Analysis of Large-System Fault with Phasor Measurements
|
|
- Thomas Parrish
- 8 years ago
- Views:
Transcription
1 Analysis of Large-System Fault with Phasor Measurements Sergio Luiz Zimath Reason Tecnology Ildemar Decker, Daniel Dotta and Marcelo Agostini Federal University of Santa Catarina 13 th Annual Fault Disturbance Analysis Conference Georgia Tech - Atlanta May 4 th
2 Introduction Generation far from load More than 80% hydro Long transmission lines Power stability issues Many Special Protection Schemes System becomes highly nonlinear Need for better monitoring Tendency to use hydro due economical benefit 2
3 Medfasee Project Project started in 2003 Development of a prototype WAMS Internet communication over VPN Installation of PMUs in universities in Brazil Study, dissemination and educational use of the WAMS technology Applications for power system monitoring, control and fault location 3
4 Medfasee Project Five geographical regions are covered (9 universities) Virtual Private Network over Internet for communication 4
5 The MedFasee Eletrosul Project Developments: First installation in a 500kV system in Brazil Main transmission utility of south 4 PMUs and 1 PDC Applications for monitoring tools and fault location Power system performance analysis 5
6 PMUs used Multifunctional device PMU Digital Fault Recorder Power Quality Recorder Continuous Recorder Travelling Wave fault locator More IEEE C compliant ONS testing at NIST: conditionally passed Sending 60 phasors per second (3Ф) 6
7 Main oscillation modes of Brazil 7
8 Itaipu Tucurui Special Protection Schema Characteristics: Automatic dropping of generation Itaipu Hydro ( MW) Tucurui Hydro (8.370 MW) Maintain integrity of the system after loosing 765 kv circuits from Itaipu transmission Power plants are 2200 miles apart 33 miliseconds delay for signal transmission 40 repeaters SPS raised in 900MW the transmission capacity from North-Southeast 8
9 July 4 th Special Protection Schema tripping 9
10 July 4 th Special Protection Schema tripping Characteristics: One-phase short circuit followed by the tripping of two circuits C1 and C2 from 765kV Foz do Iguaçu Ivaiporã. Successful generation dropping of 4 units of Itaipu and 2 units of Tucurui. Frequency Behavior 60.2 Frequência do S IN - S P M S MedFasee Frequência (Hz) UFP A UNIFE I UnB UFRJ UFC US P -S C UTFP R P UC-RS UFS C Tempo(s ) - Início: 04/07/ :35:00 GMT Distribution system Transmission system 10
11 July 4 th Special Protection Schema tripping Frequência do SIN - SPMS MedFasee Frequência (Hz) UFPA UNIFEI UnB UFRJ UFC USP-S C UTFPR PUC-RS UFSC Tem po(s) - Início: 04/07/ :35:00 GM T 11
12 Measured oscillation modes 12
13 Second Schema tripping July 22, 2009 Tripping of three 765 kv lines Only 600 kv DC link Generation shedding 3180 MW from Itaipu 627 MW from Tucurui Successful without any load lost 13
14 October 4 th 2009 lost interconnection 14
15 October 4 th 2009 lost interconnection Previous flow was south to north Frequency in south reached Hz Dominant oscillation mode measured 0.6Hz : South-Southeast North-South mode not present North-south interconnection was lost No load shedding 15
16 October 4 th 2009 lost interconnection F re q u ê n c ia (H z ) Frequencies Frequência do SIN - SPMS MedFasee UNIFEI UnB COPPE USP-SC UTFPR UFSC PUC-RS Tempo(s) - Início:04/10/ :37:00 (local) M a g n i t u d e d a F r e q u ê n c i a ( H z ) Oscillation modes Espectro de Frequências da Frequência no SIN (Janela 1) 0,6Hz UNIFEI UnB COPPE USP-SC UTFPR UFSC PUC-RS Frequência (Hz) 16
17 Now that s look when something wrong happened... 17
18 November 10 th Blackout 10:13 PM Heavy rains Three phase to ground short-circuits Three 765kV circuits from Itaipu lost at same time 600kV DC link lost due voltage collapse First time Itaipu was completely shut down 3:42 hours to restore system 18
19 November 10 th Blackout North Northeast Southeast Central west South 19
20 November 10 th Blackout Load at area Southeast/Central = 37.7 GW 65% lost (22.5 GW) in Southeast 27% lost (0.9 GW) in Central Generation lost in corridor = 11.9 GW 31.5 % from generation on area 20
