Fire Incident at Bukit Panjang Exchange on 9 October 2013 ( Incident )
|
|
|
- Rosalind Hudson
- 10 years ago
- Views:
Transcription
1 FACT SHEET (May 2014) Fire Incident at Bukit Panjang Exchange on 9 October 2013 ( Incident ) 1. A fire broke out at the Bukit Panjang exchange (the Exchange ) 1, at around 1402hrs on 9 October 2013, at one of the four lead-in entry locations in the Exchange s cable chamber. The fire damaged optical fibre cables and affected telecommunication services provided by multiple operators in the northern and western parts of Singapore, including fixed voice, broadband Internet access and mobile services. The service disruption also affected telecom and broadcast services to close to 270,000 subscribers 2, including residential users, some government agencies, businesses, financial institutions, and multi-application kiosks providing e-commerce and payment services. The affected services were fully restored on 17 October 2013 at 0220hrs. 2. IDA has found that Singapore Telecommunications Limited ( SingTel ), CityNet Infrastructure Management Pte Ltd ( CityNet ) and OpenNet Pte Ltd ( OpenNet ) had not fulfilled their respective obligations, such as to provide sufficiently resilient telecommunication systems and services, and to restore services to affected end users as quickly as possible when the service disruptions occurred. Cause of the Incident 3. IDA has conducted its investigations and review of the resiliency of SingTel s key fixed line infrastructure involved in the Incident 3. IDA had formed a review panel, comprising relevant telecommunications network and fire experts, to assist in its investigations and review. 4. Based on IDA s investigations, IDA has concluded that the service disruptions were due to a fire in the cable chamber of the Bukit Panjang Exchange, which was most likely caused by hot works carried out by SingTel on its cables on 9 October IDA noted that instead of using a SingTel-issued blowtorch, an unauthorised blowtorch was used to 1 Bukit Panjang exchange, formerly owned by SingTel, is now owned and managed by CityNet. CityNet is a trusteemanager of the NetLink Trust, which owns the telecom exchanges, ducts and manholes used to support the Nationwide Broadband Network ( NBN ). SingTel owns 100% of the units in the NetLink Trust at present. Besides Bukit Panjang exchange, CityNet owns and manages six other telecom exchanges. 2 The number of subscribers here refers to the absolute number of subscriptions across all service providers, e.g., a user could have signed on to both fixed voice and broadband Internet services. In this case, this counts as two subscriptions. 3 IDA has started a broader review of key fixed-line infrastructure of key telecom operators, to review the overall resiliency of telecom networks in Singapore.
2 heat and shrink a thermo fit to seal a cable duct. The flame of the unauthorised blowtorch was almost twice as hot as that of a SingTel-issued blowtorch. 5. In addition, IDA s investigations also revealed that SingTel did not ensure that the hot works safety procedures and protocols were adhered to by its workers, and there were also several shortcomings and/or failures on SingTel s part which contributed to the Incident, as summarised below: a) Use of unauthorised blowtorch: SingTel did not comply with its own standard operating procedures ( SOPs ), which required all equipment used for hot works to be inspected before use. b) Likely failure of SingTel worker to observe a full 30-minute fire watch: This was required under SingTel s and CityNet s SOPs. c) The fire alarm had been deactivated prior to hot works in accordance with SingTel and CityNet s SOPs, as smoke from such works could trigger false alarms. However, there was no re-activation of the fire alarm when SingTel s worker left the Exchange s cable chamber unattended during his lunch, which was not in accordance with the SOPs. d) Failure to ensure proper supervision of the hot works: Proper supervision plays a key role in ensuring safety before, during and after the hot works. However, there was no such supervision of the hot works by CityNet or SingTel on 9 October e) IDA also found a piece of material in the vicinity of the fire (i.e., a small burnt piece of cardboard) which should not have been present, indicating that there could be other possible materials contributing to the fire. 6. IDA found that the fire, and consequently the service disruption, could have been prevented had SingTel enforced its SOPs and work safety practices. Service Restoration 7. Service restoration work commenced around 1815hrs (after SCDF s site clearance) on 9 October 2013, via a two-pronged approach: (i) diverting of telecommunication traffic from affected cables to other spare cables at the Exchange that were not affected by the Incident; and (ii) repairing the damaged cables, where damaged sections of the fibre cables were cut away and rejoined (or spliced) strand-by-strand. SingTel completed the
