Solar shading for low energy buildings
|
|
|
- Silas McKinney
- 10 years ago
- Views:
Transcription
1 Solar shading for low energy buildings FEBRUARY 2012 Edition 1 How shutters and blinds reduce the energy needs of buildings and improve their thermal and visual comfort
2 MEMBERS OF THE ES-SO TECHNICAL COMMITTEE Chairman : Hervé LAMY (SNFPSA) Ralf BAUR (ITRS) Richard BEUHORRY (SNFPSA) David BUSH (BBSA) Jean-Paul CLEMENT (SNFPSA) Alberto DANIELI (ASSITES) Yvon DEBIEZ (SNFPSA) Gonzague DUTOO (SNFPSA) Pascal NORDE (SNFPSA) Gabriele TRÖSCHER (ITRS) Copyright ES-SO, 2012 Request for permission to make copies of any part of this guidebook should be addressed to: ES-SO vzw Naessenslaan 9 B-1860 Meise, Belgium [email protected] Cover page credits: Somfy, Warema, Mermet, Ferrari Page 1
3 FOREWORD This book is about solar shading, its influence on the energy balance and energy consumption of a building. As buildings account for almost 40% of total primary energy use in Europe, pressure has grown to make them more energy-efficient. The savings potential is huge: it is not rare today to have buildings that consume more than 250 kwh/m²a, whereas state-of-the-art technology in modern buildings shows figures well below 100 kwh/m²a. Several countries are working on legislation limiting maximum energy use to 50 kwh/m²a by the year 2015 or shortly after that. At the same time, Passive and Active house technology is gaining market share and the European Parliament has said that it would like all new buildings to be near zero energy from 2019 onwards. Solar shading is a term we use to cover all the techniques to limit the entry of excessive solar energy, ranging from shade trees over fixed awnings to fully automated blinds and shutters. Outdoor weather conditions light and heat change constantly in the course of one day. That s why, in the context of this book, there is some emphasis on automated solar shading systems (blinds, awnings, shutters, etc) so that optimum effect can be obtained. Controlling the entry of solar heat and light will have a considerable effect on the energy needs of a building, as we will demonstrate. However, solar shading is but one element of the building s envelope, along with glazing, window frames, walls, roofs and floors. To expect automated solar shading to help reduce energy consumption, the selection of the best system must be made in the early design stage of the building process. Many factors must be taken into account, from the outdoor climate to the immediate environment, the building s orientation and the user s profile and many others. Building physics will show how each of these factors have their effect. Building simulation software may quantify these effects. As architects will be moving towards nearly zero-energy buildings, the increased layers of thermal insulation can easily provoke overheating in summer conditions. Dynamic shading will then become an essential element in the building s concept. Solar shading installations must be installed by professionals; experience shows that in the installation stage, mistakes must be prevented to secure the expected results. Sometimes, external shading systems are considered like the bricks and concrete of the building s skin: you just don t look after them. But systems with moving parts need to be taken care of. These and other aspects will be discussed in this book. We hope you ll find it of interest. Peter Winters President ES-SO, the European Solar-Shading Organization Page 2
4 Page 3 Solar shading for low energy buildings
5 CONTENTS I. INTRODUCTION... 5 II. BASIC PRINCIPLES... 6 II.1. Different types of radiation... 6 II.2. Solar radiation... 6 II.3. Influence of the position of the sun... 7 II.4. The long wave infrared... 8 II.5. How a material is affected by radiation... 9 III. THE THERMAL AND VISUAL CHARACTERISTICS OF BLINDS AND SHUTTERS III.1. Thermal transmittance (U value) III.2. Total solar energy transmittance gtot (solar factor) III.2.1. General III.2.2. Simplified calculation method: EN III.2.3. Detailed calculation method: EN III.3. Light transmittance τv III.3.1. General III.3.2. Simplified calculation method: EN III.3.3. Detailed calculation method: EN III.4. Comparison of the simplified and detailed calculations IV. HOW BLINDS AND SHUTTERS REDUCE THE ENERGY NEEDS OF A BUILDING IV.1. Textinergie tool IV.1.1. What is Textinergie? IV.1.2. Impact of the location IV.1.3. Impact of the orientation IV.2. ES-SO and REHVA guidebook IV.2.1. Stockholm IV.2.2. Madrid V. HOW BLINDS AND SHUTTERS IMPROVE THE VISUAL AND THERMAL COMFORT OF A BUILDING V.1. Impact of shutters on summer comfort V.2. Impact of solar shading on visual comfort Page 4
6 I. INTRODUCTION Solar shading is a key element for improving the energy efficiency and daylight management of existing buildings and optimising the low-energy designs of new buildings. This technology is still underutilised although it provides a major impact on the reduction of energy consumption of the built environment whilst improving the thermal and visual comfort of the occupants. Indeed, solar protection devices enable adjustment of the properties of windows and façades to the weather conditions and the need of the occupants. A proper management of these systems can then maximise the solar heat gains in winter hence reducing the heating loads and minimise these heat gains in summer hence reducing the cooling loads, while at the same time providing good visual comfort to the occupants. In order to make the right choice in term of products and façade management when designing a new building or preparing works to an existing one, it is necessary to take into consideration the characteristics of solar protection devices. Indeed, these products impact the insulation level of the façade, its solar transmittance and its visual transmittance. As a consequence, it is necessary to find the best balance between all these characteristics depending on the building properties, its location and orientation. This technical guidebook is intended to give the basic knowledge to understand how solar shading characteristics are evaluated and what are the physical properties involved in the transmission of the solar radiation. It is mainly based on calculation methods provided by European standards. Examples of simulations carried out in Europe showing the impact of solar shading on the energy loads of buildings are also presented. Although it is mainly intended to be used by solar shading manufacturers and installers, this guidebook will also be useful to building designers and energy engineers. Page 5
7 II. BASIC PRINCIPLES This chapter shows some basic elements of the different types of radiation that have to be considered in the performance of solar protection devices and the position of the sun. It also shows how a material behaves when it is affected by such radiation. II.1. Different types of radiation People are exposed to a large variety of radiation that could be natural or artificial. Radiation has differing wavelengths (see Figure 1). FIGURE 1 CLASSIFICATION OF VARIOUS ELECTROMAGNETIC RADIATION DEPENDING OF THEIR WAVELENGTH A solar protection device is concerned with these two types of radiation: The solar radiation with wavelength between 280 nm to 2500 nm that is subdivided into three parts: UV, visible and short wave infrared. This radiation is emitted by the sun (see II.2). The long wave infrared with wavelength between 2500 nm to nm that is due to the temperature level of a material (e.g. a heater or any warm surface). This radiation is in the infrared which is in the invisible range (see II.4). II.2. Solar radiation The sun produces an enormous amount of energy (66 million W/m²) that is transmitted to the Earth through radiation. Only a fraction of this energy reaches the atmosphere (around 1300 W/m²). Around 15% of this radiation is then absorbed by the atmosphere and emitted in all directions in the form of diffuse radiation. Around 6% is reflected back into the space. The remaining part (79%) is directly transmitted to the ground through the atmosphere. As a consequence, the energy of solar radiation hitting the ground is much lower than at the limit of the atmosphere. It is generally considered that the energy reaching the ground when there is a clear blue sky is around 1000 W/m². Hence, when considering a solar protection device, it is necessary to divide the global incident radiation into three parts (see Figure 2). Page 6
