Fire protection for townhouses that share a common wall. Gypsum Fire Wall

Size: px
Start display at page:

Download "Fire protection for townhouses that share a common wall. Gypsum Fire Wall"

Transcription

1 Fire protection for townhouses that share a common wall Gypsum Fire Wall Systems SA-925

2 Fire walls between adjoining townhouses must provide fire-resistive ratings to ensure the safety of occupants in adjacent dwellings. Noise attenuation is also important, to ensure that townhouse dwellers are not disturbed by sound from their neighbors. Fire and Sound Separation

3 User s Guide This brochure explains: Where fire walls are used The components of fire wall systems How to select and specify the appropriate components of a fire wall system Pages Understand Your System Overview 4 Applications Components Performance Testing Select Your System Performance Selector 9 Design Details Design Your System 12 Good Design Practices Specify Your System 13 Application Guide Specifications For More Information Customer Service Web Site 3 CGC Gypsum Fire Wall Systems

4 Overview Effective fire resistance and sound attenuation are important considerations in townhouse design. A fire wall can be used in townhouses up to four stories (13.4 m (44 )) tall and with all common floor-ceiling heights. It must either be continuous from the foundation to the underside of the protected roof sheathing, or continue through the roof to form a parapet. The fire wall is designed to allow for collapse of the construction on the fire-exposed side without collapse of the entire wall. To do this, aluminum breakaway clips attach the separation wall to the adjacent framing. When one side is exposed to fire, the clips are designed to soften and break away, allowing the structure on the fire side to collapse, while the clips on the exposed fire side of the separation wall continue to support the wall. This allows the fire wall to remain intact, protecting the adjacent townhouse. Typical Fire Wall Assembly 50 x 100 mm (2 x 4) stud framing SHEETROCK gypsum panels (as required) 25.4 mm (1 ) SHEETROCK Gypsum Liner Panels sound batts min. 19 mm (3/4 ) airspace between 50 mm (2 ) fire wall and wood framing 50 mm (2 ) H-studs 610 mm (24 ) o.c. 50 mm (2 ) CGC C-Runners CGC aluminum breakaway clip fire blocking as required fire blocking as required 4 CGC Gypsum Fire Wall Systems

5 Applications CGC Fire Wall Systems are lightweight, non-loadbearing gypsum panel partition assemblies used to provide fire-resistive protection for common walls in townhouse construction. These systems install quickly and easily. Because they weigh at least 50% less than masonry walls, installation proceeds rapidly. In addition, use of these assemblies gains valuable floor space for the building interior, since thickness is 89 mm (3-1/2 ) compared to 200 to 300 mm (8 to 12 ) for a masonry wall without interior finish. 5 CGC Gypsum Fire Wall Systems

6 Components CGC Fire Wall Systems have been comprehensively tested for fire resistance ratings only when all of the system components are used together. Substitutions of any of the components are not recommended and are not supported by CGC. Refer to the appropriate product material safety data sheet for complete health and safety information. Gypsum Liner Panels SHEETROCK Gypsum Liner Panels Noncombustible core encased in water-resistant 100% recycled green face and back paper ULC/UL classified for fire resistance (type SLX) Panels are 25.4 mm (1 ) thick and 610 mm (24 ) wide with beveled edges and are available in mm (8-14 ) lengths Refer to product submittal sheet WB2278 for complete information SHEETROCK HUMITEK Gypsum Liner Panels Noncombustible core encased in a water- and mold-resistant, 100%-recycled blue face and back paper ULC/UL classified for fire resistance (type SLX) Panels are 25.4 mm (1 ) thick and 610 mm (24 ) wide with beveled edges and are available in mm (8-14 ) lengths Refer to product submittal sheet WB2313 for complete information Metal Framing Components CGC Steel C-Runner, CGC Steel H-Stud Galvanized steel CGC Aluminum Breakaway Clip Performs as a break-away fuse by melting or yielding from the rise in temperature on the fire side of the wall Allows the fire-engulfed structure to collapse independent of the fire wall Related Products Acoustical sealant Highly elastic, water-based sealant CGC All Purpose Joint Compound Versatile performer: tape, finish, texture, laminate, or skim coat Combines single-package, ready-mixed convenience with good taping and topping performance Refer to product submittal sheet J60A for complete information 6 CGC Gypsum Fire Wall Systems