3 restoration of its fibre cables on 11 October 2013 around 0715hrs, and full restoration of SingTel s fixed line services was achieved at 1500 hours on 14 October 2013 (i.e., after 120 hours and 58 minutes). 8. IDA also noted that SingTel had certain business continuity management ( BCM ) policies and processes in place, and that SingTel had implemented these during the Incident. However, SingTel s BCM did not have specific contingency plans to address serious service outage situations of such a scale as the Bukit Panjang incident. Network Resilience 9. In terms of SingTel s network resilience, IDA s observations are that while SingTel s overall network architecture design is found to be generally in line with international practice, there are still areas for improvement. In particular: a) The use of flame and lead sealants in the cable chamber is an outdated and hazardous practice, and is not in line with industry best practices and standards. This view was also supported by SingTel s own consultant. SingTel had started the process of replacing the use of lead sealants with Multi Cable Transit system 4 but progress has been slow 5. If the use of lead sealants had been fully replaced, no hot works would have been required and the Incident would not have occurred. b) Eight out of the 53 fibre cable rings connecting through the Exchange were temporarily routed using one single cable entry point, representing a single point of failure for that Exchange. While such temporary routing of fibre cable rings is sometimes unavoidable due to construction work, the original routings should be restored as soon as possible, e.g., when works are completed. 10. Additionally, IDA found that SingTel had wrongly assumed that fibre paths were diverse for certain enterprise customer services without fully testing them. This points to improvements required in SingTel s operational processes. 11. The above findings are also consistent with SingTel s own Board Committee of Inquiry ( BCOI ) findings. 4 The Multi Cable Transit system is a cable sealing system that provides protection from fire, smoke, water and blast pressures at the point where cables enter an exchange through the cable chamber. The use of this system does not require hot works. 5 SingTel targets to replace these by July 2014.
4 Assessment SingTel 12. IDA has found SingTel to be in breach of the Code of Practice for Telecommunication Service Resiliency 2008 ( Service Resiliency Code ). Under the Telecommunications Act (Cap. 323) ( TA ), IDA may impose a financial penalty of up to 10% of a licensee s annual gross turnover ( AGTO ), or S$1 million, whichever is higher. 13. In determining the final financial penalty, IDA took into consideration all the relevant factors, including but not limited to the length of the Incident, the number of affected subscribers, and the fact that the Incident was a serious one which could have been prevented. 14. On the other hand, IDA also acknowledged the presence of several mitigating factors, including SingTel s commitment to invest in enhancing network resilience. Some of the commitments SingTel made include: (i) replacing lead duct seals in exchanges with the Multi Cable Transit system which does not require heating; (ii) installation of automatic fire suppression systems within cable chambers in all its exchanges; (iii) centralised monitoring of smoke detectors and fire alarms; (iv) enhancing the physical security of cable chambers, in particular, installing CCTVs to prevent unauthorised access; and (v) enhancing its Operations Support System and processes to ensure compliance to fibre path diversity requirements for enterprise customers with redundancy and path diversity needs. IDA also considered the compensation SingTel had given to its end users and the way it managed the Incident, including its pro-activeness and transparency in public communications and the convening of a BCOI. IDA will require SingTel to put in place these committed improvement measures, and monitor the progress and implementation. 15. Taking into account all the relevant factors, including the mitigating factors, as well as the caps set out above, IDA has imposed a financial penalty of S$6 million on SingTel. A service outage of this magnitude is unprecedented. With increasing dependency of businesses and consumers on communications, a very strong signal must be sent to telecom operators that they must take network resilience very seriously and invest in the relevant upgrades to ensure against service outages.