8 Direct radiation, which is the solar radiation neither absorbed nor reflected by the atmosphere, Diffuse radiation, which is the part of the solar radiation absorbed by the atmosphere and emitted in all directions, Reflected radiation which corresponds to the reflection of the direct and diffuse radiation on the ground. FIGURE 2 INCIDENT PARTS OF THE SOLAR RADIATION This radiation is grouped into three main sections which form the Solar Spectrum: Ultraviolet (UV): from 250 nm to 380 nm, these rays are invisible to the human eye and may be dangerous in case of overexposure. They age materials and damage surfaces and colours. Visible: from 380 nm (violet) to 780 nm (red), these rays are detected by the human retina and enable the sight of shapes, relief and colours. Short wave Infrared (IR): from 780 nm to 2500 nm, these rays are invisible but are felt as heat. FIGURE 3 SPECTRAL IRRADIANCE AT THE SEA LEVEL FOR THE SOLAR SPECTRUM The power of a radiation is represented by its irradiance (in W/m²). For a given wavelength, it is called spectral irradiance (in W/m².nm). Figure 3 gives the distribution of the spectral irradiance of the solar spectrum at the sea level. II.3. Influence of the position of the sun In addition, the solar irradiance depends on the position of the sun in the sky (altitude and azimuth). This position varies throughout the year and during the day (see Figure 4). It also depends on the latitude. Figure 5 shows the solar irradiance on vertical surfaces in summer (21 June) and in winter (21December). As these graphs have been calculated with a cloudless sky and without consideration of the surrounding buildings, the level indicated can be considered the maximum solar irradiance a vertical surface can receive. FIGURE 4 POSITION OF THE SUN IN THE SKY Page 7
9 These figures are for a latitude of 50 N. At other latitudes, these figures will be different. However, in Europe, the general pattern is the same North Facade 21 jun 21 dec East Facade 21 jun 21 dec W/m² W/m² South Facade 21 jun 21 dec West Facade 21 jun 21 dec W/m² W/m² FIGURE 5 IRRADIANCE FOR NORTH, EAST, WEST AND SOUTH VERTICAL SURFACE AT 50 N OF LATITUDE (SOURCE ES-SO & REHVA GUIDEBOOK) It can be seen that: North exposed façades, receive the lowest level of solar irradiance. Only a small amount of solar radiation hits the vertical surface at the beginning of the morning and late in the evening in summer. East and west orientated façades show a symmetric pattern: the east surface will receive the largest part of the radiation before noon, whereas the west surface receives it in the afternoon. It can be seen that the irradiance is at a maximum when it is composed of the direct part of the radiation. After noon for the east façade and before noon for the west façade, the radiation is mainly composed of the diffuse part coming from the sky. That is the reason why it is lower. South exposed façades receive solar radiation almost throughout the day. That is why it is essential to maximize the glazed surfaces on this orientation to optimize the solar gain that could enter the building in winter and to protect the façades in summer to avoid overheating. Because of the low altitude of the sun, it can be seen that the irradiance is higher in winter than in summer. It is here also important to ensure glare protection of the building users. II.4. The long wave infrared All materials continuously emit radiation in the form of energy in all directions. While the solar spectrum comprises short wavelength radiation emitted at various temperatures, the thermal radiation is mainly composed of long wavelength infrared radiation emitted at low temperature. In practice, this means that a material which is irradiated by solar radiation will warm up and emit long wavelength radiation to the surrounding area. This radiation will then warm up the materials in the vicinity which will once again emit radiation, and so on. Page 8
10 A heater is a perfect example of a material which emits long wave infrared radiation. Any material warmed up by solar radiation becomes a kind of a heater. The capacity of a material to emit this type of radiation is given by its emissivity (see II.5). As long as a material has no openings, it is opaque to the long wave infrared. Therefore walls and glazing do not allow the transmission of this type of radiation. Therefore, heat is kept in the room. This is known as the greenhouse effect. II.5. How a material is affected by radiation When it irradiates a surface (glazing, fabric or slat for example), incident radiation splits into three parts (see Figure 6): A part which is transmitted through the material. It is characterised by the transmittance τ, the ratio of the transmitted flux to the incident flux A part which is reflected by the material. It is characterised by the reflectance ρ, the ratio of the reflected flux to the incident flux A part which is absorbed by the material which is characterised by the absorptance α so that τ + ρ + α = 100% FIGURE 6 BEHAVIOUR OF A RADIATION IN CONTACT WITH A MATERIAL For a given incident radiation E, the transmitted radiation is equal to τ x E, the absorbed radiation to α x E and the reflected radiation to ρ x E. Transmittance, reflectance and absorptance are characteristics specific to the material. With a fabric for example, these values will mainly depend on the type of material, on the openness of the fabric and the colour. It also depends on the wavelength of the solar radiation. It is possible to measure these properties for specific wavelength (for example for 250, 260, 270, etc.). These values are called spectral data. However, they are often defined for: The complete solar spectrum, i.e. from 250 nm to 2500 nm (see Figure 3). These properties are identified by the subscript e (for energetic or solar ) : τe, ρe and αe, The visible part of the spectrum, i.e. from 380 nm to 780 nm. In this case these characteristics are used to calculate the visual properties of the product (mainly the light transmittance) and they are identified by the subscript v (for visible ) : τv, ρv and αv, The long wave infrared radiation, i.e. from 2500 nm to nm. These values are necessary for the detailed calculation of some of the thermal characteristics of the products. They are identified by the subscript IR : τir, ρir and the emissivity ε (in this case the emissivity is equal to αir). In this case, they are called integrated data. Page 9
11 NOTE In all cases, the relationship between transmittance, absorptance and reflectance is governed by the following generic formula: 1 = τe + ρe + αe for the complete solar spectrum 1 = τv + ρv + αv for the visible part of the solar spectrum 1 = τir + ρir + ε for the long wavelength infrared radiation In practice, only two values are needed to characterise a material (e.g. τe and ρe or τir and ε). In addition, it should be noted that a radiation is transmitted in two ways. The transmittance τ comprises: Direct transmittance, stated as τn-n, for which the radiation is not affected by the material, and Diffuse transmittance, noted τn-dif, which corresponds to the diffusion in all directions of the radiation by the material (see Figure 7). FIGURE 7 DIRECT AND DIFFUSE VISUAL TRANSMITTANCE The sum of the direct and diffuse transmitted part is equal to the total value: e.g. τv,n-n + τv,n-dif = τv Finally, reflectance and absorptance may also depend on the product sides, for example in case of coating or colour difference. Two values may then be necessary: ρ and ρ for example corresponding to the two faces of a fabric. Figure 8 illustrates the characteristics of the shutter or blind material (fabric, slat or lath) required for a detailed calculation of the thermal and visual properties of the product. This figure does not consider the characteristics of the glazing which are also needed. This part is detailed in III.2 and III.3. FIGURE 8 ILLUSTRATION OF THE MATERIAL CHARACTERISTICS These characteristics are measured in accordance with the European Standard EN Blinds and shutters - Thermal and visual comfort - Test and calculation methods. Page 10
12 III. Solar shading for low energy buildings THE THERMAL AND VISUAL CHARACTERISTICS OF BLINDS AND SHUTTERS The previous chapter presented the properties of the solar radiation and the way this radiation is modified by the material of the shutter or blind. This chapter will identify how the visual and thermal characteristics of solar shading products are determined. III.1. Thermal transmittance (U value) The U value (designated by Uw) represents the thermal losses going through a window. For a single window (with a blind or a shutter in the retracted position), this coefficient depends on the U value of the glazing (Ug) and the frame (Uf) and the link between the glazing and the frame (ψg). It is calculated according to the European Standard EN ISO with the following formula: U w = A gu g + A f U f + I g ψ g A g + A f The lower the Uw value the better the insulation of the window. A U value is given in W/m².K. FIGURE 9 ILLUSTRATION OF THE UW VALUE A solar protection device extended in front of a window introduces an additional air space characterised by an additional thermal resistance designated by R (in m².k/w). The R value is calculated according to the European Standard EN and depends mainly on the air permeability of the device and the thermal resistance of the curtain (designated by Rsh). According to EN 13125, the air permeability of a shutter or a blind is calculated considering the peripheral gaps of the curtain (see Figure 10). FIGURE 10 CALCULATION OF ETOT ACCORDING TO EN For external and internal blinds, EN also considers openings that may be present in the curtain (the openness factor of a fabric for example). The air permeability criteria is then expressed by the following formula: Pe = etot + 10p where etot is calculated according to Figure 10 and p is the ratio between the total opening area and the total area of the curtain. Page 11