7 Performance Testing CGC Fire Wall Systems have been independently tested to meet performance requirements for fire resistance, structural performance and sound control. Performance Tests Extensive testing and continuous improvements ensure that CGC Fire Wall Systems will provide the vertical fire resistance and sound performance that projects demand. Testing Methods CGC Fire Wall Systems have been tested to ensure long-term performance. All CGC products and systems undergo exhaustive testing to ensure that they meet exacting standards. CGC s products are Classified as to fire resistance and fire-hazard properties. As part of this protocol, Underwriters Laboratories of Canada, (ULC) and Underwriters Laboratories Inc. (UL) periodically audit production of these materials to ensure compliance with necessary properties. ULC and UL are independent, not-for-profit product safety testing and certification organizations that have tested products for public safety for over a century. Products and systems are tested in accordance with ASTM standards. ASTM International is one of the largest voluntary standards development organizations in the world, and is a trusted source for technical standards for materials, products, systems, and services. Sound Transmission Class (STC) rates the effectiveness of walls and other components at blocking airborne sound. Testing Results Fire Protection Fire walls must ensure that fire does not spread from one townhouse to the next. Building codes mandate that fire walls are tested according to specific test standards, such as CAN/ULC S101, or ASTM E119, Standard Test Method for Fire Tests of Building Construction and Materials, or its equivalent. Fire resistance testing ensures that this critical performance component will not be compromised when the system is properly installed. Fire testing results in the following: ULC/UL Classification of all gypsum panel components for fire resistance ULC/UL listing of system fire resistance Sound Control Sound control test data demonstrate the effectiveness of CGC Fire Wall Systems in attenuating sound. This means that occupants of adjacent buildings will have more privacy. STC ratings up to 60 are available. Moisture/Mold The best way to minimize damage from moisture and mold is to minimize or eliminate exposure to water before, during and after construction. In all cases where moisture intrusion occurs, eliminate all sources of moisture immediately. SHEETROCK HUMITEK Gypsum Liner Panels have a noncombustible, moisture-resistant core encased in a water- and moldresistant, 100% recycled blue face and black paper. When used in conjunction with good construction practices, this product will minimize, but not eliminate, the risk of moisture damage. 7 CGC Gypsum Fire Wall Systems

8 Performance Testing Sustainability The LEED (Leadership in Energy and Environmental Design) program is a guideline for building solutions established by the U.S. Green Building Council (USGBC). LEED's mission is to transform the building industry by establishing a common standard of measurement to define what constitutes a green building. To this end, LEED provides a framework for assessing building performance and meeting sustainability goals. This framework assigns points for certain sustainability criteria, such as sustainable site development, water savings, energy efficiency, materials selection and indoor environmental quality. Specific products cannot be LEED-certified, because there are many contingent factors in each project that must be considered. However, certain products may assist you in obtaining LEED points for your design solution. For example: CaGBC LEED Credits MR 2 Construction Waste 2.1 Divert 50% of project waste (by weight or volume) from landfill (1 point) Management 2.2 Divert another 25% of project waste (by weight or volume) from landfill (1 point) Recycled Content MR If sum of project materials by value have 7.5% post-consumer or 15% post-industrial (1 point) 4.2 If sum of project materials by value have 15% post-consumer or 30% post-industrial (1 point) Local/Regional Materials MR If 10% of project materials are shipped less than 800 km (500 miles) by truck, or less than 2400 km (1500 miles) by rail (1 point) 5.2 If 20% of project materials are shipped less than 800 km (500 miles) by truck, or less than 2400 km (1500 miles) by rail (1 point) Low-Emitting Materials EQ Drywall installation (less than 50g/L per CSCAQM, Table 1) (1 point) The following chart lists CGC Fire Wall System products that may be eligible for LEED points. Using products with a high recycled content is only one part of the equation. Another key measure of sustainability is embodied energy, which assesses the total energy required to produce a particular material or building component and get it to a building site. For example, if you use a product with a high recycled content but need to ship it across the country, the embodied energy costs of transportation may outweigh any environmental advantages of using a recycled product. It may be more environmentally sound to ship products made of virgin material from a plant close to a job site. CaGBC LEED Credits MR 4.1 and 4.2 EQ 4 MR 5.2 Product Family Post- Post- Embodied Density VOC c Mfg. Raw Materials Consumer Industrial Energy a,b lbs./cu.ft. Efficiency (% by weight) SHEETROCK Panels ~5% 0%-95% 3.6MJ/kg none 95+% 95% gypsum, 5% paper, percent varies across 95% 1% starch; special panel with 23 plants nationwide d 36.5% wax and glass fibre Joint Compound Drying Type MJ/kg 100 <2 g/l 98% Limestone and latex Joint Compound Setting Type MJ/kg 100 none 98% Plaster of paris, limestone & mica SHEETROCK Acoustical Sealant 0 0 <65 g/l Limestone, water, acrylic polymer For more information on LEED, visit the following web sites: U.S. Green Building Council Leadership in Energy & Environmental Design Canada Green Building Council Notes (a) Megajoules per kilogram. (b) Transportation of gypsum board accounts for over 10% of the board s embodied energy, while mining accounts for less than 1%. (c) Section of the Material Specifications adopted by the Collaborative for High Performance Schools (CHPS) for VOC emissions. All FIBEROCK panels use FGD gypsum, but the FGD gypsum content of SHEETROCK panels changes from plant to plant and even day to day at any one plant, due to availability. The recycled contents above are approximate. While FGD gypsum is not available everywhere in Canada, CGC does have plants strategically located to meet your needs. Evaluation should be made for each job on the benefits of using FGD instead of natural gypsum. 8 CGC Gypsum Fire Wall Systems