5 CityNet 16. As the owner and manager of the Exchange, CityNet did not meet its Licence obligation as a Facilities-Based Operator to maintain and operate telecommunication systems 6, which include the cable chamber in the Exchange, in an adequate and satisfactory manner. In particular, IDA found that there were procedural lapses on CityNet s part, such as a lack of robust approving process for hot works in the Exchange 7, and the failure to ensure safety of the work area and compliance with proper operating procedures 8. IDA also found that CityNet failed to ensure a proper fire watch 9, did not have in place a proper fire alarm deactivation protocol 10 and there was a lack of physical security at the cable chamber 11. Had CityNet done so, the fire might have been prevented, or CityNet might have helped to minimally reduce the fire risk and/or helped to detect the fire earlier, which would be relevant for the efficacy and timeliness of the firefighting and service restoration efforts for the Incident. 17. Nevertheless, IDA took into account the corrective measures committed by CityNet as mitigating factors. Some of the commitments CityNet made include: (i) replacing the lead duct seals in all cable chambers; (ii) installing gas suppression systems and more fire extinguishers in all cable chambers; (iii) installing a centralised alarm monitoring system to monitor critical building alarms, including smoke detectors (and other fire warning alarm systems); and (iv) installing an electronic access system, together with CCTVs located at the entrance of each cable chamber. IDA will require CityNet to put in place these committed improvement measures, and monitor the progress and implementation. 18. Accordingly, IDA has imposed a financial penalty of S$300,000 on CityNet Under Condition 6 (Basic Obligation to Support Public Telecommunication Licensees) of CityNet s FBO licence, it is provided that [CityNet] shall establish, install, maintain and operate the Systems and shall: where [CityNet] has available ducts and associated manholes, provide access to and use of such ducts and manholes; and where [CityNet] has no available ducts and associated manholes, procure or deploy such ducts and manholes and provide access to and use thereof, to any Public Telecommunication Licensee designated by IDA under Section 6 of the Act that requests [CityNet] for such ducts and associated manholes (as the case may be). 7 SingTel s hot work application was approved although it was incomplete and SingTel had submitted the wrong application form. CityNet did not appear to have any formal criteria or standards by which hot works applications would be assessed. 8 CityNet did not carry out a physical check of the area at and around the hot works to ensure that the area was safe for commencement of hot works. 9 CityNet s hot work application form required the signature of (a) person carrying out the hot works and (b) CityNet s representative, both before and after the completion of hot works. However, these were not implemented. 10 CityNet did not specify any measures to be taken to monitor the site while the fire alarm was deactivated. 11 Physical access to the cable chamber was not tightly controlled. 12 Under the TA, CityNet may be liable for a financial penalty of up to S$1million or 10% of its AGTO, whichever is higher.
6 OpenNet 19. OpenNet is the Network Company ( NetCo ) responsible for the design, build and operation of the passive infrastructure layer of the NBN. While not a direct contributor to the cause of the Incident, OpenNet has been found to contribute to the delay in service restoration to affected users. 20. IDA found that OpenNet could have expedited the restoration and recovery process, such as by adopting more appropriate service restoration processes for larger scale service disruptions. As a result, the duration of service disruptions to affected users was unnecessarily prolonged. In this regard, IDA found OpenNet to have contravened its obligations under the Code of Practice for Next Gen NBN NetCo Resiliency, and has imposed a financial penalty of S$200, IDA has required OpenNet to enhance its BCM and work with the other operators on an end-to-end BCM in the multi-layered NBN. Other affected telecom licensees 22. IDA has also carried out investigations into whether Nucleus Connect Pte Ltd ( Nucleus Connect ) and StarHub Limited ( StarHub ), as downstream operators, have breached their respective service resiliency codes as a result of this Incident. For both StarHub and Nucleus Connect, the Incident s impact has crossed the relevant threshold for their fixed-line telephone services and end-user connections respectively. Other than the fact that both operators did not cause the Incident, IDA has also reviewed the recovery efforts of both StarHub and Nucleus Connect, and found no evidence that both licensees had acted in a manner that led to delays in service restoration. 23. Accordingly, IDA has decided not to take further enforcement actions on StarHub and Nucleus Connect. Areas of Improvement 24. The Incident highlighted the need to re-examine the systemic resilience of all critical parts of Singapore s infocomm infrastructure as well as the efficacy of inter-operator coordination in the multi-layered NBN, in a crisis situation such as this Incident, to bring about speedy service recovery. IDA has embarked on a review of the resilience of all critical parts of Singapore s infocomm infrastructure and the review is expected to be completed in the second half of The review will help to identify any other potential weakness in the critical networks and seek to address them to minimise the risk of
