KLIC-DI SKY PRODUCT MANUAL INTERFACE KNX DAIKIN SKY ZN1CL-KLIC-DI. Edition 6 Version 1.5

Size: px
Start display at page:

Download "KLIC-DI SKY PRODUCT MANUAL INTERFACE KNX DAIKIN SKY ZN1CL-KLIC-DI. Edition 6 Version 1.5"

Transcription

1 PRODUCT MANUAL KLIC-DI SKY INTERFACE KNX SKY ZN1CL-KLIC-DI Edition 6 Version 1.5

2 Index 1. Introduction Installation KLIC-DI Installation Elements Description Configuration Basic Control Advanced Functionalities Parameterization Default Configuration General Mode Fan speed Scenes Temperature Limitation Automatic switch off Errors management Initial configuration Annex I. Communication Objects Annex II. Correspondence Error Codes of Daikin Units ZENNiO AVANCE Y TECNOLOGÍA 2

3 1. INTRODUCTION The KLIC-DI is an interface that allows a bidirectional communication between a KNX domotic system and the commercial air-conditioning units of the series Sky Air manufactured by Daikin. Due to this bidirectional communication, the air conditioning unit can be controlled in the same way that using an IR remote controller and the real status of the airconditioning unit is checked and sent to the KNX bus for its monitoring. Figure 1 KLIC-DI In case of using a wired remote control in the same communication bus of the unit, the KLIC-DI will communicate with this remote control acting one device as master control while the other device will act as slave control. It is important to verify that the KLIC-DI and the wired remote control are configured with different type of control. This way, the control acting as slave will update its status when the master orders it and will communicate its status changes when they are modified from the own slave control. Device Features: Small enclosure: 90 x 60 x 35 mm (2 DIN rail units) Designed to be installed inside distribution boxes or electrical mounting boxes. KLIC-DD controls commercial and industrial air conditioners (bi-directional communication) of the series Sky Air and VRV from Daikin. Daikin control protocol. ZENNiO AVANCE Y TECNOLOGÍA 3

4 Control over all Daikin air-conditioning functionality. Error management handles Daikin error codes as well as any communication errors that may arise. LED indicators allow monitoring of the bidirectional traffic flow. Integrated EIB/KNX Bus Coupling Unit. Complete data saving in case of Bus Power Failure. CE Compliant ZENNiO AVANCE Y TECNOLOGÍA 4

5 2. INSTALLATION 2.1. KLIC-DI INSTALLATION The KLIC-DI installation is performed the same way that any other KNX device. We just need to connect the device to KNX bus through the specific KNX connector. On the other hand, this device is connected to the Daikin internal unit PCB (P1/P2 connectors), using a 2-wire cable. If the wired remote control from Daikin is also used, it is necessary to make sure that the wired remote control is in mode slave if the KLIC-DI is configured as master control. And vice versa, if the KLIC-DI is configured as slave control, the wired remote control must be in master position. Once the device is provided with power supply from the bus, both, the physical address and the KLIC application program can be downloaded. This device does not need any external supply, since it just works with the power supply of KNX bus. Connections to daikin P1/P2 bus diagrams Figure 2 Connecting KLIC-DI to P1/P2 bus ZENNiO AVANCE Y TECNOLOGÍA 5

6 Figure 3 Connecting KLIC-DI to bus P1/P2 with wired remote control (slave mode) Diagrams Leyend A B C P1 - P2 KLIC DI Daikin Wired remote control Daikin SKY or VRV unit Daikin connection bus 1-2 Zennio connection terminal * The wired remote control must operate in the opposite mode to KLIC-DI Notes The model FDXS E is controlled by KLIC-DD (see datasheet) because the internal unit does not have P1/P2 port ELEMENTS DESCRIPTION Prog: To set the device programming mode. When initially pushed, after Powering, secure mode is set. Led: Luminous signal which indicates the state of the device. Besides including the programming red LED (typical in any KNX device), the KLIC-DI incorporates two more LEDs, blue and green ones, in order to inform about the bidirectional communication between KNX and Daikin, resulting very useful in the installation process. We can know the meaning watching the color: ZENNiO AVANCE Y TECNOLOGÍA 6

7 Red: programming LED. If it is ON indicates Programming mode. LED blinkling every 0,5s, the device is set in Secure Mode. Green: failure in the KLIC-DI power supply (this happens when the KLIC-DI is not connected to the Daikin device and/or when the Daikin device is not connected to the power supply line). Blinking green: communication data from Daikin device to KLIC-DI. Blinking blue: communication data from KLIC-DI to the Daikin device. Communication Cable: 2-wire cable, direct to PI/P2 connectors that can be found at the PCB of the internal unit, or in the wired remote control. Nº Description 1 EIB connector 2 Programming LED 3 Programming button 4 2-wire communication terminal ZENNiO AVANCE Y TECNOLOGÍA 7

8 3. CONFIGURATION 3.1. BASIC CONTROL With KLIC-DI, the air conditioning unit can be monitored and controlled the same way it is done with the wired remote control provided with the air conditioning unit. By means of bus KNX, it can be controlled the following basic functionalities of the air conditioning system: ON/OFF of the air conditioning unit. Setpoint Temperature. Between 16 and 32 ºC. Operating Mode: Auto, Heat, Dry, Fan and Cool. Fan Speed: 2 or 3 speed levels configuration. (Check out the available levels in the Daikin unit) These functionalities have associated a machine status, which is periodically sent to KLIC-DI. When KLIC-DI receives a status different from the previous one from the machine, it updates the status of the corresponding parameter in the bus KNX ADVANCED FUNCTIONALITIES Besides the basic control over the air conditioning system, KLIC-DI offers other advanced functionalities that give an added value with regard to the wired remote control: Scenes Configuration: allows establishing a specific parameters combination for the air conditioning machine. Temperature Limitation: Daikin air conditioning systems are limited in temperature (usually to the range ºC. Please verify the range for a particular model in the corresponding Daikin manual). This KLIC functionality allows configuring custom temperature ranges for the modes Heat and Cool by means of the ETS in such a way that the setpoint temperature will remain in the range. In case of receiving from the bus KNX a temperature command with a value out of the configured limits, the temperature value sent to the machine will be the corresponding limit value. ZENNiO AVANCE Y TECNOLOGÍA 8