21 November 10 th Blackout Sequence of events B-G A-G C-G 21
22 November 10 th Blackout Sequence of events Lines in fault 22
23 November 10 th Blackout North: 63,6 Hz South: 58,6 Hz Resynchroniza tion in 15 s? One 500kV line kept linking areas Asynchronous operation between areas 23
24 November 10 th Blackout Frequency Power flow (MW) adjacent 500Kv line 24
25 November 10 th Blackout After 90 s finally separated 25
26 November 10 th Blackout November10th Blackout Flashover 26
27 November 10 th Blackout Actual status Final report still not ready Large discussions about responsibility Not a single cause Transmission utility penalized in US$ 30 millions State owned Presidential Election this year Politicians talking about power system were very funny 27
28 November 10 th Blackout As the cause is raining solution is: 28
29 February 10 th 2010 System separation Large flow northsouth Fault caused by a tree on one 500kV circuit Automatic separation in tree systems North NORTE Marabá Itacaíunas C1 C1 Gurupi C3 C2 C4 1φg C1 C2 Tucuruí C2 Colinas Miracema C3 C3 C2 C2 C1 C1 C1 C2 Peixe 2 Açailândia Imperatriz Ribeiro Gonçalves C1 C2 Presidente Dutra São João do Piauí NORDESTE Northeast NORDESTE Teresina II Boa Esperança Sobradinho Northeast C1 C2 Peixe Rio das Éguas C1 C2 Serra da Mesa C3 Samambaia Serra da Mesa 2 CO/SE/S South-Central Bom Jesus da Lapa 2 Sem escala. LT ligada LT desligada 29
30 February 10 th 2010 System separation Sequence of tentative to restore the line 30
31 February 10 th 2010 System separation Detail of when it started 31
32 February 10 th 2010 System separation How far it has gone North South/Southeast Northeast 32
33 February 10 th 2010 System separation System restored after 13 minutes 33
34 February 10 th 2010 System separation All system modes measured!!! 34
35 Paper in IEEE GM
36 Conclusion Effectively measured all oscillation modes and dumplings during faults Analysis of the bulk power system using distribution level Very easy installation Excellent educational tool Upgraded to 14 PMUs this year 36
37 Thanks! 37
System Protection Schemes in Eastern Denmark
System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives
More informationWide Area Monitoring Current Continental Europe TSOs Applications Overview
Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main
More informationFRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003
F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify
More informationAllen Goldstein NIST Synchrometrology Lab Gaithersburg, MD allen.goldstein@nist.gov
Time Synchronization in Electrical Power Transmission and Distribution Systems Allen Goldstein NIST Synchrometrology Lab Gaithersburg, MD allen.goldstein@nist.gov Abstract Synchronization of measurements
More informationUNIVERSITETET FOR MILJØ- OG BIOVITENSKAP. Smartgrid. Terje Gjengedal. The Norwegian University of Life Sciences. www.umb.no
Smartgrid. Terje Gjengedal The Norwegian University of Life Sciences The grid a key for efficient electricity utilization The Power system Medium Voltage (1-36 Production Transmission distribution G Extra
More informationDevelopment of Monitoring, Protection, and Control Technologies & Impact on Modern Electric Networks. Vahid Madani
1 Development of Monitoring, Protection, and Control Technologies & Impact on Modern Electric Networks Vahid Madani Pacific Gas and Electric Company Incorporated in California in 1905 One of the largest
More informationContext: significant penetration of DG = increased risks for system security
Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:
More informationEvolution of Control for the Smart Transmission Grid
Evolution of Control for the Smart Transmission Grid Anjan Bose Washington State University Pullman, WA SCE Smart Grid Research Symposium California Institute Of Technology October, 2011 The Past (before
More informationTodos los derechos reservados para XM S.A. E.S.P.