7 widespread service disruptions. In addition, IDA has worked with the industry to put in place a set of coordination processes to improve inter-operator communication and coordination during major service disruptions. To ensure that such a coordination process stays relevant to the operators and industry, IDA will review the coordination process from time to time. 25. IDA is also looking into the need for greater network monitoring capability across the multi-layered network infrastructure to enhance the overall resiliency of the NBN. 26. IDA will continue to review its regulatory frameworks to ensure that telecommunication operators take proactive steps to enhance the resilience of their networks and services. IDA will also explore ways to further strengthen the resilience of Singapore s telecommunication networks through multiple operators, networks, and different technology platforms. ISSUED BY CORPORATE AND MARKETING COMMUNICATIONS DIVISION About Infocomm Development Authority of Singapore The mission of the Infocomm Development Authority of Singapore (IDA) is to develop information technology and telecommunications within Singapore with a view to serve citizens of all ages and companies of all sizes. IDA does this by actively supporting the growth of innovative technology companies and start-ups in Singapore, working with leading global IT companies as well as developing excellent information technology and telecommunications infrastructure, policies and capabilities for Singapore. For more news and information, visit For media clarifications, please contact: Adrian CHAN (Mr) Manager Corporate and Marketing Communications Division, IDA [email protected] Angie LOW (Ms) Senior Manager Corporate and Marketing Communications Division, IDA [email protected]
PROPOSED APPROACH TO FIXED-WIRELESS BROADBAND DEPLOYMENT AND SERVICE PROVISIONING IN SINGAPORE
PROPOSED APPROACH TO FIXED-WIRELESS BROADBAND DEPLOYMENT AND SERVICE PROVISIONING IN SINGAPORE A RESPONSE TO AUTHORITY'S CONSULTATION PAPER OF 16 FEBRUARY 2000 SINGAPORE TELECOMMUNICATIONS LIMITED 1. SUMMARY
BROADCASTING ACT (CHAPTER 28) Code of Practice for Television Broadcast Standards
BROADCASTING ACT (CHAPTER 28) Code of Practice for Television Broadcast Standards 1 In exercise of the powers conferred by section 6 of the Broadcasting Act (Cap. 28), the Media Development Authority of
PROPOSED CONSOLIDATION INVOLVING STARHUB PTE LTD AND SINGAPORE CABLE VISION LTD CONSULTATION DOCUMENT
PROPOSED CONSOLIDATION INVOLVING STARHUB PTE LTD AND SINGAPORE CABLE VISION LTD CONSULTATION DOCUMENT 1. To what extent, if any, would the proposed Consolidation be likely to reduce competition by eliminating
GUIDELINES ON SUBMISSION OF APPLICATION FOR FACILITIES-BASED OPERATOR LICENCE
GUIDELINES ON SUBMISSION OF APPLICATION FOR FACILITIES-BASED OPERATOR LICENCE 1 INTRODUCTION 1.1 The Singapore telecommunication services market was fully liberalised from 1 April 2000. As required under
Verizon, 911 Service and the June 29, 2012, Derecho
Verizon, 911 Service and the June 29, 2012, Derecho August 13, 2012 Verizon, 911 Service, and the June 29, 2012 Derecho Late in the evening of Friday June 29, 2012, a severe storm hit the Mid-Atlantic
INFOCOMM DEVELOPMENT AUTHORITY OF SINGAPORE CODE OF PRACTICE FOR THE PROVISIONING OF COAXIAL CABLE HOME NETWORKING SOLUTIONS
INFOCOMM DEVELOPMENT AUTHORITY OF SINGAPORE CODE OF PRACTICE FOR THE PROVISIONING OF COAXIAL CABLE HOME NETWORKING SOLUTIONS 21 July 2014 Contents Chapter 1 Preliminary... 3 1.1 Citation and commencement...
FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE
Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or
BROADCASTING ACT (CHAPTER 28) Code of Practice for Television Broadcast Standards
BROADCASTING ACT (CHAPTER 28) Code of Practice for Television Broadcast Standards 1 In exercise of the powers conferred by section 6 of the Broadcasting Act (Cap. 28), the Media Development Authority of
Ofcom guidance on security requirements in sections 105A to D of the Communications Act 2003
Ofcom guidance on security requirements in sections 105A to D of the Communications Act 2003 Guidance Publication date: 08 August 2014 About this document The legislation that applies to telecoms providers