9 Indoor temperature and Reference temperature: the Sky Air machines has several temperature sensors for measuring the temperature in different internal points. The Indoor temperature is the measured internal value and it is used together with the Reference temperature for controlling the modes Auto-Cool and Auto- Heat of the air-conditioning machine. The Reference temperature is the real temperature in the room to acclimatize. It is necessary to communicate this parameter to the machine by means of the corresponding communication object and it is hardly recommended to link this communication object with a temperature sensor (installed in the room) which periodically updates the temperature value. The modes Auto-Heat and Auto-Cool can be controlled in three different ways by the Daikin machine: 1. The machine receives the Reference temperature and, according to a pre-configured hysteresis by the Daikin installer, it establishes the corresponding auto mode. 2. The machine uses the Indoor temperature and, according to a preconfigured hysteresis by the Daikin installer, it establishes the corresponding auto mode. 3. The machine establishes the auto mode according to the average value of the Reference temperature and the Indoor temperature. The temperature value used by the machine in order to switch beatween the Modes Auto-Cool and Auto-Cool depends on the configuration established in the Dakin machine installation. This value, in any of the previous cases is compared to the setpoint temperature in such a way that if the setpoint temperature is higher the Auto-Heat mode is established and if the setpoint temperature is lower than this value, the Auto-Cool is established. Take into account: It is hardly recommended to link the Reference temperature to a temperature sensor that periodically monitors the real temperature in the room because the way of switching between the different Auto modes might not be known and this fact can lead to a wrong functioning of the Auto mode. The Reference temperature has a default value equal to 25ºC. Auto Switch Off: allows temporarily switching off the machine if a status change in the communication object associated to it, takes place. An example of this functionality could be the use of a window sensor, associated to the auto switch off, that allows switching off the machine if the window is opened. ZENNiO AVANCE Y TECNOLOGÍA 9

10 Errors Management: this functionality allows the sending of messages to the bus informing about errors. Errors management handles Daikin error codes as well as any communication errors that may arise Besides informing about the apparition of possible errors it can be also configured the sending of the error type. In case of internal errors, the numerical code associated to the error type is shown in the following table: Error Number Type of Internal Error 1 Problems with the data reception (speed, parity, etc.) 2 Communication waiting time exceeded (Time-out) 3 Incorrect checksum 4 Incorrect response from the machine Regarding the numerical code associated to the external errors type, look up the manual of the installed air-conditioning system or the Annex II Correspondence Error Codes of Daikin Units. Initial Configuration: All machine status must have an initial value after installing the system or a power failure. With this purpose, it has been included in the KLIC the possibility of defining the initial status for the ON/OFF, temperature, fan and speed of the machine. These initial values can be sent both to the bus KNX and the air conditioning unit. Type of Control: Master/Slave It is important to take into account the type of control, master or slave, with which the KLIC-DI is going to be configured. The remote control master in the installation is in charge of the communication with the machine and it will retransmit the instructions and status between the machine and the slave remote control in case of having one. In spite of the master/salve configuration, all the functionalities can be set from both remote controls. This functionality allows including in the installation both the KLIC-DI and the Daikin wired control and choosing the desired master/slave configuration whenever the KLIC-DI and the wired control are not configured with the ZENNiO AVANCE Y TECNOLOGÍA 1 0

11 same type of control. In case of having both controls configured as masters, the screen of the Daikin control will show the error 88 and the error U5 will be sent to the bus. Take into account: When switching the type of control of the Daikin wired control between master and slave, it is necessary to remove the power supply from the wired control and connecting it again for rebooting the wired control in the suitable mode Important: The wired control BRC1E51A7 can only operate as master control. In case of using this model of wired control in the installation, it is necessary configuring the KLIC-DI as slave control. ZENNiO AVANCE Y TECNOLOGÍA 1 1

12 4. PARAMETERIZATION For starting to parameterize the device it is necessary, once the ETS has been opened, importing the data base of the product KLIC-DI SKY 1.5.vd2. Then the KLIC is added to the project where it is desired to include the device. Click with the right mouse button the right button on the device and select Edit Parameters.. for starting with the configuration. In the following sections there is a detailed explanation about each of the different functionalities of the device in ETS DEFAULT CONFIGURATION This section shows the default configuration from which the device configuration starts. If the window Edit Parameters is opened for the first time, the KLIC General configuration by default will be found. Next figure shows the General window with the default values: Figure 4 Default General Configuration ZENNiO AVANCE Y TECNOLOGÍA 1 2

13 As we can see in the previous figure all the advanced functionalities: scenes, temperature limitation, auto switch off, errors management and initial configuration are disabled by default. If the Mode and Fan are selected, it will be seen that both the Individual Modes and the Simplified Modes (Cool/Heat) are disabled by default while the Fan is configured for 2 different fan speeds and the step control is also disabled. Figure 5 Default Mode Configuration Figure 6 Default Fan Configuration In the next figure, it can be watched the available communication objects by default: they allow sending the ON/OFF to the Split, setpoint temperature, mode and fan speed (two speeds), as well as receiving the status of these variables from the Split. Figure 7 Default Communication Objects ZENNiO AVANCE Y TECNOLOGÍA 1 3

14 4.2. GENERAL From the parameterization window General the advanced functionalities can be enabled: Scenes Temperature Limitation Auto OFF Errors Management Type of Control Indoor Temperature Sending Time Initial Configuration As we select the functionalities in the pull down lists, the access to the functionality configuration window will appear in the Menu at the left and the corresponding communication objects are enabled. This window also allows configuring the type of control for the remote control: Master/Slave Figure 8 General ZENNiO AVANCE Y TECNOLOGÍA 1 4