13 The following tables give the formulae determined in EN for the calculation of the R value for shutters, external blinds and internal and mid-pane blinds. TABLE 1 CALCULATION OF R OF SHUTTERS Very high air permeability (etot > 35 mm) R = 0,08 m².k/w High air permeability (15 mm < etot 35 mm) R = 0,25.Rsh + 0,09 Average air permeability (8 mm < etot 15 mm) R = 0,55.Rsh + 0,11 Low air permeability (etot 8 mm) R = 0,8.Rsh + 0,14 Very low air permeability (etot 3 mm and e1+ e3=0 or e2+ e3=0 ) R = 0,95.Rsh + 0,17 TABLE 2 - CALCULATION OF R OF EXTERNAL BLINDS High and very high air permeability (Pe 35 mm) Average air permeability (8 mm Pe < 35 mm) Low air permeability (Pe < 8 mm) R = 0,08 m².k/w R = 0,11 m².k/w R = 0,14 m².k/w TABLE 3 - CALCULATION OF R OF INTERNAL AND MID-PANE BLINDS High and very high air permeability (Pe 80 mm) Average air permeability (20 mm Pe < 80 mm) Low air permeability (Pe < 20 mm) R = 0,08 m².k/w R = 0,11 m².k/w R = 0,14 m².k/w The effect of the additional thermal resistance of a shutter or a blind on the window is given by the following formula: 1 U ws = 1 + R U w This formula is defined in the standard EN ISO For a given window, it can be used to evaluate the improvement of the U value of a window provided by a blind or the shutter in the extended position. Table 4 gives examples of calculations for three different R values and three different types of windows. The R values considered are: 0,08 m².k/w, for example a very permeable external blind, 0,15 m².k/w, for example a standard roller shutter in aluminum, 0,25 m².k/w, for example a air tight roller shutter. Page 12
14 TABLE 4 EXAMPLE OF UWS CALCULATION Window with single glazing Uw = 4,90 Window with double glazing Uw = 1,8 Window with double glazing Uw = 1,2 R (m².k/w) R (m².k/w) R (m².k/w) 0,08 0,15 0,25 0,08 0,15 0,25 0,08 0,15 0,25 Uws (W/m².K) 3,52 2,82 2,20 1,57 1,42 1,24 1,09 1,02 0,92 Improvement factor 28,2% 42,4% 55,1% 12,6% 21,3% 31,0% 8,8% 15,2% 23,0 % It can be seen from these examples that in all cases, the shutter or the blind decreases the U value of the window (Uws < Uw) and therefore reduces the heat losses when the outdoor temperature is cold. Of course the effect of the shutter or blind is higher when the window has a low performance: it halves the U value in case of a single glazing. However, it still has a good effect for a high performance window: an airtight shutter will still reduce the U value of a double glazing window with a Uw value of 1,2 W/m².K (which means a window using a glazing with a Ug = 1,0 W/m².K) by 23%. III.2. Total solar energy transmittance gtot (solar factor) III.2.1. General The total solar energy transmittance, also called solar factor, represents the part of the incident flux which is transmitted into a room. g is the solar factor of the glazing alone. gtot is the solar factor of the combination of a glazing and a solar protection device. The value of g or gtot is between 0 and 1: 0 means no radiation is transmitted into the room and 1 means all radiation is transmitted. The g value of a glazing alone is determined by the calculation method given in the EN 410. There are two methods for the calculation of the gtot of a solar protection device associated to a glazing: Either a simplified method given by EN , Or a detailed method given in EN Both methods use the properties of the glazing and of the material constituting the solar protection device fabric, laths or slats as shown in II.5. III.2.2. Simplified calculation method: EN The standard EN gives a simplified method to evaluate the gtot value. This calculation takes into consideration the U value and the g value of the glazing and the energetic transmittance and reflectance of the solar protection device. The standard specifies that the deviation of the simplified calculation compared to the exact values lie within the range between +0,10 and -0,02. It is therefore strongly recommended that the detailed calculation method (see III.2.3) is used to determine the benefits of solar gain and thermal comfort. Page 13
15 The advantage of this standard is that calculations can be made easily without a help of a calculation tool. Indeed the formulae to be used are the following: For an external blind or shutter: g tot = τ e g + α e G G 2 + τ e (1 g) G G 1 With G1 = 5 W/m².K ; G2 = 10 W/m².K and G = U g G 1 G 2 For an internal blind: With G2 = 30 W/m².K and G = U g G 2 g tot = g 1 gρ e α e G G 2 For a mid-pane blind: With G3 = 3 W/m².K and G = U g G 3 In all these equations: g tot = τ e g + g(α e + (1 g)ρ e ) G G 3 τe is the solar transmittance of the blind or shutter ρe is the solar reflectance of the blind or shutter with 1 = τe + ρe + αe (see II.5) αe is the solar absorptance of the blind or shutter g is the solar factor of the glazing Ug is the thermal transmittance of the glazing G1, G2 and G3 are fixed values defined by the standard It should be noted that these formulae can be applied only if the solar transmittance and reflectance of the solar protection devices are within the following ranges: 0 τe 0,5 and 0,1 ρe 0,8 and with the additional requirement that the solar factor g of the glazing is between 0,15 and 0,85. In all other cases, calculation according to EN should be carried out. Page 14
16 III.2.3. Detailed calculation method: EN As this method tries to represent the real physical behaviour of the combination of a blind and a glazing when it is struck by a radiation, this method of calculation is far more complex than the formulae given by EN It requires the use of a specific calculation tool. The principle of the calculation is to consider the blind, the glazing and the gas space as separate layers in defined positions (see Figure 11), each layer having its own properties (transmittance, reflectance, emissivity, etc.). The external conditions (temperature, solar irradiance, ventilation,...) are also considered. The goal of the calculation is to evaluate the interaction of each layer with these conditions. FIGURE 11 EXAMPLE OF LAYERS IN CASE OF AN EXTERNAL BLIND ASSOCIATED TO A DOUBLE GLAZING Therefore, this calculation consists of three parts: The solar radiation transfer This part of the gtot is quantifying the part of the incident solar radiation which is transmitted into the room through multiple transmission and reflection of both faces of each layer of the system. The temperature of the system has no impact in this calculation. Figure 12 gives an example of the calculation that has to be carried for a system made of an external blind and a double glazing. In this example, the calculation leads to solve the following matrix of flux: E1 = Φ E2 = ρ1e3 + τ 1E4 E3 = ρ'ee2 + τee1 E4 = ρ2e5 + τ'2e6 E5 = ρ'1e4 + τ1e3 E6 = 0 Page 15
17 FIGURE 12 ILLUSTRATION OF THE SOLAR DIRECT TRANSMITTANCE FOR AN EXTERNAL BLIND AND A DOUBLE GLAZING This transfer is characterised by the direct solar transmittance τe of the system blind and glazing. It relates to the complete solar spectrum. The heat transfer This type of transfer considers the impact of the external and internal temperature in conjunction with the effect of the solar irradiance (that will increase the temperature of each material by absorption). This transfer is subdivided into two parts (see Figure 13): Transfer by thermal radiation This transfer is due to the emission of long wave infrared radiation (see II.4) by each layer being warmed up by the external temperature and the solar radiation. The heat is transmitted from one layer to the next one through this radiation. This transfer is characterised by the thermal radiation factor gth. Conductive and convective heat transfer The conductive heat transfer is due to direct heat circulation within the material of the layer and the gas space in-between by a direct molecular interaction. The convective heat transfer is due to heat displacement from the material of the layer to the gas space (e.g. the air space of a double glazing). This transfer is characterised by the convection factor gc. Page 16
18 FIGURE 13 ILLUSTRATION OF THE HEAT TRANSFER FOR AN EXTERNAL BLIND AND A DOUBLE GLAZING The presence of a stack effect in case of an internal blind This effect is due to the air displacement inside the air space created between the glazing and the internal blind. It is due to the heating of the airspace by the glazing which generates an upward heat flow between the glazing and the blind (see Figure 14). This effect is characterised by the ventilation factor gv. Page 17 FIGURE 14 ILLUSTRATION OF THE STACK EFFECT IN CASE OF AN INTERNAL BLIND The gtot value is then given by the addition of the solar direct transmittance τe, the thermal radiation factor gth, convection factor gc and the ventilation factor gv: (1) gv = 0 in the case of an external blind gtot = τe + gth + gc + gv (1) Therefore EN gives a good description of the solar factor. However it requires the consideration of different physical phenomena that have to be considered simultaneously. The use of a specific calculation tool is therefore necessary.
