Pumping Technology OMEGA ECOFLEXX GLANDED PUMPS INSTALLATION AND OPERATION MANUAL

Size: px
Start display at page:

Download "Pumping Technology OMEGA ECOFLEXX GLANDED PUMPS INSTALLATION AND OPERATION MANUAL"

Transcription

1 OMEGA ECOFLEXX GLANDED PUMPS INSTALLATION AND OPERATION MANUAL IMPORTANT INFORMATION These instructions must be read and understood before installing, commissioning, operating or maintaining the equipment.

2 This installation guide gives basic instructions which are to be observed during installation, operation and maintenance of the pump. It is therefore imperative that this document be read by the responsible person/operator prior to the installation and always be kept available at the site. It is not only the general safety instructions under the main heading Safety that are to be observed, but also the specific information provided under the other main headings. SAFETY DANGER Warns of the risk of electric shock, if the precautions are not observed. DANGER Warns of the risk of damage to persons, property or the unit, if the precautions are not observed. CONSTRUCTION AND APPLICATION PUMP MEDIUM Smedegaard Omega pumps are of the in-line type construction with the motor mounted directly to the pump body. The pumps are suitable for commercial and industrial heating systems, district heating schemes, water treatment plants, general water transfer duties and refrigeration plants. Clean, thin, non-aggressive and non-explosive fluids (similar viscosity and specific gravity to water) without any solids or fibres. Antifreeze without any mineral oil (special model upon request). TECHNICAL DATA Note: If any liquid other than water is being pumped, we recommend that you contact Smedegaard, or their representative, as the pump characteristics may change. Electrical data Max. working pressure NPSH requirements Temperature see nameplate 10 bar see pump performance in Omega range leaflet -15 o C to +120 o C AIRBORNE SOUND PRESSURE LEVEL 950 rpm max. 65 db(a) 1450 rpm 0.12 kw to 1.5 kw - max. 47 db(a), 3 kw to 7.5 kw - max. 60 db(a), 11 kw to 45 kw - max. 69 db(a) 2900 rpm 0.12 kw to 3 kw - max. 53 db(a), 4 kw to 11 kw - max 62 db(a), 15 kw to 45 kw - max. 78 db(a) 2

3 INSTALLATION Fig. 1 The pump can be installed with the pump shaft vertical or horizontal (see Fig.1). Direction of flow through the pump casing is indicated by an arrow. Ensure pipework alignment is correct and the pump and pipework is adequately supported. Sharp bends should be avoided adjacent to the pump. If pump is mounted in vertical pipework, flow should be upwards. If flow is downwards (not recommended) it must be ensured that no air is able to collect in the pump body. Pumps should never be allowed to operate for a long period in a closed valve condition. To avoid accumulation of impurities in the pump, ensure that it is not mounted at the lowest point in a system. It is recommended that isolating valves are fitted on either side of the pump. The system should always be thoroughly flushed out to clear any solder, steel wool, plaster or any other foreign matter that may be lodged in the pump. To avoid this risk of the accumulation of air within the pump body the pump should not be situated at the highest point of the system. This may be critical in the case of HWS (bronze) pumps. Twin headed pumps fitted into horizontal pipework and with horizontal motor shaft, then fit an automatic air vent into the top casing. If the head is mounted in the horizontal position then rotate the head to ensure the air vent is at the top. See Fig 2. Filler Pipe Open Open Closed Closed Fig. 3 3