15 And the Sending Time for the Indoor Temperature. This temperature is sent by the machine when the indoor temperature changes. In order to avoid an excessive sending of telegrams with this temperature, it has been implemented this parameter. This way, the indoor temperature will be sent every certain period of time specified with this parameter and only if the temperature has changed MODE As it has been previously seen in the default configuration, the specific Mode window allows the user select: Individual Modes When selecting the Individual Modes, two 1-bit communication objects will be enabled, one for controlling the mode and another one for receiving the status from the split, for each mode (Auto, Cool, Only Fan, Heat and Dry) besides the 1-byte communication objects for controlling and indicating the Mode that exist by default. If the option Individual Modes is activated, the operating mode of the machine will be sent by means of the 1-bit Sending object associated to the mode. Moreover the Mode will be also sent to the bus KNX by means of both the 1- byte Mode objects for controlling and indicating the status of the corresponding mode. Simplified Modes The selection of the Simplified Modes will enable a 1-bit communication object with the same name that will allow choosing between Mode Cool (value 0) and Mode Heat (value 1). For this communication object, the corresponding status communication object does not exist. Figure 9 Mode 4.4. FAN SPEED In this window it can be selected the number of fan levels that the air conditioning unit has: 2 or 3 levels. ZENNiO AVANCE Y TECNOLOGÍA 1 5

16 The fan speed has associated two 1-byte communication objects that respectively controls and indicates the fan speed. The control object records the fan speed in percentage. For this reason this value will be interpolated in such a way that corresponds to the selected number of levels. The status object will show the fan speed according to the interpolated percentages. Two Levels of Fan Figure 10 Fan Speed If the fan speed configuration has 2 levels, the fan speed percentages will be interpolated in the following way: Initial Speed Percentage Interpolated Speed Percentage Level 0 49% 25 % Minimum % 100 % Maximum Three Levels of Fan On the other hand, with a fan speed configuration of 3 levels, the fan speed percentages will be interpolated according to next table: Initial Speed Percentage Interpolated Speed Percentage Level 0 32% 25 % Minimum % 50 % Medium % 100 % Maximum Besides configuring the number of levels the Fan window allows selecting the Step Control. Step Control The selection of Step Control enables a 1-bit object for increasing or decreasing the fan speed level: Value 1 : Increase ZENNiO AVANCE Y TECNOLOGÍA 1 6

17 Value 0 : Decrease The Step Control is not cyclical which means that if the fan speed is Minimum (0%), when the speed level is decreased, the speed will remain at this mode until the level is increased again. The same way, when the speed level is at 100%, the level will remain at this maximum until the speed is decreased SCENES A scene involves the synchronized sending of several commands to the air conditioning unit with the objective of generating a determined climate environment in the room. KLIC offers the possibility of configuring up to 4 scenes. Figure 11 Scenes Once the Scenes are enabled in General, the option Scenes appears in the Menu. Figure 12 Scenes Configuration Example ZENNiO AVANCE Y TECNOLOGÍA 1 7

18 For each of the 4 scenes, the variables that can be configured are: Scene1-4: Scene Number: Scene number within the installation. ON/OFF: No change, switching ON or OFF the Split. Temperature: No change or temperature value between 16 C and 32 C. Mode: No change, auto, heat, dry, fan or cool. Fan: No change, minimum, medium o maximum TEMPERATURE LIMITATION The air conditioning unit has defined upper and lower temperature limits that cannot be exceeded (the limits are usually 32ºC and 16ºC respectively). Nevertheless, KLIC offers the possibility of establishing new temperature limits if they are specified within the Daikin limits of the unit that is going to be used (Look up the Daikin unit manual). The temperature limits can be personalized for the two modes with associated temperature: Cool and Heat. Figure 13 Temperature Limitation ZENNiO AVANCE Y TECNOLOGÍA 1 8

19 Once the limitation is enabled, when a value out of the range is sent from the bus KNX, the value that will be sent to Daikin unit will be the corresponding temperature limit and this new temperature value will be notified to the bus KNX. As a new functionality, it has been included a 1-bit communication object that will allow the user enabling (object to 1 ) or disabling (object to 0 ) these personalized temperatures restoring the Daikin default range. Take into account: When configuring in ETS the temperature limitation, this functionality is automatically enabled by default and the personalized ranges will control the unit performance when it switches on AUTOMATIC SWITCH OFF When this option is enabled, the air conditioning unit will be temporarily switched off if a status change in the associated binary communication object is produced. This functionality has two configurable parameters: Delay for Auto-OFF: Number of seconds that KLIC-DI delays the air conditioning unit switching off. Figure 14 Auto-OFF 4.8. S MANAGEMENT The Errors Management window allows enabling the sending of messages to the bus indicating any error that may arise: internal errors of the communication between the KLIC-DI and the Daikin unit or external errors, errors in the own Daikin unit. It can be enabled the internal errors, the external errors or both: Internal Errors: Yes or no. External Errors: Yes or no. ZENNiO AVANCE Y TECNOLOGÍA 1 9

20 Every error type has associated two communication objects: the binary one indicates if an error has occurred and the 1-byte object that indicates the code identifying the error. Figure 15 Errors Management 4.9. INITIAL CONFIGURATION The initial configuration window allows configuring the initial machine status after the installation or a power failure. The variables that can be initialized are the following: ON/OFF: Last, ON or OFF. Temperature: Last or custom. Mode: Last, auto, heat, dry, fan or cool. Fan: Last, auto, minimum, minimum-medium, medium, maximum-medium or maximum. Moreover, it can be configured the Sending of status to the Bus or Split and when it must be carried out: Send Initial Configuration to?: Yes or no. Delay: number of seconds that the KLIC delays the sending of status to the ZENNiO AVANCE Y TECNOLOGÍA 2 0