Reliability Improvements in Latin America for the 21st Century i-pcgrid Workshop 2013 Innovations in Protection & Control for Greater Reliability Infrastructure Development Outline Description of the Colombian
More informationAdvanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
More informationREAL TIME DYNAMICS MONITORING SYSTEM (RTDMS ) AND PHASOR GRID DYNAMICS ANALYZER (PGDA) USER TRAINING FOR ERCOT
REAL TIME DYNAMICS MONITORING SYSTEM (RTDMS ) AND PHASOR GRID DYNAMICS ANALYZER (PGDA) USER TRAINING FOR ERCOT SEPTEMBER 16-17, 2014 Electric Power Group. Built upon GRID-3P platform, U.S. Patent 7,233,843,
More informationAssessment of power swing blocking functions of line protective relays for a near scenario of the Uruguayan system
Assessment of power swing blocking functions of line protective relays for a near scenario of the Uruguayan system C. Sena, R. Franco, A. Giusto. Instituto de Ingeniería Eléctrica Facultad de Ingeniería
More informationErasmus Mundus External Cooperation Windows. EU-BRAZIL STARTUP Call for applications outcome 08/02/2010
L15a0900007 L15a0900027 L15a0900041 L15a0900051 L15a0900057 L15a0900080 L15a0900081 L15a0900084 L15a0900088 L15a0900090 L15a0900093 L15a0900095 L15a0900096 L15a0900099 L15a0900106 L15a0900107 L15a0900115
More informationAD11-6-000 FERC Technical Conference February 8, 2011 Statement of Ron Litzinger. President, Southern California Edison Company
AD11-6-000 FERC Technical Conference February 8, 2011 Statement of Ron Litzinger President, Southern California Edison Company Good afternoon, Chairman Wellinghoff, Commissioners, and FERC staff. I am
More informationPHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE
PHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE INTRODUCTION OUTLINE Conventional control centers Introduction to Synchrophasors A generic PMU Applications of PMU Role of GPS Cost profile of PMU with
More informationObjectives. This paper also presents some improvements in the restoration processes of the São Paulo Area of the NIS.
CIGRE 2008 C2-110 Requirements in Design and Implementation of Restoration Facilities and Procedure in Order to Improve Power System Restoration: The Brazilian Experience Paulo Gomes and Antonio P. Guarini
More informationSynchrophasor projects: STRONgrid and SPANDEx
Synchrophasor projects: STRONgrid and SPANDEx Kjetil Uhlen Statnett pilot project Nordic R&D collaboration Outline Short about STRONgrid (Nordic R&D collaboration) Short about the plan for SPANDEx (control
More information1. Introduction... 1. 2. Synchrophasor Technologies... 1
Table of Contents 1. Introduction... 1 2. Synchrophasor Technologies... 1 3. Advanced Applications Software and their Benefits... 4 3.1 Online (Near Real-Time Applications)... 5 3.2 Offline (Not real-time)
More informationBIGDATAANALYTICS FOR ELECTRICPOWERGRID OPERATIONS MANU PARASHAR CORPORATE POWER SYSTEMS ENGINEER JULY 29, 2015
BIGDATAANALYTICS FOR ELECTRICPOWERGRID OPERATIONS MANU PARASHAR CORPORATE POWER SYSTEMS ENGINEER JULY 29, 2015 Agenda Big Data in the Energy Industry Solution Architecture/Approach for Managing Big Data
More informationScope of Restoration Plan
RWG Area Restoration Review Worksheet (10/28/09) EOP-006-02 Directory 8 EOP-005 NYSRG Rule G Text Restoration Plan Requirement R1.Each Reliability Coordinator shall have a Reliability Coordinator Area
More informationData Management Issues associated with the August 14, 2003 Blackout Investigation
Material derived from PNNL-SA-40401 Originally presented June 8, 2004 Data Management Issues associated with the August 14, 2003 Blackout Investigation Jeff Dagle, PE Chief Electrical Engineer and Team
More informationONS in the Brazilian Power Industry
ONS in the Brazilian Power Industry Visit of Tractebel Rio de Janeiro April 19 th, 2009 Hermes J. Chipp General Director The Brazilian Power Sector Institutional Structure The Brazilian Power Sector Institutional
More informationInfraestrutura no Brasil: Projetos, Financiamentos e Oportunidades
