Effective Electric Efficiencies Efficiency Metrics for CHP Systems: Total System and Effective Electric Efficiencies Combined heat and power (CHP) is an efficient and clean approach to generating power and thermal energy from a single

More information

Site Identification No.: 197809AAO Application No.: 15030051

Site Identification No.: 197809AAO Application No.: 15030051 Project Summary for a Construction Permit Application from Midwest Generation for a Natural Gas Conversion Project for the Joliet Electric Generating Station Joliet, Illinois Site Identification No.: 197809AAO

More information

OROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW

OROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW ISRAEL ELECTRIC OROT RABIN POWER STATION UNITS 1-4 4 x 350 MW COAL BOILER CONVERSION TO LOW NO X NATURAL GAS AND COAL FIRING BY PRIMARY AND SECONDARY MEASURES INSTALLATION Replacing the Burner Management

More information

OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS

OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS CONFERENCE PROCEEDINGS OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS by Edward K. Levy, Nenad Sarunac, and Carlos Romero Energy

More information

Review of Potential Efficiency Improvements at Coal-Fired Power Plants

Review of Potential Efficiency Improvements at Coal-Fired Power Plants Review of Potential Efficiency Improvements at Coal-Fired Power Plants Introduction The Clean Air Markets Division, U.S. Environmental Protection Agency requested that Perrin Quarles Associates, Inc.,

More information

PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS

PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS ASME ORC 2015 3rd International Seminar on ORC Power Systems 12-14 October 2015, Brussels, Belgium PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS Vittorio

More information

Bill Maxwell, U.S. Environmental Protection Agency, OAQPS (C439-01)

Bill Maxwell, U.S. Environmental Protection Agency, OAQPS (C439-01) TO: Bill Maxwell, U.S. Environmental Protection Agency, OAQPS (C439-01) FROM: Jeffrey Cole, RTI International DATE: December 2003 SUBJECT: Methodology for Estimating Cost and Emissions Impact for Coal-

More information

Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant:

Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant: 31 Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant: Construction of Group 1 of the Tokyo Electric Power Company s Kawasaki Thermal Power Station KIYOSHI KAWAKAMI

More information

Committed to make a better world

Committed to make a better world Committed to make a better world 1. Higher Availability & Reliability 2. Highest Plant efficiency 3. Lower Heat Rate 4. Minimum Auxiliary Power Consumption 5. Minimum Emission of Pollutants Committed to

More information

State of the Art (SOTA) Manual for Boilers and Process Heaters

State of the Art (SOTA) Manual for Boilers and Process Heaters State of the Art (SOTA) Manual for Boilers and Process Heaters Original Date: July 1997 Revision Date: February 22, 2004 State of New Jersey Department of Environmental Protection Air Quality Permitting

More information

Appendix 5A: Natural Gas Use in Industrial Boilers

Appendix 5A: Natural Gas Use in Industrial Boilers Appendix 5A: Natural Gas Use in Industrial Boilers Industrial boilers consumed 2.1 Tcf of natural gas in 2006, accounting for 36% of total natural gas in manufacturing. 1 In this appendix, we provide further

More information

Improving the Thermal Efficiency of Coal-Fired Power Plants: A Data Mining Approach

Improving the Thermal Efficiency of Coal-Fired Power Plants: A Data Mining Approach Paper 1805-2014 Improving the Thermal Efficiency of Coal-Fired Power Plants: A Data Mining Approach Thanrawee Phurithititanapong and Jongsawas Chongwatpol NIDA Business School, National Institute of Development

More information

Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance

Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance The Boiler MACT, 40 CFR 63, Subpart DDDDD, was vacated in 2007 by the U.S Court of Appeals and the 2004 rule

More information

48 No Change to Content of Form Permitted

48 No Change to Content of Form Permitted 13. FORM 2A BREAKDOWN OF FIXED CONSTRUCTION PRICE All prices are in Canadian dollars as at the Closing Time. 1. Design, Permits, and Construction Management including project development expenses, mobilization,