21 Figure 16 Initial Configuration ZENNiO AVANCE Y TECNOLOGÍA 2 1

22 ANNEX I. COMMUNICATION OBJECTS SECTION NUMBER LENGHT IN/OUT FLAGS VALUES RANGE INITIAL RESET NAME OBJECT FUNCTION 0 1 bit I W 0/1 0 ON/OFF Turn ON the Split(1); Turn OFF the Split(0) 1 2 bytes I W Temperature Temperature sent to the Split 2 1 byte I W Mode Auto(0); Heat(1); Cool(3); Fan(9);Dry(14) 3 1 byte I W Fan With 2 levels: Minimum (0-49%); Maximum (50%- 100%) With 3 levels: Minimum (0-32%); Medium(33%- 65%); Maximum (66%-100%) 4 1 bit R-T 0/1 ON/OFF (Status) Split State (ON/OFF) 5 2 bytes R-T Temperature (Status) Temperature received from the split GENERAL 6 1 byte R-T Mode (Status) Mode received from the split 7 1 byte R-T Fan (Status) With 2 levels: Minimum (25%); Maximum (100%) With 3 levels: Minimum (25%); Medium(50%); Maximum (100%) 20 1 byte I W Scenes Set Scene Value (Scene Number) 21 1 bit I W 0/1 Temperature Limitation Enable(1); Disable(0) 22 1 bit I W 0/1 Auto-OFF Enable(1); Disable(0) 27 2 bytes R-T Indoor Temperature (Estado) Temperature measured by the machine 28 2 bytes W Reference Temperature Reference temperature 8 1 bit I W-T 0/1 Auto Mode Set Auto Mode(1); Nothing(0) ZENNiO AVANCE Y TECNOLOGÍA 2 2

23 SECTION NUMBER LENGHT IN/OUT FLAGS VALUES RANGE INITIAL RESET NAME OBJECT FUNCTION 9 1 bit I W-T 0/1 Cool Mode Set Cool Mode (1); Nothing (0) 10 1 bit I W-T 0/1 Heat Mode Set Heat Mode (1); Nothing (0) 11 1 bit I W-T 0/1 Fan Mode Set Fan Mode (1); Nothing (0) 12 1 bit I W-T 0/1 Dry Mode Set Dry Mode (1); Nothing (0) 13 1 bit I W 0/1 Simplified Mode Cool(0); Heat(1) 14 1 bit R-T 0/1 Auto Mode (Status) Auto Mode Enabled (1); Disabled (0) MODE 15 1 bit R-T 0/1 Cool Mode (Status) Cool Mode Enabled (1); Disabled (0) 16 1 bit R-T 0/1 Heat Mode (Status) Heat Mode Enabled (1); Disabled (0) 17 1 bit R-T 0/1 Fan Mode (Status) Fan Mode Enabled (1); Disabled (0) 18 1 bit R-T 0/1 Dry Mode (Status) Dry Mode Enabled (1); Disabled (0) FAN 19 1 bit I W 1 Fan [1bit] (Status) Down(0); Up(1) 23 1 bit R-T 0/1 Internal Error (Status) No error(0); Error(1) S MANAGEMENT 24 1 byte R-T 1-4 Type of Internal Error (Status) 25 1 bit R-T 0/1 External Error (Status) No error(0); Error(1) Err.Reception(1);Timeout (2); Incorrect Checksum (3); Incorrect Response(4) 26 1 byte R-T Type of External Error (Status) Check Daikin Errors Table ZENNiO AVANCE Y TECNOLOGÍA 2 3

24 ANNEX II. CORRESPONDENCE S OF UNITS Next table shows the correspondence between the external error code provided by KLIC-DI at the Bus KNX and the breakdown codes of the Daikin units: E1 97 J1 145 U M1 385 T1 433 X E2 98 J2 146 U M2 386 T2 434 X E3 99 J3 147 U M3 387 T3 435 X E4 100 J4 148 U M4 388 T4 436 X E5 101 J5 149 U M5 389 T5 437 X E6 102 J6 150 U M6 390 T6 438 X E7 103 J7 151 U M7 391 T7 439 X E8 104 J8 152 U M8 392 T8 440 X E9 105 J9 153 U M9 393 T9 441 X9 10 0A 58 EA 106 JA 154 UA 202 7A 250 4A 298 1A 346 MA 394 TA 442 XA 11 0H 59 EH 107 JH 155 UH 203 7H 251 4H 299 1H 347 MH 395 TH 443 XH 12 0C 60 EC 108 JC 156 UC 204 7C 252 4C 300 1C 348 MC 396 TC 444 XC 13 0J 61 EJ 109 JJ 157 UJ 205 7J 253 4J 301 1J 349 MJ 397 TJ 445 XJ 14 0E 62 EE 110 JE 158 UE 206 7E 254 4E 302 1E 350 ME 398 TE 446 XE 15 0F 63 EF 111 JF 159 UF 207 7F 255 4F 303 1F 351 MF 399 TF 447 XF 16 A0 64 H0 112 L G0 352 N0 400 V0 448 Y0 17 A1 65 H1 113 L G1 353 N1 401 V1 449 Y1 ZENNiO AVANCE Y TECNOLOGÍA 2 4

25 18 A2 66 H2 114 L G2 354 N2 402 V2 450 Y2 19 A3 67 H3 115 L G3 355 N3 403 V3 451 Y3 20 A4 68 H4 116 L G4 356 N4 404 V4 452 Y4 21 A5 69 H5 117 L G5 357 N5 405 V5 453 Y5 22 A6 70 H6 118 L G6 358 N6 406 V6 454 Y6 23 A7 71 H7 119 L G7 359 N7 407 V7 455 Y7 24 A8 72 H8 120 L G8 360 N8 408 V8 456 Y8 25 A9 73 H9 121 L G9 361 N9 409 V9 457 Y9 26 AA 74 HA 122 LA 170 9A 218 6A 266 3A 314 GA 362 NA 410 VA 458 YA 27 AH 75 HH 123 LH 171 9H 219 6H 267 3H 315 GH 363 NH 411 VH 459 YH 28 AC 76 HC 124 LC 172 9C 220 6C 268 3C 316 GC 364 NC 412 VC 460 YC 29 AJ 77 HJ 125 LJ 173 9J 221 6J 269 3J 317 GJ 365 NJ 413 VJ 461 YJ 30 AE 78 HE 126 LE 174 9E 222 6E 270 3E 318 GE 366 NE 414 VE 462 YE 31 AF 79 HF 127 LF 175 9F 223 6F 271 3F 319 GF 367 NF 415 VF 463 YF 32 C0 80 F0 128 P K0 368 R0 416 W0 464 Z0 33 C1 81 F1 129 P K1 369 R1 417 W1 465 Z1 34 C2 82 F2 130 P K2 370 R2 418 W2 466 Z2 35 C3 83 F3 131 P K3 371 R3 419 W3 467 Z3 36 C4 84 F4 132 P K4 372 R4 420 W4 468 Z4 37 C5 85 F5 133 P K5 373 R5 421 W5 469 Z5 38 C6 86 F6 134 P K6 374 R6 422 W6 470 Z6 39 C7 87 F7 135 P K7 375 R7 423 W7 471 Z7 40 C8 88 F8 136 P K8 376 R8 424 W8 472 Z8 ZENNiO AVANCE Y TECNOLOGÍA 2 5