SINGAPORE TELECOMMUNICATIONS LIMITED REVIEW OF THE CODE OF PRACTICE FOR INFO-COMMUNICATIONS FACILITIES IN BULDINGS ( COPIF )
SINGAPORE TELECOMMUNICATIONS LIMITED REVIEW OF THE CODE OF PRACTICE FOR INFO-COMMUNICATIONS FACILITIES IN BULDINGS ( COPIF ) 1. STATEMENT OF INTEREST 1.1 Singapore Telecommunications Ltd ( SingTel ) is
OPERATIONAL EQUIVALENCE REPORT FOR THE JUNE QUARTER
OPERATIONAL EQUIVALENCE REPORT FOR THE JUNE QUARTER 31 August 2012 FINAL TELSTRA UNRESTRICTED OPERATIONAL EQUIVALENCE REPORT PAGE 1/18 Contents 1. Executive summary 3 2. Introduction 6 2.1. The interim
Advanced Fire Protection in Data Centres
Advanced Fire Protection in Data Centres Jeff Klein, Honeywell Life Safety, 26 June 2012, Copyright 2012 System Sensor Europe. All rights reserved. The Challenge for Mission Critical Data Centres Fuel
CONSULTATION PAPER ISSUED BY THE INFO-COMMUNICATIONS DEVELOPMENT AUTHORITY OF SINGAPORE
CONSULTATION PAPER ISSUED BY THE INFO-COMMUNICATIONS DEVELOPMENT AUTHORITY OF SINGAPORE PROPOSED MACHINE-TO-MACHINE ( M2M ) ACCESS CODE ALLOCATION FRAMEWORK 11 April 2013 PART I: PART II: PART III: PART
Oracle Maps Cloud Service Enterprise Hosting and Delivery Policies Effective Date: October 1, 2015 Version 1.0
Oracle Maps Cloud Service Enterprise Hosting and Delivery Policies Effective Date: October 1, 2015 Version 1.0 Unless otherwise stated, these Oracle Maps Cloud Service Enterprise Hosting and Delivery Policies
UGANDA COMMUNICATIONS COMMISSION
UGANDA COMMUNICATIONS COMMISSION GUIDELINES ON TYPE APPROVAL OF TELECOMMUNICATIONS AND RADIO COMMUNICATIONS EQUIPMENT IN UGANDA 1.0 INTRODUCTION The public radio and telecommunications networks have been
INFO-COMMUNICATIONS DEVELOPMENT AUTHORITY OF SINGAPORE TELECOMMUNICATION ACT (CHAPTER 323)
INFO-COMMUNICATIONS DEVELOPMENT AUTHORITY OF SINGAPORE TELECOMMUNICATION ACT (CHAPTER 323) ADVISORY GUIDELINES ON CONTRACT PERIOD AND EARLY TERMINATION CHARGES FOR TELECOMMUNICATION SERVICES OFFERED TO
Clarity Assurance allows operators to monitor and manage the availability and quality of their network and services
Clarity Assurance allows operators to monitor and manage the availability and quality of their network and services clarity.com The only way we can offer World Class Infocomm service is through total automation
CENTRAL BANK OF KENYA (CBK) PRUDENTIAL GUIDELINE ON BUSINESS CONTINUITY MANAGEMENT (BCM) FOR INSTITUTIONS LICENSED UNDER THE BANKING ACT
CENTRAL BANK OF KENYA (CBK) PRUDENTIAL GUIDELINE ON BUSINESS CONTINUITY MANAGEMENT (BCM) FOR INSTITUTIONS LICENSED UNDER THE BANKING ACT JANUARY 2008 GUIDELINE ON BUSINESS CONTINUITY GUIDELINE CBK/PG/14
COMMUNICATIONS ALLIANCE LTD NATIONAL BROADBAND NETWORK FIBRE READY DISTRIBUTION NETWORKS
COMMUNICATIONS ALLIANCE LTD NATIONAL BROADBAND NETWORK FIBRE READY DISTRIBUTION NETWORKS National Broadband Network - Fibre Ready Distribution Networks Industry Guideline Communications Alliance Ltd (formerly
Section 1: Definitions
ARTICLE XIV: REGISTRATION AND ENFORCEMENT OF ALARM SYSTEMS Section 1: Definitions A. Alarm Company is a person or business that sells, provides, monitors, maintains, services, repairs, alters, replaces,
Call reduction guidance for false alarm/ unwanted fire signals
Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately
TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING
TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING A.K. Tang 1 1 President, L&T Engineering and Project Management Consultant, Mississauga. Canada Email: [email protected] ABSTRACT: Telecommunication
ICTNPL5071A Develop planning strategies for core network design
ICTNPL5071A Develop planning strategies for core network design Release: 1 ICTNPL5071A Develop planning strategies for core network design Modification History Not Applicable Approved Page 2 of 15 Unit
Appendix 3 Disaster Recovery Plan
Appendix 3 Disaster Recovery Plan December 13, 2006 Revision XXQwest Government Services, Inc. 4250 North Fairfax DriveArlington, VA 22203(Delete this page)revision history Revision Number Revision Date
Fire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
Comments of Verizon Business. Regarding the Public Consultation Paper:
Comments of Verizon Business Regarding the Public Consultation Paper: Review of Direct and Indirect Interconnection Arrangements Between Telecommunications Licensees 8 December 2006 Contact Information:
General Tariff Information. Public Fixed Telecommunications Networks and Services Tariff Number B19-01. Tariff Effective Date
General Tariff Information Service Provider Name Qatar Telecom (QTel) Q.S.C. License Public Fixed Telecommunications Networks and Services Tariff Number B19-01 Service Name Global Ethernet Tariff Type
Security Whitepaper: ivvy Products
Security Whitepaper: ivvy Products Security Whitepaper ivvy Products Table of Contents Introduction Overview Security Policies Internal Protocol and Employee Education Physical and Environmental Security
UNDERGROUND TELECOMMUNICATIONS CABLES ACROSS PRIVATE LAND