4 Air Venting Closed Circuits Open valves on suction and discharge, allowing water to enter the pump casing. Open the air vent screw on the pump seal chamber (see Fig. 2) and allow all the air to escape. Close the air vent screw. Open Circuits - Flooded suction Proceed as for closed circuits above but with discharge valve closed. Open Circuits - Suction lift, with foot valve (see Fig. 3). Break the pipework at a suitable place on the discharge side of the pump. Open suction and discharge valves and fill pump and pipework to level of break. Open the air vent screw on the pump seal chamber (see Fig. 2) and allow all the air to escape from this area. Close the air vent screw. The water level in the pipe should remain constant, proving that the foot valve is holding. Reconnect the pipework. It is very important that the pump is fully vented otherwise the mechanical seal can be damaged. ELECTRICAL CONNECTION AND DIRECTION OF ROTATION Motors should always be connected, through a suitable starter, to the mains supply. Ensure that the electrical supply available agrees with the motor details shown on the nameplate. Connection details are shown inside the terminal box cover. Refer to the motor data plate to check for star/delta connection. If the pump is supplied with an inverter fitted, then refer to the inverter operating and maintenance instructions. The direction of rotation is shown with an arrow on the motor cowl and should always be checked after wiring. ALL OMEGA RANGE UNITS UP TO OMEGA SHOULD ROTATE IN AN ANTI- CLOCKWISE DIRECTION WHEN VIEWED FROM THE MOTOR NON-DRIVE END. ALL OMEGA RANGE UNITS OMEGA 12 AND ABOVE SHOULD ROTATE IN A CLOCKWISE DIRECTION WHEN VIEWED FROM THE MOTOR NON-DRIVE END. The direction of rotation of three phase motors can be altered by interchanging any two of the three main connecting leads. Single phase motors have the direction of rotation pre-set before despatch. STARTING THE PUMP MUST NOT RUN WITHOUT WATER. Open suction valve and close discharge valve. Start the pump and slowly open the discharge valve until fully open. The pump should never be allowed to operate for long periods in a closed valve condition. SERVICE/MAINTENANCE Motor bearings fitted to Omega pumps are sealed for life and do not need greasing. The mechanical seal fitted to this range of pumps should be checked periodically and replaced if necessary. We recommend that the casing O ring (and circlip when fitted) is replaced when a mechanical seal is changed. 4

5 OMEGA ECOFLEXX PRESSURE TRANSDUCER FITTING GUIDE Warning: If the transducers are not fitted prior to the operation of the pump it will not run/operate SINGLE PUMP Remove both pump flange tapping screws with a 6mm Allen Key/T-Bar and replace with the transducers. PTFE tape/loctite or similar maybe required to obtain a water tight seal but in most cases is not required. Fit the transducer cables to the transducers taking care to correctly align, screwing up the knurled collar and pushing in the plug as you tighten. Wire back to the Drives cutting out the White & Black, connecting Discharge transducers to S1N (blue) and S1P (brown). Suction transducers to S2N (blue) and S2P (brown). TWIN PUMP Remove both pump flange tapping screws with a 5mm allen key and replace with ¼ nipple & ¼ equal tee using PTFE tape/loctite or similar to obtain a watertight seal. Fit the transducers into the equal tee, some PTF tape/ Loctite or similar maybe required to obtain a water tight seal but in most cases is not required. Care should be taken that the transducer wires are fitted correctly in the terminals (it is easy to clamp the cables behind the terminals) and the correct cable colours are inserted into the corresponding terminals or Error 1 will be shown. 5

6 SINGLE PHASE WIRING Discharge Transducer Blue Brown To Motor Fault Signal Run Signal Remote Stop/Start (Bridge To Run) MCB-C Ground L N 1Phase /60 Brown Suction Transducer Blue 6

7 Blue Suction Transducer Brown Analogue Input MCB-C /60Hz Power Supply 0/10 VDC 4-20mA Ground Remote (Bridge To Run) Stop/Start To Motor Fault Signal Run Signal Brown Discharge Transducer Blue THREE PHASE WIRING 7

8 PUMP WIRING Each drive is connected to the pump terminals U, V and W. The direction of rotation should be checked, if it is not correct then either, switch any two of the wires to the pump terminals U V W or, reverse the direction of rotation using menu option Dr-20 in the FlexDrive. OMEGAFLEX VARIABLE SPEED DRIVE UNITS QUICK ADJUSTMENT GUIDE Upon initial startup the user menu will display P for *actual pressure across the pump. Using the Up & Down buttons other information can be accessed. P pressure actual/achieved in Bar S pressure setting in Bar H output in Hz O output in % U voltage of the DC link A output current in Amps O outlet pressure in Bar I inlet pressure in Bar Adjustments to the program can only be made whilst the pump is stopped. With the power supply on and the pump stopped use the Up & Down buttons to select S (looks like a 5) in the user menu. If the pump when stopped and the pressure removed, displays in the user menu I and O the outlet transducer needs to be corrected within parameter Pr 4 to the value of 0.3. Make sure the valves either side of the pump are opened, the bleed screw is replaced following venting/bleeding and before the pump is put into operation, failure to do so will result in damage to the pump. Press the Up & Down buttons together until Pr is displayed then use the Up & Down buttons to select Pr 4 for adjustment of the outlet transducer or Pr 6 to adjust the inlet transducer. Care must be taken not to change any other settings parameters. Following this press Set/Reset to see End appear then press and hold the Up & Down buttons together, the display will change to show Dr press and hold Up & Down buttons again, this will take you back to the user menu and will display P. If any further settings require adjustment please contact Smedegaard. Service call outs caused by the users failure to set up the VSD units correctly will result in charges. Press and hold the Set/Reset button until the display flashes and S changes to d then adjust the setpoint (displayed in Bar) to the desired setting using the Up & Down buttons. Press the Set/Reset button and End should appear in the display confirming that the setpoint adjustment has been saved. Press the Run/Stop button or replace the P1 CG link to put the pump back into normal operation. *Note Upon initial start-up up the unit will display a differential pressure across the pump even though it is not running and the transducers will require calibrating. The pump may not run when the Run/Stop button is pressed if the differential pressure shown across the pump is greater or equal to the pressure setting. Transducer Correction First remove all pressure off the pump - this can be done by closing the valves either side of the pump and opening the pump bleed screw. I displays the inlet pressure and O displays the outlet pressure which can be selected with the Up & Down buttons from the user menu. Example If the pump when stopped and the pressure removed, displays in the user menu I and O the inlet transducer needs to be corrected within parameter Pr 6 to the value of