26 41 C9 89 F9 137 P K9 377 R9 425 W9 473 Z9 42 CA 90 FA 138 PA 186 8A 234 5A 282 2A 330 KA 378 RA 426 WA 474 ZA 43 CH 91 FH 139 PH 187 8H 235 5H 283 2H 331 KH 379 RH 427 WH 475 ZH 44 CC 92 FC 140 PC 188 8C 236 5C 284 2C 332 KC 380 RC 428 WC 476 ZC 45 CJ 93 FJ 141 PJ 189 8J 237 5J 285 2J 333 KJ 381 RJ 429 WJ 477 ZJ 46 CE 94 FE 142 PE 190 8E 238 5E 286 2E 334 KE 382 RE 430 WE 478 ZE 47 CF 95 FF 143 PF 191 8F 239 5F 287 2F 335 KF 383 RF 431 WF 479 ZF 48 E0 96 J0 144 U M0 384 T0 432 X0 ZENNiO AVANCE Y TECNOLOGÍA 2 6

27 ZENNIO TECHNICAL DOCUMENTATION SIGN UP! TECHNICAL SUPPORT 2 7

PRODUCT MANUAL IRSC. IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC. Program version: 5.14 Manual edition: 5.14_a

PRODUCT MANUAL IRSC. IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC. Program version: 5.14 Manual edition: 5.14_a PRODUCT MANUAL IRSC IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC Program version: 5.14 Manual edition: 5.14_a INDEX Document updates... 3 1. Introduction... 4 1.1. IRSC controller... 4 1.2. Installation...

More information

IntesisBox KNX LG Air Conditioning

IntesisBox KNX LG Air Conditioning IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit

More information

PRODUCT MANUAL LUMENTO X4 LED. LED Controller ZN1DI-RGBX4. Program version: 1.0 Manual edition: a

PRODUCT MANUAL LUMENTO X4 LED. LED Controller ZN1DI-RGBX4. Program version: 1.0 Manual edition: a PRODUCT MANUAL LUMENTO X4 LED LED Controller ZN1DI-RGBX4 Program version: 1.0 Manual edition: a INDEX 1. Introduction...3 1.1. Lumento X4... 3 1.2. Installation... 4 2. Configuration...6 3. ETS Parameterization...7

More information

PRODUCT MANUAL. InZennio Z38i. KNX Touch Panel ZN1VI-TP38i. Program version: 2.2 Manual edition: a

PRODUCT MANUAL. InZennio Z38i. KNX Touch Panel ZN1VI-TP38i. Program version: 2.2 Manual edition: a PRODUCT MANUAL InZennio Z38i KNX Touch Panel ZN1VI-TP38i Program version: 2.2 Manual edition: a INDEX Document updates... 3 1. Introduction... 4 1.1. InZennio Z38i... 4 1.2. Installation... 5 2. Configuration...

More information

IntesisBox DK-RC-ENO-1iC. EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines

IntesisBox DK-RC-ENO-1iC. EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines IntesisBox DK-RC-ENO-1i DK-RC-ENO-1iC EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines User's Manual r1 eng Issue Date: 02/2012 Intesis Software S.L. All Rights Reserved.

More information

Inwall 4 Input / 4 Output Module

Inwall 4 Input / 4 Output Module Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...

More information

KNX Panasonic Air Conditioners

KNX Panasonic Air Conditioners IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line

More information

IntesisBox. KNX SAMSUNG Air Conditioning. Gateway for integration of Samsung air conditioners into KNX control systems. RS485.

IntesisBox. KNX SAMSUNG Air Conditioning. Gateway for integration of Samsung air conditioners into KNX control systems. RS485. IntesisBox KNX SAMSUNG Air Conditioning Gateway for integration of Samsung air conditioners into KNX control systems. Integrate Samsung Air Conditioners into KNX. KNX EIB Bus IntesisBox RS485 MIM-B13x/B04A

More information

Inwall Room Temperature Unit

Inwall Room Temperature Unit Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall

More information

IntesisBox KNX Mitsubishi Heavy Industries AC

IntesisBox KNX Mitsubishi Heavy Industries AC IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)

More information

Modbus Server SAMSUNG Air Conditioners

Modbus Server SAMSUNG Air Conditioners IntesisBox Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung Air Conditioning Systems from any master device TCP or RTU (BMS, PLC, SCADA, HMI, TouchPanel ) Master TCP Master

More information

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master

More information

IntesisBox DK-RC-KNX-1

IntesisBox DK-RC-KNX-1 IntesisBox DK-RC-KNX-1 Interface KNX for DAIKIN Air Conditioners (SKY & VRV) AC Indoor Unit Wired Remote Control DK-RC-KNX-1 KNX / EIB bus IntesisBox DK-RC-KNX-1 allows monitoring and control, fully bi-directionally,