19 In this case the protection device is retracted In this case the external protection device is extended FIGURE 15 ILLUSTRATION OF GTOT In this case the internal protection device is extended III.3. Light transmittance τv III.3.1. General Light transmittance τv represents the part of daylight which is transmitted into a room. Like the solar factor, it is necessary to distinguish the visual transmittance of a glazing alone and of a glazing used with a solar protection device. Unfortunately, according to the European standards, the notation used is the same (τv in both cases). For clarification, the notation τv,tot is used in this guidebook to identify the case of a solar protection device used with a glazing. The value of τv is between 0 and 1: 0 means no light is transmitted into the room and 1 means all visible radiation is transmitted. The reference τv calculation standards are the same than for the solar factor: EN 410 for a glazing alone and two possibilities for a solar protection device associated to a glazing: Either a simplified method given by EN , Or a detailed method given in EN III.3.2. Simplified calculation method: EN The conditions of use of this standard are the same than for the calculation of the solar factor (see III.2.2). According to EN , the formulae to be used for the calculation of τv,tot are: For an external blind or shutter: τ v,tot = τ vτ v,blind 1 ρ v ρ v,blind Page 18
20 For an internal blind or shutter: τ v,tot = τ vτ v,blind 1 ρ v ρ v,blind Where: τv is the visual transmittance of the glazing τv,blind is the visual transmittance of the blind or shutter ρv is the visual reflectance of the side of the glazing facing the incident radiation ρ'v is the visual reflectance of the side of the glazing opposite to the incident radiation ρv,blind is the visual reflectance of the side of the blind or shutter facing the incident radiation ρ'v,blind is the visual reflectance of the side of the blind or shutter opposite to the incident radiation III.3.3. Detailed calculation method: EN In the visual part of the spectrum, no heat transfer or ventilation factor has to be considered. Therefore the calculation principle of the solar radiation transfer (see III.2.3) applies for radiation between 380 nm and 780 nm instead of the complete solar spectrum. This calculation method considers the part of the radiation which is transmitted without any deviation from the blind or the shutter, i.e. the direct visual transmittance τv,n-n, and the part of the radiation which is diffused in all directions after reflection by the blind or shutter, i.e. the diffuse visual transmittance τv,n-dif (see Figure 16). The total visual transmittance is then made of the two parts: τv,tot = τv,n-n + τv,n-dif FIGURE 16 ILLUSTRATION OF THE VISUAL TRANSMITTANCE OF AN INTERNAL BLIND Page 19
21 III.4. Comparison of the simplified and detailed calculations The simplified and detailed calculation methods can both be used to calculate the solar factor gtot and the visual transmittance τv,tot. For the same combination of glazing and blind, a comparison can be made of the different colours of the same fabric. Three configurations of colourways are shown in Table 5. TABLE 5 PROPERTIES OF THE FABRIC Colour of the fabric White pearl White grey Grey Solar transmittance τe 0,13 0,09 0,05 Solar reflectance ρe (1) 0,53 0,44 0,21 Visual transmittance τv 0,11 0,07 0,03 Diffuse visual transmittance τv,n-dif 0,08 0,04 0,01 Visual reflectance ρv (1) 0,58 0,47 0,18 Long wave IR transmittance τir (2) 0,03 0,03 0,03 Emissivity ε (1) 0,89 0,89 0,89 (1) The properties of both sides of the blind are identical. Therefore : ρe = ρ'e ; ρv = ρ'v and ε = ε' (2) Equal to the openness coefficient of the fabric In EN 14501, typical glazing that are used as benchmarks have been defined to enable comparisons to be made. The standard glazing C according to the standard (double glazing , with low emissivity coating in position 3 (outer surface of the inner pane), space filled with argon) is considered below (see Table 6). TABLE 6 PROPERTIES OF THE GLAZING External pane Internal pane Solar transmittance τe 0,85 0,58 Solar reflectance on the side of the 0,08 0,30 incident radiation ρe Solar reflectance on the side 0,08 0,24 opposite to the incident radiation ρ'e Visual transmittance τv 0,90 0,82 Visual reflectance on the side of the 0,08 0,08 incident radiation ρv Visual reflectance on the side 0,08 0,04 opposite to the incident radiation ρ'v Long wave IR transmittance τir 0,00 0,00 Emissivity on the side of the incident 0,89 0,04 radiation ε Emissivity on the side opposite to the incident radiation ε' 0,89 0,89 Page 20
22 The results for an external blind are shown in Table 7. TABLE 7 CALCULATION OF GTOT AND τv,tot FOR AN EXTERNAL BLIND Method of calculation Simplified Detailed (1) gtot τv,tot gtot τe gth + gc τv,tot τv,n-diff White Pearl 0,12 0,09 0,11 0,08 0,03 0,09 0,06 White grey 0,10 0,06 0,09 0,05 0,04 0,06 0,03 Grey 0,10 0,02 0,08 0,03 0,05 0,02 0,01 (1) calculations carried out with the software Win-Shelter developed by the Italian National agency for new technologies, Energy and sustainable economic development and available at the following address : The results for an internal blind are shown in Table 8. TABLE 8 CALCULATION OF GTOT AND τv,tot FOR AN INTERNAL BLIND Method of calculation Simplified Detailed (2) gtot τv,tot gtot τe gth + gc gv τv,tot τv,n-diff White Pearl 0,40 0,09 0,38 0,06 0,13 0,19 0,09 0,06 White grey 0,43 0,06 0,41 0,04 0,16 0,21 0,06 0,03 Grey 0,50 0,02 0,49 0,015 0,225 0,25 0,02 0,01 (2) calculations carried out with the software Physalis developed by BBS Slama (12, rue Colbert BP Clermont-Ferrand Cedex 1France ; +33 (0) ; [email protected]) In all cases, for the gtot determination, the detailed calculation method gives better results than the simplified one. It should be noticed on these examples that the difference in the results obtained is higher for dark fabrics when the blind is external and for light coloured fabrics when the blind is internal. The greatest benefit of the detailed calculation method is to differentiate the part of the flux which is transmitted as radiation or as heat. However, these examples show that the simplified method gives the same results for visual transmittance. This could allow easy and accurate calculation using this method. Even if the results are not shown in these tables (as not considered in the standard EN ), it can be seen that a calculation of the diffuse visual transmittance is also possible with the simplified calculation method. Page 21
23 Shade Specifier Database The British Blind & Shutter Association (BBSA), in conjunction with partners in the European Solar Shading Organisation (ES-SO), have developed a database of solar shading materials. This database includes independently validated energy performance data of blind and shutter fabrics and materials to European standards. The database calculates the energy performance of blind and shutter products when used in combination with reference glazing defined in the European Standards EN and EN All calculations are performed in accordance with the relevant European standards and procedures that have been covered in Chapter III. The benefits of solar shading have been known for centuries. However, comparison of specific and independently proven performance characteristics of solar shading materials has not been possible, until now. Shade Specifier allows the specifier and building owner to make an informed choice. This process used by the Shade Specifier database is identical to that used by the glazing industry and is a robust and effective way of ensuring the integrity of the database. Outputs include: Total solar energy transmittance, gtot Visible transmittance, Tvis Thermal transmittance, U-value. Page 22
24 IV. Solar shading for low energy buildings HOW BLINDS AND SHUTTERS REDUCE THE ENERGY NEEDS OF A BUILDING Previous chapters show the characteristics of products and what could be the impact of the solar shading when used in conjunction with a window or glazing system. This chapter presents the impact of solar shading on the energy demand of a building. It refers to existing tools or studies. IV.1. Textinergie tool IV.1.1. What is Textinergie? Textinergie is a simple tool which quantifies potential energy savings in office buildings by using fabric solar protection devices. It has been developed by the French association of blinds and shutters manufacturers and installers (SNFPSA). It is accessible at the following address: Textinergie compares the energy needs within a room before and after being fitted with solar protection devices. The user selects: The climatic zone, The facade orientation, The glazed surface of the room, The type of double glazing (B, C or D as defined in EN 14501), The position of the blind (internal or external), The type of fabric, The fabric colour. Once the configuration has been defined, Textinergie gives two different levels of results: Simplified results: percentage of energy saving associated with air-conditioning and other installations (air-conditioning + heating + artificial lighting), Detailed results: calculated temperature ( C); needs (kwh) and percentage of energy saving for each unit (air-conditioning, heating and lighting); daylight (lux). The results are given for a glazing with or without blinds. Calculations have been carried out using a dynamic simulation software for an entire year with a time interval of five minutes. These simulations have been carried out and their results incorporated into a database. The user selections draw directly from this database. It enables an estimate of the impact of various parameters and helping the user in the choice of the optimal technical solution. IV.1.2. Impact of the location Figure 17 below shows the energy needs for heating, air-conditioning and lighting for a 20 m² office space in various European cities. The office space is equipped with clear double glazing (glazing C according to EN 14501) and is south facing. The glazed surface represents 80% of the façade. The blind is installed externally and its colour is dark neutral. Page 23