9 OMEGAFLEX DRIVE SETTINGS Please note that under normal circumstances all the below settings are carried out at the factory. To make any adjustments the pump/drive must be stopped and not enabled to run. *To make the adjustments we may require resetting the unit back to factory settings first of all. First hold up & down together to see pr in the menu then cycle to pr90 press set/reset and change 0 to 1 and press set/reset to confirm. The second thing to do is to hold up & down together to see pr then once again to see dr, cycle to dr90, press set/reset and change 0 to 1 and press set/reset. *It may not be necessary to carry out the above but in doing so the user can be sure all settings within are correct. Holding up & down together to get to the pr menu the following parameters require changing or checking: pr2 needs to be set to 0, pr3 should be set to the maximum rating of the transducer e.g. 10 for a 0-10 bar transducer, and the same for pr5. Now the dr menu requires setting up. To get into the dr menu hold up & down to see pr then once again to see dr. dr3 needs to be set to 20 (minimum frequency in HZ to allow for sufficient cooling of the motor) dr10 needs to set to the motor capacity shown on the motor plate (KW), dr11 is 2 or 4 pole motor rpm 4 pole (DR 2)/ 2800 rpm 2 pole (DR 1) displayed again on the motor plate, dr 12 is the amp rating of the motor, dr 13 is the RPM of the motor, dr 14 is the voltage, dr 17 must be set to 0, dr 32 must be set to 5. dr 20 will change rotation direction 0-clockwise 1-anti To change or view the status of any parameter set/reset should be pressed and again to confirm a changed setting. EXTERNAL SPEED CONTROL For 4-20ma input the following parameters require changing: dr2-3, dr64 - l1 min input current, dr65 - corresponding frequency to l1 min input current - 20 (this should not be set below 20hz to allow for sufficient motor cooling), dr66 - l1 max input current, dr67 - corresponding frequency to l1 max input current - 50 (50hz max output of motor). For 0-10v input speed of the pump the following parameters will require changing: dr2-2, dr60 - V1 min input voltage, dr61 - corresponding frequency to V1 min input voltage - 20(this should not be set below 20hz to allow for sufficient motor cooling), dr62 - V1 max input voltage, dr63 - corresponding frequency to V1 max input voltage - 50 (50hz max output of motor). The recommended method for remote start/stop is via the use of terminals P1 & CG, link to run. For this application parameter dr1 should be set to 1. The power supply to the inverter should be via a class C or D MCB rated at 1.5 times the rated output of the drive. The drive must be stopped/not in run mode to enable changing of any parameters and do not switch off the power supply to the drive following changing any parameters for a few minutes as there is a delay before saving to memory. If the enable contact is utilised (CG and Run or P1, Closed link for Run, Open link for Stop/Standby) dr1 in the menu needs to be changed from 0 to 1 and there is a blue dip switch on the PCB board that needs to be changed to NPN, we are currently setting units this way from factory with a link between P1 & CG so it may have to be checked to see if it is present. 9