9 Performance Selector 2 Hour Fire-rated Construction Non-loadbearing Acoustical Performance Reference Construction Detail Description Test Number STC ARL Index 25.4 mm (1 ) SHEETROCK Gypsum Liner Panels ULC Des W314 SA mm (2 ) CGC H-Studs 610 mm (24 ) o.c. or UL Des U mm (3 1 2") minimum 19 mm (3/4 ) air space both sides separating liner panels from adjacent construction 292 mm (11 1 2") Fire wall (non-loadbearing) ULC Des W RAL-TL SA mm (1 ) SHEETROCK Gypsum Liner Panels or UL Des U mm (2 ) CGC H-Studs 610 mm (24 ) o.c. Protected wall (bearing or non-loadbearing) of wood or steel studs each side min 19 mm (3/4 ) from liner panels 12.7 mm (1/2 ) SHEETROCK Gypsum Panels RAL-TL Based on 50 mm (2 ) mineral wool batt on one side RAL-TL Based on 2x4s and 75 mm (3 ) mineral wool batt one side 58 RAL-TL Based on 2x4s and 50 mm (2 ) mineral wool batt on both sides 60 RAL-TL Based on 2x4s and 75 mm (3 ) mineral wool batt on both sides Note These systems do not provide a fire rating for adjacent wood- or steel-framed walls. 9 CGC Gypsum Fire Wall Systems

10 Design Details Basic Interfaces Intersection at Roof 50 mm (2") CGC C-Runner roof rafter saw cut roof deck roof truss Exterior Wall Intersection (as required) SHEETROCK Gypsum Panels 2 X 4 stud weather barrier fire blocking as required SHEETROCK Gypsum Panels as required 50 mm (2") CGC H-Stud 50 mm (2") CGC C-Runners 2 x 4 stud framing 1.6 mm (0.063") CGC aluminum breakaway clip 25.4 mm (1") SHEETROCK Gypsum Liner Panels exterior sheathing exterior cladding Intermediate Floor Foundation two 50 mm (2") CGC C-Runners 10 mm ( 3 /8") TYPE S pan head screw 31 mm (1 1 /4") TYPE W or S screw sound insulation (optional) sealant fire blocking as required acoustical sealant 25.4 mm (1") SHEETROCK Gypsum Liner Panels joist 50 mm (2") CGC C-runner power-driven fastener 610 mm (24") o.c. sealant as required Runner Installation Components 35 mm (1 3 /8") 50 mm (2") 50 mm (2") space runner 6 mm ( 1 /4") apart 25 mm (1") 50 mm (2") 50 mm (2") 64 mm (2 1 /2") CGC C-Runner CGC H-Stud 1.6 mm (.063 ) CGC Aluminum Breakaway Clip 10 CGC Gypsum Fire Wall Systems

11 Clip Spacing Requirements 1220 mm roof (4') plywood roof deck Typical firewall roof parapets (height as required by code) ledgers trusses attic 15.9 mm ( 5 /8") SHEETROCK FIRECODE Gypsum Panel (as required) ceiling line intermediate floor/ceiling assembly fire wall 7 m (23') upper most 7 m (23') of wall requires CGC aluminum clips at 3 m (10') o.c. fire blocking at floor line intermediate floor/ceiling assembly intermediate floor/ceiling assembly 13.4 m (44') proven structural stability to 13.4 m (44'); Additional CGC aluminum clips must be added 1.5 m (5') o.c. for the wall section below the upper most 7 m (23') 50 mm (2") H-stud adjacent framing Note As allowed by code, 16 mm (5/8 ) SHEETROCK FIRECODE Core Gypsum Panels may be used as underlayment to roof sheathing with panels extending 1220 mm (4 ) on both sides of fire wall and possibly roof side at rake end. Clip placement on page 10 is for typical construction. 11 CGC Gypsum Fire Wall Systems