25 3500 Energy needs (kwh) ,0 % - 24,6 % - 32,4 % - 27,5 % - 62,0 % - 75,2 % Artificial lighting Air-conditioning Heating Without blinds With blinds Without blinds With blinds Without blinds With blinds Without blinds With blinds Without blinds With blinds Without blinds With blinds Stockholm Berlin London Paris Madrid Rome FIGURE 17 ENERGY NEEDS FROM TEXTINERGIE FOR VARIOUS EUROPEAN CITIES The use of an external blind consistently leads to major energy savings in all cases. It can be seen that heating needs are higher when the blind is installed. This is due to a lack of free solar energy entering into the room when the blind is extended. Indeed, the principle of operation of the blind is based on the visual comfort of the occupant: the blind rolls down when the natural light on a sensor placed on a desk reaches 500 lux in summer and 900 lux in winter. Therefore, the shading may be extended during sunny days in winter thereby limiting the free heating of the room. The principle of operation also assumes that artificial lighting is only activated when the solar protection device is fully retracted and the daylight level is insufficient. Therefore, the presence of the blind does not have any impact on the artificial light needs. However, as the air-conditioning energy needs are significant, the total results are still very positive and lead to major energy savings. IV.1.3. Impact of the orientation Figure 18 below presents the impact of the office orientation for three European countries: Stockholm, Paris and Rome. As expected, results are optimum for the east, west and south exposed façades. However, the orientation for which the energy saving rate is maximised varies depending on the city: it is the east façade for Stockholm (-28,1%), the west façade for Paris (-31%) and the south orientation for Rome (- 75,2%). Although, results are lower, the use of blinds on the north-west exposed façade still results in energy savings for the three cities. Page 24
26 FIGURE 18 ENERGY NEEDS FROM TEXTINERGIE FOR VARIOUS ORIENTATION IN THREE EUROPEAN CITIES IV.2. ES-SO and REHVA guidebook In 2010, ES-SO and REHVA (Federation of European Heating, Ventilation and Air-conditioning Associations) have jointly published a guidebook on solar shading 1. This guidebook contains reference to energy demand calculations carried out on a model office in three European cities (only two are presented here). The software EnergyPlus has been used for the calculations. The details of the parameters used for the calculations are available in the ES-SO & REHVA guidebook. A summary of the results of these calculations is given in the next clauses. IV.2.1. Stockholm Figure 19 shows the annual energy demand for different orientations for the model office in Stockholm. 1 Solar Shading, how to integrate solar shading in sustainable buildings Page 25
27 Clear double glazing kwh/m²a north east south west kwh/m²a north east south west 200 Without blinds 200 With external blinds Low emissivity double glazing kwh/m²a north east south west kwh/m²a north east south west 200 Without blinds 200 With external blinds Solar control glazing kwh/m²a north east south west kwh/m²a north east south west Without blinds With external blinds The red line represents the heat supplied to the room by the heating system, the blue line the heat removed from the room by the HVAC system. The yellow line represents the electric energy needed for lighting. The green line represents the total primary energy for heating cooling and lighting (see the ES-SO / REHVA guidebook for the detailed calculation method) FIGURE 19 ANNUAL ENERGY BALANCE FOR THE MODEL OFFICE IN STOCKHOLM (SOURCE ES-SO & REHVA GUIDEBOOK) The energy demand is clearly dominated by heating. On south orientations the heating energy is significantly lower for all glazing types than for north orientations, due to passive solar heating in winter. In summer, there is considerable solar heat gain on south orientations, resulting in a significant energy demand for cooling. This effect is clearly stronger for glazing with higher g-values. The situation becomes markedly different when external solar shading is installed, as shown in the right column of Figure 19. The annual energy demand for cooling is significantly reduced by over 70% on south orientations. Solar shading results in slight increases in the energy demand for heating and lighting. This is due to the fact that the shading intercepts solar energy that would have contributed to day-lighting and passive solar heating. It can be seen that the primary energy demand in absolute terms is the lowest for the low emissivity glazing combined with solar shading. Page 26
28 Figure 20 shows the cooling load as a function of window orientation for three different glazing types. Solid lines represent the situation without shading, the dotted lines represent cooling loads with solar shading. Red represents double glazing, orange low-e glazing and blue solar control glazing W/m² north east south west FIGURE 20 - COOLING LOAD AS A FUNCTION OF THE FAÇADE ORIENTATION (SOURCE ES-SO & REHVA GUIDEBOOK) IV.2.2. Madrid Figure 21shows the energy demand as a function of the orientation of the office in Madrid. In this case, the energy demand is clearly dominated by cooling. On south orientations, heating is almost negligible, due to passive solar heating in winter. In summer, there is a considerable solar heat gain on south orientations, resulting in a significant energy demand for cooling. Solar shading substantially reduces the primary energy demand for other than-north orientations. In this case the lowest primary energy requirement is attained with a combination of solar control glazing and exterior solar shading. Combining solar control glazing with solar shading is a somewhat unusual choice. Normally, solar control glazing is viewed as an alternative to exterior shading. In this case, the primary energy demand for an office fitted with solar control glazing and solar shading is about 30% lower than for the same office fitted with solar control glazing only. Page 27
29 Clear double glazing kwh/m²a north east south west kwh/m²a north east south west 200 Without blinds 200 With external blinds Low emissivity double glazing kwh/m²a north east south west kwh/m²a north east south west 200 Without blinds 200 With external blinds Solar control glazing kwh/m²a north east south west kwh/m²a north east south west Without blinds With external blinds The red line represents the heat supplied to the room by the heating system, the blue line the heat removed from the room by the HVAC system. The yellow line represents the electric energy needed for lighting. The green line represents the total primary energy for heating cooling and lighting (see the ES-SO / REHVA guidebook for the detailed calculation method) FIGURE 21 ANNUAL ENERGY BALANCE FOR THE MODEL OFFICE IN MADRID (SOURCE ES-SO & REHVA GUIDEBOOK) Page 28
30 V. HOW BLINDS AND SHUTTERS IMPROVE THE VISUAL AND THERMAL COMFORT OF A BUILDING The previous chapter presented the impact of solar shading on the energy demand of cooled office premises. But these products also play a major role in the internal thermal and visual comfort of the occupants. This chapter presents results of studies concerning this important consideration in building design. V.1. Impact of shutters on summer comfort In 2010, a study has been carried by the Engineering Office TBC for the French Association of Blinds and Shutters Manufacturers (SNFPSA). According to the results of thermal simulations carried out with the calculation software Comfie+Pleïade 2 in a typical dwelling for three locations in France, the use of roller shutters in warm conditions reduces the maximum temperature by up to 6 C. Figure 22 shows the maximum temperature achieved in the dwelling for different operating modes of roller shutters: A clock mode: roller shutters are extended from 8h to 18h, An external temperature mode: roller shutters are 50% extended if the outdoor temperature is over 23 C and completely extended if the outdoor temperature is over 26 C, An light level mode: roller shutters are fully extended if the incident luminance is above Lux T ( C) Paris La Rochelle Nice Shutters opened all day Clock mode External temperature mode Illuminance mode FIGURE 22 MAXIMUM TEMPERATURE FOR DIFFERENT OPERATING MODES OF ROLLER SHUTTERS (SOURCE TBC AND SNFPSA) 2 Pleiades + Comfie used the calculation system Comfie developed by the Energetic Centre of the Engineering School Mines ParisTech. Page 29
31 Detailed results are shown in the Table 9 below. TABLE 9 MAXIMUM TEMPERATURE FOR DIFFERENT OPERATING MODES OF ROLLER SHUTTERS Paris La Rochelle Nice Shutters opened all day 34,46 C 36,26 C 38,89 C Clock mode -3,41 C -3,04 C -5,13 C External temperature mode -3,31 C -3,10 C -1,78 C Light level mode -5,05 C -3,23 C -6,37 C The use of roller shutters during warm days reduces the maximum temperature in all cases. The light level operating mode gives the best compromise as it is the most efficient in terms of limitation of overheating but also as it allows the occupants to benefit from daylight when the incident luminance is lower than Lux or when the façade is not exposed. The period of discomfort is defined as the time where the internal temperature is either under 16 C or over 27 C. It is then possible to define a rate of discomfort defined as the ratio of the number of hours where the house is occupied and the temperature is either under 16 C or over 27 C and the total number of hours of occupancy. Table 10 presents the results of the calculation of the rate of discomfort for three locations and operating modes considered. In practice, it should be noted that as the heating is activated at 19 C, these values only consider the period when the temperature is over 27 C. TABLE 10 RATE OF DISCOMFORT FOR DIFFERENT OPERATING MODES OF ROLLER SHUTTERS Paris La Rochelle Nice Shutters opened all day 19,6 % 23,6 % 39,1 % Clock mode 4,1 % (- 15,5 %) 6,9 % (- 16,7 %) 30,4 % (- 8,7 %) External temperature mode 14,9 % (- 4,7 %) 18,1 % (- 5,5 %) 39,0 % (- 0,1 %) Light level mode 4,3 % (-15,3 %) 5,8 % (- 17,8 %) 27,6 % (- 11,5 %) The light level mode is the best option to reduce the rate of discomfort (between 11% and 18% depending on the climatic area). The clock mode provides similar results but again, would not consider the daylight level available that could be seen as uncomfortable for the occupants. The external temperature mode is the least effective, especially in the Nice area where there is no benefit. It should be noticed that the Nice area is the warmest in France and that additional provisions (such as the thermal inertia of the building) should be taken to achieve a reasonable level of comfort. V.2. Impact of solar shading on visual comfort As it relies on a personal perception, visual comfort varies from one person to another. It is a subjective issue. Nevertheless, there is no doubt that daylight is usually preferred to artificial lighting as the primary source of light. However, situations causing visual discomfort can easily arise in a naturally-lit office. Occasionally, the light may be too bright or the contrasts too great. To fully harvest the benefits of daylight, it needs to be controlled. Page 30