10 Display Content Description Restarting Remarks Er-01 tsf Pressure sensor error O 7-2 Er-02 top High pressure alarm O Er-03 tlp Low pressure alarm O 7-3 Er-04 tul Low level alarm O Er-05 tash Drive arm short trip X 7-4 Er-06 toc Drive H/W over current trip O Drive H/W over current 7-5 Er-07 SOC restriction trip O Er-08 tmoh Motor overheat (TMOH) O Er-09 toh Drive overheat trip O 7-5/6 Er-10 tlv DC-Link low voltage trip O Er-11 tov DC-Link high voltage trip O 7-6/7 Er-12 tol Overload operation trip O Er-13 tdol Drive overload operation trip O 7-8 Er-14 tgf Ground trip X Er-15 tlde Communication IC X 7-7 duplication trip Er-16 tce Communication error X Er-17 tio Input error X Er-18 too Output error X Er-20 tes External fault input X 7-8 Er-21 tlt Allowable time elapsed X 10

11 FAULT FINDING Fault Cause Action Motor does not start Electrical supply isolated Check motor terminals for correct voltage Blown Fuses Replace fuses and check current Loose electrical connections Tighten all electrical connections Motor runs and then cuts out Undersized wiring Rewire with larger cable Starter overload tripped Check overload sizing with motor F.L.C Incorrect motor links Check motor links for star/delta Pump failing to deliver Not primed Bleed pump of air Suction valve not fully open Open Valve Foot valve not fully submerged (open circuits) Lower suction pipework Air leaks in suction pipework Recheck all joints Wrong Rotation Change Rotation (check wiring phases) Foreign body in pump case Clear obstruction Pump leaking Mechanical seal damaged Replace seal Casing O Ring damaged Replace O ring Pump unduly noisy Pipework not supported correctly Check pipe supports Pipework causing undue strain on pump casing Cavitation (closed systems) Cavitation (open systems) Resupport pipework or reinstall pipework Increase static head Increase size of suction pipework Insufficient flow Incorrect rotation Change rotation (check wiring phases) Low voltage Check Electrical supply Air leaks in suction pipework Recheck all joints Valves not fully open Open all valves Partially clogged pump or pipework Clear obstructions Pump too small Replace pump Motor does not start but emits a hum Foreign body in pump casing Check motor is free to turn 1 phase motors, faulty capacitor Pump will operate correctly if spun but if it fails to re-start, replace capacitor 3 phase motors, phase dropped Check the supply phase 11

12 EC-DECLARATION OF CONFORMITY Representative and manufacture: Smedegaard Pumps Limited 10 Beech Business Park Bristol Road Bridgwater Somerset UK TA6 4FF Machine: Type: Circulation Pump Omega ECOFlexx No: From to Consist of: Pump, Motor Manufactured in accordance with the Machinery Directive 2006/42/EC on the approximation of the laws of machines. Standards used: EN 12100:2011 -EMC Directive, ie. Council Directive 2004/108/EC of 15 December 2004 to approximate the laws of Member States relating to electromagnetic compatibility. Standards used: EN , EN Low Voltage Directive (2006/95/EC) Standards used: EN :2006, EN :2012 -Commission Regulation (EU) No 640/2009 Implementing Directive 2005/32/EC of the European Parliament and of the Council with regard to eco design requirements of water pumps. -Commission Regulation (EU) No 547/2012 Implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to eco design requirements for water pumps. FlexDrive Council Directive Equipment Description Device name/type Serial European Standards Test Certificate No: Declaration: 89/336/EEC Amendment 2004/108/EC Inverter motor drives FlexDrive D02S0191AJG Emission / Immunity BS EN : 2006 Class A (industrial) EMC1392 We hereby declare that the above Device complies with the required Emission and Immunity standards stated above Copenhagen date Tommy Andersen Managing Director - Smedegaard Group Whilst every care has been taken to ensure that data is correct, no responsibility can be accepted for inaccuracies or misprints. It is SMEDEGAARD policy to continually improve and develop the product range. We reserve the right to change specifications without prior notice. Smedegaard Pumps Ltd - United Kingdom Tel. +44 (0) Fax +44 (0) [email protected] T. Smedegaard A/S - Denmark Tel Fax [email protected] Omega 24/05/2013

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

MODEL 300505 INSTALLATION INSTRUCTIONS

MODEL 300505 INSTALLATION INSTRUCTIONS WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 [email protected] Your pump has been carefully packaged at the factory to prevent damage during shipping.