12 Good Design Practices Use this section as a reference if questions arise during the design or application of CGC Fire Wall Systems. This section is an overview of good design, application, installation and safety considerations that should be addressed when CGC s products and systems are used. This section outlines some major issues, but is not intended to be a comprehensive review. We recommend that architects and contractors seek the assistance of safety professionals, especially at the professional construction site, because there are many factors to consider that are not included here. For safety and material handling information, please refer to Chapter 13 of The Gypsum Construction Handbook, Centennial Edition. 1 System Performance CGC Inc. conducts tests on products and systems to meet performance requirements of established test procedures specified by various agencies. Upon written request we will provide test certification for published fire, sound, structural and other pertinent data covering systems designed and constructed according to our published specifications. Substitutions of any of the components are not recommended and are not supported by CGC Inc. 2 Clip Attachment Fire wall systems require attachment of aluminum breakaway clips to adjacent framing on both sides of the H-Studs. Clips are attached to each stud and vertical C-Runners with one 10 mm (3/8 ) TYPE S screw, and to adjacent framing with one 31 mm (1-1/4 ) Type W or TYPE S Screw. The system may be stacked to a maximum height of 13.4 m (44 ), and normally require a vertical clip spacing of 3 m (10 ) o.c. max. However, when the wall has a stacked height exceeding 7 m (23 ), clip spacing along each stud below the 7 m (23 ) stacked height must be reduced to 1.5 m (5 ) o.c. max. (see illustration on page 11). When the fire wall system is used as an exterior wall, with adjacent framing on only one side, clips must be spaced as noted in Section 3.2 of the Application Guide Specifications. Note, for this case, that two 10 mm (3/8 ) TYPE S screws are required for clip attachment to the vertical H-Studs. 3 Sound Control For maximum sound control with wall systems, seal the entire perimeter and between the horizontal, back-to-back Construction C-Runners at the intermediate levels with a minimum 6 mm (1/4 ) bead of Acoustical Sealant. 4 Limitations For use as a common 2-hr. fire resistance rated wall separating townhouses. Not to be used for shear walls. 5 Additional See SA100, Fire-Resistant Assemblies, for fire- and sound-rated systems; SA200, Acoustical Assemblies, for sound- Information rated systems; and SA934, Moisture-Resistant Assemblies, for information on moisture resistance. 12 CGC Gypsum Fire Wall Systems

13 Application Guide Specifications This guide specification is provided to assist you in specification of CGC Fire Wall Systems. If you have additional questions or would like more information regarding this or other CGC products and systems, please contact CGC at Part 1: General 1.1 Specify to meet project requirements. Scope 1.2 A. All materials, unless otherwise indicated, shall be manufactured by CGC Inc., and shall be installed in accordance Qualifications with its current printed directions. B. System must be built in accordance with applicable model code research reports. 1.3 All materials shall be delivered in their original unopened packages and stored in an enclosed shelter providing Delivery and Storage protection from damage and exposure to the elements. Damaged or deteriorated materials shall be removed from the of Materials premises. Installed panels should be protected from the environment and dry before enclosing the wall. Warning: Store all SHEETROCK Gypsum Panels flat. Panels are heavy and can fall over, causing serious injury or death. Do not move unless authorized. Use caution not to exceed floor limits or cause tripping hazards. 1.4 In cold weather during gypsum panel joint finishing, temperature within the building shall be maintained within the Environmental range of 13 to 21 C (55 to 70 F). Adequate ventilation shall be provided to carry off excess moisture. Storage and Conditions installation of products must be protected at all times from adverse environmental conditions and elements. Part 2: Products 2.1 A. 25 mm (1 ) SHEETROCK Gypsum Liner Panels (HUMITEK), 610 mm (24 ) wide, beveled edge, lengths as required. Materials B. CGC Steel H-Studs (200HS25), galvanized, lengths as required. C. CGC Steel C-Runners (200CR25) galvanized, x 3 m (10 ) length. D. CGC Aluminum Angle Clip 50 x 64 x 1.6 mm (2 x 2-1/2 x ) Aluminum Breakaway Clips. E. Joint Treatment Select a CGC Joint System. F. Fasteners Screws (31 mm (1-1/4 ) Type W) (31 mm (1-1/4 ) TYPE S) (10 mm (3/8 ) TYPE S, pan head). G. Sound batts 25 mm (1 ), 38 mm (1-1/2 ), 50 or 75 x 400 mm (2 or 3 x 16 ) or 610 x 1220 mm (24 x 48 ). H. Acoustical sealant. 13 CGC Gypsum Fire Wall Systems