More information

PRODUCT MANUAL SKX OPEN SKX ADVANCE ZN1RX-SKXOPEN. Edition 2 Version 1.1

PRODUCT MANUAL SKX OPEN SKX ADVANCE ZN1RX-SKXOPEN. Edition 2 Version 1.1 PRODUCT MANUAL SKX OPEN SKX ADVANCE ZN1RX-SKXOPEN Edition 2 Version 1.1 INDEX 1. Introduction... 3 1.1. SKX Interface... 3 1.2. SKX Installation... 5 1.3. SKX Advance: Application Program... 5 1.3.1. SKX

More information

Victims Compensation Claim Status of All Pending Claims and Claims Decided Within the Last Three Years

Victims Compensation Claim Status of All Pending Claims and Claims Decided Within the Last Three Years Claim#:021914-174 Initials: J.T. Last4SSN: 6996 DOB: 5/3/1970 Crime Date: 4/30/2013 Status: Claim is currently under review. Decision expected within 7 days Claim#:041715-334 Initials: M.S. Last4SSN: 2957

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

DATING YOUR GUILD 1952-1960

DATING YOUR GUILD 1952-1960 DATING YOUR GUILD 1952-1960 YEAR APPROXIMATE LAST SERIAL NUMBER PRODUCED 1953 1000-1500 1954 1500-2200 1955 2200-3000 1956 3000-4000 1957 4000-5700 1958 5700-8300 1959 12035 1960-1969 This chart displays

More information

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Integrations LGAC-KNX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Document updates: Version Data Description V1.0 2015.05.25 Finish new document HVAC Controller User Manual INDEX 1. Overview...1

More information

1.- L a m e j o r o p c ió n e s c l o na r e l d i s co ( s e e x p li c a r á d es p u é s ).

1.- L a m e j o r o p c ió n e s c l o na r e l d i s co ( s e e x p li c a r á d es p u é s ). PROCEDIMIENTO DE RECUPERACION Y COPIAS DE SEGURIDAD DEL CORTAFUEGOS LINUX P ar a p od e r re c u p e ra r nu e s t r o c o rt a f u e go s an t e un d es a s t r e ( r ot u r a d e l di s c o o d e l a

More information

How To Use A Power Supply On A Powerline 2.2 (Ai)

How To Use A Power Supply On A Powerline 2.2 (Ai) KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang

More information

IntesisBox KNX Modbus TCP master

IntesisBox KNX Modbus TCP master IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration

More information

IntesisBox KNX - LON

IntesisBox KNX - LON IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,

More information

Name Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage

Name Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage Description Supports DALI interface driver Programming Supports 0-10V Programmable Driver Programming Supports Other Controllers (TDD-ANPNx, SDD-AAPNx) Off-line programming capability Auto programming

More information

Light scene push button 8gang comfort flush-mounted 751688xx

Light scene push button 8gang comfort flush-mounted 751688xx 751688xx Documentation Product name: Light scene push button 8gang comfort Design: flush-mounting type (Up) ETS search path: Push button / Push button general / Light scene push button 8gang comfort Functional

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1

ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1 Product Manual ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1 Intelligent Installation Systems This manual describes the function of the EIB monitoring module EUB/S 1.1 with the Application program

More information

IntesisBox KNX Modbus RTU master

IntesisBox KNX Modbus RTU master IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1

ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1 Product Manual ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1 Intelligent Installation Systems This manual describes the function of the Switch

More information

CODES FOR PHARMACY ONLINE CLAIMS PROCESSING

CODES FOR PHARMACY ONLINE CLAIMS PROCESSING S FOR PHARMACY ONLINE CLAIMS PROCESSING The following is a list of error and warning codes that may appear when processing claims on the online system. The error codes are bolded. CODE AA AB AI AR CB CD

More information

DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Gateway KNX-DALI DALIX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode: COMMUNICATION INSTRUCTION MANUAL TEMPERATURE CONTROLLER KT4, KT8 and KT9 No.KTC1E6 2009.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

More information

KNX Interface. User Manual PM00A00IRI

KNX Interface. User Manual PM00A00IRI KNX Interface User Manual PM00A00IRI 1/9 1. Index 1. Index...2 2. Preface... 3 2.1. Overview... 3 2.2. System description... 3 2.3. Application programs... 3 2.4. Documentation... 3 3. Mechanical reference...

More information

Manual. IP Sensor and Watchdog IPSW2210. I P S W 2 2 1 0 M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry.

Manual. IP Sensor and Watchdog IPSW2210. I P S W 2 2 1 0 M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry. IP Sensor and Watchdog IPSW2210 Manual Relay Output Power input 12VDC adapter LED Indicators 1 wire 2 Dry Output Green : Power Yellow: Link temperature & humidity contact inputs LED indicator sensor input

More information

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x B.IQ push button 3-5gang with room Product name: Design: ETS search path: B.IQ push button 3-, 4-, 5gang with room thermostat and display V2 Flush-mounted Push button / B.IQ / B.IQ push button xgang with

More information

Simple Self-Diagnosis by Malfunction Code

Simple Self-Diagnosis by Malfunction Code Simple Self-Diagnosis by Code After Sales Service Division (SM-TS2) Detail Division 0 Indoor Unit System Others A C E F H J L P U M 7 8 9 External device activated (unified) Protection devices activated

More information

1 Serial RS232 to Ethernet Adapter Installation Guide

1 Serial RS232 to Ethernet Adapter Installation Guide Installation Guide 10/100 Mbps LED (amber color ) Link/Activity LED (green color ) 1. Introduction Thank you for purchasing this 1-port RS232 to Ethernet Adapter (hereinafter referred to as Adapter ).

More information

RadioRA 2 (QS) Lighting and Climate Control. g! 5.4 Fan Controller: g! 6.4.200 RadioRA2 Inclusive Software v5.0.8 or newer

RadioRA 2 (QS) Lighting and Climate Control. g! 5.4 Fan Controller: g! 6.4.200 RadioRA2 Inclusive Software v5.0.8 or newer Manufacturer: Model Number(s): Minimum Core Module Version: Comments: Lutron Document Revision Date: 8/5/2013 OVERVIEW AND SUPPORTED FEATURES Integration Note RadioRA 2 (QS) Lighting and Climate Control

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI Simplay-UG-02003-A July 2015 Contents 1. Overview... 4 1.1. SL-8800 HDCP Protocol Analyzer Test Equipment... 4 1.2. HDCP 2.2/HDCP 1.x Protocol Analyzer

More information

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB , GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well

More information

ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8

ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8 ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8 Quick Start A This device is a Z-Wave Actuator. Triple click one of the buttons on the device will include the device.