More information

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Ergo-Pro Single Line Solar Station Installation and Operating Instructions Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

Oil - kerosene burners

Oil - kerosene burners Installation, use and maintenance instructions Oil - kerosene burners One stage operation CODE MODEL TYPE 3747469 G0 474T5 90 (0) - 05/008 TECHNICAL FEATURES Thermal power output 95 3 kw 8 8 kg/h Fuel

More information

Operating instructions

Operating instructions 6302 6959 02/2006 GB For the user Operating instructions Logano G215 WS Oil and gas-fired boilers Please read thoroughly before use. Overview Regulations and directives Installation: 90/396/EEC gas appliance

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

Hydraulic Trouble Shooting

Hydraulic Trouble Shooting Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders

More information

Wiring Instructions and Operating Manual 12 POINT ULTRABEAM REMOTE MONITORING SYSTEM

Wiring Instructions and Operating Manual 12 POINT ULTRABEAM REMOTE MONITORING SYSTEM Wiring Instructions and Operating Manual 12 POINT ULTRABEAM REMOTE MONITORING SYSTEM Hycontrol Limited, Larchwood House, Orchard Street, Redditch, Worcestershire, B98 7DP, UK. Tel: +44 (0)1527 406800 Fax:

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

IMPORTANT SAFETY NOTICE

IMPORTANT SAFETY NOTICE IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds

More information

ZOP, ZOT SIGMA PUMPY HRANICE GEAR PUMPS 426 1.99 21.04

ZOP, ZOT SIGMA PUMPY HRANICE GEAR PUMPS 426 1.99 21.04 SIGMA UMY HRANICE GEAR UMS SIGMA UMY HRANICE, s.r.o. Tovární 605, 753 01 Hranice, Czech Republic tel.: +420 581 661 111, fax: +420 581 602 587 Email: [email protected], 426 1.99 21.04 Application In

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Operation Instructions. KleeBlower Compressor/Vacuum pumps. Models: KB129 KB8415

Operation Instructions. KleeBlower Compressor/Vacuum pumps. Models: KB129 KB8415 Operation Instructions KleeBlower Compressor/Vacuum pumps Models: KB129 KB8415 Brd. Klee A/S All rights reserved Edition 01/2012 Head office: Branch office: Brd. Klee A/S Klee Engineering Ltd Gadagervej

More information

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES 01D351-GB FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES DOLOMIT FLOAT SWITCHES The DOLOMIT float switches find application in liquid level control in tanks and wells; they require connection

More information

Standard offering (pumps)

Standard offering (pumps) MDM PUMPS LTD Spring Lane Malvern, Worcs. England. WR14 1BP This outlines what we typically supply. Tel: +44 (0)1684 892678 Fax: +44 (0)1684 892841 E-mail: Website: Standard offering (pumps) [email protected]

More information

Conlift1, Conlift2, Conlift2 ph+

Conlift1, Conlift2, Conlift2 ph+ GRUNDFOS DATA BOOKLET Conlift1, Conlift2, Conlift2 ph+ Small lifting stations 50 Hz CONLIFT1, CONLIFT2, CONLIFT2 ph+ Table of contents 1. Product overview 3 Conlift for condensate applications 3 Applications

More information

SunMaxx Solar Filling Station Operating Instructions

SunMaxx Solar Filling Station Operating Instructions SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...

More information

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19 Table of Contents Overview 1 Pump Disassembly 2 Control Disassembly / Reassembly 7 Pump Reassembly 13 Adjustment Procedures DR Control 19 Adjustment Procedures DRG Control 20 Adjustment Procedures DFR

More information

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the

More information

Designed for multi-injector endurance testing, the

Designed for multi-injector endurance testing, the Designed for multi-injector endurance testing, the ETB Test Bench can optionally provide shot-to-shot mass measurement. The injectors are precisely subject to variable controls and hydraulic pressures

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS 2 This water heater must be installed (water and electrical installation), commissioned and serviced

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine

More information

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk 1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance

More information

CRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ

CRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CRN32-2-2 A-F-G-E-HQQE 3x4D 5 HZ Grundfos Pump 96122352 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn32/96122352/crn-32-2-2-a-f-g-e-hqqe.html

More information

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will

More information

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction

More information

Thermo Top - Troubleshooting Tree

Thermo Top - Troubleshooting Tree Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may

More information

CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ

CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ GRUNDFOS DATA BOOKLET CRN5-5 A-FGJ-G-E-HQQE 3x23/4 5HZ Grundfos Pump 96517184 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn5/96517184/crn-5-5-a-fgj-g-e-hqqe.html