14 Part 3: Execution 3.1 A. Foundation Solid Wall Position 50 mm (2 ) C-Runner and securely attach to foundation with power-driven fasteners at both ends and spaced 610 mm (24 ) o.c. Space adjacent runner sections 6 mm (1/4 ) apart. Caulk under runner at foundation with min. 6 mm (1/4 ) bead of acoustical sealant. B. First Floor Install H-studs and liner panels to a convenient height (max. 610 mm (2 )) above the floor line. Install two thicknesses of 25 mm (1 ) liner panels vertically in C-Runner with long edges in H-Stud. Install H-Studs and liner panels alternately until wall is completed. Cap top of panels with horizontal C-Runner. Fasten C-Runner flanges at all corners both sides with 10 mm (3/8 ) TYPE S screws. C. Intermediate Floors and Bottom of Trusses Cap top of liner panels and H-Studs with C-Runner. Attach C-Runner for next row of panels to the C-Runner below with end joints staggered at least 300 mm (12 ). Fasten the C-Runners together with double 10 mm (3/8 ) screws at ends and 610 mm (24 ) o.c. Attach all H-Studs and vertical C-Runners to adjacent framing with Aluminum Breakaway Clips. Clips attaching H-Studs and vertical C-Runners to adjacent framing on both sides require attachment to the H-Stud and C-Runner with one 10 mm (3/8 ) TYPE S screw. Clips attaching H-Studs and vertical C-Runners to adjacent framing on only one side and with exterior exposure on the other side require attachment to the H-Stud and C-Runner with two 10 mm (3/8 ) TYPE S screws. Attachment to the adjacent framing is with one 31 mm (1-1/4 ) Type W or TYPE S screw. Locate horizontal C-Runner joint within 610 mm (2 ) of the intermediate floor. Install fire blocking between the solid wall system and adjacent framing at floor lines, bottom of truss line, and any other locations required by the applicable code. D. Roof Continue installing H-Studs and liner panels for succeeding stories as described. Cut the liner panels and H-Studs to roof pitch and length as necessary to follow the roof pitch. At roof, cap liner panels and H-Studs with C-Runner. Attach all H-Studs to adjacent framing with Aluminum Breakaway Clips. Clips attaching H-Studs and vertical C-Runners to adjacent framing on only one side and with exterior exposure on the other side require attachment to each vertical framing member with two 10 mm (3/8 ) TYPE S screws. 3.2 CGC Fire Wall Systems are suitable for exterior walls with an appropriate weather barrier installed over the system Exterior Wall and under an exterior cladding. Exterior exposure is limited to 718 Pa (15 psf) wind load and requires vertical clip spacing of 1220 mm (4 ) o.c. maximum. Exterior exposure requires attachment of the aluminum breakaway clips to each vertical steel framing member with two 10 mm (3/8 ) TYPE S screws. Attachment of the clips to adjacent framing is with one 31 mm (1-1/4 ) Type W or TYPE S screw. Uppermost clips should be placed as close to the roof line as practical attachment allows. 14 CGC Gypsum Fire Wall Systems

15 About the cover: Project Townhomes at Meridian Square Indianapolis, IN Design and Construction Ryland Homes Photographer Albert Vecerka/Esto

16 Customer Service Web Site Metric Specifications CGC Inc., will provide metric conversions on its products and systems to help specifiers match metric design sizes. In addition, some products are available in metric dimensions from selected manufacturing plants. Refer to SA100, Fire-Resistant Assemblies, for additional information and a Table of Metric Equivalents. Trademarks The following trademarks used herein are owned by United States Gypsum or a related company: FIRECODE, SHEETROCK, USG. LEED is a registered trademark of the U.S. Green Guilding Council. Notice We shall not be liable for incidental and consequential damages, directly or indirectly sustained nor for any loss caused b application of these goods not in accordance with current printed instructions or for other than the intended use. Our liability is expressly limited to replacement of defective goods. Any claim shall be deemed waived unless made in writing to us within thirty (30) days from date it was or reasonably should have been discovered. Note All products described here may not be available in all geographic markets. Consult your local sales office or representative for information. Safety First! Follow good safety and industrial hygiene practices during handling and installation of all products and systems. Take necessary precautions and wear the appropriate personal protective equipment as needed. Read material safety data sheets and related literature on products before specification and/or installation. CGC Inc. 350 Burnhamthorpe Rd. W., 5th Floor Mississauga, ON L5B 3J1 SA-925 EWB-W152/rev , CGC Inc., CP Printed in Canada