More information

10 Nuclear Power Reactors Figure 10.1

10 Nuclear Power Reactors Figure 10.1 10 Nuclear Power Reactors Figure 10.1 89 10.1 What is a Nuclear Power Station? The purpose of a power station is to generate electricity safely reliably and economically. Figure 10.1 is the schematic of

More information

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

HOW TO SELECT A LOW VOLUME (L.V ) BOILER HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement

More information

A Review on Power Generation in Thermal Power Plant for Maximum Efficiency

A Review on Power Generation in Thermal Power Plant for Maximum Efficiency International Journal of Advanced Mechanical Engineering. ISSN 2250-3234 Volume 4, Number 1 (2014), pp. 1-8 Research India Publications http://www.ripublication.com/ijame.htm A Review on Power Generation

More information

Hybrid Power Generations Systems, LLC

Hybrid Power Generations Systems, LLC Coal Integrated Gasification Fuel Cell System Study Pre-Baseline Topical Report April 2003 to July 2003 Gregory Wotzak, Chellappa Balan, Faress Rahman, Nguyen Minh August 2003 Performed under DOE/NETL

More information

IPM Model Updates to Cost and Performance for APC Technologies. SCR Cost Development Methodology. Final. March 2013

IPM Model Updates to Cost and Performance for APC Technologies. SCR Cost Development Methodology. Final. March 2013 Final Project 12847-002 Systems Research and Applications Corporation Prepared by 55 East Monroe Street Chicago, IL 60603 USA 312-269-2000 LEGAL NOTICE This analysis ("Deliverable") was prepared by Sargent

More information

University of Iowa Power Plant

University of Iowa Power Plant University of Iowa Power Plant Contents Purpose... 2 History... 3 Cogeneration... 6 Boilers... 7 Environmental Impact... 10 Steam Turbine Generators... 12 Modernization... 14 Biomass Fuel Initiative...

More information

Source: EIA Natural Gas Issues and Trends 1998

Source: EIA Natural Gas Issues and Trends 1998 7.0 System Redesign Analysis 7.1 Emissions Natural gas is a clean burning fossil fuel. It consists of a mixture of hydrocarbon gases, primarily Methane (CH 4 ). In analyzing the combustion process, it

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

INDEX 9-7-100 GENERAL

INDEX 9-7-100 GENERAL REGULATION 9 INORGANIC GASEOUS POLLUTANTS RULE 7 NITROGEN OXIDES AND CARBON MONOXIDE FROM INDUSTRIAL, INSTITUTIONAL AND COMMERCIAL BOILERS, STEAM GENERATORS AND PROCESS HEATERS INDEX 9-7-100 GENERAL 9-7-101

More information

Overview of Waste Heat Recovery for Power and Heat

Overview of Waste Heat Recovery for Power and Heat Overview of Waste Heat Recovery for Power and Heat Dave Sjoding Northwest Clean Energy Application Center Washington State University Extension Energy Program Waste Heat Recovery for Power and Heat Workshop

More information

6 CONSIDERATION OF ALTERNATIVES

6 CONSIDERATION OF ALTERNATIVES 6 CONSIDERATION OF ALTERNATIVES 6.1.1 Schedule 4 of the Town and Country Planning (Environmental Impact Assessment) (Scotland) Regulations 2011 sets out the information for inclusion in Environmental Statements

More information

INTEC Engineering GmbH Heating Solutions for the Marine Industry

INTEC Engineering GmbH Heating Solutions for the Marine Industry INTEC Engineering GmbH Heating Solutions for the Marine Industry Thermal Oil Heaters Heating Solutions for the Marine Industry Compared to conventional plants using hot water or steam, thermal oil as a

More information

SEATTLE STEAM COMPANY FREQUENTLY ASKED QUESTIONS

SEATTLE STEAM COMPANY FREQUENTLY ASKED QUESTIONS SEATTLE STEAM COMPANY FREQUENTLY ASKED QUESTIONS What products/services does Seattle Steam provide? The company provides thermal energy (heat) produced at two central heating plants in downtown Seattle.