32 Glare is usually caused by direct sunlight falling on objects in the office or high exterior luminance values within the field of view. Glare can also occur when using a computer display: the luminance of the reflection of the surroundings may be higher than the luminance of the computer screen. Figure 23 presents the luminance level in an office when the solar shading is extended or retracted. It shows that solar shading significantly reduces the luminance ratios avoiding an important difference of luminance between the computer screen and the surroundings that would create a visual discomfort. Without solar shading With solar shading FIGURE 23 LUMINANCE LEVEL WITH AND WITHOUT SOLAR SHADING IN AN OFFICE (PHOTOS SOMFY) The ES-SO and REHVA guidebook published in 2010 (see IV.2) presents a summary of scientific research showing the influence of the use of daylight on factors related to worker and student productivity: By maximizing the use of daylight without glare and providing daylight responsive lighting controls, a median productivity benefit of 3,75% was found by Carnegie Mellon University. [CMU 2004] On average, major health complaints are between 20% and 25% lower for occupants close to an exterior window, compared to those that work in the interior core without access to view and daylight. [Hart 1999, Hart 1994] Access to windows and daylight resulted in a 15% reduction of absenteeism. [Thay 1995] Direct sun penetration into classrooms, especially through unshaded east or south facing windows, is associated with negative student performance. [Hesh 2003b] Students with adequate natural daylight in their classrooms showed 20% faster progress in maths tests and 26% in reading tests during one year. [Hesh 1999] From the above it may be concluded that natural daylight has a significant and positive influence on occupant health, wellbeing and productivity. However, adaptive control of daylight is needed to guarantee the conditions of good visual comfort at all times. Page 31
33 Page 32
34 Bibliography (1) European Standards EN Blinds and shutters - Thermal and visual comfort - Performance characteristics and classification EN Blinds and shutters - Thermal and visual comfort - Test and calculation methods EN Shutters and blinds - Additional thermal resistance - Allocation of a class of air permeability to a product EN Solar protection devices combined with glazing - Calculation of solar and light transmittance - Simplified method EN Solar protection devices combined with glazing - Calculation of total solar energy transmittance and light transmittance - Detailed calculation method EN ISO Thermal performance of windows, doors and shutters - Calculation of thermal transmittance - General EN 410 Glass in building - Determination of luminous and solar characteristics of glazing (2) Guidebooks Guide de la Fermeture et de la Protection Solaire», 2010, co-edited by SEBPTP and Metal Services Solar Shading, how to integrate solar shading in sustainable buildings, 2010, edited by REHVA, 40 rue de Washington, 1050 BRUSSELS, BELGIUM; [email protected] (3) Research Création d'un outil d'aide au choix optimisé du vitrage du bâtiment selon des critères physiques, écologiques et économiques, pour un meilleur confort visuel et thermique, Magali Bodart, UCL, Avril Analyse de l apport énergétique du volet roulant, TBC & SNFPSA, Mars 2010 [CMU 2004] Guidelines for High Performance Buildings [Hart 1994] Hartkopf, V., V. Loftness, S. Duckworth, S. Lee, P. Drake, J. Posner, and G. Rainer. The Intelligent Workplace Retrofit initiative: DOE Building Studies. Produced under contract for the U.S. Department of Energy, December [Hart 1999] Hartkopf, V., Loftness, V. Global relevance of total building performance, Automation in Construction 8, (1999) pp [Hesh 1999] Heschong, Mahone, Daylighting in Schools: An investigation into the relationship between daylighting and human performance, [Hesh 2003b] Heschong, L., Windows and Classrooms: A Study of Student Performance and the Indoor Environment. Report prepared for the California Energy Commission, [Thay 1995] Thayer, Burke Miller, Daylighting & Productivity at Lockheed, Solar Today, Vol.9, (4) Informative links ES-SO web site: Textinergie tool: Win-Shelter software : Page 33
35 Page 34
36 T he Energy Performance of Buildings Directive ( EPBD ) and in particular its stringent 2010 Recast version, requires that, from 2020 onward, all new buildings in Europe shall be nearly zeroenergy. This goal is achievable only through the optimisation of the building envelope. Within the building envelope, the glazed part plays a key role as it allows light and heat to enter into the building. However, light and heat levels vary throughout the year. They need to be controlled firstly to reach the goal of nearly zero-energy and, secondly, to ensure the comfort of the building s occupants. Solar shading which covers a huge variety of products and controls is designed to answer these needs as it adapts the glazed envelope properties to the weather conditions and the human needs. That is why solar shading cannot be considered as a secondary equipment of the glazed envelope but should be integrated in the building design at the very first stage of the project s development. In this way, the performance impact of the building development can be assessed and the heating and cooling equipment specified accordingly. The visual and thermal comfort of the occupants can also be determined well in advance avoiding possible modifications of the building façade or the internal environment after commissioning. This guide book is intended to give the technical information needed to evaluate the performance of solar shading. It contains the basic principles required to understand the physical properties involved in the radiation transmission. It then highlights the standardised calculation methods that are used to evaluate the thermal and visual characteristics of blinds and shutters. Finally, from technical studies and research, it provides an overview of the impact of solar shading on the energy consumption of buildings and the occupants comfort. Although it is intended to be used by solar shading manufacturers and installers, this guidebook will be of interest to building designers and energy engineers. ES-SO vzw Naessenslaan 9 B-1860 Meise, Belgium [email protected]
What is Solar Control?
A better environment inside and out. Solar, Safety and Security Window Films: Tech Bulletin Understanding Solar Performance Solar Gard solar control window films use advanced technology to benefit consumers
Adaptive strategies for office spaces in the UK climate
International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate
Tech Bulletin. Understanding Solar Performance
Tech Bulletin Understanding Solar Performance Bekaert solar control window films use advanced technology to benefit consumers with quality solutions that enhance comfort and decrease energy use. By understanding
Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015
EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW
The Industry s Most Advanced Sun-Sensing, Adaptive-Tinting Technology For Dynamic Windows
by The Industry s Most Advanced Sun-Sensing, Adaptive-Tinting Technology For Dynamic Windows In Alliance with OCCUPANT COMFORT All of the windows above have the same exterior tint of glass. Why such a
Solar Energy Utilisation in Buildings
Solar Energy Utilisation in Buildings P. Karava, PhD Assistant professor Department of Civil and Environmental Engineering University of Western Ontario 2 Modern Buildings Change in architectural style
SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much?
SOLAR ENERGY How much strikes the earth? How much can my building get? When is it too much? The sun: friend of foe? Drawing by Le Corbusier ENGS 44 Sustainable Design Benoit Cushman-Roisin 14 April 2015
Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi
Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction
Unbeatable energy efficient glass curtain wall system
Unbeatable energy efficient glass curtain wall system CONTENT Introduction 1 System 2 World Class Engineering 4 Unit Selection 5 Energy Efficiency & Comfort 10 Maximised Installation Efficiency 12 Aesthetics
Elegance SC. Solar Control
Elegance SC Solar Control Sapa Building System Building Understanding In an age of global warming, the reduction of carbon emissions is a key factor when both selecting materials for a building and how
Full credit for this chapter to Prof. Leonard Bachman of the University of Houston
Chapter 6: SOLAR GEOMETRY Full credit for this chapter to Prof. Leonard Bachman of the University of Houston SOLAR GEOMETRY AS A DETERMINING FACTOR OF HEAT GAIN, SHADING AND THE POTENTIAL OF DAYLIGHT PENETRATION...
THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel
THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING R.M.J. Bokel Department of Architecture, Delft Technical University, Delft, The Netherlands,
ENERGY SAVING WINDOW FILMS S LAR CONTROL
ENERGY SAVING WINDOW FILMS S LAR CONTROL Overview Managing Solar Heat Gain - Solar Control Window Film With an ever increasing need to achieve outstanding energy efficiency within buildings without compromising
Passive Solar Design and Concepts
Passive Solar Design and Concepts Daylighting 1 Passive Solar Heating Good architecture? The judicious use of south glazing coupled with appropriate shading and thermal mass. Summer Winter Passive solar
Introduction. 1. Heat Transfer. In Townsville s climate it is essential to choose building materials that perform well in our local conditions.
In Townsville s climate it is essential to choose building materials that perform well in our local conditions. Choosing the correct materials and insulation will improve the overall thermal performance
LOW-E PHOTOVOLTAIC GLASS TECHNICAL GUIDE
LOW-E GLASS TECHNICAL GUIDE SELECTIVE INFRARED RADIATION FILTER Infrared radiation coming from natural sun light can cause a heat build-up inside building; This situation leads to thermal imbalance during
Solar Heating Basics. 2007 Page 1. a lot on the shape, colour, and texture of the surrounding
2007 Page 1 Solar Heating Basics Reflected radiation is solar energy received by collectorsfrom adjacent surfaces of the building or ground. It depends a lot on the shape, colour, and texture of the surrounding
Constructions Database User Guide <Virtual Environment> 5.9
Constructions Database User Guide 5.9 Page 1 of 35 Contents 1. Introduction...3 2. Units...4 3. Main Dialogue Project Constructions...5 3.1. Outline...5 3.2. Construction Classes
Exemplary Retrofitting of an Old School in Stuttgart - EROS -
Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in
Window Performance Basics
Window Performance Basics Keeping cool in summer, warm in winter, comfortable all the time,... and saving energy too Ross McCluney, Ph.D., Prinicipal Research Scientist Florida Solar Energy Center Windows
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
Selecting Energy Efficient Replacement Windows in Nevada
Selecting Energy Efficient Replacement Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows
Selecting Energy Efficient New Windows in Texas
Selecting Energy Efficient New Windows in Texas www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified
Selecting Energy Efficient New Windows in Georgia
Selecting Energy Efficient New Windows in Georgia www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE
Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE Abuimara, Tareq A 1 ; Tabet Aoul, Kheira A. 1 1 Department of Architectural Engineering, United Arab
Residential Windows, 3 rd edition Corrected index 1
Residential Windows, 3 rd edition Corrected index 1 A absorptance definition, 78 determinants of, 78 79 energy performance and, 78 tinted glass, 84 acoustical properties of windows, 60 61 acrylic glazing
ResearcH JournaL 2009 / VOL 01.01. www.perkinswill.com
ResearcH JournaL 2009 / VOL 01.01 www.perkinswill.com PERKINS+WILL RESEARCH JOURNAL / VOL 01.01 05. CONTEXT BASED DESIGN OF DOUBLE SKIN FACADES Climatic Considerations During the Design Process Ajla Aksamija,
Pilkington Activ. The forecast will always be clear and cool. Pilkington Activ Range Self-cleaning and solar control glass for conservatories.
Pilkington Activ The forecast will always be clear and cool. Pilkington Activ Range Self-cleaning and solar control glass for conservatories. Thermal insulation. When it comes to conservatories, we think
Diego Ibarra Christoph Reinhart Harvard Graduate School of Design
Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #2 Load Schedules GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard Graduate School of Design OVERVIEW
Selecting Energy Efficient New Windows in Arizona
Selecting Energy Efficient New Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
User operations and preferences in a test room equipped with advanced natural and artificial light sources
User operations and preferences in a test room equipped with advanced natural and artificial light sources Michele Zinzi, Gaetano Fasano ENEA-UDA Italian Agency for Energy, Environment and New Technologies,
Electromagnetic Radiation (EMR) and Remote Sensing
Electromagnetic Radiation (EMR) and Remote Sensing 1 Atmosphere Anything missing in between? Electromagnetic Radiation (EMR) is radiated by atomic particles at the source (the Sun), propagates through
ENERGY AUDIT. Project : Industrial building United Arab Emirates (Case study) Contact person (DERBIGUM):
ENERGY AUDIT Project : Industrial building United Arab Emirates (Case study) Contact person (DERBIGUM): Leonard Fernandes DERBIGUM project reference : UAE -2014 - EA 103 Author : Daniel Heffinck (DERBIGUM)
ATM S 111, Global Warming: Understanding the Forecast
ATM S 111, Global Warming: Understanding the Forecast DARGAN M. W. FRIERSON DEPARTMENT OF ATMOSPHERIC SCIENCES DAY 1: OCTOBER 1, 2015 Outline How exactly the Sun heats the Earth How strong? Important concept
Energy Efficient Hospital Patient Room Design: Effect of Room Shape on Windowto-Wall Ratio in a Desert Climate
Energy Efficient Hospital Patient Room Design: Effect of Room Shape on Windowto-Wall Ratio in a Desert Climate Ahmed Sherif Hanan Sabry Rasha Arafa Ayman Wagdy [Department of Construction and Architectural
CHAPTER 3. The sun and the seasons. Locating the position of the sun
zenith 90 summer solstice 75 equinox 52 winter solstice 29 altitude angles observer Figure 3.1: Solar noon altitude angles for Melbourne SOUTH winter midday shadow WEST summer midday shadow summer EAST
Case Study Family Room Renovation 3br family home, Melbourne
Family Room Renovation 3br family home, Melbourne In a Nutshell With time and budget constraints we often renovate just one room at a time. This case study looks at a family room renovation where the key
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING LI CHUNYING DOCTOR OF PHILOSOPHY CITY UNIVERSITY OF HONG KONG FEBRUARY 2012 CITY UNIVERSITY OF HONG KONG 香 港 城 市 大 學 Performance Evaluation of Water-flow
CHAPTER 6: WINDOWS AND DOORS
Chapter 6: Windows and Doors 89 CHAPTER 6: WINDOWS AND DOORS Windows and doors connect the interior of a house to the outdoors, provide ventilation and daylight, and are important aesthetic elements. Windows
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004
Parametric Analysis of School Classroom Typologies' Energy Performance
PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Parametric Analysis of School Classroom Typologies' Energy Performance MAUREEN TREBILCOCK
Selecting Energy Efficient New Windows in Florida
Selecting Energy Efficient New Windows in Florida www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified
Energy Pathways in Earth s Atmosphere
BRSP - 10 Page 1 Solar radiation reaching Earth s atmosphere includes a wide spectrum of wavelengths. In addition to visible light there is radiation of higher energy and shorter wavelength called ultraviolet
THE EUROPEAN GREEN BUILDING PROGRAMME. Building Envelope Technical Module
THE EUROPEAN GREEN BUILDING PROGRAMME Building Envelope Technical Module Contents 1. Introduction...1 2. Inventory of systems...2 3. Assessment of energy saving technical measures...4 4. Action Plan...12
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
薄 膜 對 提 高 樓 宇 窗 戶 性 能 的 研 究 分 析
Hui, S. C. M. and Kwok, M. K., 2006. Study of thin films to enhance window performance in buildings, In Proceedings of the Sichuan-Hong Kong Joint Symposium 2006, 30 June-1 July 2006, Chengdu, China, pp.
ESCI 107/109 The Atmosphere Lesson 2 Solar and Terrestrial Radiation
ESCI 107/109 The Atmosphere Lesson 2 Solar and Terrestrial Radiation Reading: Meteorology Today, Chapters 2 and 3 EARTH-SUN GEOMETRY The Earth has an elliptical orbit around the sun The average Earth-Sun
Pilkington Activ self-cleaning glass. The clear choice for your conservatory.
Self-cleaning Pilkington Activ self-cleaning glass. The clear choice for your conservatory. Pilkington Activ Range Self-cleaning and solar control glass for conservatories and orangeries. Conservatories
Energy savings in the residential area are essential in
Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations
Evaluation of Window Energy Rating Models for Different Houses and European Climates
Evaluation of Window Energy Rating Models for Different Houses and European Climates J. and A. Roos Department of Materials Science, The Ångström Laboratory Uppsala University P.O. Box 534, S-751 21 Uppsala
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Dept. Building Environment Science &Technologies Politecnico di Milano Italy Research funded
SELECTIVE GLAZING FOR SUN CONTROL
SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level
Module 3.7. Thermal bridging
Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable buildings
International Conference Passive and Low Energy Cooling 935 for the Built Environment, May 25, Santorini, Greece The Sino-Italy Environment & Energy Building (SIEEB): A model for a new generation of sustainable
Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality
EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION
EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION The Weather Envoy consists of two parts: the Davis Vantage Pro 2 Integrated Sensor Suite (ISS) and the
WALLS Three common wall types are described below, with their insulation solutions.