Fire protection for townhouses that share a common wall. Area Separation Wall. Systems

Fire protection for townhouses that share a common wall. Area Separation Wall. Systems Fire protection for townhouses that share a common wall Area Separation Wall Systems Area separation walls between adjoining townhouses must provide fire-resistive ratings to ensure the safety of occupants

More information

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein

More information

CertainTeed. Shaftliner For A rea Separation Firewalls

CertainTeed. Shaftliner For A rea Separation Firewalls CertainTeed Shaftliner For A rea Separation Firewalls M2Tech Shaftliner Type X for Area Separation M2Tech Shaftliner is a specially formulated product for applications where enhanced mold resistance is

More information

H-Stud Area Separation Wall System

H-Stud Area Separation Wall System 12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic

More information

DensGlass Shaftliner for Area Separation Walls

DensGlass Shaftliner for Area Separation Walls DensGlass Shaftliner for Area Separation Walls Product Overview Coated Fiberglass Mats Moisture-Resistant Gypsum Core DensGlass Shaftliner 2014 Georgia-Pacific Gypsum LLC Table of Contents Overview................

More information

eading Performance Solutions

eading Performance Solutions eading Solutions Manage Risk Save Time and Money Grow Business Responsive Leadership As a construction professional, you face countless challenges. Every day you are expected to finish projects efficiently

More information

Moisture Control. System Solutions to Prevent Mold

Moisture Control. System Solutions to Prevent Mold System Solutions to Prevent Mold How a systems approach to managing moisture is the most effective strategy for minimizing the growth of mold. Moisture Control Architects, designers, contractors and maintenance

More information

MOLD AND MOISTURE RESISTANT PAPERLESS SOLUTIONS FOR AREA SEPARATION WALLS

MOLD AND MOISTURE RESISTANT PAPERLESS SOLUTIONS FOR AREA SEPARATION WALLS MOLD AND MOISTURE RESISTANT PAPERLESS SOLUTIONS FOR AREA SEPARATION WALLS Product Overview Georgia-Pacific Gypsum has removed the paper facings and replaced them with fiberglass mats for superior mold

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

Comprehensive test information on fire-rated assemblies incorporating CGC products and systems. Fire-Resistant

Comprehensive test information on fire-rated assemblies incorporating CGC products and systems. Fire-Resistant Comprehensive test information on fire-rated assemblies incorporating CGC products and systems Fire-Resistant Assemblies SA-100 One of the most critical issues for architects is ensuring that building

More information

Gypsum Board Systems Manual

Gypsum Board Systems Manual CertainTeed Gypsum Board Systems Manual Fire Resistance and Sound Control Design Manual Division 09 GYPSUM BOARD SYSTEMS MANUAL TABLE OF CONTENTS Introduction General Fire Resistance...1 Sound Control...3

More information

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Fire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No.

Fire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No. BULLETIN No. 28 (a) Fire Protection CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8 Floor Assembly No. NRC764-FF22 Fire Endurance Period 1 74 minutes Sound

More information

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction

More information

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior

More information

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors Roxul Safe n Sound Sound Control and Fire Safety From One Batt Insulation Roxul

More information

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB

More information

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection PB301 July 2009 Lightweight Building Solutions Bushfire Protection www.boral.com.au/bushfireprotection Attached or adjacent within 6m roofed structures such as garages, carports, verandas and the like,

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Comprehensive information on fire-rated assemblies incorporating USG products and systems. Fire-Resistant. Assemblies

Comprehensive information on fire-rated assemblies incorporating USG products and systems. Fire-Resistant. Assemblies Comprehensive information on fire-rated assemblies incorporating USG products and systems Fire-Resistant Assemblies One of the most critical issues for architects is ensuring that building design addresses

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Fire & Soundproofing Insulation Roxul SAFE N SOUND Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Roxul SAFE N SOUND Sound control and fire safety from one batt Insulation.