More information

The Future of Coal-Based Power Generation With CCS UN CCS Summit James Katzer MIT Energy Initiative web.mit.edu/coal/

The Future of Coal-Based Power Generation With CCS UN CCS Summit James Katzer MIT Energy Initiative web.mit.edu/coal/ The Future of Coal-Based Power Generation With CCS UN CCS Summit James Katzer MIT Energy Initiative web.mit.edu/coal/ 1 Times Are Changing As Yogi Berra said: The Future Ain t What It Used to Be 2 Overview

More information

Adapting Gas-Power Generation to New Role in Low-Carbon Energy Systems

Adapting Gas-Power Generation to New Role in Low-Carbon Energy Systems Adapting Gas-Power Generation to New Role in Low-Carbon Energy Systems Sandra Scalari Enel Ingegneria e Ricerca SpA Copenhagen, May 27-28 th 2014 Enel Presentation Generation Shift & Market in Europe Enel

More information

Energy Efficient Operations and Maintenance Strategies for Boilers

Energy Efficient Operations and Maintenance Strategies for Boilers Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must

More information

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin Drying of Woody Biomass BioPro Expo & Marketplace / Atlanta, GA / March 14-16, 2011 Drying of Woody Biomass Conventional Direct Fired Dryer Technology Proprietary work of the Copyright Owner Issues with

More information

NAWTEC18-3541 CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY

NAWTEC18-3541 CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED BOILER AND INCINERATION TECHNOLOGY Proceedings of the 18th Annual North American Waste-to-Energy Conference NAWTEC18 May 11-13, 2010, Orlando, Florida, USA NAWTEC18-3541 CONCEPTS AND EXPERIENCES FOR HIGHER PLANT EFFICIENCY WITH MODERN ADVANCED

More information

4 th EU Sout Africa Clean Coal Working Group Meeting

4 th EU Sout Africa Clean Coal Working Group Meeting 4 th EU Sout Africa Clean Coal Working Group Meeting Hybrid Concentrated Solar Power (CSP) Concept Case Study for the Medupi Power Stationy Falk Hoffmeister Head of Sales and Business Development. Dr.

More information

How To Run A Power Plant

How To Run A Power Plant CO 2 Capture at the Kemper County IGCC Project 2011 NETL CO 2 Capture Technology Meeting Kemper County IGCC Overview 2x1 Integrated Gasification Combined Cycle (IGCC) 2 TRansport Integrated Gasifiers (TRIG

More information

Assessment of Solar-Coal Hybrid Electricity Power Generating Systems 13

Assessment of Solar-Coal Hybrid Electricity Power Generating Systems 13 Journal of Energy and Power Engineering 6 (2012) 12-19 D DAVID PUBLISHING Assessment of Solar-Coal Hybrid Electricity Power Generating Systems Moses Tunde Oladiran 1, Cheddi Kiravu 1 and Ovid Augustus

More information

ELECTRIC GENERATION EFFICIENCY

ELECTRIC GENERATION EFFICIENCY TOPIC PAPER #4 ELECTRIC GENERATION EFFICIENCY On July 18, 2007, The National Petroleum Council (NPC) in approving its report, Facing the Hard Truths about Energy, also approved the making available of

More information

Low Load Operational Flexibility for Siemens G-class Gas Turbines

Low Load Operational Flexibility for Siemens G-class Gas Turbines Low Load Operational Flexibility for Siemens G-class Gas Turbines Power-Gen International 2008 Orlando, Florida www.siemens.com Power-Gen International Orlando, Florida December 2008 2 Low Load Operational

More information

ERCOT Analysis of the Impacts of the Clean Power Plan Final Rule Update

ERCOT Analysis of the Impacts of the Clean Power Plan Final Rule Update ERCOT Analysis of the Impacts of the Clean Power Plan Final Rule Update ERCOT Public October 16, 2015 ERCOT Analysis of the Impacts of the Clean Power Plan Final Rule Update In August 2015, the U.S. Environmental

More information

Performance Monitoring For Gas Turbines

Performance Monitoring For Gas Turbines Performance Monitoring For Gas Turbines Introduction Managing an asset requires numerous technologies designed to assess health. While most gas turbines in the field are fitted with some type of mechanical