More information

SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24

SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24 SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24 OPERATING & MAINTENANCE INSTRUCTIONS 1205 PARTS & SERVICE For Spare Parts and Service,please contact your nearest dealer, or CLARKE International,

More information

WD-AMX Water Detection Controllers

WD-AMX Water Detection Controllers Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation

More information

Technical Information

Technical Information Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS Section: MOYNO 500 PUMPS Page: 1 of 8 Date: March 1, 1998 SERVICE MANUAL MOYNO 500 PUMPS 300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS Mechanical Seal Models Packing Gland Models MODELS DESIGN FEATURES

More information

How To Use A Flowmeter

How To Use A Flowmeter INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual Goodway Technologies Corporation 420 West Avenue Stamford, CT 06902-6384 (203)359-4708 Sales: 1-800-333-7467 Customer Service: 1-800-370-2855

More information

ATTENTION This is a general warning that failure to follow instructions could result in poor functioning of the unit.

ATTENTION This is a general warning that failure to follow instructions could result in poor functioning of the unit. 1. Description The macerating system of this unit is installed in a case, specifically designed for horizontal outlet spigots. This macerator is manufactured in a factory which is quality certified to

More information

Operators manual Basic water heater

Operators manual Basic water heater Operators manual Basic water heater Isotemp Basic water heater has been designed and produced to ensure that your water heater will give long and trouble free operation for many years. It is important,

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

GERONIMO ANALOGUE HEAVY DUTY TELEPHONE

GERONIMO ANALOGUE HEAVY DUTY TELEPHONE GERONIMO ANALOGUE HEAVY DUTY TELEPHONE Installation and Connection Instructions K a l i k a L t d., I n n o v a t i o n H o u s e, A l e x a n d e r B e l l C e n t r e, H o p k i n s o n Wa y, A n d o

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT POSEION 2-29, 2-25 & 2-22 POSEION 2-29, 2-25 & 2-22 XT Repair Manual Index A. Safety precautions 3 B. Technical data 4 C. Structure 5-6. Service / Repair 7-23 E. Tools 24 F. Function 25-26 G. Electric

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

SECURITY SYSTEM ADP-CAN

SECURITY SYSTEM ADP-CAN INSTALLATION INSTRUCTION SECURITY SYSTEM ADP-CAN Introduction Motorcar security system ADP-CAN is for motorcars provided with CAN net. It is for the work with the motorcar factory security systems or remote

More information

A1000 Cheat Sheet (Open Loop Vector)

A1000 Cheat Sheet (Open Loop Vector) A1000 Cheat Sheet (Open Loop Vector) The following procedure is a supplement to supplied with this equipment and will guide the user in properly wiring the A1000 and. It will also show the user how to

More information

1115 4G SERIES GOVERNOR. 4-20 ma ANALOGUE DIGITAL SPEED SETTING

1115 4G SERIES GOVERNOR. 4-20 ma ANALOGUE DIGITAL SPEED SETTING 1115 4G SERIES GOVERNOR with 4-20 ma ANALOGUE & DIGITAL SPEED SETTING PO Box 28, 9300AA Roden, The Netherlands Tel: +31 505019888 Fax: +31 505013618 E-mail: [email protected] 1115 4G

More information

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

Carpet Washer. vax.co.uk VRS5W. Vax Careline: (UK) 0844 412 8455 (ROI) 1-800 928 308. Vax model number: Version 1.0

Carpet Washer. vax.co.uk VRS5W. Vax Careline: (UK) 0844 412 8455 (ROI) 1-800 928 308. Vax model number: Version 1.0 VRS5W Powermax User Guide V1.0.qxd:V1.0 23/7/10 15:35 Page 1 Vax Careline: (UK) 0844 412 8455 (ROI) 1-800 928 308 Carpet Washer Vax model number: VRS5W instruction manual Version 1.0 Please read carefully

More information

BOWIE PUMPS OPERATION - MAINTENANCE

BOWIE PUMPS OPERATION - MAINTENANCE BOWIE PUMPS OPERATION - MAINTENANCE PUMPING PRINCIPLE: The meshing owieeof the gears cause a slight depression, with the resulting enmeshing of the gears causing a vacuum drawing the fluid being pumped

More information

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft

More information

MINI MCR-SL-R-UI(-SP)