More information

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description

More information

SAMPLE INSTRUCTIONS. Best Barns USA Assembly Book. the Denver. 12'x 12' or 12'x16' Revised November 29, 2010

SAMPLE INSTRUCTIONS. Best Barns USA Assembly Book. the Denver. 12'x 12' or 12'x16' Revised November 29, 2010 Best Barns USA Assembly Book Revised November 29, 2010 SAMPLE INSTRUCTIONS the Denver 12'x 12' or 12'x16' Manufactured by Reynolds Building Systems, Inc. 205 Arlington Drive Greenville, PA 16125 724-646-3775

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

FireWall. High performance fireresistant. FireWall. www.british-gypsum.com

FireWall. High performance fireresistant. FireWall. www.british-gypsum.com FireWall FireWall High performance fireresistant wall system FireWall is a non-loadbearing wall which provides up to 240 minutes fire resistance. It is used in certain ground floor basement situations

More information

Life safety assurance for modern building designs. Shaft Wall. Systems

Life safety assurance for modern building designs. Shaft Wall. Systems Life safety assurance for modern building designs Shaft Wall Systems Walls that enclose elevator shafts, stairwells and other vertical shafts are the lifeline of a building. Should a fire occur, firefighters

More information

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings INSULATION FOR PRE-ENGINEERED METAL BUILDINGS ROXUL SAFE 55 & 65 and ROXUL PLUS MB Insulation for Pre-Engineered Metal Buildings ROXUL SAFE AND ROXUL PLUS MB Exterior Wall Insulation for Pre-Engineered

More information

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357

More information

How To Repair A Boat Landing Deck With A Boat Bed

How To Repair A Boat Landing Deck With A Boat Bed RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing

More information

WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING

WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING IMPORTANT NOTICES AND INFORMATION Read these instructions in their entirety prior to installing windows. Any local building code requirements

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

Wood-frame Construction, Fire Resistance and Sound Transmission

Wood-frame Construction, Fire Resistance and Sound Transmission Fire Resistance and Sound Transmission For many years, wood-frame construction has been providing Canadians with high-quality, affordable housing. This goes from town houses to multi-storey apartment buildings,

More information

Discipline: Structural Issued 04-26-06

Discipline: Structural Issued 04-26-06 California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This

More information

FIRESTOPPING & SMOKE SEALS

FIRESTOPPING & SMOKE SEALS SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows

Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read

More information

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Sun Windows General Information Sun New Construction Window Installation Instructions

Sun Windows General Information Sun New Construction Window Installation Instructions Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199 CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

GYPSUM BOARD Guide Specification. National Gypsum Company SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 SECTION INCLUDES

GYPSUM BOARD Guide Specification. National Gypsum Company SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 SECTION INCLUDES GYPSUM BOARD Guide Specification (Specifier Note: The purpose of this guide specification language is to assist the specifier in correctly specifying gypsum board products and their installation. The specifier

More information

Fiberglas, Exterior Wall Thermal Insulation

Fiberglas, Exterior Wall Thermal Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

CertainTeed. For Shaftwalls SHAFTLINER

CertainTeed. For Shaftwalls SHAFTLINER CertainTeed For Shaftwalls SHAFTLINER GlasRoc Shaftliner is a paperless mold and moisture resistant gypsum board combining reinforcing glass mats and a specially formulated fire and moisture resistive,

More information

Lightweight Partition Design for Residential and Commercial Buildings

Lightweight Partition Design for Residential and Commercial Buildings Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation

More information

The Case for Cross Laminated Timber: Part 2

The Case for Cross Laminated Timber: Part 2 Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

AUTHORIZATION TO MARK

AUTHORIZATION TO MARK AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

C05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction

C05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05 Specialist partitions Introduction Specialist partitions This section details specialist lightweight systems where high-security,

More information

GreenGuard Housewrap Installation Guide

GreenGuard Housewrap Installation Guide 000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be

More information

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF... Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

Best Barns USA Assembly Book

Best Barns USA Assembly Book Best Barns USA Assembly Book Revised November 27, 2013 the Easton - R 12'x 20' Manufactured by Reynolds Building Systems, Inc. 205 Arlington Drive Greenville, PA 16125 724-646-3775 This manual is copyrighted.