More information

Rule 1146.2 - EMISSIONS OF OXIDES OF NITROGEN FROM LARGE WATER HEATERS AND SMALL BOILERS

Rule 1146.2 - EMISSIONS OF OXIDES OF NITROGEN FROM LARGE WATER HEATERS AND SMALL BOILERS Rule 1146.2 - EMISSIONS OF OXIDES OF NITROGEN FROM LARGE WATER HEATERS AND SMALL BOILERS (a) Purpose and Applicability The purpose of this rule is to reduce NOx emissions from natural gas-fired large (commercial)

More information

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication

More information

The Regulatory Impact Analysis (RIA) for the Mercury Air Toxics Standard (MATS)

The Regulatory Impact Analysis (RIA) for the Mercury Air Toxics Standard (MATS) The Regulatory Impact Analysis (RIA) for the Mercury Air Toxics Standard (MATS) Kevin Culligan U.S. Environmental Protection Agency (EPA) Associate Division Director, Sector Policies and Programs Division

More information

How To Evaluate Cogeneration

How To Evaluate Cogeneration Power topic #7018 Technical information from Cummins Power Generation Inc. Evaluating cogeneration for your facility: A look at the potential energy-efficiency, economic and environmental benefits > White

More information

Routine and Emergency Boiler Operation

Routine and Emergency Boiler Operation Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here

More information

POTENTIAL ECONOMIC IMPACTS OF A STRICTER OZONE STANDARD

POTENTIAL ECONOMIC IMPACTS OF A STRICTER OZONE STANDARD POTENTIAL ECONOMIC IMPACTS OF A STRICTER OZONE STANDARD July 2014 Overview A new study by NERA Economic Consulting and commissioned by the National Association of Manufacturers (NAM) reveals that a new

More information

Steam Turbine Concepts for the Future Volatile Power Market

Steam Turbine Concepts for the Future Volatile Power Market Steam Turbine Concepts for the Future Volatile Power Market Power-Gen Europe June 12 14, 2012 Michael Wechsung Thomas Loeper Radim Znajda Siemens AG - Energy Sector Fossil Power Generation Agenda Situation

More information

Energy Efficiency in Steam Systems

Energy Efficiency in Steam Systems Energy Efficiency in Steam Systems Fundamentals of Energy Efficiency: An Introductory Workshop April 2008 John S. Raschko, Ph.D. Mass. Office of Technical Assistance www.mass.gov/envir/ota (617) 626-1093

More information

Clean Power Plan: MISO Analysis ADEQ/APSC Stakeholder Meeting

Clean Power Plan: MISO Analysis ADEQ/APSC Stakeholder Meeting Clean Power Plan: MISO Analysis ADEQ/APSC Stakeholder Meeting 8/28/2014 The generation fleet in MISO is being affected by timing, fuel prices and multiple phases of environmental regulations. MATS CSAPR

More information

IVISIONS STEAM PLANT DIVISIONS TOTAL TURNKEY SOLUTIONS. INDUSTRIAL BOILER & MECHANICAL

IVISIONS STEAM PLANT DIVISIONS TOTAL TURNKEY SOLUTIONS. INDUSTRIAL BOILER & MECHANICAL IVISIONS INDUSTRIAL BOILER & MECHANICAL STEAM PLANT DIVISIONS TOTAL TURNKEY SOLUTIONS. FIELD SERVICE & REPAIR DIVISION Rely on IB&M's field service experts for your steam plant. Our Field Service & Repair

More information

www.universityquestions.in

www.universityquestions.in DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT: ME6701-POWER PLANT ENGINEERING YEAR/SEM: III/V UNIT-I COAL BASED THERMAL POWER PLANTS 1. What are the processes of rankine cycle?