APPENDIX 5: Building Envelope Insulation is vitally important for temperature controlled buildings. If fuel (and therefore money) is being used to heat a building, less fuel (and money) will be used if
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Greenhouse Glazing Effects on Heat Transfer for Winter Heating and Summer Cooling
Greenhouse Glazing Effects on Heat Transfer for Winter Heating and Summer Cooling David R. Mears, Ph.D. Bioresource Engineering Department of Plant Biology and Pathology Rutgers University 20 Ag Extension
ENERGY EFFICIENT WINDOWS & DOORS A GUIDE TO THERMAL PERFORMANCE. www.rehau.co.uk. Building Solutions Automotive Industry
ENERGY EFFICIENT WINDOWS & DOORS A GUIDE TO THERMAL PERFORMANCE www.rehau.co.uk Building Solutions Automotive Industry INTRODUCTION IMPROVING THE ENERGY EFFICIENCY OF WINDOWS AND DOORS Background Environmental
Optimum Solar Orientation: Miami, Florida
Optimum Solar Orientation: Miami, Florida The orientation of architecture in relation to the sun is likely the most significant connection that we can make to place in regards to energy efficiency. In
Opening the Bonnet. Prof Darren Woolf WYSINWYG 1
Opening the Bonnet Prof Darren Woolf WYSINWYG 1 WYSINWYG What You See Is NOT What You Get: Looking inside the Pandora s Box Prof Darren Woolf WYSINWYG 2 WYSIWYG implies a user interface that allows the
Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels. W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd.
Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd. 1 The Kingspan Group Energy independent buildings for a sustainable
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Energy Efficiency in Buildings
Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:
Case Study 13 Schools of Architecture and Design, Wellington tertiary education institute, New Zealand
Case Study Schools of Architecture and Design, Wellington tertiary education institute, New Zealand Winter Summer daylight intermediate, intermediate, climate temperate, oceanic altitude m heating degree
Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving
346 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving S. Ferrari Politecnico
Miami Science Museum DoE Modelling Grant. Light Planning. 19 December 2008 Concept Design
DoE Modelling Grant 19 December 2008 Concept Design 155 Avenue of the Americas, New York NY 10013 Tel +1 212 229 2669 Fax +1 212 229 1056 www.arup.com Job Number 131761 au Introduction Table of Contents
Self-Cleaning. The forecast will always be clear and cool. Pilkington Activ Range Self-cleaning and solar control glass for conservatories.
Self-Cleaning The forecast will always be clear and cool. Pilkington Activ Range Self-cleaning and solar control glass for conservatories. Conservatories bringing the outside in. Pilkington Activ has made
The Three Heat Transfer Modes in Reflow Soldering
Section 5: Reflow Oven Heat Transfer The Three Heat Transfer Modes in Reflow Soldering There are three different heating modes involved with most SMT reflow processes: conduction, convection, and infrared
Module 2.2. Heat transfer mechanisms
Module 2.2 Heat transfer mechanisms Learning Outcomes On successful completion of this module learners will be able to - Describe the 1 st and 2 nd laws of thermodynamics. - Describe heat transfer mechanisms.
Klosterenga, Oslo, Norway, 1998-2000 page - 1
Klosterenga, Oslo, Norway, 1998-2000 page - 1 Introduction Klosterenga is an urban revitalisation project close to the city centre of Oslo. The 3 apartments were built with a focus on energy saving. Next
Diego Ibarra Christoph Reinhart Harvard Graduate School of Design
Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #3 Construction Assemblies, Load Reduction & Shading GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard
Green Building Handbook for South Africa Chapter: Lighting Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Lighting Luke Osburn CSIR Built Environment Lighting consumes between about 29-35% of the energy used within commercial office space while lighting only
Overview. What is EMR? Electromagnetic Radiation (EMR) LA502 Special Studies Remote Sensing
LA502 Special Studies Remote Sensing Electromagnetic Radiation (EMR) Dr. Ragab Khalil Department of Landscape Architecture Faculty of Environmental Design King AbdulAziz University Room 103 Overview What
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS
HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS Saim Memon Philip C. Eames Centre for Renewable Energy Systems
The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study
The Importance of Building Criteria on Cooling Energy Demand of a Low Cost Residential House: Thailand Case Study WARAPORN RATTANONGPHISAT 1,2,*, FEDERICO M. BUTERA 2, R.S. ADHIKARI 2 AND CHALERMPORN YOOPRATETH
KNX for building and room automation simple and efficient
The worldwide standard for home and building control KNX for building and room automation simple and efficient Save energy and effort with a comprehensive portfolio for electrical and HVAC applications.
1. At which temperature would a source radiate the least amount of electromagnetic energy? 1) 273 K 3) 32 K 2) 212 K 4) 5 K
1. At which temperature would a source radiate the least amount of electromagnetic energy? 1) 273 K 3) 32 K 2) 212 K 4) 5 K 2. How does the amount of heat energy reflected by a smooth, dark-colored concrete
The Reunion experience
Barcelona Workshop Experience on Net Zero Energy Buildings October 3rd 2012 1 The challenge of designing Net Zero Energy Buildings in Tropical Climates The Reunion experience Prof. François GARDE, PhD,
Energy efficient home design
Energy efficient home design GUIDELINES How an energy efficient home can help you live in comfort and save money An energy efficient home is designed to provide shade and allow cooling breezes to enter
1. Theoretical background
1. Theoretical background We consider the energy budget at the soil surface (equation 1). Energy flux components absorbed or emitted by the soil surface are: net radiation, latent heat flux, sensible heat
New technical solutions for energy efficient buildings
- New technical solutions for energy efficient buildings State of the Art Report Energy efficient building design Authors: Heimo Staller, Angelika Tisch, IFZ Oct. 2010 Background In the building sector
3. Pre-design applications
3. Pre-design applications 7S9X0 Environmental Performance of Buildings TU/e Dept. of the Built Environment Building Performance group Environmental Performance of Buildings 7S9X0 TU/e TU/e Building Building
Dynamic Solar Shading and Glare Control for Human Comfort and Energy Efficiency at UCSD: Integrated Design and Simulation Strategies
Dynamic Solar Shading and Glare Control for Human Comfort and Energy Efficiency at UCSD: Integrated Design and Simulation Strategies Christopher Meek Department of Architecture University of Washington
Holistic Approach in Delivering Government Buildings The Low Carbon Concept
International Conference on Planning for Low Carbon Cities 22 May 2009 Holistic Approach in Delivering Government Buildings The Low Carbon Concept Ir. HO Sai-king, Assistant Director (Building Services),
CO2 Emissions. Indirect CO 2. Emissions Electricity and Heat Production 25 % Direct Emissions AFOLU 24 % Energy 1,4% Buildings 6,4 % Industry 11 %
CO2 Emissions Direct Emissions AFOLU 24 % Buildings 6,4 % Transport 14 % 49 Gt CO2 eq (2010) Indirect CO 2 Emissions Electricity and Heat Production 25 % Energy 1,4% Industry 11 % Transport 0,3 % Industry
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
Energy Savings with Window Retrofits
Center for Energy and Environment Energy Savings with Window Retrofits Presentation to Energy Design Conference & Expo Duluth, MN February 25, 2014 Agenda v Background v Introduction: What are window retrofits?
Green Heating. Pupil Research Brief. Teachers Notes. Syllabus Coverage Subject Knowledge and Understanding. Route through the Brief UPIL ESEARCHER
R P UPIL ESEARCHER Green Heating I NITIATIVE Pupil Research Brief Teachers Notes Syllabus Coverage Subject Knowledge and Understanding all types of electromagnetic radiation form a continuous spectrum
CONSERVATION AND LIGHTING
CONSERVATION AND LIGHTING Light is essential for the examination and enjoyment of collection items. But in a museum light also means damage: dyes and pigments fade or change appearance and the materials
MCQ - ENERGY and CLIMATE
1 MCQ - ENERGY and CLIMATE 1. The volume of a given mass of water at a temperature of T 1 is V 1. The volume increases to V 2 at temperature T 2. The coefficient of volume expansion of water may be calculated