INVESTMENTS IN THE ELECTRICITY SECTOR Mauricio Tolmasquim President of the Energy Research Office (EPE) ELECTRICITY GENERATION Power Auctions Modalities New Energy Auctions A-3 and A-5 (three-year and
More informationHVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson
A firewall against disturbances in high-voltage grids Lennart Carlsson Interconnections between grids are desirable because they not only permit economies through the sharing of reserves, but they also
More informationRisk of Large Cascading Blackouts
Risk of Large Cascading Blackouts EUCI Transmission Reliability Conference Washington DC, October 2006 Ian Dobson ECE Department University of Wisconsin joint work with Ben Carreras, Oak Ridge National
More informationBrochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
More informationXI Seminário Técnico de Proteção e Controle 18 a 21 de novembro de 2012 Florianópolis Santa Catarina Brasil
XI Seminário Técnico de Proteção e Controle 18 a 21 de novembro de 2012 Florianópolis Santa Catarina Brasil XI STPC ST 045 Recent Advances and Experience with Power System Oscillation Monitoring and Control
More informationSynchrophasors Redefining SCADA Systems
Synchrophasors Redefining SCADA Systems Mangapathirao V. Mynam, Ala Harikrishna, and Vivek Singh Schweitzer Engineering Laboratories, Inc. Presented at GRIDTECH 2013 New Delhi, India April 3 4, 2013 Previous
More informationSubstation Automation Systems. We are exceptional grid stability PSGuard Wide Area Monitoring System
Substation Automation Systems We are exceptional grid stability PSGuard Wide Area Monitoring System We are exceptional grid stability PSGuard Wide Area Monitoring System 2 We are exceptional grid stability
More informationElectric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas
Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables
More informationMidwest Reliability Organization Procedure For NERC PRC-012
Midwest Reliability Organization Procedure For NERC PRC-012 A. Introduction The following procedure developed by the MRO Protective Relay Subcommittee (PRS) and Transmission Assessment Subcommittee (TAS)
More informationWide Area Monitoring, Control, and Protection
Wide Area Monitoring, Control, and Protection Course Map Acronyms Wide Area Monitoring Systems (WAMS) Wide Area Monitoring Control Systems (WAMCS) Wide Area Monitoring Protection and Control Systems (WAMPACS)
More informationPreliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines
Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,
More informationSMART GRID TO BUILD SUSTATAINABILITY IN ELECTRIC SYSTEM
SMART GRID TO BUILD SUSTATAINABILITY IN ELECTRIC SYSTEM Kriti 1 1 Assistant professor, Deptt. of Electronics &Instrumentation Engg., Galgotias College of Engineering & Technology, Gr. Noida, U.P., India
More informationOscillation Monitoring System
Oscillation Monitoring System Mani V. Venkatasubramanian Washington State University Pullman WA Oscillation Monitoring System IEEE C37.118 Real-time PMU data stream TCP or UDP OpenPDC OMS SQL server OMS
More informationPresentation to Investors
Presentation to Investors September 2011 Disclaimer This presentation may contain forward-looking statements, Such statements are not statements of historical facts but reflect the beliefs and expectations
More informationEngineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
More informationSmart Grid Demonstration Lessons & Opportunities to Turn Data into Value
Smart Grid Demonstration Lessons & Opportunities to Turn Data into Value Matt Wakefield Senior Program Manager Berlin, Germany December 3rd, 2012 EPRI Smart Grid Demonstration Projects Integration of Distributed
More informationVoltage Source HVDC Overview Mike Barnes Tony Beddard
Voltage Source HVDC Overview Mike Barnes Tony Beddard Note: This is a version with images removed which have copyrighted other than from the University of Manchester, for web publication. Should a conference
More informationCO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