More information

MATS and Boiler Rules

MATS and Boiler Rules em feature MATS and Boiler Rules Practical, Data-Driven Standards by Gina McCarthy Gina McCarthy is Assistant Administrator for Air and Radiation at the U.S. Environmental Protection Agency. The U.S. Environmental

More information

ENERGY EFFICIENCY AUDITING

ENERGY EFFICIENCY AUDITING GUIDANCE NOTE ON ENERGY EFFICIENCY AUDITING July 2003 ENVIRONMENTAL PROTECTION AGENCY An Ghníomhaireacht um Chaomhnú Comhshaoil PO Box 3000, Johnstown Castle, Co.Wexford, Ireland Telephone: +353-53-60600

More information

System Assessment Capabilities for Fossil Fuel Power Stations

System Assessment Capabilities for Fossil Fuel Power Stations System Assessment Capabilities for Fossil Fuel Power Stations Technical Services LifeCycle Advantage Educational Services Consulting Technology Advantage The mission of Flowserve Technical Services is

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

Wolverine Clean Energy Venture

Wolverine Clean Energy Venture Prepared for: Wolverine Power Supply Cooperative Cadillac, Michigan Supplement to CAA Section 112(g) MACT Auxiliary Boiler Amended Application No. 317-07 Wolverine Clean Energy Venture Rogers City, MI

More information

TECHNICAL PUBLICATION

TECHNICAL PUBLICATION TECHNICAL PUBLICATION Biomass Conversion Strategies for Existing Power Plants Evaluation Criteria and Feasibility Analysis by Curtis Schaaf Boiler Design Engineer Riley Power Inc. Kevin Toupin Director,

More information

DESIGN CHALLENGES AND OPERATIONAL EXPERIENCE OF A MEGA MED SEAWATER DESALINATION PLANT IN TIANJIN

DESIGN CHALLENGES AND OPERATIONAL EXPERIENCE OF A MEGA MED SEAWATER DESALINATION PLANT IN TIANJIN DESIGN CHALLENGES AND OPERATIONAL EXPERIENCE OF A MEGA MED SEAWATER DESALINATION PLANT IN TIANJIN Authors: Presenter: T. Efrat, Yu Haimiao Tomer Efrat Deputy Manager, Thermal Process Dept. IDE Technologies

More information

FAC 7.1: Generators. EPA Impacts on Emergency Gensets for 2015 Installations

FAC 7.1: Generators. EPA Impacts on Emergency Gensets for 2015 Installations FAC 7.1: Generators EPA Impacts on Emergency Gensets for 2015 Installations Speaker: Bob Stelzer, CTO Safety Power Inc [email protected] Speaker: Randy Sadler, SME, Safety Power Inc. [email protected]

More information

Biomass Boiler House Best Practices. Irene Coyle & Fernando Preto CanmetENERGY

Biomass Boiler House Best Practices. Irene Coyle & Fernando Preto CanmetENERGY Biomass Boiler House Best Practices Irene Coyle & Fernando Preto CanmetENERGY Growing the Margins London, Ontario March 2010 The Biomass & Renewables Group of Industrial Innovation Group (IIG) of CanmetENERGY

More information

Performance Analysis of Thermal Power Station: Case Study of Egbin Power Station, Nigeria

Performance Analysis of Thermal Power Station: Case Study of Egbin Power Station, Nigeria International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 4, Number 3 (2011), pp. 281-289 International Research Publication House http://www.irphouse.com Performance Analysis

More information

Continuous Emissions Monitoring - Program 77

Continuous Emissions Monitoring - Program 77 Program Description Program Overview Coal-fired power plants are in increased need of robust, accurate, and certifiable continuous emissions monitors (CEMs) for mercury, particulate matter (PM), acid gases,

More information

COMPARISON CONCERNING TO THE COGENERATION SYSTEMS DEVELOPMENT

COMPARISON CONCERNING TO THE COGENERATION SYSTEMS DEVELOPMENT COMPARISON CONCERNING TO THE COGENERATION SYSTEMS DEVELOPMENT Radu-Cristian DINU, Ion MIRCEA, Emilia-Marinela DINU University of Craiova, Faculty of Electrotechnique, Electroputere S.A., Craiova [email protected],

More information

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng Condensing Economizers Workshop Enbridge Gas, Toronto MENEX Boiler Plant Heat Recovery Technologies Prepared by: Jozo Martinovic, M A Sc, P Eng MENEX Innovative Solutions May 15, 2008 MENEX INC. 683 Louis