More information

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111 , GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,

More information

Tebis application software

Tebis application software Tebis application software Input products / ON / OFF output / RF dimmer Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF devices WYC81xQ

More information

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control T Series arge CD Digital Thermostat 0/0 VAC -pipe/-pipe fan coil control Data sheet Application T digital thermostats are designed for application of -speed fan and s in fan coil system. Including: -pipe

More information

Passion for KNX innovation

Passion for KNX innovation Passion for KNX innovation Touch-MyDesign 2 Touch-MyDesign is a KNX switch with capacitive buttons that satisfies the design requirements of any building thanks to its total customization: Everyone can

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is

More information

Combi switchbox with integrated 3/2 way pilot valve

Combi switchbox with integrated 3/2 way pilot valve H Combi switchbox with integrated 3/2 way pilot valve Construction The GEMÜ combi switchbox with integrated 3/2 way pilot valve for pneumatically operated quarter turn actuators has a micro-processor controlled

More information

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB Product Manual ABB i-bus KNX IP Interface IPS/S 2.1 Intelligent Installation Systems ABB This manual describes the function of the IP Interface IPS/S 2.1 with the application program IP Interface. Subject

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

UM0853 User manual. 1 Introduction. M24LRxx application software user guide

UM0853 User manual. 1 Introduction. M24LRxx application software user guide User manual M24LRxx application software user guide 1 Introduction The purpose of this user manual is to teach how to use the M24LRxx tool kit with the M24LRxx_Application_Software. It describes the M24LRxx_Application_Software

More information

Electronic Multi-Measuring Instrument

Electronic Multi-Measuring Instrument MITSUBISHI Electronic Multi-Measuring Instrument Programming Manual (CC-Link) For ver.1 remote device station Model ME96NSR-MB or ME96NSR with Optional Plug-in Module : ME-0040C-NS96 ME96SSH-MB or ME96SSR-MB

More information

The application is now available in 8 languages. (German, English, French, Spanish, Italian, Russian, Dutch, Polish)

The application is now available in 8 languages. (German, English, French, Spanish, Italian, Russian, Dutch, Polish) Product: Room Master, Premium Type: RM/S 2.1 Current application program: Room Master, Premium/2.5a ======================================================================================= to: Room Master,

More information

8-Port HDMI Switch USER MANUAL VS0801H

8-Port HDMI Switch USER MANUAL VS0801H 8-Port HDMI Switch USER MANUAL VS0801H FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits

More information

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................

More information

ABB i-bus EIB Logic Module LM/S 1.1

ABB i-bus EIB Logic Module LM/S 1.1 Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...

More information

MEMOBUS/Modbus Communications

MEMOBUS/Modbus Communications 2 2.1 MEMOBUS/MODBUS CONFIGURATION............260 2.2 COMMUNICATION SPECIFICATIONS..............261 2.3 COMMUNICATION TERMINAL RESISTANCE........262 2.4 CONNECTING A PLC...........................263 2.5

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL Installation and operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE. IMPROPER

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

Tebis TL131A application software

Tebis TL131A application software 5 Tebis TL131A application software Radio media coupler TR131 Product reference TR131A Description White media coupler TR131B Silver media coupler KNX TP products Media coupler Unidirectional radio products

More information

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Conserve package Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Gateway Can I have someone install my system for me? If you are concerned

More information

Central Controller G-50A/GB-50A Web Browser Operation Manual (For System Maintenance Engineer)

Central Controller G-50A/GB-50A Web Browser Operation Manual (For System Maintenance Engineer) Mitsubishi Electric Building Air-conditioner Control System Central Controller G-50A/GB-50A Web Browser Operation Manual (For System Maintenance Engineer) Contents 1 Introduction...1 1-1 Conventions Used

More information

IntesisBox Modbus Server - Mitsubishi Electric G50

IntesisBox Modbus Server - Mitsubishi Electric G50 IntesisBox Server - Mitsubishi Electric G50 Gateway for monitor and control Mitsubishi Electric City Multi Air Conditioning systems from any master device TCP or RTU (BMS, PLC, SCADA, HMI, TouchPanel )

More information

Product and Application Description

Product and Application Description Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

User Guide Reflow Toaster Oven Controller

User Guide Reflow Toaster Oven Controller User Guide Reflow Toaster Oven Controller Version 1.5-01/10/12 DROTEK Web shop: www.drotek.fr SOMMAIRE 1. Introduction... 3 2. Preparation of THE REFLOW CONTROLLER... 4 2.1. Power supply... 4 2.2. USB

More information

LAN / WAN Connection Of Instruments with Serial Interface By Using a Terminal Server

LAN / WAN Connection Of Instruments with Serial Interface By Using a Terminal Server Products: EFA with EFA Scan, DVRM and DVMD with Realtime Monitor or Stream Explorer DVMD-B1 LAN / WAN Connection Of Instruments with Serial Interface By Using a Terminal Server Remote control of test and

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Preface Safety warnings To avoid injury, or damage to the Modbus interface, read all installation and configuration instructions in this

More information

Movement/monitoring 1307/1.0 (6325xx)

Movement/monitoring 1307/1.0 (6325xx) /monitoring 1307/1.0 (6325xx) General In the following the device will be referred to as the movement detector. The movement block will only switch off when there is no more movement in front of the device

More information

Programmable controllers. Programming devices, software

Programmable controllers. Programming devices, software Programmable controllers Programmable controllers Programming devices, software Industrial PC HMI Open communications Services SIMATIC S5-90U SIMATIC S5-95U SIMATIC S5-90U SIMATIC S5-95U SIMATIC S5-100U

More information

INSTALLATION GUIDE 1

INSTALLATION GUIDE 1 INSTALLATION GUIDE 1 Setting information MAC-558IF-E address(mac) MAC-558IF-E serial number(id) MAC-558IF-E code(pin) Indoor unit model name Indoor unit serial number Outdoor unit model name Outdoor unit

More information

3.5 EXTERNAL NETWORK HDD. User s Manual

3.5 EXTERNAL NETWORK HDD. User s Manual 3.5 EXTERNAL NETWORK HDD User s Manual Table of Content Before You Use Key Features H/W Installation Illustration of Product LED Definition NETWORK HDD Assembly Setup the Network HDD Home Disk Utility

More information

Standard Wire & Cable Co.