More informationSecurity Policy Review: Credible Event Management. Scope and Methodology Draft for Industry 2014
Security Policy Review: Credible Event Management Scope and Methodology Draft for Industry 2014 Version Date Change 1 26/03/2014 Draft for industry Position Date Prepared By: Reviewed By: Ina Ilieva, Senior
More informationInterpretation of Remote Backup Protection Operation for Fault Section Estimation by a Fuzzy Expert System
Interpretation of Remote Backup Protection Operation for Fault Section Estimation by a Fuzzy Expert System G. Cardoso Jr., J. G. Rolim and H. H. Zürn. Abstract-- A hybrid intelligent system, combining
More informationHybrid processing of SCADA and synchronized phasor measurements for tracking network state
IEEE PES General Meeting, Denver, USA, July 2015 1 Hybrid processing of SCADA and synchronized phasor measurements for tracking network state Boris Alcaide-Moreno Claudio Fuerte-Esquivel Universidad Michoacana
More informationNERC Cyber Security Standards
SANS January, 2008 Stan Johnson Manager of Situation Awareness and Infrastructure Security Stan.johnson@NERC.net 609-452-8060 Agenda History and Status of Applicable Entities Definitions High Level of
More informationNuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the
More informationCentrais Eletricas Brasileiras S.A. - Power Plants and SWOT Analysis, 2014 Update
Brochure More information from http://www.researchandmarkets.com/reports/2934085/ Centrais Eletricas Brasileiras S.A. - Power Plants and SWOT Analysis, 2014 Update Description: Centrais Eletricas Brasileiras
More informationInternational Review of Grid Connection Requirements related with Voltage Dips for Wind Farms
International Review of Grid Connection Requirements related with Voltage Dips for Wind Farms J. A. Fuentes, M. Cañas, A. Molina, E. Gómez, F. Jiménez Abstract In this work, the Spanish grid code is compared
More informationBasics of Power System Control and Protection
Basics of Power System Control and Protection A. P. Sakis Meliopoulos Georgia Power Distinguished Professor School of Electrical & Computer Engineering Georgia Institute of Technology 1.1 School of Electrical
More informationSynchronized real time data: a new foundation for the Electric Power Grid.
Synchronized real time data: a new foundation for the Electric Power Grid. Pat Kennedy and Chuck Wells Conjecture: Synchronized GPS based data time stamping, high data sampling rates, phasor measurements
More informationVoltage Stability Improvement using Static Var Compensator in Power Systems
Leonardo Journal of Sciences ISSN 1583-0233 Issue 14, January-June 2009 p. 167-172 Voltage Stability Improvement using Static Var Compensator in Power Systems Department of Electrical/Computer Engineering,
More informationData Mining to Characterize Signatures of Impending System Events or Performance from PMU Measurements
Data Mining to Characterize Signatures of Impending System Events or Performance from PMU Measurements Final Project Report Power Systems Engineering Research Center Empowering Minds to Engineer the Future
More informationANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line
International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationPJM Interconnection LLC Regional Transmission Organization (RTO)
PJM Interconnection LLC Regional Transmission Organization (RTO) ComEd Generator Interconnection Meeting October 2015 William Patzin PJM Infrastructure Coordination October 2015 PJM 2013 Nine Major North
More informationToward standards for dynamics in future electric energy systems The basis for plug and play industry paradigm
Toward standards for dynamics in future electric energy systems The basis for plug and play industry paradigm Marija Ilić milic@ece.cmu.edu Electric Energy Systems Group (EESG) http://www.eesg.ece.cmu.edu/,
More informationChapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
More information(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.