More information

Optimal Power Plant Integration of Post-Combustion CO 2 Capture. Dr. Tobias Jockenhövel Dr. Rüdiger Schneider Michael Sandell Lars Schlüter

Optimal Power Plant Integration of Post-Combustion CO 2 Capture. Dr. Tobias Jockenhövel Dr. Rüdiger Schneider Michael Sandell Lars Schlüter Optimal Power Plant Integration of Post-Combustion CO 2 Capture Dr. Tobias Jockenhövel Dr. Rüdiger Schneider Michael Sandell Lars Schlüter Siemens AG, Energy Sector Germany POWER-GEN Europe 2009 Cologne,

More information

COST REPORT COST AND PERFORMANCE DATA FOR POWER GENERATION TECHNOLOGIES. Prepared for the National Renewable Energy Laboratory FEBRUARY 2012

COST REPORT COST AND PERFORMANCE DATA FOR POWER GENERATION TECHNOLOGIES. Prepared for the National Renewable Energy Laboratory FEBRUARY 2012 COST REPORT COST AND PERFORMANCE DATA FOR POWER GENERATION TECHNOLOGIES Prepared for the National Renewable Energy Laboratory FEBRUARY 2012 Black & Veatch Holding Company 2011. All rights reserved. GENERATION

More information

Boiler NOx Emissions and Energy Efficiency

Boiler NOx Emissions and Energy Efficiency Boiler NOx Emissions and Energy Efficiency Prepared For: Boiler Operators and Facility Managers Prepared By: 100 Montgomery Street, Suite 600 San Francisco, CA 94104 AGENDA Introduction Boiler NOx Formation

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

Iron and Steel Manufacturing

Iron and Steel Manufacturing Pollution Prevention and Abatement Handbook WORLD BANK GROUP Effective July 1998 Iron and Steel Manufacturing Industry Description and Practices Steel is manufactured by the chemical reduction of iron

More information

IMPROVING COAL PLANT EFFICIENCY

IMPROVING COAL PLANT EFFICIENCY IMPROVING COAL PLANT EFFICIENCY Some ideas to consider for existing coal units to Work Toward Compliance with the EPA Clean Power Plan, Rule 111d Coal Plant Efficiency Improvements Presentation by: Dick

More information

Advanced Steam Parameters in a Large Scale CFB Application Operating on REF and Biofuels background and experiences

Advanced Steam Parameters in a Large Scale CFB Application Operating on REF and Biofuels background and experiences Advanced Steam Parameters in a Large Scale CFB Application Operating on REF and Biofuels background and experiences Matts Strömberg Soderenergi AB, Sweden Presented at Power Gen Europe 2011 Milan, Italy

More information

Environment Impact Assessment of Thermal Power Plant for Sustainable Development

Environment Impact Assessment of Thermal Power Plant for Sustainable Development International Journal of Environmental Engineering and Management. ISSN 2231-1319, Volume 4, Number 6 (2013), pp. 567-572 Research India Publications http://www.ripublication.com/ ijeem.htm Environment

More information

Study of a Supercritical CO2 Power Cycle Application in a Cogeneration Power Plant

Study of a Supercritical CO2 Power Cycle Application in a Cogeneration Power Plant Supercritical CO2 Power Cycle Symposium September 9-10, 2014 Pittsburg, Pennsylvania USA Study of a Supercritical CO2 Power Cycle Application in a Cogeneration Power Plant Dr. Leonid Moroz, Dr. Maksym

More information

Federal Wage System Job Grading Standard for Heating and Boiler Plant Equipment Mechanic, 5309. Table of Contents

Federal Wage System Job Grading Standard for Heating and Boiler Plant Equipment Mechanic, 5309. Table of Contents Federal Wage System Job Grading Standard for Heating and Boiler Plant Equipment Mechanic, 5309 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 3 HELPER AND INTERMEDIATE

More information

INDUSTRIAL BOILER MACT FACTSHEET

INDUSTRIAL BOILER MACT FACTSHEET INDUSTRIAL BOILER MACT FACTSHEET The National Emission Standards for Hazardous Air Pollutants (NESHAP) for Industrial/Commercial/Institutional Boilers and Process Heaters (40 CFR Part 63, Subpart DDDDD),