FACT SHEET TELEPHONE 0800 327 646 I WEBSITE WWW.FEDFARM.ORG.NZ UNDERGROUND TELECOMMUNICATIONS CABLES ACROSS PRIVATE LAND BACKGROUND The Rural Broadband Initiative envisages substantially improved broadband
Risk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
NUCLEUS CONNECT PTE. LTD. INTERCONNECTION OFFER (ICO) AGREEMENT SERVICE SCHEDULE L3 VIRTUAL ROUTING DOMAIN SETUP SERVICE
NUCLEUS CONNECT PTE. LTD. INTERCONNECTION OFFER (ICO) AGREEMENT CONTENT PAGE No. Paragraph Page 1. INTRODUCTION 3 2. DEFINITIONS AND INTERPRETATION 3 3. COMMENCEMENT 4 4. ORDER HANDLING 4 5. TAKING UP
Local Access Charge ( LAC ) Bypass in relation to Voice over Internet Protocol ( VoIP ) Services
Your Ref 來 函 檔 號 : Our Ref 本 函 檔 號 : OFCA/R/CW/35/3 C 28 May 2015 By Email Circular letter to all - Unified Carrier Licensees (authorised to provide fixed internal services or mobile services) - Fixed
HealthcareBookings.com Security Set Up
HealthcareBookings.com Security Set Up Introduction... 2 Overview of the process for using HealthcareBookings.com... 2 Professionals... 2 Patients... 3 Passwords... 4 Hosting Security... 4 Overview of
SUPERVISORY AND REGULATORY GUIDELINES: PU19-0406 BUSINESS CONTINUITY GUIDELINES
SUPERVISORY AND REGULATORY GUIDELINES: PU19-0406 Business Continuity Issued: 1 st May, 2007 Revised: 14 th October 2008 BUSINESS CONTINUITY GUIDELINES I. INTRODUCTION The Central Bank of The Bahamas (
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
UK Networks & Security An Overview. Dr Andrew Powell, ENISA Workshops on CERTs in Europe, 29 May 2008
UK Networks & Security An Overview Dr Andrew Powell, ENISA Workshops on CERTs in Europe, 29 May 2008 Objectives The structure of your public communication networks The threat landscape these networks face
Todd & Cue Ltd Your Business Continuity Partner
Todd & Cue Ltd Your Business Continuity Partner Preparation and Planning We provide strategies, tools and resources to help you prepare for a business interruption whether it is caused by fire, water,
REGULATORY OPTIONS TO FACILITATE THE ADOPTION OF INTERNET PARENTAL CONTROLS PUBLIC CONSULTATION RESPONSE FROM NETSWEEPER INC.
REGULATORY OPTIONS TO FACILITATE THE ADOPTION OF INTERNET PARENTAL CONTROLS PUBLIC CONSULTATION RESPONSE FROM NETSWEEPER INC 16 May 2014 Netsweeper Inc. 104 Dawson Road Suite 100 Guelph, Ontario, N1H 1A7
Tools and Operational Data Available. 15.12.2015 1 st RESOLUTE Workshop, Florence
Tools and Operational Data Available Athens Transport Tools and Operational Data Operations Control Center (OCC): mimic panels, operations modi (full, downgraded, manual) Metro Security Systems: sensors
UNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
Next Gen NGN Framework
Next Gen NGN Framework NGNBN OpCo Network Requirement High Uplink, Downlink Access Speed Open Access, Reliable, Scalable, Secure and Upgradeable Network Support fair and equitable bandwidth allocation
Fire Alarms- Use of buildings when they are out of service
Fire Alarms- Use of buildings when they are out of service Document control information Published document name: no-alarm-gn.pdf Date issued: January 2016 Version: 4 Previous review dates: May 2014 Next
The evolution of data connectivity
Leveraging the Benefits of IP and the Cloud in the Security Sector The CCTV and alarm industry has relied on analogue or Integrated Services Digital Network (ISDN) communications to provide data connectivity
Regulatory Framework for Disaster Recovery Planning for the ICT Industry
Regulatory Framework for Disaster Recovery Planning for the ICT Industry Kingdom of Saudi Arabia Regulatory Framework for Disaster Recovery Planning for the ICT Industry Page 1 of 6 1. INTRODUCTION 1.1
Fire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
TELECOMMUNICATIONS TOWERS ON PRIVATE LAND
FACT SHEET TELEPHONE 0800 327 646 I WEBSITE WWW.FEDFARM.ORG.NZ TELECOMMUNICATIONS TOWERS ON PRIVATE LAND BACKGROUND The Rural Broadband Initiative envisages substantially improved broadband access for
Hosted Testing and Grading
Hosted Testing and Grading Technical White Paper July 2014 www.lexmark.com Lexmark and Lexmark with diamond design are trademarks of Lexmark International, Inc., registered in the United States and/or
Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal [email protected] Fax (631) 224-5458
OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal [email protected] Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for
A Quick Primer on Data Center Tier Classifications
A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute
BT Conferencing Business Continuity Management. Planning to stay in business
BT Conferencing Business Continuity Management Planning to stay in business Planning for the unexpected In today s connected world, businesses are increasingly dependent on their communications and networked
Part A OVERVIEW...1. 1. Introduction...1. 2. Applicability...2. 3. Legal Provision...2. Part B SOUND DATA MANAGEMENT AND MIS PRACTICES...