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

Design No. U419 BXUV.U419 Fire Resistance Ratings ANSI/UL 263 "Reprinted from the Online Certifications Directory with permission from UL"

Design No. U419 BXUV.U419 Fire Resistance Ratings ANSI/UL 263 Reprinted from the Online Certifications Directory with permission from UL Design No. U419 BXUV.U419 Fire Resistance Ratings ANSI/UL 263 "Reprinted from the Online Certifications Directory with permission from UL" Design/System/Construction/Assembly Usage Disclaimer Authorities

More information

Fire Barrier Duct Wrap 15A

Fire Barrier Duct Wrap 15A 3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies

More information

Uncovered Decks & Porches

Uncovered Decks & Porches Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed

More information

Fire Resistance of Brick Masonry

Fire Resistance of Brick Masonry TECHNICAL NOTES on Brick Construction 1850 Centennial Park Drive, Reston, Virginia 20191 www.gobrick.com 703-620-0010 Fire Resistance of Brick Masonry 16 March 2008 Abstract: This Technical Note presents

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES

RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES 1807 Elmwood Avenue, Suite 275 Buffalo, New York 14207 (800) 543-5155 RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES Fiberesin Wall System Provide materials and labor to complete courts

More information

PANELIZED HOME INSTALLATION GUIDELINE

PANELIZED HOME INSTALLATION GUIDELINE PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.

More information

Shingle Installation Guide

Shingle Installation Guide Shingle Installation Guide Getting Started Dedicated to improving the environment, NewTech manufactures roofing tiles that are composed of up to 90% recycled post-industrial plastic. The manufacture of

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

CertainTeed. GlasRoc Tile Backer

CertainTeed. GlasRoc Tile Backer CertainTeed GlasRoc Tile Backer Diamondback GlasRoc Tile Backer Product Overview is a superior tile substrate for walls and ceilings, especially designed by CertainTeed to meet the demands of high-moisture

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

fire separating walls #2

fire separating walls #2 210108 fire separating walls #2 ISSUE BSA has identified a number of instances of defective fire separating walls in duplexes, town houses and multi-residential complexes. The system of fire separating

More information

usg.com/me USG Middle East, Ltd. Dammam, Saudi Arabia E-mail: info@usgme.com Fax: +966 3 8121029 +966 3 8120995

usg.com/me USG Middle East, Ltd. Dammam, Saudi Arabia E-mail: info@usgme.com Fax: +966 3 8121029 +966 3 8120995 USG Middle East, Ltd. Dammam, Saudi Arabia E-mail: info@usgme.com Fax: +966 3 8121029 +966 3 8120995 Riyadh, Saudi Arabia E-mail: riyadhsales@usgme.com Fax: +966 1 4772734 +966 1 4772734 Jeddah, Saudi

More information

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product

More information

LP OSB Sheathing & Structural 1 Sheathing

LP OSB Sheathing & Structural 1 Sheathing Rated OSB Sheathing Roof Panels Span Ratings Max. Live Load Thickness Span Rating for Roofs (lbs)** 3/8" 24/0 30 7/16" 24/16 40 15/32" 32/16 70 1/2" 32/16 70 19/32" 40/20 130 23/32" 48/24 175 1-1/8" 48

More information

Superform Products Ltd.

Superform Products Ltd. TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000

More information

Underwriters Laboratories Testing Information

Underwriters Laboratories Testing Information Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum

More information

Standard from CSI Part Section Format. 06212 For Wood Framing 05160 For Metal Framing 09226 For Gypsum Sheathing

Standard from CSI Part Section Format. 06212 For Wood Framing 05160 For Metal Framing 09226 For Gypsum Sheathing Standard from CSI Part Section Format. 06212 For Wood Framing 05160 For Metal Framing 09226 For Gypsum Sheathing Specifications for SURE-BOARD Series 200 and 200W Panel for shear PART 1.0 GENERAL 1.01

More information

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016 Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.

More information

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

ISO Types 1-6: Construction Code Descriptions

ISO Types 1-6: Construction Code Descriptions ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with

More information

The Role of Acoustics in Curtain Wall Design:

The Role of Acoustics in Curtain Wall Design: The Role of Acoustics in Curtain Wall Design: Strategies to Achieve Desired Performance Criteria April 22, 2015 John LoVerde, Principal VENEKLASEN ASSOCIATES, INC. Goals Basics of Acoustics Ratings in

More information

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of

More information

Industry Leadership Building Products Experience

Industry Leadership Building Products Experience Industry Leadership Building Products Experience Full line producer National Gypsum plants have produced gypsum wallboard for homes and commercial buildings in the United States for 85 years under the

More information

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council RETAINED ON U.S.

LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council RETAINED ON U.S. ICC-ES Legacy Report ER-5043* Reissued March 2004 www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code DIVISION: 09

More information

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 8 TEST : Whisper Industries, L.L.C. Report Date: August 14, 2008 Date: July 9, 2008 Number: RESULT

More information

Built to Last. Built for Beauty. Good. Solid. Logix. TM

Built to Last. Built for Beauty. Good. Solid. Logix. TM Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a

More information

ICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-2270 Reissued September, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information