More information

Half the cost Half the carbon

Half the cost Half the carbon Half the cost Half the carbon the world s most efficient micro-chp What is BlueGEN? The most efficient small-scale electricity generator BlueGEN uses natural gas from the grid to generate electricity within

More information

The soot and scale problems

The soot and scale problems Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications

More information

COMPARISON OF PROCESS FLOWS: FLUID BED COMBUSTOR AND GLASSPACK

COMPARISON OF PROCESS FLOWS: FLUID BED COMBUSTOR AND GLASSPACK COMPARISON OF PROCESS FLOWS: FLUID BED COMBUSTOR AND GLASSPACK PURPOSE The purpose of this document is to present the assumptions and calculations used to prepare Minergy Drawing 100-0204-PP00 (attached).

More information

Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal

Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal 19 Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal TAKAO HASHIMOTO *1 KOICHI SAKAMOTO *2 YOSHIKI YAMAGUCHI *3 KOJI OURA *4 KENICHI ARIMA *5 TAKESHI SUZUKI *6 Mitsubishi

More information

JASE-world Waste to Energy Sub WG Masanori Tsukahara Hitachi Zosen Corporation 2012.11.14

JASE-world Waste to Energy Sub WG Masanori Tsukahara Hitachi Zosen Corporation 2012.11.14 Presentation of Japanese technology of waste to energy JASE-world Waste to Energy Sub WG Masanori Tsukahara Hitachi Zosen Corporation 2012.11.14 1 JASE-W established in Oct 2008 Introduction of JASE-world

More information

COGENERATION. This section briefly describes the main features of the cogeneration system or a Combined Heat & Power (CHP) system. 36 Units.

COGENERATION. This section briefly describes the main features of the cogeneration system or a Combined Heat & Power (CHP) system. 36 Units. COGENERATION 1. INTRODUCTION... 1 2. TYPES OF COGENERATION SYSTEMS... 2 3. ASSESSMENT OF COGENERATION SYSTEMS... 10 4. ENERGY EFFICIENCY OPPORTUNITIES... 14 5. OPTION CHECKLIST... 16 6. WORKSHEETS... 17

More information

GAS HEATING IN COMMERCIAL PREMISES

GAS HEATING IN COMMERCIAL PREMISES ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.

More information

GLOBACON 05 HVAC Systems for Cogen

GLOBACON 05 HVAC Systems for Cogen GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity

More information

PRINCIPLES OF FLUE GAS WATER RECOVERY SYSTEM

PRINCIPLES OF FLUE GAS WATER RECOVERY SYSTEM PRINCIPLES OF FLUE GAS WATER RECOVERY SYSTEM John H. Copen - SIEMENS Power Generation, Inc. Terrence B. Sullivan - SIEMENS Power Generation, Inc. Bruce C. Folkedahl - Energy & Environmental Research Center

More information

Electricity Use and Production Patterns

Electricity Use and Production Patterns This publication explains issues relevant to the production of electricity for the state of Wisconsin. It addresses basic power plant technologies and fuels, how the state s demand for reliable electricity

More information

PHOENIX ENERGY of NEVADA, LLC (PENV) (PENV)

PHOENIX ENERGY of NEVADA, LLC (PENV) (PENV) PHOENIX ENERGY of NEVADA, LLC (PENV) INDUCTION FIELD ENERGY POWERED INDUCED FEED WATER RE-HEAT ING STEAM WASTE HEAT ENERGY RECOVERY DRY COOLING REVERSE CONDENSER REGENERATIVE STEAM CYCLE ELECTRIC POWER

More information

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district PLANT TORINO NORD Iren Energia is the company in the Iren Group whose core businesses are the production and distribution of electricity, the production and distribution of thermal energy for district

More information

I. STEAM GENERATION, BOILER TYPES

I. STEAM GENERATION, BOILER TYPES I. STEAM GENERATION, BOILER TYPES and BOILER PLANT SYSTEMS 1 Steam Generation Water s Unique Properties: High Thermal Capacity (Specific Heat) High Critical Temperature Ideal Medium for Heat Delivery High

More information