Part A OVERVIEW...1 1. Introduction...1 2. Applicability...2 3. Legal Provision...2 Part B SOUND DATA MANAGEMENT AND MIS PRACTICES...3 4. Guiding Principles...3 Part C IMPLEMENTATION...13 5. Implementation
Business Continuity Planning and Disaster Recovery Planning
4 Business Continuity Planning and Disaster Recovery Planning Basic Concepts 1. Business Continuity Management: Business Continuity means maintaining the uninterrupted availability of all key business
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Risk Management Philosophy and Approach
Risk Management Philosophy and Approach We identify and manage risks to reduce the uncertainty associated with executing our business strategies and maximising opportunities that may arise. Risks can take
Schedule 2e. Additional terms for Ethernet services
1. SERVICE DESCRIPTION The Interoute Ethernet Clear and Ethernet Flex Services offer Circuits carrying telecommunications traffic between Network Termination Points on the Interoute Ethernet Network and/
Huawei Managed Services Unified Platform (MS UP) v1.0
Huawei Managed Services Unified Platform (MS UP) v1.0 Representation of Solution Functionality/Capability Utilizing etom, ITIL and TL 9000, Huawei Managed Services has integrated these three global standards
ISO IEC 27002 2005 (17799 2005) INFORMATION SECURITY AUDIT TOOL
9.1 USE SECURITY AREAS TO PROTECT FACILITIES 1 GOAL Do you use physical methods to prevent unauthorized access to your organization s information and premises? 2 GOAL Do you use physical methods to prevent
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE NBN Co Limited Overview of the NBN Co Facilities Access Service April 2012 Copyright This document is subject to copyright and
REACH LTD. SUBMISSION IN RESPONSE TO IDA S PUBLIC CONSULTATION POLICY FRAMEWORK FOR IP TELEPHONY AND ELECTRONIC NUMBERING IN SINGAPORE
REACH LTD. SUBMISSION IN RESPONSE TO IDA S PUBLIC CONSULTATION POLICY FRAMEWORK FOR IP TELEPHONY AND ELECTRONIC NUMBERING IN SINGAPORE 21 October 2004 Contact Details: Mr. Dermot Keilthy Director, Regulatory
Service Children s Education
Service Children s Education Data Handling and Security Information Security Audit Issued January 2009 2009 - An Agency of the Ministry of Defence Information Security Audit 2 Information handling and
Compliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
IELTS General Training Reading Task Type 4 (Matching Information) (2) teacher s notes
IELTS General Training Reading Task Type 4 (Matching Information) (2) teacher s notes Description An activity to familiarise students with matching information in a text and how to approach this type of
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
Fire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
MPLS: Key Factors to Consider When Selecting Your MPLS Provider Whitepaper
MPLS: Key Factors to Consider When Selecting Your MPLS Provider Whitepaper 2006-20011 EarthLink Business Page 1 EXECUTIVE SUMMARY Multiprotocol Label Switching (MPLS), once the sole domain of major corporations
CATERING CONTRACTORS General Code of Safety Practice
Residential & Business Services Director s Office CATERING CONTRACTORS General Code of Safety Practice CONTENTS 1 Introduction 2 2 Commencement of Work 3 3 Vehicles 3 4 Temperature control 3 5 Food hygiene
INCIDENT RESPONSE MANAGEMENT PLAN DECEMBER 2015
INCIDENT RESPONSE MANAGEMENT PLAN DECEMBER 2015 DOCUMENT CONTROL Document Controller: Resilience Coordinator Date of last update: December 2015 Date of next update: December 2016 HPRM reference: HW2007-900/27/9.009
Exhibit to Data Center Services Service Component Provider Master Services Agreement
Exhibit to Data Center Services Service Component Provider Master Services Agreement DIR Contract No. DIR-DCS-SCP-MSA-002 Between The State of Texas, acting by and through the Texas Department of Information
WiMAX technology. An opportunity that can lead African Countries to the NET Economy. Annamaria Raviola SVP - Marketing and Business Development