MINI MCR-SL-R-UI(-SP) Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

Wilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions

Wilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions Wilo SP Series Submersible Sump Pumps ECS ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions PREINSTALLATION CHECK Inspect this pump before it is used. Occasionally, pumps can

More information

Floodlight Range Installation Guide

Floodlight Range Installation Guide SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected

More information

Aquamax Australia Pty Ltd ABN 17 138 189 689

Aquamax Australia Pty Ltd ABN 17 138 189 689 Aquamax Australia Pty Ltd ABN 17 138 189 689 AQUAMAX SERVICE MANUAL Stainless Steel Electric Water Heaters AQ0903010-A Revision: A Published: November 2012 E80 to E315 Series Contents Introduction... 3

More information

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to: OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS Please read and follow all these instructions carefully before proceeding with the installation,

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

GPD 506/P5 Start-up Procedure and Checklist

GPD 506/P5 Start-up Procedure and Checklist GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass

More information

HPU14M-DS 2013 Daniels Manufacturing Corp., All Rights Reserved Page 1 of 17 REV. C 7/2013

HPU14M-DS 2013 Daniels Manufacturing Corp., All Rights Reserved Page 1 of 17 REV. C 7/2013 The DMC HPU14M is a robust, 110V electrically powered hydraulic pump, designed to provide a hydraulic system pressure of 10,000psi. This pump can be used with compatible heads and hoses, designed for a

More information

Operations Manual Blast Chiller

Operations Manual Blast Chiller Operations Manual Blast Chiller ADE- 2039-A Page 1 of 14 Contents Page 1 What is the Adande System 3 2 Adande Technology Explained 3 3 EC Declaration of Conformity 4 4 Storage of Product 5 5 Operating

More information

Hydraulic control unit series 0086-372-01

Hydraulic control unit series 0086-372-01 Technical Product Information No. 1290 EN Hydraulic control unit series 0086-372-01 Contents Page About this Technical Product Information (TPI) 2 The ORTLINGHAUS numbering system 2 About the product 3

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE RJS SELF-PRIMING SHALLOW WELL JET PUMPS a. Motor will not start: 1. No power to pressure switch due to blown fuses, open switches or loose connections. 2. Pump pressure switch not closed. b. Pump fails

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

User's Instructions. Alpha HE CB25/33 and HE SY25

User's Instructions. Alpha HE CB25/33 and HE SY25 User's Instructions Alpha HE CB25/33 and HE SY25 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Boiler Range For Technical help or for Service call... ALPHA HELPLINE Tel:

More information

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.

More information

Installation and Start-up Instruction

Installation and Start-up Instruction Screw pumps Low pressure pumps Installation and Start-up Instruction This instruction is valid for all standard low pressure pumps: LD, ACD, ACE, LE, ACG/UCG, ACF/UCF, LQ and AQ Contents age ump identification

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

Float and Thermostatic Traps Series H, C and X

Float and Thermostatic Traps Series H, C and X Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:

More information

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp. EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium

More information

Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)

Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided) ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS

More information

ATL Fuel Level Sender Probes

ATL Fuel Level Sender Probes T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

Mounting Instructions. Torque Transducer. A0329 3.2 en

Mounting Instructions. Torque Transducer. A0329 3.2 en Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................

More information

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE 4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement

More information

Get Cleaning... User Guide Vax Careline: (UK) 0844 412 8455 (ROI) 1-800 928 308. Multifunction. vax.co.uk. 6131 Series. What s your Vax model number?

Get Cleaning... User Guide Vax Careline: (UK) 0844 412 8455 (ROI) 1-800 928 308. Multifunction. vax.co.uk. 6131 Series. What s your Vax model number? 6131 Series User Guide v1.1-06.09.10:user guide 09/09/2010 11:42 Page 1 User Guide Vax Careline: (UK) 0844 412 8455 Multifunction Get Cleaning... What s your Vax model number? 6 1 3 1 What s your serial

More information

Operating Instructions Drill rig DRU160

Operating Instructions Drill rig DRU160 Operating Instructions Drill rig DRU160 Index 000 / 001 Original operating instructions 10988825 en / 20.10.2009 Congratulations! With a Hydrostress unit from TYROLIT you have chosen a tried and tested

More information

Coolflo Safe Touch Shower Mixing Valve ST20015CP

Coolflo Safe Touch Shower Mixing Valve ST20015CP Coolflo Safe Touch Shower Mixing Valve ST20015CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information