Standard Wire & Cable Co. MIL-DTL-27500 (NEMA WC27500) Cable Designation All MIL-DTL-27500 cables are designated by a combination of digits and letters (not to exceed 6) which indicates the exact construction of each cable. Please

More information

IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02

IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02 IDDERO HOME SERVER Quick start guide www.iddero.com 150302-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 IDDERO HOME SERVER CONFIGURATION...

More information

Z-Wave.Me Wall Controller

Z-Wave.Me Wall Controller Z-Wave.Me Wall Controller ZME_06443: Wall Controller Firmware Version 1.1 1 General Information about Z- Wave Safe: Generally radio systems build a direct link between the transmitter and the receiver.

More information

Projector Control Command Reference Manual

Projector Control Command Reference Manual Projector Control Reference Manual Copyright (C) NEC Display Solutions, Ltd. 2014-2015 BDT140013 Revision 4.0 Introduction This manual describes the commands used to control an NEC-made projector from

More information

How to read this guide

How to read this guide How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information

More information

KNX IP Gateway. Light-Control R. User manual-ver.1 LC-IPGW-001. KNX Gateway. KNX/EIB Intelligent Installation Systems

KNX IP Gateway. Light-Control R. User manual-ver.1 LC-IPGW-001. KNX Gateway. KNX/EIB Intelligent Installation Systems KNX Gateway Light-Control R User manual-ver.1 LC-IPGW-001 Intelligent Installation Systems Contents 1. Summary ---------------------------------------------------------------------------------------------------------------------

More information

Heating Actuators in the MIX2 Series HMG 6 T, HME 6 T and FIX2 HM 12 T

Heating Actuators in the MIX2 Series HMG 6 T, HME 6 T and FIX2 HM 12 T Heating Actuators in the MIX2 Series HMG 6 T, HME 6 T and FIX2 HM 12 T HMG 6 T 4930240 HME 6 T 4930245 HM 12 T 4940245 Updated: Dec-14 (subject to change) Page 1 of 61 Contents 1 Contents 2 FUNCTIONAL

More information

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx 756627xx, 756637xx, 756657xx Documentation Product name: Push button 2-, 3-, 5- gang RTR + display Design: UP (flush-mounting type) ETS search path: Push button / Push button xgang / Push button xgang

More information

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.es GENERAL TECHNICAL SPECIFICATIONS Temperature range: -50ºC to +99ºC type: NTC Total accuracy ( + controller): ±1ºC lead extension with cable AKO-15586:

More information

Shutter Actuator, 8-fold, 230 V AC, MDRC JA/S 8.230.1, GH Q631 0063 R0111. ABB i-bus EIB / KNX

Shutter Actuator, 8-fold, 230 V AC, MDRC JA/S 8.230.1, GH Q631 0063 R0111. ABB i-bus EIB / KNX , GH Q631 0063 R0111 2CDC 071 238 F0003 For controlling a maximum of eight independent 230 V AC shutter or sunblind drives via ABB i-bus including the functions Up/Down, Step/Stop, Move to position, Sun

More information

Belimo Gateway MP to Modbus RTU - UK24MOD

Belimo Gateway MP to Modbus RTU - UK24MOD Product information UK24MOD MODBUS RTU Belimo Gateway MP to Modbus RTU - UK24MOD Contents Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical

More information

Application Engineering

Application Engineering Application Engineering February 2011 Electronic Unit Controller Table of Contents 1. Introduction and Features... 2 1.1 Technical Specifi cations... 3 1.2 Pressure Probe Error Bypass... 3 1.3 Bump Start...

More information

MAX6683 Evaluation System/Evaluation Kit

MAX6683 Evaluation System/Evaluation Kit 19-2343; Rev 1; 3/07 MAX6683 Evaluation System/Evaluation Kit General Description The MAX6683 evaluation system (EV system) consists of a MAX6683 evaluation kit (EV kit) and a companion Maxim CMODUSB board.

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

Technical Manual MDT Rain sensor

Technical Manual MDT Rain sensor 9/2012 Technical Manual MDT Rain sensor SCN-RS1R1.01 Technical Manual Rain sensor SCN RS1R1.01 1.1. Settings at the ETS Software Selection at the product database: Manufacturer: MDT Technologies Product

More information

HDMI Matrix Switch USER MANUAL VM0404H

HDMI Matrix Switch USER MANUAL VM0404H HDMI Matrix Switch USER MANUAL VM0404H FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits

More information

Temp. & humidity Transmitter Instructions

Temp. & humidity Transmitter Instructions Temp. & humidity Transmitter Instructions AQ3485/AQ3485Y www.aosong.com 1 Product Overview AQ3485/ AQ3485Y outdoor network temperature and humidity transmitter is accurate measurement of relative humidity

More information

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification: PURPOSE Verify that communication is established for the following products programming option (488.2 compliant, SCPI only): DCS - M9C & DCS M130, DLM M9E & DLM-M9G & DLM M130, DHP - M9D, P series, SG,

More information

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages

More information

Please refer to the chapters below for detailed information about all aspects of the products usage.

Please refer to the chapters below for detailed information about all aspects of the products usage. EUR_STELLAZ Wall Radiator Thermostat Valve Control Firmware Version : 0.4 Quick Start S This device is a wireless sensor. All operation is performed using the little button behind the round hole in the

More information

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6

More information