WiMAX technology An opportunity that can lead African Countries to the NET Economy Annamaria Raviola SVP - Marketing and Business Development Agenda Telecommunications in Africa: the present picture Wi-MAX:
Corporate Profile. A TPG Telecom Company
Corporate Profile A TPG Telecom Company PIPE Networks Corporate Overview PIPE Networks is recognised as one of the market leaders in the telecommunications industry, proving we are capable of delivering
Co-location Arrangements for Interconnecting Canadian Carriers
COMPETITOR ACCESS TARI 2nd Revised Page 95 Cancels 1st Revised Page 95 Co-location Arrangements for Interconnecting Canadian Carriers 1. Service Description Co-location is an arrangement whereby Interconnecting
WHITEPAPER MPLS: Key Factors to Consider When Selecting Your MPLS Provider
WHITEPAPER MPLS: Key Factors to Consider When Selecting Your MPLS Provider INTRODUCTION Multiprotocol Label Switching (MPLS), once the sole domain of major corporations and telecom carriers, has gone mainstream
PAPER-6 PART-1 OF 5 CA A.RAFEQ, FCA
1 Chapter-4: Business Continuity Planning and Disaster Recovery Planning PAPER-6 PART-1 OF 5 CA A.RAFEQ, FCA Learning Objectives 2 To understand the concept of Business Continuity Management To understand
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
NHS 111 National Business Continuity Escalation Policy
NHS 111 National Business Continuity Escalation Policy 1 NHS England INFORMATION READER BOX Directorate Medical Operations Patients and Information Nursing Policy Commissioning Development Finance Human
Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment
Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment 3 Company Overview Confisio DataCenter was formed to help organisations tackle the ever increasing challenges
BT Assure DoS Mitigation UK
BT Assure DoS Mitigation UK Annex to the Internet Connect UK Schedule Contents A note on we and you... 2 1. Service Summary... 2 2. Service Standard Components... 2 3. Service Options... 2 4. Service Management
DISASTER RECOVERY AND BUSINESS CONTINUITY
DISASTER RECOVERY AND BUSINESS CONTINUITY ISO 9001/27001 PARTNER ONLY NODE4 LIMITED 03/01/2014 DISASTER RECOVERY PLAN This plan will be held at Node4 s premises located at Pride Park in Derby and also
Information Crib Sheet Internet Access Service Agreement
Information Crib Sheet Internet Access Service Agreement 1. Definitions and Interpretation This Service Agreement is to be read in conjunction with the Conditions for Communications Services (the Conditions
Security in Space: Intelsat Information Assurance
Security in Space: Intelsat Information Assurance 14/03/6997 Intelsat Information Assurance Intelsat maintains the highest standards of Information Assurance by assessing and building the Intelsat infrastructure,
THREATS AND VULNERABILITIES FOR C 4 I IN COMMERCIAL TELECOMMUNICATIONS: A PARADIGM FOR MITIGATION
THREATS AND VULNERABILITIES FOR C 4 I IN COMMERCIAL TELECOMMUNICATIONS: A PARADIGM FOR MITIGATION Joan Fowler and Robert C. Seate III Data Systems Analysts, Inc. 10400 Eaton Place, Suite 400 Fairfax, VA
University of Prince Edward Island. Emergency Management Plan
Emergency Management Plan March 2012 ON CAMPUS Emergency Dial Security Assistance Dial 566-0384 OFF CAMPUS SUPPORT AGENCIES Fire & Ambulance... 9-1-1 Charlottetown Fire Department... 566-5548 Fire Marshal...
Fire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
POSITION DESCRIPTION. Role Purpose. Key Challenges. Key Result Areas
POSITION DESCRIPTION Position Title Manager, Technical Services Support Position Number Reports to Manager Technology Services Functional Auth HRM Auth Region IT Services Centre Head Office Date Feb 2011
CHAPTER 8. Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13)
CHAPTER 8 Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13) Section Title Number 5-8-1 Title 5-8-2 Declaration of Purpose 5-8-3 Definitions 5-8-4 Administrative Rules 5-8-5 Supervised Fire
Emergency Telephone Systems
Standard Issued Date: 22 May 2014 Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the NSW Government and its