(e) condition based maintenance means a set of maintenance actions based on continuous or frequent assessment of equipment condition, which is obtained from either of or a combination of embedded sensors,
More informationExecutive Summary... ii
Table of Contents Executive Summary... ii 1. Introduction... 1 1.1 The American Reinvestment and Recovery Act of 2009... 1 1.2 SGIG and Grid Modernization... 2 1.3 Organization of this Report... 3 2. The
More informationFACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB
BSES, Delhi - Distribution Network improve power quality System design for optimal techno-economic distribution network based on current and future load forecast Analysis of existing sub-transmission and
More informationPower System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
More informationIEEE PES Transmission and Distribution Committee Integration of Renewable Energy into the Transmission and Distribution Grids Subcommittee
IEEE PES Transmission and Distribution Committee Integration of Renewable Energy into the Transmission and Distribution Grids Subcommittee Start Time: 3:00 PM 1. Welcome and Introductions Chairman: Ernst
More information1. Operating Highlights. 2. Distribution OPERATING PREVIEW. Market
Rio de Janeiro, January 29, 2016 - Light S.A. (BMF&BOVESPA: LIGT3) discloses a preview of its operating information regarding the distribution, generation and commercialization/services segments for the
More informationGrid codes for renewable energy integration
Rabat 2015-06-02 Grid codes for renewable energy integration Harald G Svendsen SINTEF Energy Research Norway harald.svendsen@sintef.no Work Package leader for grid integration activities in the EuroSunMed
More informationBig Data: Using Smart Grid to Improve Operations and Reliability. LaMargo Sweezer-Fischer Power Delivery Grid Automation Manager FPL July 2014
1 Big Data: Using Smart Grid to Improve Operations and Reliability LaMargo Sweezer-Fischer Power Delivery Grid Automation Manager FPL July 2014 2 NextEra Energy is a premier U.S. power company comprised
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationSmart Grid: Concepts and Deployment
Smart Grid: Concepts and Deployment Dr. S. Chakrabarti Department of Electrical Engineering IIT Kanpur email: saikatc@iitk.ac.in Smart Grid 1 Outline Defining the smart Grid Need for smart grid Smart grid
More informationGuidelines for Large Photovoltaic System Integration
1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More informationControl Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, andreas.olenmark@one-nordic.se.
More informationLocal Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
More informationOffshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
More informationFederal Energy Regulatory Commission. Small Entity Compliance Guide Mandatory Reliability Standards (Order No. 693)
Federal Energy Regulatory Commission Small Entity Compliance Guide Mandatory Reliability Standards (Order No. 693) This Guide is prepared in accordance with the requirements of section 212 of the Small
More informationGeneral Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
More informationAgenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman. sergio.fujii@areva-td.com. ethan.boardman@areva-td.com
Agenda do Mini-Curso Sérgio Yoshio Fujii sergio.fujii@areva-td.com Ethan Boardman ethan.boardman@areva-td.com Agenda do Mini-Curso Sistemas de Distribuição (DMS) Characteristics of Distribution Network
More informationTransmissão em Corrente Contínua
Transmissão em Corrente Contínua Panorama Atual e Perspectivas Futuras no Brasil Multi-Terminal HVDC Classic Some Considerations Brazilian SC B4 Paulo Fischer de Toledo, ABB Basic considerations Traditional
More informationMAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS
MAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS BRENDAN KIRBY and ERIC HIRST Consulting in Electric-Industry Restructuring Oak Ridge, Tennessee Restructuring the electric-power industry
More informationPJM Merchant Transmission Request. Queue #R75. Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study
PJM Merchant Transmission Request Queue #R75 Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study 413038v1a March 2007 PJM Interconnection 2007. All rights reserved. Preface The intent of the
More informationECE 586b Course Project Report. Auto-Reclosing
ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1
More informationAlberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5
A. Introduction 1. Title: 2. Number: 3. Purpose: To specify consistent and sustainable security management controls that establish responsibility and accountability to protect BES cyber systems against
More informationBrazilian Smart Grid: Regulatory Issues and R&D Projects
Brazilian Smart Grid: Regulatory Issues and R&D Projects André Pepitone da Nóbrega Director Brussels, Belgium June 18th, 2012 Brazilian Electric Power Highlights Source: BIG/ANEEL Apr/2012, PDE 2020 Facilities
More informationElectrical Considerations for HVDC Transmission Lines. Joe Mooney, PE
Electrical Considerations for HVDC Transmission Lines Joe Mooney, PE POWER Engineers has met the standards and requirements of the Registered Continuing Education Program. Credit earned on completion of
More informationStudy to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid
Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy
More informationWhy Data Modeling Using the CIM is Important to Big Data Analytics
Why Data Modeling Using the CIM is Important to Big Data Analytics (14PESGM2447) Margaret Goodrich Director of Systems Engineering SISCO, Inc. margaret@sisconet.com Topics Legacy use of data modeling for
More informationIndustrial IT for Substation Automation & Protection
Industrial IT for Substation Automation & Protection Exploit the potential of ABB substation automation Improve your performance In view of the increasingly competitive arena where power providers are
More informationTreasure Valley Electric Plan - Community Advisory Committee
Treasure Valley Electric Plan - Community Advisory Committee What is a transmission line and why are they necessary? A transmission line is used to conduct electricity between two points. Without high
More informationWhen the Power Fails: Designing for a Smart Meter s Last Gasp
When the Power Fails: Designing for a Smart Meter s Last Gasp Daniel Pruessner 1/10/2012 5:25 PM EST Overview Smart meter designers have an unusual predicament: The meter is powered from the same bus that
More informationApplication of On-line Monitoring Systems in the view of Maintenance Engineering of Eletrobras Furnas
1 Application of On-line Monitoring Systems in the view of Maintenance Engineering of Eletrobras Furnas Fabio Abreu Pinto, Eletrobras Furnas, Jorge Santelli da Silva, Eletrobras Furnas, and Marcos E. G.
More informationBalancing and Reserve Power by PV Plants. Ken Christensen MSEE, BSEE Global Product Manager, SMA Utility-Scale and Hybrid Solutions
Balancing and Reserve Power by PV Plants Ken Christensen MSEE, BSEE Global Product Manager, SMA Utility-Scale and Hybrid Solutions IEEE PES 2014 2 Disclaimer IMPORTANT LEGAL NOTICE This presentation does
More informationDistribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
More informationRM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
More informationSolar Power Plant Design and Interconnection
Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive
More informationPHASOR DATA REQUIREMENTS FOR. Protection Applications. White Paper Final Draft. Prepared by: C. Martinez, M. Parashar, J. Dyer, J.
C onsortium for E lectric R eliability T echnology S olutions Real Time Wide-Area Monitoring, Control and Protection PHASOR DATA REQUIREMENTS FOR Real Time Wide-Area Monitoring, Control and Protection
More informationBrazil. Economic upswing and sustainable energy development. Marcelo Khaled Poppe
Economic upswing and sustainable energy development Marcelo Khaled Poppe Primary energy supply Oil 47.1% Nuclear 1.2% Coal 7.4% Natural Gas 5.5% Traditional biomass (unsustainable) 3.4% New renewable Modern
More informationRenewable Energy Interconnection Requirements for the US. IEEE PES Meeting Denver, CO July 26-30, 2015 J. Charles Smith, Executive Director, UVIG
1 Renewable Energy Interconnection Requirements for the US IEEE PES Meeting Denver, CO July 26-30, 2015 J. Charles Smith, Executive Director, UVIG 2 Outline of Topics Background and Introduction NERC Integrating
More informationABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
More informationThe Brazilian Electricity Model: An Overview of the Current Structure and Market Design
The Brazilian Electricity Model: An Overview of the Current Structure and Market Design Élbia Melo 1, Evelina Maria de Almeida Neves 2, Luiz Henrique Alves Pazzini 3 Câmara de Comercialização de Energia
More informationF05D Meeting on Damped AC Voltage Testing
October 28 th, 2008 from 03.30-5.30 pm in San Antonio, TX Agenda F05D Damped AC Voltage Testing 1 Agenda F05D Damped AC Voltage Testing Welcome: Introduction On-site testing voltages e.g. IEC 60060-3 High
More informationPSS E. High-Performance Transmission Planning Application for the Power Industry. Answers for energy.
PSS E High-Performance Transmission Planning Application for the Power Industry Answers for energy. PSS E architecture power flow, short circuit and dynamic simulation Siemens Power Technologies International
More informationAlberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1
A. Introduction 1. Title: 2. Number: 3. Purpose: To prevent and detect unauthorized changes to BES cyber systems by specifying configuration change management and vulnerability assessment requirements
More informationP1 Policy 1: Load-Frequency Control and Performance [C]
P1 Policy 1: Load-Frequency Control and Performance [C] Chapters A. Primary Control B. Secondary Control C. Tertiary Control D. Time Control Introduction The GENERATION of power units and CONSUMPTION of
More information